4 in. x 4 in. Electrical Box (2-1/8 in. deep)
Screws
-Use 8-32 screws for a 4 in. x 4 in. electrical box
-Use 8-32 screws for a 4 in. x 4 in. electrical boxScrews
Document: Installation Instructions
Product: TrueAlert ES Addressable
Ceiling Mount Speaker Indoor
Notification Appliances
UL listed TrueAlert ES indoor product identification reference
Type Cover colors Models Operation
Components:
49SV-APPLC
49HFV-APPLC
49SV-APPLC-BA
49HFV-APPLC-BA
49SVH-APPLC-BA
49HFVH-APPLC-BA
49SVH-APPLC
49HFVH-APPLC
Components:
49SO-APPLC
49HF-APPLC
49SO-APPLC-BA
49HF-APPLC-BA
Ceiling Mount
Speaker/Visible
(S/V)
Ceiling Mount
Speaker Only
(SO)
Red
White
Black
Red
White
Black
Note: For information on appliance testing consult TrueAlert ES Addressable Appliances Troubleshooting Guide (579-1049).
Mounting instructions
Kit contents: Appliance (x1): with 8-32 1 in mounting screws (x2).
Not included:
Tightening torque: 12-15 in/lbs, do not over tighten.
Order a cover separately for each appliance.
Electrical box: 4 in square, 2-1/8 in minimum depth required.
1. Select the desired location and install the electrical box using screws suitable for the mounting surface.
2. Connect the building wires to the terminal block on the rear of the appliance. See Wiring instructions on page 2.
3. Secure the appliance to the electrical box by using the provided hardware.
4. Set the appliance settings. See Setting the address DIP switch on page 3.
5. Attach the cover to the appliance.
Covers:
49SVC-CK
49SVC-CRALT
49SVC-CRFIRE
49SVC-CRS
49SVC-CRBC
49SVC-CWBC
Covers:
49SOC-CK
49SOC-CW
49SOC-CR
49SOC-CWALT
49SOC-CRALT
49SVC-CWFIRE
49SVC-CRFEU
49SVC-CRBF
49SVC-CWALT
49SVC-CWBA
49SVC-CRBA
49SVC-CWS
49SVC-CWBF
49SVC-CWFEU
49SOC-CRFIRE
49SOC-CRS
49SOC-CWFIRE
49SOC-CWS
These appliances provide an audio (SO) or
audible/visible (S/V) warning of an alarm
condition when activated from the control
panel of a compatible UL/ULC Listed,
Simplex Fire Alarm System. Consult Simplex
Fire Alarm panel documentation for
compatibility information.
Speakers may be turned ON/OFF
individually under control of a compatible
panel.
S/V models ‘49HFV’ have Hi intensity
strobes; models ‘49SV’ have standard range
strobes.
4 in. x 4 in. Electrical Box (2-1/8 in. deep)
Figure 1. Mounting instructions
IMPORTANT. When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires immediate attention
of all occupants.
LOCATION REFERENCE. Location and quantity of Appliances required must conform to the applicable local standards and guidelines (the National Fire
Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate model building codes, and so on)
and specific requirements of the Local Authority Having Jurisdiction (AHJ). These Notification Appliances are not intended for installation within hazardous
locations as defined by the National Electrical Code (NEC) or NFPA.
SAFETY. Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and instructions may
result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high voltage. To avoid electrical hazards
and avoid damage to appliances, make sure that the electrical power for the notification appliance circuit is disconnected at the control panel before
installing, repairing, or internally adjusting any notification appliances. Even with electrical power removed, some notification appliances (such as visible
strobes) store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH EXPOSED CIRCUITRY.
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are
subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status.
Listings and approvals under Simplex Time Recorder Co. SIMPLEX, and the product names listed in this material are marks and/or registered
marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire
Protection Association (NFPA).
579-1203
Rev. B
*05791203B*
![](/html/da/da61/da6103144315ea35be2d3e1d6178be87d51eafbc98bc0d7052abec9152123442/bg2.png)
579-1203 Installation Instructions
S/V Appliance Back Side
Terminal 1: ‘NAC+’
Terminal 2: ‘NAC-’
Terminal 3: ‘Audio+’
Terminal 4: ‘Audio-’
(T-tapping example)
Class A Wiring (See Notes)
From Compatible SLC
Controller (See Notes)
Audio - Audio +
12
SLC +
CKT CKT
S/V, S/O
34
Audio -
Audio +
12
SLC - SLC +
CKT CKT
S/V, S/O
34
SLC -
Audio Audio +
To Next Appliance
or Compatible SLC
Controller
(See Notes)
Audio -
Audio +
12
SLC - SLC +
CKT CKT
S/V, S/O
34
Audio Audio +
12
CKT
S/V, S/O
34
Audio -
Audio +
12
SLC -
SLC +
CKT
S/V, S/O
34
Audio -
Audio +
12
SLC -
SLC +
CKT
S/V, S/O
34
Audio -
12
SLC -
SLC +
CKT
S/V, S/O
34
Audio +
Audio Audio +
From Amplifier
Audio +
Audio -
Class B Wiring (See Notes)
From Compatible SLC
Controller (See Notes)
From Amplifier
Audio +
Audio -
SO Appliance Back Side
Terminal 1: ‘NAC+’
Terminal 2: ‘NAC-’
Terminal 3: ‘Audio+’
Terminal 4: ‘Audio-’
P2
J2
1
P2
J2
1
P2/J2
P2/J2
Wiring instructions
WARNING: Make sure that all power is disconnected before starting the installation.
1. At the electrical box, connect the building wiring to the CKT + and CKT - terminals on the backplate.
2. Torque terminal block screws 12-15 inch-pounds to ensure proper continuity.
3. Ensure that correct polarity is maintained for each strobe unit.
4. Signal line circuit (SLC) wiring must be twisted pair (TWP). CKT Terminals accept two Wires: 12-18 American wire gauge (AWG)
TWP .
IMPORTANT: Do not bring conduit through the rear of the electrical box. Strip lead insulation to 7/16 inch maximum.
Wiring Notes
1. Assign a maximum of 127 active appliances to a circuit. Assign a maximum of 51 active strobe appliances to a powered circuit. The maximum wire
2. Notification appliances are rated using an individual module label.
3. Maintain the correct polarity on the terminal connections.
4. Terminals 1 through 4 can each accommodate two wires, one wire going in and one wire going out to the next appliance.
5. These appliances are rated to the operating voltage limits of 23-30
6. The TrueAlert IDNAC S/V and SO can only be operated through a compatible power supply and amplifier.
7. T-tapping is not allowed for Class A wiring.
8. TrueAlert SLC wiring connections are supervised and power-limited.
resistance between appliances is 26
instructions.
ohms. Refer to the Field Wiring Diagrams of the driving compatible fire alarm control panel for further
permanent damage to this equipment if it operates outside of these limits.
Figure 2. Wiring instructions
volts DC (VDC). The appliance may fail to operate as intended, and may cause
2