Fire detectors in the building are grouped into zones (searchable areas).
Zones can be Isolated by pressing the zone’s isolate pushbutton on the panel – this prevents an
alarm from activating the panel outputs.
When a non-isolated detector detects an alarm, the fire panel rings the bell, calls the fire brigade,
activates the Warning or Evacuation System and any other programmed functions.
The Fire Panel display consists of two sections – the Operator Interface (upper section) and the
Zone Isolate pushbutton switches & indicators (lower section).
The Operator Interface indicates common Alarm, Fault & Isolation Status on LEDs, and point
(detector) status on the LCD.
When an Alarm, Fault or Isolation occurs, the buzzer will operate until the corresponding
acknowledge (Ack) key is pressed.
Silence the Bell: Press the EXT BELL ISOLATE key.
Isolate signals to Evacuation System: Press the
WARN SYS ISOLATE key. This will turn off warning
sounders powered by the Fire Panel.
Isolate a Zone: Press the appropriate Zone Isolate
pushbutton and the Zone Isolated LED will turn on.
Acknowledge an Isolation: Press the ISOLATE ACK
key.
Acknowledge an Alarm: Press the FIRE ALARM ACK
key.
Acknowledge a Fault: Press the FAULT ACK key.
The panel is reset by pressing SYSTEM RESET. If the alarm won’t reset the point may still be
activated. Press FIRE ALARM ACK when the point alarm is displayed, then press DISABLE, ENTER.
Press FAULT ACK (to acknowledge the fault caused by disabling a point), then press SYSTEM RESET
again. The disabled detector must be re-enabled when the condition is cleared.
Operator Interface
Zone Isolate
Pushbuttons
Page 4
Manufacturer’s Details
Approvals
Manufacturer
Copyright and
Trademark
Information
Document
Australian Standard AS 4428.1, Control and Indicating Equipment. SSL Listing No. afp1682
The 4100U-S1 is manufactured by Tyco Safety Products for : Tyco Services, Fire & Safety
47 Gilby Road
Notting Hill
VIC 3168
AUSTRALIA
All specifications and other information shown were current as of document revision date, and are
subject to change without notice.
Tyco, Simplex, the Simplex logo, MAPNET II, IDNet, TrueAlarm, SmartSync, WALKTEST,
MINIPLEX, and TrueAlert are trademarks of Tyco International Services AG or its affiliates in the U.S.
and/or other countries. VESDA is a trademark of Vision Products Pty Ltd.
Simplex fire alarm technology is protected by the following U.S. Patent Numbers:
TrueAlarm analog smoke detection: 5,155,468; 5,173,683 and 5,543,777. IDNet and
MAPNET II addressable communications; 4,796,025. TrueAlert addressable notification;
6,313,744 and 6,426,697. SmartSync horn/strobe control; 6,281,789.
No part of this document may be reproduced or transmitted in any form or by any means, electronic
or mechanical, for any purpose, without the express written consent of Tyco Safety Products.
Document Number : LT0395
Cross Reference : 579-197
Issue : 1.0 13 February 2006
Firmware
Revision
Amendments
11.10
23 March 2006 LT0395 Issue 1.0 Original based on LT0351 1.0-C
ii
Page 5
Product/Site
If installed as per the Installation Manual this product complies with Class B limits of AS/NZS 3548.
Cautions &
Warnings
4100U-S1 Panel Supplied by:
Installation Location
Contract/Job Number
As installed, FIP System Drawing Number
Panel Installation Date
Panel Commissioned Date
Weekly Battery Test Day & Time
Maintenance Company
Telephone
Service Contract
Some of the operation of the 4100U-S1, as described in this manual, is dependent on
custom configuration as performed by the field engineer. If the configuration is not as per
the recommended template, then operation may differ and compliance to AS4428.0 may
be invalid.
The 4100U-S1 has a facility to allow levels of passcode protection. The operation of all the
standard functions as described in this manual is to be programmed to not require entry of
a passcode.
ZONE ISOLATIONS - The zone isolate status is not stored in non-volatile memory, so if the panel
is powered down and back up, or if the CPU is reset, all zones will be de-isolated.
iii
Page 6
Table of Contents
Approvals..................................................................................................................... ii
Manufacturer................................................................................................................ ii
Copyright and Trademark Information......................................................................... ii
Document .................................................................................................................... ii
Firmware Revision....................................................................................................... ii
Amendments................................................................................................................ ii
Product/Site ................................................................................................................ iii
Cautions & Warnings.................................................................................................. iii
This chapter provides an overview of the 4100U-S1 operator interface and describes the
normal appearance of the operator interface.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Typical Panel Layout 1-2
Basic System Description 1-3
Control Keys 1-6
Normal Appearance of Operator Interface 1-7
1-1
Page 12
Typical Panel Layout
A
Y
Overview
The 4100U-S1 is supplied with an Operator Interface plus one Expansion Bay in a 21U sized
cabinet.
The Zone Isolate modules are fitted into the Expansion bays from left to right. The first zone
is at the top of the leftmost module.
Operator Interface
lphanumeric display, Keypad,
Acknowledge & Control Keys.
Zone Isolate Modules
Red LED indicates alarm,
Yellow LED indicates isolation,
Pushbutton isolates & de-isolates
Isolate
Pushbutton
Red Alarm
LED
Figure 1-1. Zone detail
ellow
Isolate
LED
Fire Control
Emergency Operating Instructions
SYSTEM IS NORMAL
08:23:43 am MON 11-DEC-00
Figure 1-1. Typical Panel Layout
Ancillary
Controls
These are optional,
panel (site) specific
controls
1-2
Page 13
Basic System Description
Overview
Control Keys
& Indicators
The Simplex 4100U-S1 Fire Alarm Control Panel (FIP) has three general functions.
• It monitors fire alarm initiating points (smoke detectors, heat detectors etc.).
• It activates fire alarm notification devices (bells, strobes, brigade call) when an initiating
point activates.
• It monitors and controls ancillary building equipment (fan controls, relays, etc).
Note: The term point is used extensively throughout this manual. It is a generic
term used to refer to an individual component of the system, such as a single
smoke detector, a single break-glass manual call point, etc.)
The operator interface, shown in Figure 1-2, allows a system operator to control and monitor
the site-specific components connected to the 4100U-S1 FIP.
Entry
Keypad
Table 1-1. Components of the Operator Interface
LED/ Description Refer To
Zone Alarm LED
Control Keys
ALARMS
Fire Alarm LED
Fire Alarm Ack Key
Priority 2 Alarm LED and
Ack Key
Figure 1-2. Operator Interface
This LED flashes when any Zone
Alarm LED is on and the zone is not
isolated. It goes steady when all
zones in alarm are isolated.
Typical functions include: Alarm Test,
Fault Test, Bell Isolate, Warning
System Isolate & ACF Isolate.
The Fire Alarm LED flashes to
indicate the presence of an
unacknowledged alarm condition.
Other components of the system,
such as the horns and strobes, also
activate to indicate the presence of
an alarm.
The Fire Alarm Ack key allows you to
indicate that you have observed the
presence of an alarm.
Not normally used in Australia.
Chapter 1
Chapter 2
Chapter 2
N/A
Continued on next page
1-3
Page 14
Basic System Description, Continued
Overview,
(continued)
Table 1-1. Components of the Operator Interface (continued)
LED/Key Description Refer To
SYSTEM WARNINGS
Isolate LED and Ack Key
Fault LED and Ack Key
Alarm Silenced LED/Alarm
Silence Key
AC Power LED
System Reset Key
Event Time Key
Entry Keypad
Enable & Disable Keys
On/Off/Auto Keys
Arm & Disarm Keys
More Info.
Lamp Test
Menu / Next / Previous /
< / >
The System Warning LEDs –
Isolation and Fault – indicate when
abnormal, non-fire conditions occur.
When any zone is isolated, this LED
turns on and the buzzer sounds until
Isolate Ack is pressed.
When any fault occurs this LED turns
on and the buzzer sounds until Fault
Ack is pressed.
Not normally used in Australia
Indicates the presence of AC power
at the panel.
Pressing this key directs the panel to
reset all attached devices and clear
all acknowledged alarms, faults, and
isolation conditions.
Used to display the time at which an
acknowledged alarm, fault, or
isolation condition occurred.
Used to call up points for monitoring
and control.
Pressing these keys allows you to
enable or disable devices attached to
the panel.
Pressing these keys allows you to
force a device (such as a relay) ON
or OFF. The Auto key returns
control of the device to the panel.
Used with security points. These
keys allow you to turn security
devices on (arm) or off (disarm).
Used in some options to request
information.
Pressing this turns on all LEDs to
show that they operate.
Press the Menu key to display the
menu options on the LCD. Next &
Previous allow stepping through
options/events, < & > allow cursor
movement in the LCD.
Continued on next page
Chapter 3
Chapter 3
Chapter 3
N/A
N/A
Chapter 2
Chapter 2
Chapter 5
Chapter 4
Chapter 4
N/A
Chapter 9
Chapter 9
Chapter 5 on
1-4
Page 15
Basic System Description, Continued
Overview,
(continued)
Table 1-1. Components of the Operator Interface (continued)
LED/Key Description Refer To
Displays text describing abnormal
conditions for devices attached to the
Alphanumeric Display
Important Note: The degree to which you are allowed to control the system depends
on the passcode assigned to you. See Chapter 7 for details on this. Standard Fire
Fighter operations do not require logging in.
panel (e.g., smoke detector in main
lobby is in alarm). Also displays
system prompts and messages.
1-5
Page 16
Control Keys & Indicators
Overview
Control Keys &
The control keys and indicator LEDs are located on the far left of the Operator Interface.
A control key is pressed to perform the labelled function, and the associated LED turns on to
show the function is active. Pressing the key again de-selects the function and turns off the
LED.
• Zone Alarm - The red indicator is on when
there is an active (non-isolated) alarm in any
zone.
• Fault Test On – This indicator lights when
zone fault tests have been enabled by pressing
the ALARM/FAULT TEST key. When this
indicator is on, and a zone isolate key is
pressed, a fault test is performed on that zone.
• Alarm/Fault Test –This key cycles between
Alarm Test, Fault Test, and Normal for zone
test modes. The indicator lights when zone
alarm tests are enabled, the Fault Test On
indicator lights when fault tests are enabled,
and both these indicators are off when
alarm/fault tests are not enabled.
When this indicator is on, and a zone isolate
key is pressed, an alarm test is performed on
that zone. Any programmed outputs will
operate (including the Brigade signal). If the
zone was already isolated then the test will not
de-isolate it, i.e. the programmed outputs will
not operate.
• A/C Auto/Reset – The indicator lights when
the air conditioning system has been
automatically controlled by the 4100U.
Pressing the key will reset the air conditioning
system to normal operation.
• ACF Isolate – When this key is active, it
prevents ancillary controls: door holders,
security trips etc. from operating.
• Bell Isolate - When this key is active, it
prevents the fire alarm bell from operating.
• Warn Sys Isolate - When this key is active, it
prevents the Warning System from operating.
CAUTION: OPERATION OF THESE KEYS MAY CAUSE ALARM SIGNALS TO
SOUND OR FAULT CONDITIONS TO BE GENERATED BY THE SYSTEM.
These keys can be pressed at any time. The key feedback (beep on buzzer) and the LED
turning on/off may be the only acknowledgment of the action.
Figure 1-3. Control Keys &
LEDs
1-6
Page 17
Normal Appearance of Operator Interface
Description
The 4100U-S1 operator interface panel shows the following under normal conditions.
• Green AC Power LED is ON – indicating the panel is receiving AC Power.
• All other LEDs off.
• Alphanumeric display reports that the system is normal and shows the current time
and date, as shown below.
SYSTEM I S NORMAL
08:23:45 MON 18 - SEPT-0 0
Note: If the appearance of the operator interface is not as shown
above, refer to the information in Chapters 2 and 3 for instructions
on managing the alarm, fault, or isolate condition.
1-7
Page 18
1-8
Page 19
Chapter 2
Managing Alarm Conditions
Introduction
In this Chapter
An alarm condition occurs when an actuating device (such as a manual call point, smoke
detector, etc.) activates. The 4100U-S1 indicates the presence of the alarm condition through
messages it displays on the alphanumeric display, by illuminating the ALARM indicator
LEDs, and by activating the building’s EWS and external bell.
This chapter describes using the Operator Interface Panel keys to investigate and manage
alarm conditions.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Acknowledging Alarms 2-2
Isolating (Silencing) the EWS or External Bell 2-4
Isolating ACF Outputs 2-5
Resetting Air Conditioning Control 2-6
Displaying Event time 2-7
Resetting Points 2-8
2-1
Page 20
Acknowledging Alarms
What the System
Does When an
Alarm Occurs
When the first alarm condition is detected by the 4100U-S1, the panel does the following to
indicate the presence of the alarm.
• Red Fire Alarm and common Zone Alarm LED indicators flash
• Red Zone Alarm LED flashes on the display module showing the affected zone.
• Sounder (buzzer) pulses
• Emergency Warning System (EWS) and External bell activate
• Alphanumeric display on the operator interface shows the location and type (smoke, call
point, etc.) of the point in the alarm condition. An example is shown in
Figure 2-1.
• Any programmed outputs, including the Brigade connection, operate.
The first step in managing an alarm condition is to acknowledge the alarm. Acknowledging
an alarm does two important things:
• It records the time and date at which you observed the presence of the alarm and stores
that information in the system’s historical log.
• If multiple alarms are present, the system displays specific data for the next alarm when
you press the <FIRE ALARM ACK> key.
2-2
Page 21
Acknowledging Alarms, Continued
Procedure
Use the following procedure to acknowledge alarm(s).
1. Unlock and open the enclosure door. Read the alphanumeric display . It alternates
between the display shown in fig 2.1 & the summary shown below.
* * * ALARM* * * Press < FI RE ALARM ACK> to review .
ALARMS = 1 I SOLATED = 0 FAULT = 0
2. Press the <FIRE ALARM ACK> key. Pressing the ACK key causes the following to
occur:
• Buzzer silences
• Fire Alarm indicator changes from flashing to steady ON. Note that the Zone
Alarm indicator continues to flash until the zone is isolated or reset.
2-3
Page 22
Isolating (Silencing) the EWS or External Bell
Overview
Isolating the EWS
Isolating the
External Bell
Isolating the Zone
When an alarm condition occurs, the building’s warning system activates to warn the
building’s occupants about the alarm condition. In addition, the external bell sounds to
indicate the location of the 4100U-S1 FIP. During maintenance or testing, these outputs can
be prevented from activating by isolating them before an alarm occurs. In a real alarm
situation, they should be left operating until Brigade personnel choose to turn them off.
While the alarm exists and the zone is unisolated, pressing the <WARN SYS ISOLATE> key
(control key) toggles the state of the warning system output.
The following occurs when the <WARN SYS ISOLATE> key is first pressed.
• Warning System Isolate indictor turns steady ON.
• The Emergency Warning System (EWS) turns OFF. If the EWS is a separate system (e.g.
EWIS), then you may have to manually reset the EWIS panel.
The occurrence of another alarm will not activate the EWS again until the warning system is
de-isolated. When the panel has been reset, leave the EWS de-isolated.
While the alarm exists and the zone is unisolated, pressing the <EXT BELL ISOLATE> key
toggles the state of the external bell output.
When the bell is sounding due to an alarm condition, pressing the < EXT BELL ISOLATE>
key once does the following
• EXT BELL ISOLATE indicator turns steady ON.
• The External Bell turns OFF.
The occurrence of another alarm will not activate the external bell again until it is de-isolated.
When the panel has been reset, leave the external bell de-isolated.
Note that pressing the Isolate key for every zone that is in alarm will turn on each
corresponding zone isolate LED and turn off all outputs activated by the zone being in alarm,
such as the warning system and external bell.
Note also that with a point or zone in alarm (e.g. by use of Alarm Test) the above function
Isolate keys can be used during testing to briefly turn on an output and check that it works.
2-4
Page 23
Isolating ACF Outputs
Overview
Operation
Restoration
The Ancillary Control Facility (ACF) consists of relay outputs which can be used to control
equipment which is not part of the 4100U-S1 fire alarm system, such as shutting down air
conditioning or returning lifts to a certain floor.
During maintenance or testing, these outputs can be isolated, to prevent unwanted annoyance
to the building occupants.
Press the ACF ISOLATE key once. The ACF ISOLATE indicator will light, and the Isolate
indicator above the Isolate Ack key will flash. The LCD will display a message:
ACF I SOLATE
PRESS < ACK> key to acknowledsge
Press the Isolate Ack key to acknowledge that the ACF is isolated.
Note that isolation takes effect immediately from pressing the ACF ISOLATE key, not from
when the Isolate Ack key is pressed.
Press the ACF ISOLATE key once. The ACF ISOLATE indicator goes out.
Note: If there are any alarm conditions still active, the ACF outputs will operate as
programmed, e.g., shutdown equipment.
2-5
Page 24
Resetting Air Conditioning Control
Overview
Indication
Resetting
The Ancillary Control Facility (see previous section) is used to control building air
conditioning systems during a fire alarm.
During the management of the alarm, it is often desirable to be able to delay restoring the air
conditioning system to normal operation, e.g., to clear smoke even after the alarm conditions
have been cleared.
The A/C RESET control allows this delayed restoration.
When a zone alarm occurs, among the other alarm indications, the A/C AUTO indicator lights
to show that the 4100U-S1 has taken control of the air conditioning system. This operation
remains in effect even after all alarms have been cleared and the 4100U-S1 system has been
reset and is back to normal.
Before the A/C AUTO operation can be reset, all alarms must be acknowledged, and the
system must be reset via the System Reset key.
Once the system reset is complete, and there are no alarms present, the A/C AUTO RESET
key can be pressed to restore the air conditioning system to normal operation.
2-6
Page 25
Displaying Event time
Procedure
1. Select the point by repeatedly pressing the <ALARM ACK> key (for a point in alarm),
<FAULT ACK> (for a point in fault), or <ISOLATE ACK> (for an isolated point) until
the desired point is displayed.
2. Press the <EVENT TIME> key. The time and date that the point entered that state will be
displayed.
2-7
Page 26
Resetting Points
Overview
Reset Procedure
The Alarm state and some Fault conditions latch within the panel so they can be
acknowledged and viewed. When the latched states are no longer required they can be reset.
The condition that caused each point to go into alarm must be cleared before the system can
reset to the normal state, (e.g. smoke cleared from smoke detectors, glass replaced in manual
call point).
Press the <SYSTEM RESET> key. What happens next depends on whether all alarm
conditions are clear or not, as follows:
• If all Alarm Conditions are Clear, the system outputs two messages. One
indicates that the system is processing the action. This message is followed by a
message stating, “No Alarms Present - System Reset Complete.” If the individual
acknowledge option is enabled on the system, you may also need to acknowledge the
alarm again when it clears.
• If any Alarm Condition is Not Clear, the system attempts to reset the point for
25 seconds. During this interval, it displays a message that reads, “System Reset in
Progress”. If the point fails to clear, the system displays a message that reads
“Alarms Present – System Reset Aborted”.
Note: If this occurs, you must clear (fix) the condition that is causing the
alarm or disable the point from the panel. Refer to “Disabling a Point” in
Chapter 4 for information on doing this.
2-8
Page 27
Chapter 3
Managing Fault and Isolate Conditions
Introduction
In this Chapter
Fault conditions are used to indicate something wrong, e.g. the presence of a field wiring
problem (circuit break, short or ground), somewhere between the 4100U-S1 and one of its
points. Faults are also used to indicate a problem with the 4100U-S1’s option cards, power
supplies, network card, etc.
Note that disabling a point introduces a fault condition into the system.
Isolate conditions exist when one or more zones have been manually isolated by an operator,
e.g. to prevent a false alarm when maintenance work (e.g. building repairs, welding) is being
done in an area.
This chapter describes using the operator interface keys to investigate the details of the fault
condition, and to view isolate conditions.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Acknowledging Fault or Isolate Conditions 3-2
Viewing Fault or Isolate Conditions 3-4
3-1
Page 28
Acknowledging Fault or Isolate Conditions
How the 4100U-S1
Indicates the
Presence of a Fault
When a fault or isolate condition is detected by the 4100U-S1, the operator interface does the
following:
• The yellow “FAULT” or “ISOLATE” indicators flash
• The sounder (buzzer) sounds steady
• The alphanumeric display on the interface panel indicates the fault or isolate condition, as
The first step in managing a fault or isolate condition is to acknowledge the condition.
Acknowledging a fault or isolate condition does two important things:
• It records the time and date at which you observed the presence of the condition and
stores that information in the system’s historical log.
• When you press the <FAULT ACK> or <ISOLATE ACK> key, the system displays
specific data on the location of the condition. (In the case of Isolate it gives confirmation
on the LCD that you have isolated the correct zone).
It is important to understand that the 4100U-S1 can be configured with either Global or Individual Acknowledge. These options function as follows:
• Global Acknowledge. When global acknowledge is enabled, one press of the
<FAULT ACK> key acknowledges every point that is currently reporting a fault
condition. Similarly for <ISOLATE ACK>.
• Individual Acknowledge. If individual acknowledge is enabled, the <FAULT ACK>
key must be pressed repeatedly to individually acknowledge each fault condition.
Similarly for <ISOLATE ACK>.
.
Continued on next page
3-2
Page 29
Acknowledging Fault or Isolate Conditions, Continued
Panel Operating
Procedure – Fault
Condition
1. Unlock and open the panel door. The yellow Fault indicator (LED) will be flashing and
the sounder (buzzer) sounding. The alphanumeric display shows a message similar to the
following. (This example shows a fault. The screen for isolate conditions is similar).
2. Press the <FAULT ACK> key. The manner in which the system responds depends on
whether global or individual acknowledge is enabled on the panel.
• Global Acknowledge. The panel acknowledges all faults that are currently active,
displays the message “Global Acknowledge” for approximately two seconds, turns
off the sounder, and changes the FAULT indicator from a flashing state to ON
steady.
• Individual Acknowledge. The panel acknowledges only the fault that is currently
displayed on the alphanumeric display. If additional faults remain, the sounder does
not turn off and the FAULT indicator continues to flash. Use the <NEXT> and
<PREVIOUS> keys to display information on the other faults and then use the
<FAULT ACK> key to acknowledge them.
The sequence is the same for Isolate.
* * FAULT* * Press FAULT ACK to review.
ALARMS = 0 FAULTS = 1 I SOLATES = 0
Resetting Fault
Conditions
Most faults automatically clear from the system when the problem causing the fault (wiring,
device, etc.) has been fixed. Some faults, such as open circuit faults on IDNet
communications lines, latch until they are reset manually or cleared by pressing the
<SYSTEM RESET> key once the fault condition has been fixed.
3-3
Page 30
Viewing Fault or Isolate Conditions
Overview
You can view the list of acknowledged fault or isolate conditions at any time by using the
following procedure.
1. Press the <FAULT ACK> or <ISOLATE ACK> key to enter the fault or isolate list. The
first fault or isolate condition in the list appears in the display. The top line indicates the
custom label of the point. The bottom line contains two parts. The left side of the bottom
line shows the type of device. The right side of the bottom line identifies the type of
condition, fault or isolate.
2. At this point, each time you press the <FAULT ACK> or <ISOLATE ACK> key, the
next point in the list appears. You can also use the <NEXT> or <PREVIOUS> keys to
step through the list.
3-4
Page 31
Chapter 4
Testing and Controlling Points
Introduction
In this Chapter
This chapter describes using the panel’s action keys (ALARM TEST, On, Off, etc.) to test and
control system zones and points.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Alarm and Fault Test for Zones 4-2
Isolating and De-isolating 4-3
Disabling and Enabling Points 4-4
Turning a Point ON or OFF 4-5
4-1
Page 32
Alarm and Fault Test for Zones
Alarm Test
Fault Test
Alarm Test forces a zone into the alarm state. Once the zone is in alarm, you can check to see if
the system reacts in the way that it has been programmed (i.e., do signals sound in the correct
manner? do relays function correctly? etc.).
Note: When you force a zone into alarm if the zone is not isolated then any outputs that
are programmed to activate on alarm will activate, including Brigade signalling.
Follow these steps to perform an alarm test on a zone.
1. Press the <ALARM/FAULT TEST> key (on the Control Keypad until “ALARM TEST
READY” is displayed). The ALARM TEST LED will turn on.
2. While the ALARM TEST LED is on, press and hold the appropriate <ZONE ISOLATE>
key. The red Zone Alarm LED will turn on while the button is pressed.
Note: The Alarm Test function is cancelled if the Alarm/Fault Test key is pressed again,
or after 1 minute of no testing.
The fault test allows you to simulate a fault condition on a zone. This allows you to test the
manner in which the FIP reacts to the fault. For example, you may want to verify the operation
of the brigade interface.
Note: When you force a zone into fault if the zone is not isolated then any outputs that
are programmed to activate on fault will activate, including Brigade signalling.
Follow these steps to perform a fault test on a zone.
1. Press the <ALARM/FAULT TEST> key (on the Control Keypad) until “FAULT TEST
READY” is displayed on the LCD. The FAULT TEST LED will turn on.
2. While the FAULT TEST LED is on, press and hold the appropriate <ZONE ISOLATE>
key.
Note: The Fault Test function is cancelled if the Alarm/Fault Test key is pressed again,
or after 1 minute of no testing.
4-2
Page 33
Isolating and De-isolating Zones
Overview
Isolating a Zone
De-Isolating a Zone
This section describes isolating and de-isolating zones. Isolating a zone does not prevent any of
the points within the zone from going into the alarm state, but does prevent the activation of any
outputs that are programmed to operate when the zone is in alarm.
Pressing the <ISOLATE> key on a Zone Isolate module toggles the Isolate status. I.e., if the
state of the zone is de-isolated, pressing the key isolates the zone. Likewise, if the state of the
zone is isolated, pressing the key de-isolates the zone.
A zone is isolated by pressing the appropriate Zone Isolate key on the Zone Isolate Module. Zone
Isolate modules are located below the Operator Interface. Each Zone Isolate Module supports 8
zones.
1. Press the ISOLATE key so that the Zone Isolate LED turns on. (Do not hold the key down).
2. Press the <ISOLATE ACK> key to acknowledge the isolate operation.
Zones are de-isolated by pressing the appropriate Zone Isolate key on the Zone Isolate Module.
1. Press the ISOLATE key so that the Zone Isolate LED turns off.
2. If individual acknowledge operation is selected, press the <ISOLATE ACK> key to
acknowledge the de-isolate operation.
4-3
Page 34
Disabling and Enabling Points Disabling and Enabling Points
Overview
Disabling a
point
Situations such as a malfunctioning detector causing false alarms, or an activated detector that
prevents the system from being reset, can be temporarily overcome by disabling that particular
point. Disabling a point allows the system to be reset while repairs are being made. It takes the
point “offline”. Disabling a point prevents the point from entering an alarm condition for the
duration of time it is disabled.
Follow these steps to disable a point.
1. Select the point that you want to disable. Refer to Chapter 5 for information on
selecting points.
2. Press the <DISABLE> key.
3. Press the <ENTER> key.
The system generates a fault condition and message, indicating that the point is disabled.
Note: To disable a point that is in alarm, press the <ALARM ACK> key until the desired
point is displayed, then press the <DISABLE> key and the <ENTER> key.
Enabling a
point
Follow these steps to enable a point.
1. Select the disabled point that you want to enable, e.g. by repeatedly pressing the
<FAULT ACK> key until the desired point is displayed.
2. Press the <ENABLE> key.
3. Press the <ENTER> key.
Note: The system displays a message indicating that the point will be enabled in 60
seconds. If the state of the device is such that an alarm condition will occur when the
point is enabled, the system warns you that this will occur. You can abort the enable
operation before the countdown timer expires by pressing the <DISABLE> key.
4-4
Page 35
Turning a Point ON or OFF
Overview
Turning a Point
OFF
It may be necessary during maintenance of the system to turn the outputs (for example
notification devices and relays) off.
Turning an output point off is effectively isolating that output. Once turned off, the output will
not turn on, even if an alarm condition that is programmed to turn it on, occurs. After the
maintenance it is necessary to return the output to automatic control.
Turning an output point on forces the output to activate, even if there is no condition present that
is programmed to turn it on. Some control points (e.g. Sonalert (buzzer) Inhibit, see below) are
normally off, and may be turned on to perform a function. These must later be restored to “off”,
not “auto“.
1. Select the output point that you want to turn off. Refer to Chapter 5 for information on
selecting points.
2. Press the OFF key.
3. Press the <ENTER> key to confirm the operation.
Turning an output point on or off generates a “Manual Override Fault,” which is used to remind
you that the point has been manually turned on or off. You have to acknowledge the fault by
pressing the <FAULT ACK> key.
Turning a Point
ON
Returning a Point to
Automatic Operation
Sounder (buzzer)
1. Select the output point that you want to force ON. Refer to Chapter 5 for information on
selecting points.
2. Press the ON key.
3. Press the <ENTER> key to confirm the operation.
Turning an output point on or off generates a “Manual Override Fault,” which is used to remind
you that the point has been manually turned on or off. You have to acknowledge the fault by
pressing the <FAULT ACK> key.
When you are ready to return the point to automatic operation (i.e., the system, not the operator,
controls the point), you need to select the point, e.g. by repeatedly pressing <FAULT ACK>
until the point is displayed, then press the <AUTO> key and the <ENTER> key.
A loud buzzer is used in the Australian 4100U-S1 to meet the requirements of AS4428 (70dB at
1m with the door closed).
If doing testing or maintenance on the system with an operator at the panel, the buzzer may be
inhibited by turning point P198 on.
Note that the point must be turned off when the panel is to have its door closed.
4-5
Page 36
Page 37
Chapter 5
Selecting Points for Status or Control
Introduction
In this Chapter
Many of the operations that can be accomplished from the operator interface first require you to
select the point on which you want to perform the operation. Points can be selected in one of three
ways.
• Alarm, Fault, or Isolate List. Points that are reporting an alarm, fault or isolate condition
can be selected from the alarm, fault or isolate list by repeatedly pressing the <ALARM
ACK> key (for a point in alarm), <FAULT ACK> (for a point in fault), or <ISOLATE
ACK> (for an isolated point), until the desired point is displayed.
• Using the Menu.
• Using the Entry keys.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Selecting Points from the Menu 5-2
Selecting Points with the Entry Keypad 5-3
5-1
Page 38
Selecting Points from the Menu
A
Overview
Procedure
Every system point is part of the “Select a List of Points” list in the main menu. All points can be
displayed sequentially by address order using this list option. To facilitate a search for a particular
point, lists may be selected by point category (monitors, signals, auxiliary, input/output, pseudo
points, etc.). A list of points may be selected, then scrolled through by using the <NEXT> and
<PREVIOUS> keys.
The following lists are available for selection from the “Select a List of Points” option from the
Main Function Menu:
• All Monitor Points
• All Signal Points
• All Auxiliary Relay Points
• All Auxiliary Feedback Points
• All Zones of 24-Point I/O Card
• All Digital Pseudo Points
• All Analogue Pseudo Points
• All List Pseudo Points
• All Points by Address List
• All Network Points.
1. Press the <MENU> key to enter the panel’s menu system.
2. Press the <NEXT> key until the alphanumeric display reads as follows:
3. Press <ENTER>. The display reads as follows:
4. Press the <NEXT> key to scroll through the categories of points until the appropriate category
is shown. Press the <ENTER> key. The first point in the selected category appears. In the
example below, the point shown is the first one in the monitor zone category.
5. Press the <NEXT> key to scroll through the list of points in the category. When the point that
you want to select is displayed, press <ENTER>.
Press < NEXT> or < PREVI OUS> to scroll
Select a List of Points?
Press < ENTER> to select a list of point s
ll Monitor Zones?
MONI TOR CARD 1 ZONE NUMBER 1
FI RE MONI TOR ZONE NORMAL
5-2
Page 39
Selecting Points with the Entry Keypad
Overview
Selecting Points
The Entry Keypad, shown below, allows you to quickly select points. For example, pressing the
ZONE key on the upper left side of the keypad selects the monitor zone category. After selecting
a category, messages on the display prompt you for the specific point in the category. After a
point has been displayed, you can scroll through all the points in the system from that point, or
select another point directly by entering another identifier using the keypad.
You can use the keypad to select either a local point or a network point. A local point is one that is
physically connected to the panel you are currently at, and a network point is one that is located on
a different panel but has been programmed so that it can be selected and controlled from the panel
you are at.
There may be several ways of selecting a point. For a point associated with a card, e.g. a device
on an IDNet loop, you can use the Address key <ADDR> to first enter the card address, then enter
the point number. If you know the full loop address, then use the IDNet key. The format for
entering a point identifier address requires a hyphen between levels For example, a module with
address 12 on IDNet loop 4 may have two sub-points. The address of sub-point 2 is IDNet 4-12-2.
Only numbers and the hyphen keys are valid entries. The maximum number of digits allowed in
an identifier input is eleven (11), including the hyphens, excluding the <ENTER> key. See the
following table for other examples.
Refer to the following table for information on using the keypad to select local points on this
panel.
Figure 5-1. Numeric Keypad
Press this Key on Keypad Data to Enter
<ZONE>, followed by <ENTER>, where ZONE
ZONE – allows you to select a
Monitor Zone point.
represents a zone card and is a number from x to
y. After selecting a zone, use <NEXT> and
<PREVIOUS> to scroll through the points.
<SIG>, followed by <ENTER>, where SIG
SIG – allows you to select a
Signal point.
represents a signal card and is number from x to y.
After selecting a signal card, use <NEXT> and
<PREVIOUS> to scroll through the signal points.
Continued on next page
5-3
Page 40
Selecting Points with the Entry Keypad, Continued
Selecting Points,
(continued)
Press this Key on Keypad Data to Enter
AUX – allows you to select an
Auxiliary Relay
FB – allows you to select a
feedback point.
IDNet –allows you to select an
IDNet, Mapnet or VESDA
point.
P / A / L – allows you to select
a digital (P), analog (A), or List
(L) pseudo point.
NET – allows you to select a
network point.
ADDR = sw address of the
card in the system.
<AUX>, followed by <ENTER>, where AUX
represents an auxiliary relay and is a number from x
to y.
<FB>, followed by <ENTER>, where FB represents
a feedback point and is a number from x to y.
<IDNET> followed m-dd, followed by <ENTER>,
where m represents the IDNet channel number and
dd is the device address. For example, to select
point M1-13, you would press the IDNet key and
then enter 1 (channel). Next press the <-> key to
enter the dash, and then press the 1 and 3 keys to
enter 13 (device number).
Note 1: Although the <IDNET> key is pressed, the
LCD displays M (for MAPNET).
Note 2: New multipoint IDNet devices use sub-point
addressing. These sub-points are
addressed as c-dd-s, where s is the sub point. Example: A FRIAM device has a
relay at sub-point 1 & an input at sub-point
2.
Enter the number corresponding to the digital
pseudo, analog pseudo, or list point. For example,
pressing the <P> key then <2>, <ENTER> selects
the Lamp Test Key pseudo point.
Enter a network node number, followed by
<ENTER>. The system then prompts for the type
of point you want to select. Press the keypad key
corresponding to the type of point (Zone, Signal,
etc.) Use the descriptions above for information on
selecting the specific point.
For example, to select zone 3 on node 2, you would
press the <NET> key, <2> then <ENTER>. Next
press <ZN> (key 1), <3> then <ENTER> for zone 3.
Specify the address using the format c-p-s, where c
is the card, p is the point, and s is the subpoint.
You must insert the dash between the components
of the address. Use the <-> key to do this.
For example, to select address 0-7-3 (Brigade
Alarm Relay), you would press the <ADDR> key.
<ADDR> <0> <-> <7> <-> <3> <ENTER>
Note: System points are given a card address of
0. The first real card address is 1.
5-4
Page 41
Chapter 6
Displaying and Modifying
Detailed Point Attributes
Introduction
In this Chapter
This chapter describes displaying and modifying the attributes of a point.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Display-Only Attributes 6-2
Modifiable Point Attributes 6-4
6-1
Page 42
Display-Only Attributes
Select a Point
Points can be selected in one of three ways: through the alarm, fault, or isolate list, using the
MENU keys, or with the ENTRY keypad. Refer to Chapter 5 for information on selecting a
point.
See the Attributes
1. Press the <MORE INFO> key. When you do this, the alphanumeric display shows the
first attribute in the list. (The list is context-sensitive, meaning the list of attributes
displayed for a monitor point differs from the list of attributes displayed for an output
point, such as a relay.)
2. Press the <MORE INFO> key again. The next option in the list of attributes appears.
Continue to press the <MORE INFO> key (or use the <NEXT> and <PREVIOUS> keys)
until the option that you want to display is shown.
3. Press <ENTER> to see the detailed information for the attribute.
Summary of DisplayOnly Attributes
The following table summarizes the attributes available for display via the <MORE INFO>
key.
Table 6-1. Display-Only Attributes
Category Attribute Description
Displays the point address and zone number of the
Point address and Zone
number
selected Point. If the point’s status is monitored frequently,
record this address for use as a shortcut when
subsequently selecting the point. Refer to Chapter 5 for
information on selecting a point by address.
Displays the point type, which defines the specific function
Card Type and Point type
of the point, and the card type (for example, Class B MultiPurpose Monitor Card).
The present status of the point – Normal, Alarm, or Fault --
appears on the lower right of the display after you select a
point.
Indicates whether the point has been manually disabled
from the system.
Displays whether the Class A card is experiencing a fault
somewhere in the wiring between the card and its devices.
Displays the relay status for a control or signal point.
Status reports as “Relay Status is ON” or “Relay Status is
OFF”.
If the selected point is programmed for alarm verification,
displays the number of times the device has started, but not
completed an alarm verification cycle.
Not used in Australia.
Allows you to see the control priority for a relay. The
control priority is typically used with Custom Control.
General
Present Status (Normal,
Alarm, Fault)
Disconnect/Disable Status
Class A Fault (Status of
Class "A" Cards)
Relay status for Control or
Signal Points
Verification Tallies for AVF
devices.
Coding Status for Coded
Zones.
Control Priority for Relays
Feedback Point Status Shows the status – ON or OFF – for a feedback point.
Counts for Lists Indicates the number of points in a list.
Continued on next page
6-2
Page 43
Display-Only Attributes, Continued
Summary of DisplayOnly Attributes,
(continued)
Category Attribute Description
TrueAlarm
Sensors Only
(smoke, heat,
VESDA or 4-
20mA)
Present sensitivity selected Displays the current sensitivity of the device.
Average value Displays the average value recorded by the sensor.
Alarm value Displays the value required to trigger an alarm.
Current value (per cent of
Peak value (per cent of
Table 6-2. Display-Only Attributes (continued)
alarm)
Alarm)
Displays the current (real time) value.
Displays the maximum value reported by the device as a
percentage. Note that this is the maximum value reported
since the last time this counter was cleared.
6-3
Page 44
Modifiable Point Attributes
Overview
Select a Point
See the Attributes
Summary of
Modifiable Attributes
This section describes using the <MORE INFO> key to modify the attributes of a point.
Points can be selected in one of three ways — through the alarm, fault, or isolate list, using the
MENU keys, or with the ENTRY keypad. Refer to Chapter 5 for information on selecting a
point.
1. Press the <MORE INFO> key. When you do this, the alphanumeric display shows the
first attribute in the list. (The list is context-sensitive, meaning the list of attributes
displayed for a monitor point differs from the list of attributes displayed for an output
point, such as a relay.)
2. Press the <MORE INFO> key again. The next option in the list of attributes appears.
Continue to press the <MORE INFO> key (or use the <NEXT> and <PREVIOUS> keys)
until the option that you want to display is shown.
3. Follow the directions on the display to change the attribute. (The directions specify
which key – 1, 2, 3, or 4 -- to press to change the attribute.)
The following point attributes can be modified using the operator interface.
Table 6-3. Modifiable Attributes
Attribute Description
Card LED
Allows the state (ON or OFF) of the card LED to be
toggled.
Allows the state (ON or OFF) of an IDNet device LED
Device LED
(typically a smoke detector) to be toggled ON or OFF.
This can be very useful when two devices have been
set to the same point address.
Allows the control priority, which is a priority level used
with Custom Control to be incremented or
Control Priority Change
decremented. This option is available for all control
points – relays, notification appliances, TrueAlarm
devices with relays and sounders, and all digital
pseudo points. The priority is a value from 0-15.
Allows you to manually store a value for an analog
Analog Pseudo Point
Value and Status
pseudo point. The type of value stored depends on
the point type of the pseudo point (i.e., if the point type
is a counter, a counter value is stored; likewise, if the
point type is timer, a timer value is stored).
Allows you to manually clear alarm verification tallies.
Alarm Verification Tallies
for Monitor Points (Clear)
This is useful when attempting to determine how
frequently the system is going through the verification
cycles. Dirty devices are probable contributors to
frequent verification cycles.
Ground Fault Isolation
Relay
Allows you to manually turn on and off the GFI relay on
a card.
Continued on next page
6-4
Page 45
Modifiable Point Attributes, Continued
Summary of
Modifiable
Attributes,
(continued)
Table 6-4. Modifiable Attributes (continued)
Attribute Description
TrueAlarm Peak Analog
Values
Sensitivity (Alarm
Threshold)
Allows you to clear the peak value of a TrueAlarm
sensor.
Allows you to set the value at which the device goes into
alarm. The value can be any of the following.
• Sensitivity of smoke detectors
• Threshold of analog ZAMs
• Temperature of heat detectors
• Threshold of VESDA devices.
6-5
Page 46
Page 47
Chapter 7
Setting Access Levels and Logging In
Introduction
In this Chapter
This chapter describes setting the time and date on the system, logging in and out, and setting
access levels for use by system operators.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Operator Access Levels 7-2
Logging In and Out of the System 7-3
7-1
Page 48
Operator Access Levels
Overview
Operator access levels 1 through 4 are available to support the system. Level 1 is the lowest
operator access level and does not require a passcode to be entered to access functions
identified at this level. Level 2 through 4 require a passcode of the required level or higher to
be entered prior to performing the passcode protected functions. Controlling actions may be
classified with access levels 2 through 4. Routine actions are assigned to low access levels
while access level 4 is reserved for special, highly sensitive operations (normally reserved for
Simplex personnel). Entering a level 4 passcode enables you to access all the functions of the
system.
A valid passcode must contain a minimum of 3 digits and not more than 10 digits. The
available digits are 0 through 9. Passcodes are specified during order entry; then, programmed
during system configuration. When Passcodes are not specified, the following default
Passcodes are assigned.
LEVELPASSCODERANK
1 NONE LOWEST
2 222 SECOND
3 333 THIRD (Highest Operator Access Level)
4 XXX HIGHEST (used by Simplex trained Personnel)
The operator access level defaults to level 1 when power is first applied to the system, after 10
minutes of keypad inactivity, and when the user elects to log out. The <SYSTEM RESET> key
press has no effect upon the access level.
The only way to increase the operator access level in the system is to select the “Change Access
Level?” option in the Main Menu. Decreasing the level resets system access level to 1.
Increasing the level requires a valid level 2, 3 or 4 passcode. The user is prompted to enter a
passcode. The input is compared to all the valid system codes, and the system operator access
level is set accordingly. If an invalid code is input, you will be notified with the message
“ERROR. . . INVALID PASSCODE”, and will be allowed up to three chances to enter a valid
code. After three unsuccessful tries, the message “ACCESS DENIED” will be displayed for a
short time. The access level will not be altered, but you will no longer be in the “Change
Access Level” menu option.
If a correct passcode is entered, the message “ACCESS GRANTED” is displayed. The new
operator access level will be in effect until the keypad is inactive for 10 minutes or you
manually reset the level through the “Change Access Level” option. While entering a passcode
with the keypad, the key presses are acknowledged by a “beep”. The digits entered are not
displayed. The cursor moves along, filling the position with an X to indicate that a digit has
been entered. The <DEL> key can be used to delete the last digit. The <ENTER> key press is
required to enter the passcode into the system.
7-2
Page 49
Logging In and Out of the System
XXX
Introduction
Log In Procedure
The 4100U-S1 system uses four access levels, referred to by the numbers one through four, to
control what system operators can do with the system. The system typically operates at access
level one, which allows an operator to accomplish basic tasks without logging in to the system.
Other functions, for example certain control functions, may be passcode protected to prevent
access by unauthorized personnel.
Follow these steps to log in to the system at access level two, three, or four.
1. Obtain the passcode for the access level at which you want to operate.
2. Press the <MENU> key. The alphanumeric display shows the following message.
3. Press the <ENTER> key on the numeric keypad. The following message displays.
4. Press the 1 key on the Numeric keypad. The display shows the following message.
5. Enter the passcode for the access level. The passcode can be up to 10 numbers in length.
Press the <ENTER> key on the numeric keypad when you have finished entering the code.
An X is displayed for each digit of your passcode, as shown below.
Press < NEXT> or < PREVI OUS> to scroll
Change Access Level?
1 = Login 2 = Logout
CURRENT ACCESS LEVEL = 1
Enter a Passcode follow ed by < ENTER>
Enter a Passcode follow ed by < ENTER>
Continued on next page
7-3
Page 50
Logging In and Out of the System, Continued
Log In Procedure,
(continued)
Log Out Procedure
If the passcode entered in Step 5 is correct, the following message is shown.
After a brief pause, the system displays the granted access level, such as the level 2 message
shown below.
Press the <C/EXIT> key twice to exit out of the menu selections.
Failure to log out allows unauthorized personnel access to the various passcode protected
functions. If no keypad activity is detected for ten minutes, the system returns to Level 1
access.
Perform the following procedure to log out and return the operator access level to Level 1.
1. Press the <MENU> key. The following message is displayed.
2. Press the <ENTER> key. The following message is displayed.
Note: Logging in at access level 4 creates a non-clearable fault that requires the
system to be restarted (the CPU card is reset) to clear. This ensures that the system is
returned to its normal operating mode following service.
< ENTER> a Passcode follow ed by < ENTER>
ACCESS GRANTED
1 = Login 2 = Logout
CURRENT ACCESS LEVEL = 2
Press < NEXT> or < PREVI OUS> to scroll
Change Access Level?
1 = Login 2 = Logout
CURRENT ACCESS LEVEL = 2
Continued on next page
7-4
Page 51
Logging In and Out of the System, Continued
Log Out Procedure,
(continued)
3. Press the <2> key. After a brief pause, the display shows a message similar to the one
below.
4. Press the <C/EXIT> key twice to exit. The display shows the system status.
1 = Login 2 = Logout
CURRENT ACCESS REDUCED TO LEVEL 1
7-5
Page 52
Page 53
Chapter 8
Viewing and Clearing Historical Logs
Introduction
In this Chapter
When an abnormal condition occurs, a record of the event is placed in one of two logs
generated by the system, depending on the nature of the condition. These logs are:
• Historical Alarm Log
• Historical Fault Log
The historical logs contain a time stamp of the events surrounding abnormal conditions in the
system. The information displayed with these lists are historical data only and will not contain
any current point status. Separate lists are maintained for alarms and for isolates/faults. This
chapter describes displaying and clearing these lists.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Viewing and Clearing the Historical Alarm and Fault Logs 8-2
8-1
Page 54
Viewing and Clearing the Historical Alarm and Fault Logs
Viewing Logs
Clearing the
Logs
The Historical Alarm and Fault Logs can be viewed from the 4100U-S1 Operator Interface.
1. Press the <MENU> key.
2. Using the <NEXT> and <PREVIOUS> keys, scroll through the Main Menu items until
the "Display Historical Alarm Log?" or "Display Historical Fault Log?" menu prompt
appears on the alphanumeric display.
3. Press the <ENTER> key on the ENTRY keypad.
4. Using the <NEXT> or <PREVIOUS> keys scroll through the list of logged events, until
the desired event is shown on the display.
NOTE:Pressing the <PREVIOUS> key first, causes the most recent event to be
displayed.
5. When finished, press the <C/EXIT> key twice to escape from the main menu.
1. Press the <MENU> key.
2. Using the <NEXT> and <PREVIOUS> keys, scroll through the Main Menu items until
the "Display Historical Alarm Log?" or "Display Historical Fault Log?" menu prompt
appears on the alphanumeric display.
3. Press the <ENTER> key.
4. Press the <MORE INFO> key.
5. Press the 3 key to clear the log.
8-2
Page 55
Chapter 9
Service-Related Operations
Introduction
In this Chapter
This chapter describes service-related status and control procedures.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Setting Time and Date 9-2
Displaying Software Revision 9-3
Viewing Card Status Information 9-4
Displaying Network Node Information 9-5
Lamp Test 9-6
Displaying IDNet & Mapnet Device Status 9-7
9-1
Page 56
Setting Time and Date
Procedure
Follow these steps to set the time and date on the panel.
1. Press the <MENU> key. Press the <NEXT> or <PREVIOUS> key until the display
shows the option for setting the time and date.
2. Press the <ENTER> key. The system responds as follows:
3. Press the <MORE INFO> key. The display shows the time and date and places an
underline character under the hour, meaning it is the part of the time and date that can be
changed.
4. Set the time and date as follows:
• Time. Use the < and > keys to move the underline cursor between hours and
minutes. Use the <NEXT> and <PREVIOUS> keys to increment or decrement the
value. For example, to change the minutes, first use the < and > keys to move the
highlight cursor under the minutes field. Then use the <NEXT> and <PREVIOUS>
keys to change the value of the minutes field.
• Date. Use the < and > keys to move the underline cursor between the components of
the date field. Use the <NEXT> and <PREVIOUS> keys to increment or decrement
the value of the field until it is correct.
5. When the date and time are correct, press the <ENTER> key.
Press < NEXT> or < PREVI OUS> to Scroll
Set Time and Dat e?
Press < I NFO> to Change Time and Date
12:44:12 am WED 01-JAN- 0 0
12:44:12 am WED 01-JAN- 0 0
9-2
Page 57
Displaying Software Revision
Overview
Follow these steps to display software revision information.
1. Press the MENU key.
2. Press the <NEXT> or <PREVIOUS> keys until the prompt reads, “Display Software
Revision Level?”
3. Press <ENTER>. A display similar to the following appears.
• SYS REV. Specifies the revision of the executive software (operating system
of the FIP) loaded in the panel.
• CFIG FORMAT: Defines the compatibility of the executive and the
programmer.
• JOB: Specifies the name of the job loaded in the panel.
• REV. Specifies the revision of the job.
• DATE. Specifies the date on which the revision was built in the programmer.
9-3
Page 58
Viewing Card Status Information
Overview
Procedure
Power
Supply/Charger
Voltage and Current
Readings
Every card, including the Master Controller and all option cards, has a series of Card Status
Points associated with it. For the SPS (System Power Supply) these points include System
Voltage, System Current, Battery Voltage, etc.
1. Press the MENU key.
2. Press the <NEXT> or <PREVIOUS> keys until the prompt reads, “Display Card Status?”
3. Press <ENTER>. The general card status for the first card in the system appears
(typically SPS).
4. Press the <NEXT> or <PREVIOUS> keys to step through the cards. Each time you press
the key, the status for the next card in the system appears.
5. Press <ENTER> when the desired card is selected.
6. Step through the status points for that card using the <NEXT> or <PREVIOUS> keys.
To view the power supply voltage and current readings, perform the following procedure.
1. Press the <MENU> key. Then press the <NEXT> key until the alphanumeric display
reads:
Press < NEXT> or < PREVI OUS> to scroll
Display Card Status?
2. Press the <ENTER> key. Then press the <NEXT> key until the display reads:
CARD n, SYSTEM POWER SUPPLY
CARD STATUS NORMAL
3. Press the <ENTER> key. Then, using the <NEXT> or <PREVIOUS> key to scroll,
check voltage/current readings on the Power Supply/Charger card.
NOTES:
1. “n” = card number.
2. In most systems the SPS is the first card (card 1) so <NEXT> does not have to be
pressed.
3. The IDNet on the SPS is automatically at the next card number after the SPS.
9-4
Page 59
Displaying Network Node Information
Overview
Procedure
Network systems consist of multiple panels linked via a 4120 network. Each panel includes a
programmer-defined node number, used to identify the panel on the network. The following
section describes how to determine a panel’s node number. The node number is required
when selecting a network point. See “Selecting Points” in Chapter 5 for more information on
doing this.
1. Press the MENU key.
2. Press the <NEXT> and <PREVIOUS> keys until the prompt reads, “Display Network
Node Identification?”
3. Press <ENTER>. The display shows the network node information and indicates the
node number of the panel you are at with an asterisk (*).
9-5
Page 60
Lamp Test
Procedure
The “LAMP TEST” push-button on the Operator Interface is used to determine local lamp
(LED) failures within the system. LEDs on the 4100U-S1 Operator Interface and Switch/LED
Display Modules illuminate. All segments on the LCD also change to squares. Perform the
following procedures to determine LED or LCD failures.
1. Press the “LAMP TEST” push-button. All LEDs should illuminate (LEDs should stay
illuminated as long as the push-button is depressed). Holding the push-button in for more
than 3 seconds will test the buzzer.
2. Perform an individual lamp test on all remote LCD annunciators using the key switch on
the remote annunciator.
3. If you find defective lamps/LEDs, contact your local Tyco Service provider.
9-6
Page 61
Displaying IDNet & Mapnet Device Status
Introduction
IDNet Display
Information
IDNet Point
Addressing
The IDNet options allow the use of addressable devices and TrueAlarm sensors with the
4100U-S1 FIP. Addressable devices communicate the exact location of an alarm to the system
operator interface panel, improving recognition of the condition and subsequent response. It
also pinpoints the precise location of fault conditions via the device custom label. Throughout
this section, operations described for IDNet are also applicable for Mapnet.
When a IDNet device changes to an abnormal condition, or the operator enters a IDNet
device address, the LCD display shows the current status of the IDNet device. After entering a
IDNet device address, press the <MORE INFO> key on the operator interface panel to display
additional device information.
Each IDNet device must have a point address in order to communicate with the 4100U-S1
FIP. These point addresses along with their custom labels are located in the Programmers
Report. The Programmers Report shows the address for each device, separated by hyphens.
Hyphens must be used when entering a IDNet address into the system. An example of a
IDNet device address is "M1-5". The "M1" portion of the address identifies the IDNet loop or
channel , loop 1 or channel 1. The "5" portion of the address, identifies the device number,
number 5.
Note: New multipoint IDNet devices use sub-point addressing. These sub-points are
addressed as C-DD-S, where S is the sub-point. Example: A FRIAM device has a
relay at sub-point 1 & an input at sub-point 2 which would be accessed as M1-5-1 &
M1-5-2.
How to Display an
IDNet System Point
What To Do If an
IDNet Point Will Not
Reset
TrueAlarm Sensor
Display Values
See Chapter 5, "Selecting Points for Status or Control" for IDNet operations.
If an IDNet device will not reset, you may decide to disable the point with the <DISABLE>
key. When the disable procedure is performed, a System Fault occurs to remind you that the
point is disabled. The disable procedure is the same for all system points (see section 2, "How
to Disable a Point"). Maintenance personnel must be called immediately to repair the
malfunction.
After the IDNet point is repaired, you can enable the point again.
Using the 4100U-S1 LCD and the display/action keys, the control panel can display various
status conditions for each TrueAlarm sensor, the sensor's present selected sensitivity level as a
percent of obscuration per foot. This selected sensitivity level is the value at which the FIP
will cause an alarm condition. Seven (7) sensitivity levels are available for the TrueAlarm
photo-electric sensor. The most sensitive setting is 0.2% OBS/FT (0.5% OBS/M) with the
least sensitive setting being 3.7% OBS/FT (12% OBS/M).
Other individual sensor status conditions that can be displayed on the LCD display are shown
below. These displays are accessed by either entering an IDNet device number for a normal
device using <IDNET> key, or by pressing the <FAULT ACK> key for an abnormal device.
To display each of the categories the <MORE INFO> key and the <NEXT> and
<PREVIOUS> keys are used as shown below.
Displaying IDNet & Mapnet Device Status, Continued
TrueAlarm Sensor
Display Values,
(continued)
Press the <MORE INFO> key to obtain the next display:
Device Address: 3-1
I DNet Device: M1- 1
Press the <NEXT> key to obtain the next display:
1-Force on card LED Type: I DNet
I DNet CARD
Pressing key <1> will turn on the LED indicator on the IDNet Card in the FIP control rack and
pressing it again will turn the LED off. Press the <NEXT> key to move onto the next display.
1-Force on device LED Type: PHOTO
Variable Sensitivit y PHOTO
Pressing the <1> key will turn on the LED indicator on the selected smoke detector and
pressing it again will turn it off. Press the <NEXT> key to move onto the next display.
Level 3 - Room 74
Smoke Detector ON-LI NE
Press the <NEXT> key to move onto the next display to verify correct device type.
Level 3 - Room 74
Smoke Detector Correct Device
Press the <NEXT> key to display the current selected sensitivity.
Note: Sensitivity displayed is in % obscuration per foot.
%Obs/Ft %Obs/m %Obs/Ft %Obs/m
0.2% 0.6% 2.0% 6.5%
0.5% 1.6% 2.5% 8.2%
1.0% 3.3% 3.0% 9.8%
1.5% 5.0% 3.7% 12.1%
Table 9-1. Smoke Obscuration conversion chart.
Continued on next page
9-8
Page 63
Displaying IDNet & Mapnet Device Status, Continued
TrueAlarm Sensor
Display Values,
(continued)
To view the average value of samples received from the sensor press the <NEXT> key again.
Level 3 - Room 7 4
Average Value = 75 / Alarm Level = 135
This is the present average of the last 2048 samples received from the sensor. The Alarm
Level is the binary value that is used to determine alarm conditions. This value will change
over time as the panel compensates for environmental conditions. The alarm value will be
different for each of the (7) sensitivity levels.
To view the last binary value that was received from the sensor press the <NEXT> key again.
Level 3 - Room 7 4
Value = 75 / 6% of Alarm / 0.1% Smoke
This value is displayed as a % of alarm and a % of smoke obscuration per foot.
Press the <NEXT> key again to view the highest binary value that was received and stored
from the sensor since power-up .
1- Clear PEAK Value
PEAK= 1 06 / 5 1 % of Alarm / 1 .0 % Smoke
The peak is displayed as a % of alarm an a % of smoke obscuration per foot. Through the use
of a system pseudo point all new peak values per sensor can be stored in the history fault log
and printed on the 4100U-S1 system printer. Printing of peak values is done at the time the
peak value is received at the FIP. This peak value is helpful in determining if a sensor should
be made more or less sensitive.
9-9
Page 64
Page 65
Chapter 10
System Test Procedures
Introduction
In this Chapter
The following test features can be used when commissioning after the system is installed, and
during periodic testing as required by code. Refer to Chapter 12, Maintenance Procedures for
detail on these.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Walk Test™ 10-2
Walk Test™ FEATURES 10-5
Walk Test™ PROCEDURES 10-8
10-1
Page 66
Walk Test™
Overview
WalkTest
Group
™ by
Walk Test™ is a software-based function and is programmed to meet the customer
requirements. The system will pulse the signals for alarm conditions, then reset. The signals
will sound steady for 4 seconds to indicate fault conditions, then reset. A silent Walk Test™
may be performed (no signals will sound) and logging of events may be selected.
The auto reset/auto acknowledge operation allows for one-man testing without the need for
someone at the main control panel to acknowledge and reset the system. The Walk Test™
mode also bypasses many of the delays that are inherent to the normal reset procedure, thereby
allowing for a faster test. The automatic reset ( 5 second power drop) only occurs on the zone
that comes in after a configurable time delay (default = 15 seconds). This delay can be
optimally set (with the programming unit) for the time it should take for a zone to clear (i.e.
magnet vs smoke tester).
If an alarm condition is detected from a zone that is not in the present active Walk Test™
group, the system will operate as a fire alarm panel and the active Walk Test™ groups are
aborted. The system has an automatic abort or timeout for the Walk Test™ mode. If no zone
within the active Walk Test™ group is activated within 8 hours, the system will abort the
Walk Test™ mode and return to normal.
The 4100U-S1 will support up to eight Walk Test™ groups. This allows the building to be
divided into small portions for the Walk Test™, and allows the rest of the building to be
protected by the fire alarm panel. Each group has a list of output circuits which activate when
selected.
If you select the Walk Test™ by group mode, a system fault will be reported to remind you
that the Walk Test™ is enabled.
Whenever a Walk Test™ group is aborted, manually or automatically, the panel will sound
the abort signal (three sets of two short pulses) to indicate that group is going back into
service. If a control point in the list is already active (because of an abnormal condition), it is
not used to signal the abort.
The group is placed into normal operation 60 seconds after the abort signal is heard. This
delay protects against an unwanted alarm should an automatic abort occur while a device is
being tested.
The system is default-programmed to allow the Walk Test™ to be performed without
sounding audible signals. (See “Silent Walk Test™” and “Sig/No Sig”.) The Walk Test™
will not activate any point which is disabled. Therefore, you have the ability to manually
exclude any point from the test. (See How to Disable a Point.)
You may enable the logging of Walk Test™ events, which allows each zone with an abnormal
condition to be time tagged and added to the fault log. This is beneficial when a 100% silent
Walk Test™, without visuals, is required. When testing the devices, use the alarm LED on
the smoke detector, or a simple delay, to know when to continue to the next device. After test
completion, check the log to verify that all zones activated the correct number of times and in
the correct order.
Zone Coding Option
The system supports two types of audible signalling to indicate an alarm condition on a zone.
By default, “zone coding” is used. This code matches the “ZONE” number associated with
that point. The zone code is only used the first time a zone is reported. For subsequent alarms
on the same zone, a single “0 CODE” (two short pulses) is used. Examples of Zone Coding
are shown below.
Continued on next page
10-2
Page 67
Walk Test™, Continued
Zone Coding Option,
(continued)
Silent Walk Test
= Zone 3 (three long pulses)
= Zone 12 (one long, pause, two long pulses)
= Zone 20 (two long and two short pulses)
= Zone 102 (one long, two short, and two long pulses)
NOTE: Zero Code = 2 short pulses.
Zone coding may be disabled for each of the eight Walk Test™ groups, Group 0 through
Group 7, using the interface panel’s display. When zone coding is disabled (<F3> key to
ZERO), a “0” code is always used, even for the first alarm. This method of testing is more
appropriate for maintenance testing, once all wiring is verified.
When a control point is pulsed by Walk Test™, it is done without affecting the priority of that
point regardless of its present value. This guarantees that Walk Test™ does not interfere with
any required SMPL (software) operations during a real alarm.
®
IDNet
followed by the device’s address number. Example: M1-1 sounds a 1,1 code. M4-123
sounds a 4, 1, 2, 3 code. IDNet
monitor devices sound the zone code, with the first digit being the channel number,
®
signal devices cannot annunciate codes.
The control points to be activated (pulsed) during Walk Test™ are determined by the contents
of the control lists which are configured when programmed. Several options are available
when configuring a silent Walk Test™ control list. The first option is to NOT put any audible
signals into the control list. The second option is to disable the audible control points from the
front panel, one at a time. The last option is to use the “NO<sig” option (controlled by the
<F4> key) when in the Walk Test™ menu. If this last option is selected, none of the points in
the control list will code (see “Sig/No Sig”).
Enabling Walk Test
Walk Test™ is enabled through the interface panel’s alphanumeric LCD (Liquid Crystal
Display). Walk Test™ is passcode protected. The Walk Test™ menu will not appear unless
the operator is at the proper access level. To enter one of these levels, press the menu key,
select the “Change Access Level” option, press the <F1> key to log in, and then type in the
correct passcode for the level you desire.
Select the “Enable Walk Test™” option on the Main Menu, and press the <ENTER> key.
Then use the following keys (<1> through <4>) to select the various Walk Test™ options.
• <1> Key - Enables/disables the Walk Test™ group. Press this key to enter Walk Test™
for the specified group. Press the key again to exit Walk Test™.
• <2> Key - Enables/disables the logging of events occurring during Walk Test™. When
selected, all abnormal conditions are recorded in the historical fault log.
Continued on next page
10-3
Page 68
Walk Test™, Continued
Enabling Walk Test,
(continued)
Walk Test Operation
• <3> Key - Allows you to choose between Zone Coding and Zero Coding. In Zone Coding
a PNIS code for the tested zone is played (.e.g. Zone 12 is code 1-2). In Zero Coding, two
quick pulses (code 0) are heard. In both cases, when a fault is reported from a zone, the
signal circuits turn ON for 4 seconds.
• <4> Key - Enables/disables silent Walk Test™. When this key is pressed, it toggles the
system to audible Walk Test™, where the signal circuits are turned ON to play the codes
selected with the <F3> key, described above. Silent Walk Test™ is used in conjunction
with the logging function when audible signals might disturb the building occupants.
During the Walk Test™, the first line of the LCD shows changes, including the status of the
device under test. The second line of the LCD shows device status.
When the 4100U-S1 system is placed in Walk Test™ mode, any zone in the active Walk
Test™ group(s) can be tested in any order. If zone coding is enabled, there is an advantage in
testing all devices within one zone before going on to the next zone.
You should simulate an alarm and fault condition for each device being tested. If you are
using an audible or visual indication, wait for it to clear before you test the next device.
Otherwise, wait for an appropriate amount of time (based on the system reset delay) before
moving on to the next device. The LED on a smoke detector helps you in this area because it
indicates when the alarm is sensed, and when the detector resets. If zone coding is enabled,
verify that the code heard or seen is correct.
10-4
Page 69
Walk Test™ FEATURES
Introduction
Abort Audible and
Delay on
Reactivation
The Walk Test™ function has the following features:
• Abort Audible and Delay on Reactivation
• Active/Not Active
• Auto Abort on Alarm
• Auto Abort on Time-out
• Control Lists
• Delay Before Reset
• Log/No Log (Logging Option)
• Monitor Zone List
• Programmer Configuration
• Sig/No Sig (Silent Walk Test™ Selection)
• System Fault
• Fault Audible
• Zone Code/Zero Code.
These features are discussed in the following paragraphs.
Whenever a Walk Test™ group is aborted, either manually or automatically, the control list
sounds the abort signal “TESTING COMPLETED” (or 0-0-0) to indicate that the group is
going back into service, If a control point in the list is already active, possibly because
another alarm has come in, the “TESTING COMPLETED” message will play before the
alarm message. The group is put back into normal operating service 60 seconds after the abort
signal is heard (if there are signals in the control list). This delay protects against an unwanted
alarm should an auto abort occur while a device is being tested.
Active/Not Active
Auto Abort on Alarm
Auto Abort on TimeOut
Control List
The <1> key on the interface panel is used to toggle ON and OFF a given Walk Test™ group.
All groups are initially inactive at system start-up. Any number of groups can be enabled at
any one time. When a Walk Test™ group is enabled, its associated fault pseudo point is
turned ON and must be acknowledged. If multiple Walk Test™ groups are required, press the
fault acknowledge key after all Walk Test™ groups are selected.
When an alarm is detected from a zone that is not in the active Walk Test™ group, all normal
control functions take place and the active Walk Test™ group is aborted. When a non-audio
Walk Test™ is aborted, the system sounds a zero code three times. If an audio Walk Test™ is
aborted, the system announces “TESTING COMPLETED” over the speaker circuits for the
Walk Test™ group under test.
If there has been no activity within an active Walk Test™ group for 8 hours, the system aborts
the Walk Test™ automatically.
A Control List is a point list that contains those control points (signals and/or relays) that are
to be activated by a Walk Test™ group. By default, this list is initially filled by the system for
Group 0, and includes all signal, visual, or coded control points.
Continued on next page
10-5
Page 70
Walk Test™ FEATURES, Continued
Delay Before Reset
Logging Option
(Log/No Log)
Monitor Zone List
The programmer has the ability to set a Reset Time Delay. The delay time period starts after a
zone alarm is detected and runs until the detector is reset. The length of the delay may be
from 15 to 60 seconds, and may be adjusted depending on the method used to simulate an
alarm. A longer value is desired if smoke is used to bring in each detector. By default, the
delay is set to 15 seconds.
By default, the system enables the logging of Walk Test™ events. When logging is enabled,
each zone that comes into alarm or fault is time-tagged and added to the Historical Fault Log.
This is very beneficial in cases where a 100% silent test is required. When testing, remember
to record the identity and order of the devices tested. When the Walk Test™ is finished,
compare this record with the Historical Fault Log and verify that all zones activated correctly.
The <2> key is used to enable/disable the logging of Walk Test™ events to the Historical
Fault Log. By default, logging is enabled.
If the system is configured for a printer and the PRINT REPORT option is selected, the
Historical Fault Log is printed on the system printer.
A Monitor Zone List is a point list that contains those detection points within a defined area of
a building. This list is initially filled by the system for the first group, and includes all
detection points. It can be edited using the tag list feature of the 4100U Programming Unit.
An empty list signifies that a Walk Test™ group is not used. The programmer has the option
of changing the label of this point list so that it is more meaningful for panel operation.. You
cannot have the same zone in more than one Walk Test™ group.
Programmer
Configuration
Sig/No Sig (Silent
Walk Test™
Selection)
System Fault
Walk Test™ is a configured feature that is best programmed in the field with the 4100U
Programming Unit. By default, Walk Test™ is protected at Access level 3. The access level
required to enable your Walk Test™ is shown on the Programmer’s Report. Walk Test™
groups are selected from the LCD Main Menu. Selecting Walk Test™ on the Main menu
brings up the Walk Test™ configuration screen which lists the set-up for the Walk Test™
groups.
The <4> key is used to enable the selection of the Silent Walk Test™. By default, the Silent
Walk Test™ is enabled.
The Walk Test™ has the ability to test signal circuits for fault (i.e. open/short) conditions.
This is accomplished by using the Walk Test™ output lists (L50 through L57) as the input
lists for signal fault conditions.
For example, if a signal circuit fault occurs on a point in Walk Test™ output list L50 (Group
0), and Walk Test™ Group 0 is enabled, the Walk Test™ fault code will play on all
signal/speaker circuits in Walk Test™ list L50. Note that the signal fault is not inhibited. An
actual fault condition will occur at the operator interface panel, but will be logged as a Walk
Test™ fault for that signal. This fault automatically clears when the signal circuit is returned
to normal in a Global Acknowledge system. In an Individual Acknowledge system, Point P4
(FORCE GLOBAL ACKNOWLEDGE) must be turned ON before performing a signal circuit
Walk Test™. If Walk Test™ is not enabled for the group containing the signal circuit in fault,
the fault condition passes through without playing the Walk Test™ code.
Continued on next page
10-6
Page 71
Walk Test™ FEATURES, Continued
Fault Audible
Zone Code/Zero
Code
When a zone fault is detected, the Walk Test™ signals sound continuously for four seconds.
The <3> key is used to enable/disable Zone Coding. By default, Zone Coding is enabled.
10-7
Page 72
Walk Test™ PROCEDURES Walk Test™ PROCEDURES, Continued
How to Enter Walk
Test Mode
Once the passcode has been entered, you may enter the Walk Test™ mode by performing the
following procedures.
1. Press the <MENU> key. The LCD shows the following message.
Press < NEXT> or < PREVI OUS> to Scroll
Change Access Level?
2. Press the <NEXT> key until the LCD displays the following message.
Press < NEXT> or < PREVI OUS> to Scroll
Enable Walk Test?
3. Press the <ENTER> key. The following message is displayed.
1 = on> OFF 2 = no> LOG 3 = ?> ZONE 4 = NO< sig
WALK TEST GROUP 0
4. Select the desired Walk Test™ data using keys <1> through <4>.
• <1> Key - Key <1> is used to toggle the Walk Test™ mode.
Turn Walk Test™ ON and OFF by pressing the <1> key. Pressing
this key causes an arrow to point to the active state (which is
displayed in capital letters).
• <2> Key - Key <2> is used to enable/disable logging of Walk
Test™ events. Walk Test™ events are logged into the Historical
Fault log if selected. Pressing this key causes an arrow to point to
the active state (which is displayed in capital letters). By default,
logging is enabled.
• <3> Key - Key <3> is used to enable/disable zone coding.
Pressing this key causes an arrow to point to the active state. By
default, zone coding is enabled.
• <4> Key - Key <4> is used to enable/disable the silent Walk
Test™. Pressing this key causes an arrow to point to the active
state (which is displayed in capital letters). By default, the silent
Walk Test™ is enabled.
Continued on next page
10-8
Page 73
Walk Test™ PROCEDURES, Continued
How to Enter Walk
Test Mode,
(continued)
How to Exit Walk
Test Mode
5. Press the <1> key to enable/disable the Walk Test™ mode. The SYSTEM FAULT LED
illuminates, the tone-alert sounds, and the LCD displays the following message.
1 = ON> off 2 = no> LOG 3 = ?> ZONE 4 = NO< sig
WALK TEST GROUP 0
To enable multiple Walk Test™ groups, press the <NEXT> key to scroll to the next Walk
Test™ group. Then press the <1> key to enable that group. Continue scrolling, then press the
<1> key to select required Walk Test™ groups. Once all Walk Test™ groups are selected,
press the fault acknowledge key, then continue. When a Walk Test™ group with no
configured points is selected, the display shows the following message.
No w alk test points configured for:
WALK TEST GROUP X
Note:X equals 0 through 7.
When the Walk Test™ has been satisfactorily completed, exit from the Walk Test™ mode by
performing the following procedure.
1. Press the <MENU> key.
2. Press the <NEXT> key to select the Walk Test™ function.
3. Press the <ENTER> key.
4. Press the <1> key to turn off a Walk Test™ group. Press <NEXT>, then <1> to turn OFF
each enabled Walk Test™ group.
Note: The system activates a one-minute timer when exiting from the Walk Test™ mode.
This timer ensures that monitor points have had ample time to clear (smoke) prior to
enabling the system. After the one-minute delay, the system Walk Test™ fault
automatically clears.
5. Press <MENU>. The Change Access Level menu is shown.
6. Press <ENTER>.
7. Press <2> to log out.
8. If Access Level 4 was entered, a fault will continue to exist in the system. Access Level 4
is normally used by Simplex personnel and additional steps must be performed. Call
Simplex to restore the system.
9. Inform required personnel when system testing is completed.
Continued on next page
10-9
Page 74
Walk Test™ PROCEDURES, Continued
How to Turn a Point
Off
The <OFF> key press will turn a control point off and prevent the automatic override, thus
causing it to remain OFF. This action will result in a system fault. The normal state of all
control points is AUTO. The <OFF> key press has no effect on monitor points.
The point to be turned OFF must first be identified to the system. This is accomplished by
entering the identity of the point to be turned OFF through the ENTRY keypad, and then
pressing the <OFF> key. If the <OFF> key is passcode protected, perform the system Log In
procedures.
To turn a point OFF, perform the following procedures.
1. Ensure the point to be turned OFF is shown on the alphanumeric display. A typical point
(SIG2) is shown below.
MASTER SI GNAL POI NT 2, SI G2
SI GNAL CI RCUI T ON
2. Press the <OFF> key. A typical display is shown below.
Press < ENTER> to force OFF
SI GNAL CI RCUI T: SI G2
3. Press the <ENTER> key. A typical display is shown below.
MASTER SI GNAL POI NT 2, SI G2
SI GNAL CI RCUI T OFF
How to Turn a Point
On
4. Press the <C/EXIT> key. The display shows the following message.
* * FAULT * * Press < FI RE ALARM ACK> to
review
FI RE = 0 PRI 2 = 0 SUPV = 0 FLT = 1
The <ON> key press will manually turn a control point ON, and prevent automatic operation
by increasing its priority, causing it to remain ON. With the exception of pseudo points, this
action will result in a system fault. The normal state of all control points is AUTO. The
<ON> key press has no effect on monitor points.
The points to be turned ON must first be identified to the system. This is accomplished by
selecting/entering the identity of the required point on the alphanumeric display, and pressing
the <ON> key. If the <ON> key is passcode protected, perform the system Log In
Procedures.
Continued on next page
10-10
Page 75
Walk Test™ PROCEDURES, Continued
How to Turn a Point
On, (continued)
To turn a point ON, perform the following procedures.
1. Ensure the point to be turned ON is shown on the alphanumeric display. A typical point
(SIG2) is shown below.
MASTER SI GNAL POI NT 2, SI G2
SI GNAL CI RCUI T OFF
2. Press the <ON> key. A typical display is shown below.
Press < ENTER> to force ON
SI GNAL CI RCUI T: SI G2
3. Press the <ENTER> key. A typical display is shown below.
MASTER SI GNAL POI NT 2, SI G2
SI GNAL CI RCUI T ON
4. Press the <C/EXIT> key. The display shows the following message.
* * FAULT * * Press < FI RE ALARM ACK> to
review
FI RE = 0 PRI 2 = 0 SUPV = 0 FLT = 1
How to Return a
Point to Auto
The <AUTO> key press leaves a point in its current state (ON or OFF), but allows the system
program to control it. AUTO is the normal state for all control points. A fault exists if any
control point is taken out of the AUTO state.
The point to be turned to AUTO must first be identified to the system. This is accomplished
by selecting/entering the required point on the alphanumeric display, and then pressing the
<AUTO> key. If the <AUTO> key is passcode protected, perform the Log In Procedures.
To return a point to AUTO, perform the following procedures.
1. Ensure the point to be turned AUTO is shown on the alphanumeric display. A typical
point (SIG2) is shown below.
MASTER SI GNAL POI NT 2, SI G2
SI GNAL CI RCUI T OFF
Continued on next page
10-11
Page 76
Walk Test™ PROCEDURES, Continued
How to Return a
Point to Auto,
(continued)
How to Enable a
Disabled Point
2. Press the <AUTO> key. A typical display is shown below.
Press < ENTER> for AUTOmatic control
SI GNAL CI RCUI T: SI G2
3. Press the <ENTER> key. A typical display is shown below.
MASTER SI GNAL POI NT 2, SI G2
SI GNAL CI RCUI T OFF
4. Press the <C/EXIT> key. The display shows the following message.
SYSTEM I S NORMAL
9:27:40 WED 2 7 - SEP-00
If a device was disabled for any reason and has been restored, you can enable the point. This
point must first be identified to the system. The disabled point causes a system fault condition
which is continually shown on the alphanumeric display. This can be viewed by pressing the
<FAULT ACK> key and reading the alphanumeric display. The point can be enabled by
using the <ENABLE> key. If the <ENABLE> key is passcode protected, perform Log In
Procedures, then continue.
To enable a disabled point, perform the following procedures.
1. Press the <FAULT ACK> key until the point to be enabled is shown on the alphanumeric
display, as shown in the following example.
MONI TOR CARD 1 ZONE NUMBER 1 2
FI RE MONI TOR ZONE DI SABLE FAULT
2. Press the <ENABLE> key. The following message is displayed.
Press < ENTER> to ENABLE
MONI TOR ZONE: ZN1 2
Note:Read the warning below before performing the following step.
Continued on next page
10-12
Page 77
Walk Test™ PROCEDURES, Continued
How to Enable a
Disabled Point,
(continued)
3. Press the <ENTER> key. The alphanumeric display shows the following
message.
Please stand by . . .
ZONE 12 will ENABLE in 60 seconds
WARNING
If the zone is still in alarm, a WARNING is displayed which tells you
that the system will sound an alarm if the timer (60 seconds) times out.
TO ABORT THE ENABLE, PRESS THE <DISABLE> KEY. If an
alarm condition exists, the following is shown on the alphanumeric
display.
* * WARNI NG * * Press < DI SABLE> to abort
ZN1 2 w ill ALARM in 60 seconds
IF THE ABOVE WARNING IS SHOWN ON the ALPHANUMERIC
DISPLAY, PRESS THE <DISABLE> OR AN <FIRE ALARM ACK>
KEY. FAILURE TO ABORT THE ENABLE WILL CAUSE AN
ALARM CONDITION.
If the enable process is successful, the following message is shown on the alphanumeric
display.
ENABLE COMPLETED
What to do in Case
of System
Malfunction
4. Repeat steps 1 through 3 above to enable all required points.
5. Press the <C/EXIT> key to exit. This will allow the panel to show the Time and Date.
CALL YOUR LOCAL SIMPLEX BRANCH OFFICE, WHICH IS LISTED IN THE
YELLOW PAGES, FOR ALL MALFUNCTIONS, OR IF YOU WOULD LIKE A
QUALIFIED SIMPLEX TECHNICIAN TO ASSIST YOU WITH INSTALLATION,
TESTING AND TROUBLESHOOTING THE SYSTEM.
10-13
Page 78
Page 79
Chapter 11
Printing Reports
Introduction
In this Chapter
This chapter describes printer options and how to print a report.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Setting Printer Options 11-2
Printing a Report 11-3
11-1
Page 80
Setting Printer Options
Available Options
The 4100U-S1 includes two printer options: Select Report Printer and Terminate Current
Report. Follow these steps to set these options.
1. Press the <MENU> key.
2. Press the <NEXT> and <PREVIOUS> keys until the prompt reads, “Printer Options?”
3. Press <ENTER>.
4. Press the <NEXT> and <PREVIOUS> keys to select either of the following:
• Select Report Printer. This allows you to select which printer is to be used if more
than one is configured.
• Terminate Current Report. Select this option to terminate the report currently being
printed on the 4100U-S1’s report printer.
11-2
Page 81
Printing a Report
Overview
The system can generate any of the following reports.
Report Description
Report includes all information contained in the alarm
Alarm History Log Report
Fault History Log Report
TrueAlarm Status Report
TrueAlarm Service Report
history log – device custom label, time and date device
entered alarm.
Report includes all information contained in the fault
history log – device custom label, type of trouble, time
and date device experienced trouble.
Reports the following information for each point.
• Device Number
• Custom Label
• Current Sensitivity of the Point
• Point Status: Normal, Fault, Alarm
• Almost Dirty Status: Points which are almost dirty
have an asterisk in this field to denote this.
Reports the following information for each point.
• Device Number
• Custom Label
• Alarm Level (sensitivity level of the device)
• Average Value –
• Current Value --
• Percent of Alarm: Shows the current value for the
sensor. Value is shown as a percentage of 100
percent (alarm). For example, if the value shown is
9%, it means that the sensor is currently at 9% of
the value required to trigger an alarm.
• Peak Value. Shows the highest value that the
sensor has reached. Value is shown as a
percentage of 100 percent (alarm). For example, if
the value shown is 9%, it means that the peak value
experienced by the sensor was 9% of the value
required to trigger an alarm.
• Current State: Possible values include Normal,
Fault, Dirty, Excessively Dirty, and Almost Dirty.
Procedure
1. Press the <MENU> key. Use the <NEXT> and <PREVIOUS> keys to scroll through the
choices until the “PRINT REPORTS?” choice is displayed.
2. Use the <NEXT> and <PREVIOUS> keys to scroll through the categories of report
(Alarm History, Fault History, etc.).
3. When the category of report you want to print is displayed, press <ENTER>. The
system prompts you to confirm that you want to generate the report. Press <ENTER>
again.
The report prints on the panel’s report printer.
11-3
Page 82
11-4
Page 83
Chapter 12
Maintenance Procedures
Introduction
In this Chapter
It is a requirement of AS1851 - Part 8, Maintenance of Fire Protection Equipment, that tests be
carried out to ensure the system is fully functional.
The owner or tenant of the premises usually carries out the weekly test described. The
maintenance company, under a Service Agreement, typically carries out the monthly and annual
tests.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Weekly Tests 12-2
Monthly Tests 12-3
Annual Tests 12-4
WARNING
It is very important that adequate precautions are taken when doing any testing on the fire alarm
system. Outputs of a typical panel include calling the Brigade, activating the building evacuation
system, shutting down air conditioning, and may include release of extinguishant within the
building.
Brigade signalling must only be tested with prior arrangement and use of the “test key” or other
protocol as is applicable to the area.
12-1
Page 84
Weekly Tests
Procedure
Weekly tests should be conducted and should include the following:
a. Carry out a fire alarm call by simulating an alarm on detector zones as follows;
1. Isolate any system outputs you wish not to respond to the testing of the system, such as
the external bell (using the <EXT BELL ISOLATE> key, the warning system (using the
<WARNING SYSTEM ISOLATE>, and any other Ancillary Control functions (ACF)
including AC Shutdown and MDH controls using the <ACF ISOLATE> key.
2. Place the fire brigade transmitter selector switch in the Isolate or Test position as per the
arrangement with the brigade.
3. Operate the <ALARM TEST> key, then press and hold a zone’s Isolate key to activate
the alarm test for that zone and test the response of the system’s signals.
To check the external bell, press the <EXT BELL ISOLATE> key while still pressing
the zone isolate key.
Note: The correct operation of the bell should be checked each week.
b. Fault test a zone to check that the fault indicator and sounder (buzzer) are working. Cancel
the ALARM TEST. Press the <FAULT TEST> key, then press a zone’s Isolate key to
activate the fault test for that zone.
c. On completion of the tests ensure that all switches are in the correct operating position and
that the system has been returned to its normal status. Should a fault condition exist, or if a
circuit indicator did not illuminate when tested immediately contact your Maintenance
company to rectify the problem.
d. Record the results of the tests in the logbook and check that all tests were logged by the
system printer (if present). If the printer logs any test as having failed, immediately contact
your Maintenance company to rectify the problem.
Battery Test
The system has a weekly battery test programmed in the custom control.
This test causes the system to run off its batteries for 1 hour, with the charger turned off. The
panel supervises the battery voltage, and if that gets low, indicates a fault and aborts the test (i.e.
system reverts to running from the ac power). If an alarm occurs during the one hour test, the
test is immediately aborted.
The battery test can be forced by setting the day and time to that specified as the start time
(recommend setting time to 1 minute before programmed start time).
The start time should be recorded with the site details at the front of this manual.
12-2
Page 85
Monthly Tests
Procedure
In addition to the weekly test specified previously, the following inspection and testing
procedures should be carried out each month:
a. Check all battery terminals and electrolyte levels, where appropriate. Maintain all batteries
in a serviceable condition.
b. Check condition of battery enclosure for corrosion and ensure the batteries are stored in a
safe and secure condition.
c. Check that all visual indicators operate correctly, including those on mimic or repeater
panels.
d. Check the operation of all aural and visual indicators external to the control and indicating
equipment.
e. Simulate fault conditions on all alarm zones to ensure that fault indicators, both aural and
visual where applicable, are operating correctly from each alarm zone facility.
f. Check that all control and indicating equipment is in a clean and operational condition, and
effectively dust-sealed.
g. Ensure that all fire indicator panels, sub-indicator panels, repeater panels, and mimic panels,
are clearly visible and readily accessible (see AS1670).
h. Ensure that all controls are returned to the normal condition.
i. Record the results of all monthly maintenance procedures in the logbook, including all items
requiring corrective action, adjustment, and the like.
j. Check that items previously recorded as requiring attention have been attended to, or record
the reason why corrective actions have not been completed.
12-3
Page 86
Annual Tests
Procedure
The annual tests consist of all the inspection and testing procedures specified in the previous
clause and the following:
a. Visually inspect all detectors and sampling points for any condition which is likely to
adversely affect their operation, such as excessive deposition of dust or coating with paint.
b. Remove at least one detector on each alarm zone circuit and confirm the fault signal is
registered at the appropriate alarm zone facility.
c. Check the operation of 20 percent of the installed heat detectors and 50 percent of the
installed smoke detectors and sampling points in each alarm zone. The procedure for testing
shall be such that all detectors are checked not less than once every 5 years for heat
detectors, and not less than once every 2 years for smoke detectors and sampling points.
d. Detectors and sampling points that fail to operate shall be repaired or replaced and retested.
e. Check the operation of an ancillary control facilities and ensure that each controlled device
can be correctly initiated.
f. Check operation of all manual call points.
g. Check the power supply battery supervision. Disconnect the battery and check that a
“battery depleted/missing” fault occurs.
With the battery connected, measure the voltage with a calibrated voltmeter and compare the
reading with that displayed on the LCD when the battery voltage point status is selected
under Card Status for the SPS. They should agree to within 0.5V.
h. Visually inspect control and indicating equipment components for any evidence of
deterioration.
i. Check for any building alterations, changes in the environment, or utilisation of the
protected area which would require modifications to the system.
j. Ensure spare glasses for manual call points are available in the control panel and a tool for
replacing such glasses.
k. Record the results of all yearly maintenance procedures in the logbooks, including details of
detectors and sampling points that do not pass the visual inspection or fail to operate
satisfactorily, and notify the owner or his agent of any faults within the installation.
l. Check that each sprinkler monitor point i.e. pumps running, main stop valve shut etc.
operate correctly.
m. Test all stair pressurization fans for automatic and manual start-stop and correct status
indicator at the Fire Indicating Panel.
12-4
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.