Simplex 49SVC-CWBA, 49SVC-CRFEU, 49SVC-CRBF, 49SVC-CWALT, 49SVC-CRBA Installation Instructions Manual

...
Page 1
Cover
S/V Appliance
4 in. x 4 in. Electrical Box (2-1/8 in. deep)
Screws
-Use 8-32 screws for a 4 in. x 4 in. electrical box
Cover
SO Appliance
-Use 8-32 screws for a 4 in. x 4 in. electrical boxScrews
Document: Installation Instructions Product: TrueAlert ES Addressable
Ceiling Mount Speaker Indoor Notification Appliances
UL listed TrueAlert ES indoor product identification reference
Type Cover colors Models Operation
Components:
49SV-APPLC 49HFV-APPLC 49SV-APPLC-BA 49HFV-APPLC-BA 49SVH-APPLC-BA 49HFVH-APPLC-BA 49SVH-APPLC 49HFVH-APPLC
Components:
49SO-APPLC 49HF-APPLC 49SO-APPLC-BA 49HF-APPLC-BA
Ceiling Mount
Speaker/Visible
(S/V)
Ceiling Mount Speaker Only
(SO)
Red White Black
Red White Black
Note: For information on appliance testing consult TrueAlert ES Addressable Appliances Troubleshooting Guide (579-1049).
Mounting instructions
Kit contents: Appliance (x1): with 8-32 1 in mounting screws (x2).
Not included:
Tightening torque: 12-15 in/lbs, do not over tighten.
Order a cover separately for each appliance.
Electrical box: 4 in square, 2-1/8 in minimum depth required.
1. Select the desired location and install the electrical box using screws suitable for the mounting surface.
2. Connect the building wires to the terminal block on the rear of the appliance. See Wiring instructions on page 2.
3. Secure the appliance to the electrical box by using the provided hardware.
4. Set the appliance settings. See Setting the address DIP switch on page 3.
5. Attach the cover to the appliance.
Covers:
49SVC-CK 49SVC-CRALT 49SVC-CRFIRE 49SVC-CRS 49SVC-CRBC 49SVC-CWBC
Covers:
49SOC-CK 49SOC-CW 49SOC-CR 49SOC-CWALT 49SOC-CRALT
49SVC-CWFIRE 49SVC-CRFEU 49SVC-CRBF 49SVC-CWALT 49SVC-CWBA 49SVC-CRBA 49SVC-CWS 49SVC-CWBF 49SVC-CWFEU
49SOC-CRFIRE 49SOC-CRS 49SOC-CWFIRE 49SOC-CWS
These appliances provide an audio (SO) or audible/visible (S/V) warning of an alarm condition when activated from the control panel of a compatible UL/ULC Listed, Simplex Fire Alarm System. Consult Simplex Fire Alarm panel documentation for compatibility information. Speakers may be turned ON/OFF individually under control of a compatible panel. S/V models ‘49HFV’ have Hi intensity strobes; models ‘49SV’ have standard range strobes.
4 in. x 4 in. Electrical Box (2-1/8 in. deep)
Figure 1. Mounting instructions
IMPORTANT. When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires immediate attention
of all occupants.
LOCATION REFERENCE. Location and quantity of Appliances required must conform to the applicable local standards and guidelines (the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate model building codes, and so on) and specific requirements of the Local Authority Having Jurisdiction (AHJ). These Notification Appliances are not intended for installation within hazardous locations as defined by the National Electrical Code (NEC) or NFPA.
SAFETY. Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and instructions may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the electrical power for the notification appliance circuit is disconnected at the control panel before installing, repairing, or internally adjusting any notification appliances. Even with electrical power removed, some notification appliances (such as visible strobes) store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH EXPOSED CIRCUITRY.
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
579-1203
Rev. B
*05791203B*
Page 2
579-1203 Installation Instructions
!
S/V Appliance Back Side
Terminal 1: ‘NAC+’
Terminal 2: ‘NAC-’
Terminal 3: ‘Audio+’
Terminal 4: ‘Audio-’
(T-tapping example)
Class A Wiring (See Notes)
From Compatible SLC
Controller (See Notes)
Audio - Audio +
12
SLC +
CKT CKT
S/V, S/O
34
Audio -
Audio +
12
SLC - SLC +
CKT CKT
S/V, S/O
34
SLC -
Audio ­Audio +
To Next Appliance or Compatible SLC Controller (See Notes)
Audio -
Audio +
12
SLC - SLC +
CKT CKT
S/V, S/O
34
Audio ­Audio +
12
CKT
S/V, S/O
34
Audio -
Audio +
12
SLC -
SLC +
CKT
S/V, S/O
34
Audio -
Audio +
12
SLC -
SLC +
CKT
S/V, S/O
34
Audio -
12
SLC -
SLC +
CKT
S/V, S/O
34
Audio +
Audio ­Audio +
From Amplifier
Audio + Audio -
Class B Wiring (See Notes)
From Compatible SLC
Controller (See Notes)
From Amplifier
Audio + Audio -
SO Appliance Back Side
Terminal 1: ‘NAC+’
Terminal 2: ‘NAC-’
Terminal 3: ‘Audio+’
Terminal 4: ‘Audio-’
P2
J2
1
P2
J2
1
P2/J2
P2/J2
Wiring instructions
WARNING: Make sure that all power is disconnected before starting the installation.
1. At the electrical box, connect the building wiring to the CKT + and CKT - terminals on the backplate.
2. Torque terminal block screws 12-15 inch-pounds to ensure proper continuity.
3. Ensure that correct polarity is maintained for each strobe unit.
4. Signal line circuit (SLC) wiring must be twisted pair (TWP). CKT Terminals accept two Wires: 12-18 American wire gauge (AWG) TWP .
IMPORTANT: Do not bring conduit through the rear of the electrical box. Strip lead insulation to 7/16 inch maximum.
Wiring Notes
1. Assign a maximum of 127 active appliances to a circuit. Assign a maximum of 51 active strobe appliances to a powered circuit. The maximum wire
2. Notification appliances are rated using an individual module label.
3. Maintain the correct polarity on the terminal connections.
4. Terminals 1 through 4 can each accommodate two wires, one wire going in and one wire going out to the next appliance.
5. These appliances are rated to the operating voltage limits of 23-30
6. The TrueAlert IDNAC S/V and SO can only be operated through a compatible power supply and amplifier.
7. T-tapping is not allowed for Class A wiring.
8. TrueAlert SLC wiring connections are supervised and power-limited.
resistance between appliances is 26 instructions.
ohms. Refer to the Field Wiring Diagrams of the driving compatible fire alarm control panel for further
permanent damage to this equipment if it operates outside of these limits.
Figure 2. Wiring instructions
volts DC (VDC). The appliance may fail to operate as intended, and may cause
2
Page 3
579-1203 Installation Instructions
To Access Switches:
SO Appliance
S/V Appliance
ALARM/ ALERT
001
101
011 111
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
DIP SWITCHES 5 THROUGH 7
000
100 010
110
Hgh Candela
Std Candela
Audio Circuit Conguration
P2
J2
1
P1
DEFAULT = 1-2 1-2 : 25V, 1/4W 2-3 : 70.7V, 2W
PCB on the back side of the unit
P2
J2
1
DEFAULT = 1-2 1-2 : 25V, 1/4W 2-3 : 70.7V, 2W
Setting the address DIP switch
Each addressable TrueAlert IDNAC notification appliance has a unique address that is set using an eight-position DIP switch (ADDR1). Up to 127 unique addresses can be assigned to an SLC; however, total appliance loading available may be less due to appliance current requirements.
To set the address
1. Unclip the cover from the appliance by inserting a slotted screwdriver (or similar sized object) into the opening at either end of the cover. See Figure 3.
2. Use a small screwdriver or pen to set the switches.
3. Record the set address.
4. DIP switch position 8 determines whether this appliance is viewed by the system as an 'ALARM' (OFF) or 'ALERT' (ON) type appliance. Confirm the setting for the appliance at this address with the FACP system configuration documentation.
Setting the strobe candela setting
1. Jumpers are factory set as FACP. Leave the appliance at this setting if the candela setting is to be programmed from a 4100ES FACP. The candela setting is visible through the slot on the side of the case.
2. If manual selection is required, remove the cover and slide the CD selector to the required setting: FACP or 15/30/75/110 for standard strobe, FACP or 185/135/110 for HiCD strobe.
3. When the appliance is mounted, the candela rating is visible through the side-window of the appliance.
Note: One of the 4 candela outputs must be programmed for each appliance by
Audio circuit configuration (S/V and SO)
Use the slide switches depicted in Figure 4 for required audio circuit voltage and power tap selection.
Move jumper P2, on the PCB on the back-side of the unit, to position 2-3 for 70 V/2 W operation. Use position 1-2 for all other audio levels, see Figure 4.
Figure 3. Setting the DIP switch address
authorizing service personnel or a programming mismatch trouble will result. To set the candela through the Programmer set it to FACP. Additional information is contained in the 4100ES Programmer’s Manual (574-849).
3
Figure 4. Setting the strobe and appliance
configuration
Page 4
579-1203 Installation Instructions
R
Appliance specifications
Environmental specifications
Rated DC control/strobe voltage range
Temperature range
Humidity range
Connections
Special application 23-30 VDC
32 °F to 120 °F (0 °C to 49 °C)
10 % to 93 %, non-condensing at 104 °F (40 °C)
Terminal for 18 AWG to 12 AWG (0.82 mm
2
to 3.31 mm2)
CAUTION:
• The appliances are available in red and white. Do not paint or otherwise alter the factory finishes in any way.
Maximum RMS operating current
49[SV/HFV] visible 49[SVH/HFVH] visible
Candela
15
30
75
110
Speaker Only
Current
59 mA - -
82 mA 110 235 mA
145 mA 135 255 mA
193 mA 185 295 mA
Candela
Current
SO 9 mA
Vertical and horizontal light dispersion ratings
(ceiling to walls and floors)
Percent of rated light output at any candela setting
(room temperature)
Vertical dispersion Horizontal dispersion
Y-plane
angle
0
±5
±10
±15
±20
±25
±30
±35
±40
±45
±50
±55
±60
±65
±70
±75
±80
±85
±90
UL req output
% 327 %
100
% 293 %
90
% 281 %
90
% 197 %
90
% 168 %
90
% 142 %
90
% 143 %
45
% 155 %
45
% 156 %
45
% 134 %
45
% 115 %
55
% 104 %
45
% 103 %
40
%98 %
35
%87 %
35
%90 %
30
%96 %
30
%96 %
25
%83 %
25
Typical
output
X-plane
angle
0
±5
±10
±15
±20
±25
±30
±35
±40
±45
±50
±55
±60
±65
±70
±75
±80
±85
±90
UL Req
output
100 % 343 %
90 % 160 % 90 % 175 % 90 % 129 % 90 % 145 % 90 % 165 % 45 % 152 % 45 % 144 % 45 % 139 % 45 % 129 % 55 % 129 % 45 % 123 % 40 % 111 % 35 % 120 % 35 % 103 % 30 %75 % 30 %83 % 25 %70 % 25 %47 %
Typical
output
Speaker specifications
Input voltage 25 VRMS or 70.7 VRMS - speakers are for connection to compatible fire alarm audio circuits.
Power taps via jumper J1 1/4 W, 1/2 W, 1 W and 2 W
Frequency Response
Fire alarm 400 Hz to 4000 Hz [SV/SO]; 200 Hz to 10000 Hz [HFV/HF]
General signaling 125 Hz to 12 kHz
TrueAlert Addressable Ceiling Mount S/V and SO units- speaker switch setting (25 V or 70 V audio)
UL1480 at 10 ft ULC-S541 at 3 m
-
Tap settings in
Watts
HiSPL (SV/SO)
models
HiFi (HFV/HF)
models
HiSPL (SV/SO)
models
HiFi (HFV/HF)
models
1/4 79 77 81 78
Speaker
Only
1/2 83 81 85 82
186 84 88 85*
290 87 91 88*
1/4 79 76 79 78
Speaker
Visible
1/2 83 80 83 82
186 84 86 85*
289 87 89 88*
Note:
Reverberant dBA measurements are a minimum UL rating based on sound level measurements made in UL’s reverberant test chamber.
Anechoic dBA measurements are a minimum ULC rating based on sound pressure level measurements made in ULC’s anechoic test chamber.
The sound pressure level decreases by 3 dB at an angular displacement of 70° from the line perpendicular to the speaker’s center. The SPL decreases by 6
Only marked settings may be used for ULC fire alarm applications.
dB at an angle of 80° from that line.
579-1203
Rev. B
Loading...