Simplex 4603-9101,4100ES,4100U User Manual

UL, ULC Listed; FM, CSFM, 4603-9101 LCD Annunciator for and MEA (NYC) Approved* 4100ES and 4100U Fire Alarm Control Panels
Features
Remote LCD annunciator for use with Simplex® model:
4100ES and 4100U fire alarm control panels Legacy products 4100, 4120, and 4020 fire alarm control
panels, and 4100/4120 Universal Transponders
Information display features:
Maintained display of first alarm is available with
4100ES and with 4100U at software revision 11.11 or higher
Wide viewing angle, super-twist LCD technology with
green LED backlighting
Two lines of 40 characters each LED status indicators During battery backup, backlighting is disabled until
there is switch activity
Controls include:
Switches for system acknowledge, alarm silence, and
system reset
Four programmable control switches Lamp/LCD test
Wiring information:
RUI (Remote Unit Interface) communications require a
single twisted wire pair (see p. 3 for more information)
Separate wiring is required for 24 VDC control panel
power
Flush mount on standard electrical boxes
Options:
2975-9206, Surface mount box 4603-9111, Brushed stainless steel trim
UL Listed to Standard 864
Description
Remote Control and Annunciation is provided using
an 80 character, back-lit, alphanumeric display. Information is presented in clear, descriptive English language and includes: Point Status (alarm, trouble, etc.);
Alarm Type (smoke detector, manual station, etc.); Number of System Alarms, Supervisory Conditions, and Trouble Conditions; and a Custom Location Label.
Wiring. A single twisted wire pair provides serial RUI communications that also supports other Simplex serial annunciators on the same wire pair.
Multiple Indications. Alarm, Supervisory, and Trouble conditions are also indicated by dedicated LEDs and a tone-alert audible sounder. Each condition has a dedicated acknowledge push-button switch that silences the tone-alert but leaves the LED on until all conditions in that category are restored to normal. Switch operation is either globally or individually acknowledgeable, determined by the control panel operation.
S4603-0001-13 1/2016
System Accessories, LCD Annunciators
4603-9101 LCD Annunciator
Description (Continued)
Repeated operation of the appropriate acknowledge switch will scroll the LCD display showing activity in the sequence of occurrence. The tone-alert also pulses to indicate the operation of any of the push-button switches.
Consult local code requirements for guidance in determining applications and location of the 4603-9101 LCD annunciator.
Operation
System Controls. Notification appliances can be
deactivated by pressing the “ALARM SILENCE” switch. (Exact operation is determined by the host control panel such as visible appliances remaining on until system is reset.) Pressing the “SYSTEM RESET” switch restores the system to normal operation. When system activity is normal, the LCD displays the time, date, and “SYSTEM IS NORMAL.”
Control Switches. Four programmable “CONTROL” switches and associated LEDs are included. Typical applications include manual evacuation, door holder release bypass, and elevator capture bypass.
Keyswitch Enable. All switches on the annunciator are controlled by the “ENABLE” keyswitch with a key that is removable only in the disabled position. A brief lamp/LCD test is performed whenever the keyswitch is changed from enabled to disabled.
Battery Backup Operation. During battery backup, the LED backlighting is disabled to conserve battery power. When an annunciator switch is activated, the backlighting is automatically enabled. After approximately 30 seconds of inactivity, the backlighting will again be disabled.
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7120-0026:0179 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Product Selection
Model Description
4603-9101 Remote LCD Annunciator with beige trim
4603-9101CF
Remote LCD Annunciator with beige trim, with French keypad for Canada
4603-9111 Brushed stainless steel trim option
2975-9206 Matching surface mount box; ivory finish
2081-9044
Overvoltage protector; required where annunciator communications and power wiring exits and enters a building; refer to data sheet S2081-0016 for details
4603-9101 Operator Information
2 X 40 LCD READOUT, green LED
backlighted during normal conditions and abnormal operating conditions
FOUR PROGRAMMABLE (Yellow) LEDs,
each with pushbutton switch and custom labeling pocket
Refer to specifications on page 3 for additional details
SIX STATUS INDICATOR LEDs provide system status indications in addition to LCD information; LEDs flash to indicate the condition and then when acknowledged, remain on steady until reset; Fire Alarm and Priority 2 Alarm are red; System Supervisory, System Trouble, and Alarm Silenced are yellow; Power On is green
ALARM ACK/FIRE ALARM acknowledges a Fire Alarm condition and silences the panel and all annunciator tone-alerts
ALARM ACK/PRIORITY 2 acknowledges a Priority 2 Alarm condition and silences the panel and all annunciator tone-alerts
SUPV ACK acknowledges System Supervisory conditions and silences the panel and all annunciator tone-alerts
TROUBLE ACK acknowledges System Troubles and silences the panel and all annunciator tone-alerts
FIRE
ALARM
ALARM
ACK
PRIORITY 2
ALARM
ALARM
ACK
SYSTEM
SUPERVISORY
SUPV
ACK
SYSTEM
TROUBLE
TBL ACK
CONTROL ENABLE KEYSWITCH
controls all switch functions; key is removable only in disabled position
DISPLAY TIME
displays time of last occurrence of event
POWER
ON
ALARM
SILENCED
DISPLAY
TIME
list being displayed; or displays current time when viewing system status
ALARM
SILENCE
SYSTEM
RESET
information
SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal
ALARM SILENCE causes audible and visible notification appliances to be silenced (default operation, may be modified through panel programming for compliance with local requirements)
2 S4603-0001-13 1/2016
Loading...
+ 2 hidden pages