Simplex 4906-9256, 4906-9254, 4906-9251, 4906-9255, 4905-9946 User Manual

...
Page 1
TrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed; FM Approved; Multi-Candela Speaker/Visible MEA (NYC) Acceptance* (S/V) Appliances
Features
Individually addressed and controlled multi-candela S/V (speaker/visible) notification appliances provide:
Multi-candela xenon strobe with synchronized 1 Hz
flash rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, or 110 cd
Advanced addressable notification controlled by IDNAC
SLCs from Simplex
®
4100ES fire alarm control panels
with EPS/EPS+ power supplies (and 4009 IDNAC Repeaters) providing regulated 29 VRMS allowing strobes to operate with lower current even under battery backup
Wiring supervision to each strobe allowing “T-tapped”
connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)
TrueAlert Device Reports at the control panel detailing
appliance point ID, custom label, type, and candela setting (see sample on page 2)
Magnet test diagnostics to assist checkout and testing of
appliances and wiring
Compatibility with ADA requirements; (refer to
important installation information on page 3)
Compatibility with legacy TrueAlert addressable
systems for upgrade and replacement (see page 4)
Strobe operation is listed to UL 1971 and ULC-S526*
LED indicator and magnet test feature:
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
In diagnostic mode, the magnet test pulses the LED to
indicate appliance address AND pulses to indicate the intensity selection; a brief output of the strobe is also selectable to confirm operation
Mechanical design features:
Rugged, high impact, flame retardant thermoplastic
housings are available for wall or ceiling mount
Wall mount housings are available in red or white Wall mount options include electrical box adapters,
separate covers to convert color, and red wire guards
Ceiling mount housing is white
Audible notification appliance (speaker):
High quality voice and tone reproduction with taps for
¼, ½, 1, or 2 W, at 25 or 70.7 VRMS
Speakers have capacitor input for connection to DC
supervised NACs and are wired separately from strobes
Listed to UL 1480 and ULC S541* Compliant with NFPA 72, 520 Hz Low Frequency
Signal Requirements for Sleeping Areas
* See page 2 for additional listing details and wire guard listings. This product has been
approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7320-0026:322 for allowable values and/or conditions concerning material presented in this document. of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
S4906-0006-7 5/2014
Accepted for use – City
Wall and Ceiling Mount S/Vs with Addressable Strobes
Description
Multi-Candela TrueAlert S/Vs with speaker and addressable strobe provide convenient installation to
standard electrical boxes with extensions. The strobe is individually addressed and individually controlled with power, supervision, and control supplied from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). (See compatibility list on page 4.) Speakers are wired separately.
Strobe Application Reference
Proper selection of visible notification is de p endent on occupancy, location, local codes, and proper applications of: the National Fire Alarm and Signaling Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).
IDNAC SLC Operation Advantage
TrueAlert S/V Appliances with Addressable Strobes on IDNAC SLCs provide visible notification
using a single two-wire circuit that also confirms connection to the individual notification appliance’s electronic circuit. This operation increases circuit
supervision integrity by providing supervision that extends beyond the appliance wiring connections.
Page 2
P
-
May-14
T
V
S
S
S
IDNAC SLC Operation Advantage (Cont’d)
Reduced current allows efficient IDNAC SLC operation. With IDNAC SLCs, a constant 29 VRMS
source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power an d seco ndary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.
Reducing Installation and Testing Time. With separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of the magnet test feature improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.
Product Selection
TrueAlert Addressable Wiring Isolator
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate short circuited wiring from functionin g wi ri n g. (R efer t o dat a sheet S4905-0001 for additional information.)
TrueAlert Addressable Diagnostics
Test Features. Controllers can be selected to pulse each
appliance’s LED when it receives a supervision poll. When the controller is selected for diagnostic mode, the appliance magnet test feature provides a response at the individual appliance being tested.
Silent Appliance Magnet Test. In this test mode, in response to the magnet test, the appliance LED pulses sequentially to conveniently indicate the appliance’s address.
Operational Appliance Testing. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to indicate proper operation.
TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert (and TrueAlert ES) appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information.
Multi-Candela Addressable S/Vs
Model Lettering Listings Housing Color Mounting Dimensions Description
4906-9251 White FIRE
4906-9253 Red FIRE White
4906-9254 Red FIRE
4906-9255 Blank
4906-9256 Red ALERT
4906-9257 Red FIRE ULC
UL & ULC
UL
Red
White Ceiling
Wall
7 ¼” H x 5” W x 2 ” D (184 mm x 127 mm x 67 mm)
7 ½” (191 mm) diameter speaker housing, ½” (13 mm) deep; lens extends 2 ” (67 mm) above housing; extension into box = 2 ¾” (70 mm)
Multi-Tapped Speaker with Multi-Candela Addressable Strobe; intensity selectable as: 15, 30, 75, or 110 candela
Wall Mount S/V Adapters, Replacement Covers, Wire Guard; Ceiling Mount Tile Bridge
Model Description Dimensions
4905-9946 Surface Mount Red Adapter Skirt
4905-9947 Surface Mount White Adapter Skirt
4905-9903
2975-9145
4905-9996 Red Wall Mount S/V Replacement Cover with white “FIRE” lettering
4905-9997 White Wall Mount S/V Replacement Cover with red “FIRE” lettering
4905-9998
2905-9946 Tile Bridge for Ceiling Mount S/Vs See diagram on page 3
Adapter Plate, red, required to mount S/V on 2975-9145 mounting box (typically for retrofit)
Mounting Box, red, for surface or flush mount, requires adapter plate 4905-9903 (this box may be available for retrofit applications)
Red Wire Guard for Wall Mount S/V; with mounting plate, compatible with surface and semi-flush boxes (UL listed by Space Age Electronics Inc.)
Required when mounting to surface mounted electrical box, 4” square, 1 ½” deep with 1 ½” deep extension
7 ¾” H x 5 ” W x 3
(197 mm x 137 mm x 81 mm)
depth with S/V = 5 ” (149 mm)
5
⁄16" H x 5 ¾" W x 0.060” Thick
8
(211 mm x 146 mm x 1.5 mm)
7 " H x 5 " W x 2 ¾" D
(200 mm x 130 mm x 70 mm)
7 ¼” H x 5” W x 1 ” D
(184 mm x 127 mm x 35 mm)
1
8 ” H x 6
(213 mm x 154 mm x 79 mm)
⁄16” W x 3 ¼” D
3
⁄16” D
TrueAlert Device Reports Reference
Service Port REPORT 5 : TrueAlert Device Report 12:34:56am MON 19
POINT ID CUSTOM LABEL T14-1-1 Location Label . . . up to 40 characters T14-1-2 Break Room 5 T14-1-3 Boiler Room T14-1-4 Elec. Room 7
2 S4906-0006-7 5/2014
DEVICE
YPE
/O 15 /V 110 /V 75 /V 30
age 1
CANDELA
Page 3
Wall Mount Installation Reference
Mounting to 2975-9145 Box
2975-9145 Box
4905-9903
Adapter Plate
Wiring input
terminals and
speaker tap
selection are
accessible
from rear
Removable cover (tool required)
Address
DIPswitch
LED indicator
Magnetic test location
Intensity selection plug, accessible only from rear of
housing; factory setting is FACP, controlled by panel
Strobe intensity viewing slot
Standard Electrical Box Mounting
4" (102 mm) square box, 1-1/2"
(38 mm) deep, with a 4" square box
extension, 1-1/2" deep, by others
Transparent housing and lens assembly
Speaker assembly
Surface Mounting Reference
Showing Optional Wire Guard
Surface mount conduit and
box shown for reference
4" (102 mm) square box
Strobe assembly
profile, 1-1/2" (38 mm)
deep with 1-1/2" extension
Optional 4905-9998
Wire Guard
110 75 30 15
FACP
Surface mount adapter skirt, 3-3/16"
(81 mm) deep, required for this
mounting method: 4905-9946, Red;
4905-9947, White (conduit knockouts
are provided on all four sides)
NOTE: Applicable for Wall Mount or Ceiling Mount S/V
Speaker Directional Characteristics;
85
84
83
2 kHz
82
81
80
79
78
77
76
75
90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90
Angular Displacement (Degrees) on Horizontal Axis
Sound Pressure Level (dB) at 10 ft (3 m)
4 kHz
IMPORTANT ! INSTALLATION
MOUNTING HEIGHT REFERENCE
2975-9145 box outline
4" square box outline
C
S/V
L
82"
(2.1 m)
minimum
78-1/2"
(2 m)
minimum
4" (102 mm)
1-1/2" (38 mm)
NFPA 72 requires that the entire lens be not less than 80" and not greater than 96" above the finished floor.
Ceiling Mount S/V Install Reference and Tile Bridge Dimensions
4" (102 mm) square, 1-1/2" (38 mm) deep box with 1-1/2" extension (by others)
Wiring input terminals and speaker tap selection are accessible from rear of speaker housing
Magnetic test location
LED indicator
Bottom view
Address DIPswitch is behind strobe assembly; select address before inserting into housing
Strobe intensity viewing slot
0
11
30
15
75
Intensity selection plug,
FACP
accessible only from rear of lens housing; factory setting is FACP, controlled by panel
Magnet test location
1/2" (13 mm)
0.024" thick sheet metal, folded with 1/2" lip each side
3-3/4" (95 mm) square
cutout, centered on plate
1/4" diameter (6 mm)
holes, 4 places
13-3/8" (340 mm)
2905-9946
Tile Bridge
23-11/16"
(602 mm)
6-11/16"
(170 mm)
3 S4906-0006-7 5/2014
Page 4
TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference
Compatible Controller
4100ES with EPS+ or EPS Power Supply S4100-0100
4009 IDNAC Repeater S4009-0004
Data Sheet
Reference
Controller Output
IDNAC SLC
IDNAC SLC
Output Voltage
29 VRMS
(regulated)
Appliance Voltage Design Reference
23 VRMS
(with 6 VRMS drop)
S/V Specifications
Common Specifications (see page 2 for appliance dimensions)
Environmental 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C)
Connections
Installation Instructions 579-808
Terminal blocks for 18 AWG to 12 AWG (0.82 mm for in/out wiring
Speaker General Specifications
Input Voltage 25 or 70.7 VRMS, see Note 1 below Power Taps ¼, ½, 1, and 2 W
Frequency Response
Fire Alarm 400 to 4000 Hz
General Signaling 125 to 12 kHz
Speaker Output Ratings @ 10 ft (3 m) (see Note below)
Wattage Tap ¼ W ½ W 1 W 2 W
UL Listed Models, Reverberant Chamber Test, per UL 1480 76 dBA 79 dBA 82 dBA 85 dBA Wall Mount Models 4906-9251 and 4906-9253, Anechoic
Chamber Test, per ULC-S541 Ceiling Mount Model 4906-9257, Anechoic
Chamber Test per ULC-S541 * NOTE: Select taps as indicated to satisfy the ULC fire alarm applications requirement of 85 dBA minimum
Polar Dispersion Reference (per ULC-S541 Anechoic Chamber Testing)
25 VRMS Input 81.6 dBA 84.3 dBA 87.1 dBA* 89.7 dBA*
70.7 VRMS Input 80.9 dBA 84.1 dBA 87.3 dBA* 90.2 dBA*
77 dBA 80 dBA 83 dBA 86 dBA*
Attenuation Angle Attenuation Angle
-3 dB +/- 30° off-axis -6 dB +/- 55° off-axis
Strobe Specifications
Typical Operating Voltage Range
Flash Rate and Synchronized SLC Loading
Wall Mount Appliances
Ceiling Mount Appliances
Note: Speakers are for connection to conventional fire alarm audio circuits. Anechoic speaker output ratings are typically more
representative of actual installed sound output.
23 VRMS Current Ratings, for connection to
IDNAC Addressable SLCs
23 VRMS Current Ratings, for connection to
IDNAC Addressable SLCs
Candela Setting
23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating)
1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum 30 resistance between appliances
15 cd 30 cd 75 cd 110 cd
50 mA 75 mA 137 mA 190 mA
60 mA 92 mA 180 mA 240 mA
2
to 3.31 mm2); two wires per terminal
TrueAlert Strobe LEGACY Compatibility Reference
Compatible Controller
4100ES or 4100U with TrueAlert Power Supply S4100-0031
TrueAlert Addressable Controller (4009T) S4009-0003
Electrical Ratings Difference for Retrofit Applications
Voltage Range 17 VRMS to 31 VRMS, Special Application
Candela Setting 15 cd 30 cd 75 cd 110 cd
17 VRMS Current Ratings, use
when connected to TrueAlert Addressable SLCs per above
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4906-0006-7 5/2014
www.simplex-fire.com
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Wall
Appliances
Ceiling Mount
Appliances
Mount
Data Sheet
Reference
64 mA 98 mA 187 mA 253 mA
76 mA 128 mA 242 mA 328 mA
Controller Output
TrueAlert
Addressable SLC
Available Strobe
Intensity
15, 30, 75, and
110 cd
Appliance Voltage
Minimum
VRMS 4009 TPS, Remote TrueAlert Power Supply S4100-0037
17