4100U/TFX OPERATING INSTRUCTIONS FOR FIREFIGHTER’S AUDIO SYSTEM
_____________
____________________
_____
OPERATING MICROPHONE (MIC)
1. To make an announcement with the MIC:
TO ALL AREAS: Press ALL SPEAKERS TALK button.
TO SPECIFIC AREA: Press all desired Speaker Select buttons
TO AREA IN ALARM: Go to Step 2.
2. Remove MIC from enclosure and press MIC Talk Switch.
Turns off any active tone or message.
3. Wait for Ready to Talk LED to go ON.
4. Make announcement.
Releasing MIC Talk Switch restarts tone or message if alarm exists.
5. When finished, press the ALL SPEAKERS TALK button and all activated Speaker Select buttons. Replace MIC.
INITIATING EVACUATION SIGNAL
1. TO EVACUATE ALL AREAS: Press ALL SPEAKERS EVAC button.
TO EVACUATE SPECIFIC AREA: Press all desired Speaker Select buttons, and then press the SELECTIVE EVAC button.
2. To make an announcement with MIC, see OPERATING MICROPHONE (MIC) above.
3. Press ALL SPEAKERS EVAC or SELECTIVE EVAC button when finished.
SILENCING FIRE ALARM SIGNALS
Pressing ALARM SILENCE key silences evacuation/tone message and lights the ALARM SILENCED LED.
1. To silence alarm evacuation signals, press the
Main Panel’s ALARM SILENCE ke
USING LOCAL SPEAKER SWITCH
(Plays active tone/message on panel speaker)
1. Press LOCAL SPEAKER EVAC button.
2. When finished, press LOCAL SPEAKER EVAC button.
© 2003 Tyco Safety Products, Westminster, MA 01441-0001 USA
.
(SINGLE CHANNEL AUDIO)
YOUR SAFETY AND THE SAFETY OF THOSE AROUND YOU ALWAYS COMES FIRST.
Actions taken during a fire depend upon local practices. Be sure you know what to do.
These Instructions shall be framed and mounted adjacent to the control unit.
PHONE OPERATION
1. When remote phone is plugged in or remote handset is lifted.
Ring signal is heard on handset.
Phone LED flashes at panel.
Tone sounds at panel. (Press Phone Piezo
Silence to silence tone without picking up phone.)
2. Pick up master phone. To connect phone, press Phone Circuit Switch next to flashing LED.
Handset ring signal turns OFF.
Phone LED turns ON steady.
Tone turns OFF.
3. Use phone as required. Repeat Step 3 if another remote handset is lifted or phone is plugged in.
If necessary press the Phone Circuit button
selected in Step 2 again to put the phone on hold. Reconnect a phone on hold by pressing its Phone Select button again.
4. When finished, replace the phone on hook and press the Speaker Circuit buttons.
Note: Remote phone must be unplugged or remote handset replaced. If the remote phone is off hook more than 10 seconds, panel tone resounds and LED flashes.
RESETTING THE SYSTEM
1. When the alarm condition has been cleared, restore or replace all affected devices in accordance with the instructions provided with the device (smoke detector, motion sensor, etc).
2. Reset the system.
FIRE ALARM Condition. Press the <ALARM SILENCE> key and then press the <SYSTEM RESET> key.
PRIORITY 2 ALARM Condition. Press the
Priority 2 Reset key.
After a short delay the system returns to normal operation.
IN CASE OF TROUBLE NOTIFY:
NAME:________________________________________
TITLE: ________________________________________
ADDRESS: ____________________________________
PHONE:
579-702
Rev. C
Page 2
p
4100U/TFX OPERATING INSTRUCTIONS FOR FIREFIGHTER’S AUDIO SYSTEM
OPERATING MICROPHONE (MIC)
1. To make an announcement with the MIC:
TO ALL AREAS: Press ALL SPEAKERS TALK button.
TO SPECIFIC AREA: Press all desired Speaker Select buttons.
2. Remove MIC from enclosure and press MIC Talk Switch. Wait for Ready to Talk LED to go ON.
3. Make announcement and then release MIC Talk.
4. When finished, press the ALL SPEAKERS TALK button and all activated Speaker Select buttons. Replace MIC.
INITIATING EVACUATION SIGNAL
1. TO EVACUATE ALL AREAS: Press ALL SPEAKERS EVAC button.
TO EVACUATE SPECIFIC AREA: Press all desired Speaker Select buttons, and then press the SELECTIVE EVAC button.
2. To make an announcement with MIC, see OPERATING MICROPHONE (MIC) above.
3. Press ALL SPEAKERS EVAC or SELECTIVE EVAC button when finished. Turn off speakers by pressing all activated s
eaker select switches.
(DUAL CHANNEL AUDIO)
YOUR SAFETY AND THE SAFETY OF THOSE AROUND YOU ALWAYS COMES FIRST.
Actions taken during a fire depend upon local practices. Be sure you know what to do.
PHONE OPERATION
1. When remote phone is plugged in or remote handset is lifted.
Ring signal is heard on handset.
Phone LED flashes at panel.
Tone sounds at panel. (Press Phone Piezo
Silence to silence tone without picking up phone.)
2. Pick up master phone. To connect phone, press Phone Circuit Switch next to flashing LED.
Handset ring signal turns OFF.
Phone LED turns ON steady.
Tone turns OFF.
3. Use phone as required. Repeat Step 3 if another remote handset is lifted or phone is plugged in.
If necessary press the Phone Circuit button
selected in Step 2 again to put the phone on hold. Reconnect a phone on hold by pressing its Phone Select button again.
4. When finished, replace the phone on hook and press the Speaker Circuit buttons.
Note: Remote phone must be unplugged or remote handset replaced. If the remote phone is off hook more than 10 seconds, panel tone resounds and LED flashes.
SILENCING FIRE ALARM SIGNALS
Pressing ALARM SILENCE key silences evacuation/tone message and lights the ALARM SILENCED LED.
1. To silence alarm evacuation signals, press the Main Panel’s ALARM SILENCE key.
USING LOCAL SPEAKER ALERT SWITCH
1. Press LOCAL SPEAKER ALERT button.
2. When finished, press LOCAL SPEAKER ALERT button again.
USING LOCAL SPEAKER EVAC SWITCH
1. Press LOCAL SPEAKER EVAC button. When finished press button again.
These Instructions shall be framed and mounted adjacent to the control unit.
© 2003 Tyco Safety Products, Westminster, MA 01441-0001 USA
RESETTING THE SYSTEM
1. When the alarm condition has been cleared, restore or replace all affected devices in accordance with the instructions provided with the device (smoke detector, motion sensor, etc).
2. Reset the system.
FIRE ALARM Condition. Press the <ALARM SILENCE> key, and then press the <SYSTEM RESET> key.
PRIORITY 2 ALARM Condition. Press the Priority 2 Reset key.
After a short delay the system returns to normal operation.
IN CASE OF TROUBLE NOTIFY:
NAME:________________________________________
TITLE: ________________________________________
ADDRESS: ____________________________________
PHONE: ______________________________________
579-702