Simplex 4603-9101 User guide

Page 1
System Accessories, LCD Annunciators
UL, ULC Listed; FM, CSFM, 4603-9101 LCD Annunciator for and MEA (NYC) Approved* 4100ES and 4100U Fire Alarm Control Panels
Features
Remote LCD annunciator for use with Simplex® model:
4100ES and 4100U fire alarm control panels Legacy products 4100, 4120, and 4020 fire alarm control
panels, and 4100/4120 Universal Transponders
Information display features:
Maintained display of first alarm is available with
4100ES and with 4100U at software revision 11.11 or higher
Wide viewing angle, super-twist LCD technology with
green LED backlighting
Two lines of 40 characters each LED status indicators During battery backup, backlighting is disabled until
there is switch activity
Controls include:
Switches for system acknowledge, alarm silence, and
system reset
Four programmable control switches Lamp/LCD test
Wiring information:
RUI (Remote Unit Interface) communications require a
single twisted wire pair (see p. 3 for more information)
Separate wiring is required for 24 VDC control panel
power
Description (Continued)
Repeated operation of the appropriate acknowledge switch will scroll the LCD display showing activity in the sequence of occurrence. The tone-alert also pulses to indicate the operation of any of the push-button switches.
Consult local code requirements for guidance in determining applications and location of the 4603-9101 LCD annunciator.
Operation
System Controls. Notification appliances can be
deactivated by pressing the “ALARM SILENCE” switch. (Exact operation is determined by the host control panel such as visible appliances remaining on until system is
4603-9101 LCD Annunciator
reset.) Pressing the “SYSTEM RESET” switch restores
Flush mount on standard electrical boxes
Options:
2975-9206, Surface mount box 4603-9111, Brushed stainless steel trim
UL Listed to Standard 864
Description
Remote Control and Annunciation is provided using
an 80 character, back-lit, alphanumeric display. Information is presented in clear, descriptive English language and includes: Point Status (alarm, trouble, etc.);
Alarm Type (smoke detector, manual station, etc.); Number of System Alarms, Supervisory Conditions, and Trouble Conditions; and a Custom Location Label.
Wiring. A single twisted wire pair provides serial RUI communications that also supports other Simplex serial annunciators on the same wire pair.
Multiple Indications. Alarm, Supervisory, and Trouble conditions are also indicated by dedicated LEDs and a tone-alert audible sounder. Each condition has a dedicated acknowledge push-button switch that silences the tone-alert but leaves the LED on until all conditions in that category are restored to normal. Switch operation is either globally or individually acknowledgeable,
the system to normal operation. When system activity is normal, the LCD displays the time, date, and “SYSTEM IS NORMAL.”
Control Switches. Four programmable “CONTROL” switches and associated LEDs are included. Typical applications include manual evacuation, door holder release bypass, and elevator capture bypass.
Keyswitch Enable. All switches on the annunciator are controlled by the “ENABLE” keyswitch with a key that is removable only in the disabled position. A brief lamp/LCD test is performed whenever the keyswitch is changed from enabled to disabled.
Battery Backup Operation. During battery backup, the LED backlighting is disabled to conserve battery power. When an annunciator switch is activated, the backlighting is automatically enabled. After approximately 30 seconds of inactivity, the backlighting will again be disabled.
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7120-0026:0179 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
determined by the control panel operation.
S4603-0001-13 1/2016
Page 2
Product Selection
Model Description
4603-9101 Remote LCD Annunciator with beige trim
4603-9101CF
4603-9111 Brushed stainless steel trim option
2975-9206 Matching surface mount box; ivory finish
Remote LCD Annunciator with beige trim, with French keypad for Canada
Refer to specifications on page 3 for additional details
2081-9044
Overvoltage protector; required where annunciator communications and power wiring exits and enters a building; refer to data sheet S2081-0016 for details
4603-9101 Operator Information
2 X 40 LCD READOUT, green LED
backlighted during normal conditions and abnormal operating conditions
FOUR PROGRAMMABLE (Yellow) LEDs,
each with pushbutton switch and custom labeling pocket
FIRE
ALARM
ALARM
ACK
PRIORITY 2
ALARM
ALARM
ACK
SYSTEM
SUPERVISORY
SUPV
ACK
SIX STATUS INDICATOR LEDs provide system status
indications in addition to LCD information; LEDs flash to indicate the condition and then when acknowledged, remain on steady until reset; Fire Alarm and Priority 2 Alarm are red; System Supervisory, System Trouble, and Alarm Silenced are yellow; Power On is green
DISPLAY TIME
displays time of last occurrence of event
SYSTEM
TROUBLE
POWER
ON
ALARM
SILENCED
DISPLAY
TIME
list being displayed; or displays current time when viewing system status
TBL ACK
ALARM
SILENCE
SYSTEM
RESET
information
ALARM ACK/FIRE ALARM acknowledges a Fire Alarm condition and silences the panel and all annunciator tone-alerts
ALARM ACK/PRIORITY 2 acknowledges a Priority 2 Alarm condition and silences the panel and all annunciator tone-alerts
CONTROL ENABLE KEYSWITCH
controls all switch functions; key is removable only in
SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal
disabled position
SUPV ACK acknowledges System Supervisory conditions and silences the panel and all annunciator tone-alerts
ALARM SILENCE causes audible and visible notification appliances to be silenced (default operation, may be
TROUBLE ACK acknowledges System Troubles and silences the
modified through panel programming for compliance with local requirements)
panel and all annunciator tone-alerts
2 S4603-0001-13 1/2016
Page 3
4603-9101 LCD Annunciator Specifications
For additional information, refer to Installation Instructions 579-979.
General Operating Specifications
Voltage 18 to 32 VDC, system supplied
Normal Operating Current 110 mA (with LED backlighting on)
Battery Standby Current
Alarm Current 140 mA maximum (LED backlighting is on and tone-alert is sounding)
Operating Temperature Range 32° to 120° F (0° to 49° C)
Operating Humidity Range Up to 93% RH, non-condensing at 100° F (38° C)
Communications
4100ES/4100U Capacity, Per RUI Output
Capacity
Wiring Requirements
Standard Wiring Type Unshielded twisted pair (UTP), 18 AWG (0.82 mm2) for most applications, see below
Wiring Characteristics
Wiring Applications
RUI Data
Power Wiring 18 to 12 AWG (0.82 mm2 to 3.31 mm2) wires for 24 VDC system power
Earth Wiring
Requiring Shielded,
Twisted Pair (STP)
Class B “T-Tap” wiring
distance
Class X wiring distance Up to 2500 ft (762 m)
65 mA (during battery backup, LED backlighting is turned off after 30 seconds without switch activity)
RUI (Remote Unit Interface) external annunciator communications line SLC (signaling
Type
line circuit)
Up to 31 remote annunciators/MINIPLEX transponders per channel including the 4603-9101 LCD Annunciator, the 4602-9101 Status Command Unit (SCU), and 4602-9102 Remote Command Unit (RCU); refer to data sheet S4100-0031 for additional 4100ES information
0.58 µF (580 nF) maximum capacitance between conductors; 35 maximum total line resistance
1. Wiring that leaves the building. Also requires Isolated Loop Circuit Protectors on each end, refer to data sheet S2081-0007 for 2081-9027 (200 mA), or S2081-0008 for 2081-9028 (5 A)
2. Wiring run in 500 ft (152 m) or more of conduit.
3. Wiring closely bundled with standard IDNet communications or TrueAlert addressable communications (not required when run with IDNet+ communications).
Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device
A dedicated earth ground connection to the electrical box is required for proper ESD and EMI protection; wire in accordance with NFPA 70 (National Electrical Code) Article 250
Mounting Information
NOTE: General Conduit Entrance
Requirement
Trim Dimensions 4 ½” H x 11 13⁄16” W (114 mm x 300 mm)
Standard Trim Finish Steel, painted beige
4603-9111, Optional Trim
Boxes for Flush Mounting (supplied by others)
Conduit entrance must be located a minimum of 2 ¾” (70 mm) from the front of the box to clear assembly
Brushed stainless steel (ordered separately); supplied with both slotted and tamper resistant screws
6-Gang, 3 ½” (89 mm) deep: RACO 965, 6-gang masonry box; RACO 590, gangable switch box, 6 required; or equal
2975-9206, Surface Mount Box Option (ordered separately)
Dimensions 11
Finish Painted steel, ivory finish
3 S4603-0001-13 1/2016
31
⁄32” W x 4 ” H x 2 ¾” D (304 mm x 117 mm x 70 mm)
Page 4
Mounting Information
Flush Mount Ganged Boxes:
Requires 6-gang box, 3-1/2" (89 mm) min.
depth, use (6) RACO # 590 or equal
(supplied separately)
Flush Mount Masonry Box:
Use RACO # 965, 3-1/2" (89 mm) deep
or equal (supplied separately)
Surface Mount Box:
Simplex model 2975-9206
2-3/4” deep (70 mm)
(ordered separately)
LCD Annunciator Assembly
Trim plate
Terminal block
access at rear of
assembly, this side
Note: Review box choice with assembly layout before selecting conduit entrance location to allow easy access to terminals
ALARM
ALARM
FIRE
PRIORITY 2
SYSTEM
SUPERVISOR Y
SUPV ACK
SYSTEM
TROUBLE
TBL ACK
ALARM
ALARM
ACK
ACK
POWER
ALARM
SILENCED
ON
ALARM
SILENCE
DISPLAY
SYSTEM
RESET
TIME
Wiring Reference
Wiring Notes:
1. Communications require a single 18 AWG twisted pair.
2. Power requires two, 18 to 12 AWG wires for 24 VDC system power, plus Earth Ground to each electrical box.
3. Refer to Installation Instructions 579-979 for additional wiring specifications.
FIRE
PRIORITY 2
ALARM
ALARM
ACK
ALARM
SYSTEM
SYSTEM
POWER
DISPLAY
TIME
SILENCED
ALARM
SUPERVISORY
TROUBLE
ON
SUPV
TBL
ALARM
ALARM
SYSTEM
ACK
ACK
ACK
SILENCE
RESET
FIRE
ALARM
ALARM
ACK
ALARM
PRIORITY 2
SYSTEM
SYSTEM
POWER
DISPLAY
TIME
SILENCED
ALARM
SUPERVISORY
TROUBLE
ON
SUPV
TBL
ALARM
ALARM
SYSTEM
ACK
ACK
ACK
SILENCE
RESET
4603-9101 LCD Annunciators
Fire Alarm Control Panel
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. National Electrical Code and NFPA are registered trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4603-0001-13 1/2016