Simplex 49VO-WRF-BA, 49VO-WWF-BA, 49VO-WRQ, 49VO-WWF, 49VO-WWQ Instructions Manual

...
Page 1
UL, ULC, CSFM Listed; Visible Notification Appliances, Wall Mount FM Approved* Multi-Candela Strobes, Model Series 49VO
Features
Individually addressed and controlled multi-candela TrueAlert ES V/O (visible only) notification appliances provide:
Multi-candela xenon strobe with synchronized 1 Hz flash
rate and with intensity programmable from the cont rol panel or jumper selected as 15, 30, 75, 110, 135, or 185 cd
SLCs from Simplex
EPS/EPS+ power supplies (and 4009 IDNAC Repeaters) providing regulated 29 VRMS allowing strobes to operate with lower current even under battery backup
Wiring supervision to each appliance allowing
“T-tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)
Self-Test Mode allows an on-board sensor to detect the
strobe output and then report its status to the control panel
TrueAlert Device Reports at the control panel detailing
appliance point ID, custom label, type, and candela setting (see sample on page 3)
Magnet Test diagnostics to assist checkout and testing of
appliances and wiring and Electrical test point access without removing cover
Compatibility with ADA requirements; (refer to
important installation information on page 3)
Compatibility with legacy TrueAlert addressable systems
for upgrade and replacement (see page 4)
Listed to UL Standard 1971 and ULC Standard S526
LED Indicator and Magnet Test feature:
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
When the controller is in diagnostic mode, the Magnet
Test pulses the LED to indicate appliance address and can be set to also briefly flash the strobe
Mechanical design features include:
Rugged, high impact, flame retardant thermoplastic
housing in red with white letters or white with red letters, with clear lens, available with FIRE, ALERT, FEU, FEU/FIRE, or blank lettering
Separate covers are available to change appliance type
on-site or for replacement; covers can be easily removed without disturbing the connected housing and avoiding trouble conditions
A separate mounting plate allows wiring to be completed
before appliance is mounted; use with single gang, double gang, or 4-inch square box, flush or surface mount
In/out wiring terminals for 18 AWG to 12 AWG Optional mounting adapters are available to cover
surface mounted electrical boxes and to adapt to Simplex 2975-9145 boxes
Optional red wire guards (see page 2 for details)
* These products have been approved by the California State Fire Marshal (CSFM) pursuant
to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:0373 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
S49VO-0001-3 8/2014
®
4100ES fire alarm control panels with
TrueAlert Addressable Notification Appliances
TrueAlert ES Addressable Strobes are Available in Red
with White Lettering and White with Red Lettering
Description
TrueAlert ES addressable strobes are individually
addressed visible notification appliances that receive power, supervision, and control signals from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). (See compatibility list on page 4.)
Strobe Application Reference
Proper selection of visible notification is de p endent on occupancy, location, local codes, and proper applications of: the National Fire Alarm Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).
TrueAlert ES Operation Advantage
TrueAlert ES addressable appliances on IDNAC SLCs provide separate visible (and audible ) noti fi cat ion
using a single two-wire circuit that also confirms connection to the individual notification appliance’s electronic circuit.
This operation increases circuit supervision integrity by providing supervision that extends beyond the appliance wiring connections.
Reduced current allows efficient IDNAC SLC operation. With IDNAC SLCs, a constant 29 VRMS
source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power an d seco ndary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.
Page 2
TrueAlert ES Operation Advantage (Cont’d)
Reducing Installation and Testing Time. With
separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of Self-Test and Magnet Test features improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.
TrueAlert ES Diagnostics
Test Features. When IDNAC SLCs are in diagnostic
mode, Self-Test and Magnet Test features provide individual appliance testing. With the Self-Test feature, appliance operation can be confirmed without leaving the control panel. Additionally, each appliance’s LED can be selected to pulse when it receives a supervision poll during normal operation.
Self-Test Details. Selecting Self-Test Mode from the control panel allows on-board sensors, depending on the device type, to detect its own strobe and/or horn output and then report their status to the control panel.
Product Selection
TrueAlert ES Diagnostics (Continued)
Self-Test Details (Continued). Operation is by selected VNAC appliance groups and is either automatic (all briefly simultaneously activated) or individually activated by apply ing a magnet. (Refer to data sheet S4100-0100 for more Self-Test information.)
Silent Appliance Magnet Test. In this test mode, in response to application of a magnet, the appliance LED pulses sequentially to conveniently indicate the appliance’s address.
Operational Appliance Magnet Test. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to indicate proper operation.
TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert ES appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information.
TrueAlert Addressable Wiring Isolator
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring. (See data sheet S4905-0001.)
TrueAlert ES Wall Mount Addressable Strobes
TrueAlert ES addressable VO (strobe) appliances include cover and matching mounting plate except as noted; Dimensions with Cover = 5 ” H x 5” W x 1 ½” D (130 mm x 127 mm x 38 mm)
Model* Cover Color Wording Lens Color Model* Cover Color Wording Lens Color
49VO-WRF(-BA) Red
49VO-WWF(-BA) White 49VO-WWQ White
49VO-WRA(-BA) Red 49VO-WWA(-BA) White 49VO-WWS(-BA) White
49VO-APPLW Select cover and mounting plate separately
FIRE
Clear
ALERT
49VO-WRQ Red
49VO-WRS(-BA) Red
FEU
Clear
Blank
Separate Mounting Plate
Model Color Note
49MP-AVVOWR Red 49MP-AVVOWW White
Mounting Plate is required when ordering model 49VO-APPLW
Separate Covers (Required when ordering model 49VO-APPLW)
Model* Color Wording Model* Color Wording
49VOC-WRFIRE Red 49VOC-WWFIRE White 49VOC-WWFEU White
49VOC-WRALT Red 49VOC-WWALT White 49VOC-WWBLNG White
49VOC-WRS Red Blank 49VOC-WWS White Blank * Note: (-BA) indicates model is available either with or without the -BA suffix. Model numbers ending in -BA, APPLW models, and
separate mounting plates are assembled in the USA.
FIRE
ALERT
49VOC-WRFEU Red
49VOC-WRBLNG Red
FEU
FEU/FIRE
Mounting Adapters and Wire Guard
Model Color Description Dimensions
4905-9937 Red 4905-9940 White
4905-9931
2975-9145 Red Mounting Box, requires 4905-9931 Adapter Plate 7 " x 5 " x 2 ¾" D (200 mm x 130 mm x 70 mm)
4905-9961
Red Adapter Plate for mounting to Simplex 2975-9145 Box (typically for retrofit, mount vertical or horizontal)
Red wire guard with mounting plate, compatible with semi­flush or surface mount boxes
Surface Mount Adapter Skirt
5 ” H x 5 ¼” W x 1 ” D (136 mm x 133 mm x 41 mm) Total depth with strobe = 4 ” (111 mm)
8 5⁄16” x 5 ¾” x 0.060” Thick (211 mm x 146 mm x 1.5 mm)
1
⁄16” H x 6 1⁄16” W x 3 ” D (154 mm x 154 mm x 79 mm)
6
2 S49VO-0001-3 8/2014
Page 3
P
1
18-
Aug-14
T
V
A
A
A
TrueAlert Device Reports Reference
Service Port REPORT 5 : TrueAlert Device Report
POINT ID CUSTOM LABEL T14-1-1 Location Label . . . up to 40 characters T14-1-2 Break Room 5 T14-1-3 Boiler Room T14-1-4 Elec. Room 7
Installation Reference
Mounting is compatible with single gang,
double gang, and 4" (102 mm) square boxes,
1-1/2" (38 mm) deep, supplied separately
Transparent
housing assembly
Removable cover (when installed, use flat bladed screwdriver to release latch on left side)
Address setting DIP
switch, accessible
from rear of housing
Magnetic test location
(bottom of housing)
Electrical test point access holes
(on bottom)
Wiring terminals and
connection clips
LED indicator location
Strobe intensity
viewing slot on
side of appliance
(not to scale)
110
75 30 15
FACP
135 185
DEVICE
YPE
/O 15 /V 110 /V 75 /V 135
Wiring access hole
Mounting plate
Mounting Holes: Single gang (2) Double gang (4) 4" square (4)
Intensity selection plug, accessible from rear of housing; factory setting is FACP, controlled by panel
2:34:56am MON
age 1
CANDELA
IMPORTANT! WALL MOUNT
INSTALLATION HEIGHTREFERENCE
Electrical box outline
Bottom of lens is either even with, or slightly above bottom of compatible boxes
80" (2.03 m)
minimum
NFPA 72 requires that the entire lens be not less than 80" and not greater than 96" above the finished floor (confirm with your local codes)
Adapter Plate and Surface Mount Installation Reference
4905-9931 Adapter Plate
TrueAlert ES
Addressable Strobe
4905-9961 Optional Wire Guard
3 S49VO-0001-3 8/2014
(shown here for reference only, can be used on other mounting options)
2975-9145 Box Mounting Reference
2975-9145 Box
4905-9931 Adapter Plate
Surface Mount Side View Reference
(Surface mount conduit and
box shown for reference)
Optional
4905-9961
Wire Guard
TrueAlert ES
Addressable
Strobe
4" square box profile, 1-1/2" (38 mm) deep
Optional surface mount adapter skirt,
1-1/2" deep: 4905-9937, Red;
4905-9940, White (conduit knockouts
are provided on all four sides)
Page 4
TrueAlert ES Appliance and IDNAC SLC Controller Compatibility Reference
Compatible Controller and additional TrueAlert ES Appliances
Data Sheet Reference
Controller
Output
IDNAC SLC
Output Voltage
Appliance Voltage
Design Reference
4100ES with EPS+ or EPS Power Supply S4100-0100 4009 IDNAC Repeater S4009-0004
TrueAlert ES Audible Only (Horns) S49AO-0001 TrueAlert ES Audible/Visible S49AV-0001
TrueAlert ES Weatherproof Appliances
TrueAlert ES Strobe Specifications
UL Listed S49WP-0001
ULC Listed S49WP-0002
IDNAC SLC
29 VRMS
(regulated)
23 VRMS
(with 6 VRMS drop)
Electrical Ratings
Typical Operating Voltage Range 23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating)
Supervisory Requirements 1 unit load
SLC Loading Maximum of 63 addresses per SLC, 75 unit loads
Candela Setting 15 cd 30 cd 75 cd 110 cd 135 cd 185 cd
23 VRMS Current Ratings, for typical design of
IDNAC Addressable SLCs (6 VRMS drop)
47 mA 57 mA 100 mA 132 mA 160 mA 208 mA
General Specifications
Temperature Range
32 to 122 F (0 to 50 C)
Humidity Range 10% to 93%, non-condensing @ 104° F (40° C)
UTP, unshielded twisted pair recommended
IDNAC SLC Wiring Specifications (refer to control panel installation instructions for more information)
Maximum wire length allowed with “T-Taps” for Class B wiring per SLC = 10,000 ft (3048 m)
Maximum wire length to any appliance = 4000 ft (1219 m) Maximum wiring resistance between compatible appliances = 26
2
Connections
Terminal blocks on mounting plate for 18 AWG to 12 AWG (0.82 mm
3.31 mm
2
); two wires per terminal for in/out wiring
to
Installation Instructions 579-1031
Notes: Refer to compatibility table above for fire alarm control panel and power supply operation type.
TrueAlert ES Strobe LEGACY Compatibility Reference
Compatible Controller
4100ES or 4100U with TrueAlert Power Supply
4009 TPS, Remote TrueAlert Power Supply
TrueAlert Addressable Controller (4009T)
Electrical Ratings Reference for Retrofit Applications
17 VRMS Current Ratings, use when
connected to TrueAlert Addressable SLCs per above
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S49VO-0001-3 8/2014
www.simplex-fire.com
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Data Sheet
Reference
S4100-0031
S4100-0037
S4009-0003
Voltage Range 17 VRMS to 31 VRMS, Special Application
Candela Setting 15 cd 30 cd 75 cd 110 cd
Controller Output
TrueAlert
Addressable SLC
Available Strobe
Intensity
15, 30, 75, and 110 cd 17 VRMS
Appliance Voltage
62 mA 75 mA 133 mA 178 mA
Minimum
Loading...