Simplex 4100U Application User guide

Page 1
Smoke Management Application Guide
574-465 Rev. D
Page 2
Page 3
Page 4
Page 5
Copyrights, Trademarks, and Patent Data
Copyrights
Trademarks
Patent Data
©2004, 2011 SimplexGrinnell LP. All rights reserved. Specifications and other information shown were current as of publication and are subject to change without notice.
To further the science of Smoke Management, Tyco Safety Products hereby grants permission to reproduce or transmit this reference document in any form or by any means, electronic or mechanical, for the purpose of obtaining information on the science of Smoke Management. We retain the rights of our respective trademarks.
Simplex, the Simplex logo, TrueSite, TrueAlarm, and IDNet are either trademarks or registered trademarks of Tyco International Ltd and its affiliates and are used under license. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
Walk Test is protected by US Patent No. 4,725,818.
MAPNET II® addressable communications is protected by U.S. Patent No. 4,796,025.
IDNet is patent pending.
TrueAlarm® Analog Detection is protected by U.S. Patent No. 5,155,468.
TrueAlarm® Detector Base is protected by U.S. Patent No. 5,173,683.
Windows® is a registered trademark of the Microsoft Corporation.
VESDA Scanner and MiniVESDA-50 are trademarks and the name VESDA® and VESDA® E70-D are registered trademarks of Vision Systems.
All other logos are trademarks or registered trademarks of their respective companies.
Page 6
Page 7
Page 8
System Requirements ................................................................................................. 2-2
General Requirements ............................................................................................. 2-2
Agency Requirements ............................................................................................. 2-2
System Design Parameters ......................................................................................... 2-3
Verifying System Integrity During Non-Emergency Conditions ............................... 2-3
Weekly Self-Test ...................................................................................................... 2-3
Verifying System Integrity During Emergency Conditions ....................................... 2-3
Automatic Activation ................................................................................................ 2-3
Subsequent Automatic Activation ............................................................................ 2-4
Automatic Activation By a Manual Pull Box ............................................................. 2-4
Manual Operation .................................................................................................... 2-4
Automatic Override of Manual Activation ................................................................ 2-4
Chapter 3 Smoke Control System Components 3-1
Introduction .............................................................................................................. 3-1
In this Chapter ......................................................................................................... 3-1
Smoke Control System ................................................................................................ 3-2
Smoke Control System ............................................................................................ 3-2
4100U/4100ES Panels ............................................................................................... 3-3
4100U/4100ES Panel ............................................................................................. 3-3
4190 TrueSite Workstation and 24 Point I/O Graphic Interface .................................. 3-4
4190 TrueSite Workstation (TSW) ........................................................................... 3-4
24-Point I/O Graphic Interface (4100-7401) ............................................................ 3-4
Optional and Peripheral System Components ............................................................ 3-5
Optional System Components ................................................................................. 3-5
Peripheral Components ........................................................................................... 3-6
Firefighter Smoke Control Station ............................................................................... 3-7
Firefighter Smoke Control Station (FSCS) .............................................................. 3-7
FSCS Ordering Information ..................................................................................... 3-9
About the Fire Alarm Control Panel ....................................................................... 3-10
Chapter 4 Installing the Smoke Control System 4-1
Introduction .............................................................................................................. 4-1
In this Chapter ......................................................................................................... 4-1
General Smoke Control Interconnections ................................................................... 4-2
Overview .................................................................................................................. 4-2
UUKL Addressable Monitor/Control Devices for 4100U/4100ES ............................ 4-3
Reference Information ............................................................................................. 4-4
Four Story Building Smoke Control Example .......................................................... 4-5
Dedicated Smoke Control System Wiring ................................................................... 4-6
Overview .................................................................................................................. 4-6
Dedicated Damper Control ...................................................................................... 4-6
Dedicated Fan Control ............................................................................................. 4-8
Non-Dedicated Smoke Control System Wiring Diagrams ......................................... 4-10
Overview ................................................................................................................ 4-10
Non-Dedicated Damper Control ............................................................................ 4-10
Non Dedicated Fan Control ................................................................................... 4-13
iv
Page 9
Chapter 5 Smoke Control System Programs 5-1
Introduction .............................................................................................................. 5-1
In this Chapter ......................................................................................................... 5-1
Smoke Control Program Requirements ...................................................................... 5-2
Introduction .............................................................................................................. 5-2
Emergency Operation .............................................................................................. 5-2
Automatic Program .................................................................................................. 5-2
Dedicated Smoke Control System Weekly Self-Test .............................................. 5-2
Dedicated Smoke Control System Weekly Self-Test .................................................. 5-3
Custom Control Programming Example .................................................................. 5-3
Equation 1: Start Self-Test ...................................................................................... 5-3
Equation 2: Turn ON Stair Pressure Fan ................................................................. 5-3
Equation 3: Test Stairwell Air Pressure ................................................................... 5-4
Equation 4: Reset Stair Pressure Fan to OFF ......................................................... 5-4
Equation 5: End of Program .................................................................................... 5-4
Smoke Control System Custom Control Equations ..................................................... 5-5
Introduction .............................................................................................................. 5-5
Smoke Control System CC Equation Summary ...................................................... 5-5
Equation 1: Set Up Normal Conditions at Startup ................................................... 5-7
Equation 2: Clear Faults on Startup ........................................................................ 5-7
Equation 3: Set Normal Conditions at Reset ........................................................... 5-8
Equation 4: Set Normal Conditions at Reset ........................................................... 5-8
Equation 5: Initialize Normal Conditions at Reset ................................................... 5-9
Equation 6: Normal Conditions Complete After Reset ............................................ 5-9
Equation 7: Smoke Control Initiate ........................................................................ 5-10
Equation 8: Smoke Control Reset ......................................................................... 5-10
Equation 9: Initiate Smoke Zone 1 ........................................................................ 5-10
Equation 10: Activate Smoke Control Zone 1........................................................ 5-11
Equation 11: Initiate Smoke Zone 2 ...................................................................... 5-11
Equation 12: Activate Smoke Control Zone 2........................................................ 5-12
Equation 13: Initiate Smoke Zone 3 ...................................................................... 5-12
Equation 14: Activate Smoke Control Zone 3........................................................ 5-13
Equation 15: Initiate Smoke Zone 4 ...................................................................... 5-13
Equation 16: Activate Smoke Control Zone 4........................................................ 5-14
Equation 17: Supply Fan Duct Smoke Alarm ........................................................ 5-14
Equation 18: Stair Press Fan Duct Smoke Alarm ................................................. 5-14
Equation 19: Report TBL if Supply Fan Not ON .................................................... 5-15
Equation 20: Report TBL if Supply Fan Not OFF .................................................. 5-15
Equation 21: Report TBL if Exhaust Fan Not ON .................................................. 5-15
Equation 22: Report TBL if Exhaust Fan Not OFF ................................................ 5-15
Equation 23: Report TBL if Stair Press Fan Not ON ............................................. 5-16
Equation 24: Report TBL if Stair Press Fan Not OFF ........................................... 5-16
Equation 25: Report TBL if Main EXH Damper Not Open ..................................... 5-16
Equation 26: Report TBL if Main EXH Damper Not Closed .................................. 5-16
Equation 27: Report TBL if Main SUP Damper Not Open ..................................... 5-17
Equation 28: Report TBL if Main SUP Damper Not Closed .................................. 5-17
Equation 29: Report TBL if Main RET Damper Not Open ..................................... 5-17
Equation 30: Report TBL if Main RET Damper Not Closed .................................. 5-17
Equation 31: Report TBL If SUP Damper 1 Not Open .......................................... 5-18
Equation 32: Report TBL If SUP Damper 1 Not Closed ........................................ 5-18
Equation 33: Report TBL If SUP Damper 2 Not Open .......................................... 5-18
Equation 34: Report TBL If Sup Damper 2 Not Closed ......................................... 5-18
Equation 35: Report TBL If SUP Damper 3 Not Open .......................................... 5-19
Equation 36: Report TBL If SUP Damper 3 Not Closed ........................................ 5-19
Equation 37: Report TBL If SUP Damper 4 Not Open .......................................... 5-19
v
Page 10
Equation 38: Report TBL If SUP Damper 4 Not Closed ........................................ 5-19
Equation 39: Report TBL if EXH Damper 1 Not Open .......................................... 5-20
Equation 40: Report TBL If EXH Damper 1 Not Closed ........................................ 5-20
Equation 41: Report TBL If EXH Damper 2 Not Open .......................................... 5-20
Equation 42: Report TBL If EXH Damper 2 Not Closed ........................................ 5-20
Equation 43: Report TBL If EXH Damper 3 Not Open .......................................... 5-21
Equation 44: Report TBL If EXH Damper 3 Not Closed ........................................ 5-21
Equation 45: Report TBL If EXH Damper 4 Not Open .......................................... 5-21
Equation 46: Report TBL If EXH Damper 4 Not Closed ........................................ 5-21
Equation 47: Manual Control SUP AIR Damper 1 Open ....................................... 5-22
Equation 48: Manual Control SUP Air Damper 1 Close ........................................ 5-22
Equation 49: Manual Control SUP Air Damper 2 Open ........................................ 5-22
Equation 50: Manual Control SUP Air Damper 2 Close ........................................ 5-22
Equation 51: Manual Control SUP Air Damper 3 Open ........................................ 5-23
Equation 52: Manual Control SUP Air Damper 3 Close ........................................ 5-23
Equation 53: Manual Control SUP Air Damper 4 Open ........................................ 5-23
Equation 54: Control SUP Air Damper 4 Close ..................................................... 5-23
Equation 55: Manual Control EXH Air Damper 1 Open ........................................ 5-24
Equation 56: Manual Control EXH Air Damper 1 Close ........................................ 5-24
Equation 57: Manual Control EXH Air Damper 2 Open ........................................ 5-24
Equation 58: Manual Control EXH Air Damper 2 Close ........................................ 5-24
Equation 59: Control EXH Air Damper 3 Open ..................................................... 5-25
Equation 60: Manual Control EXH Air Damper 3 Close ........................................ 5-25
Equation 61: Manual Control EXH Air Damper 4 Open ........................................ 5-25
Equation 62: Manual Control EXH Air Damper 4 Close ........................................ 5-25
Equation 63: Manual Control Stair Press Fan ON ................................................. 5-26
Equation 64: Manual Control Stair Press Fan OFF ............................................... 5-26
Equation 65: Manual Control Main Supply Fan ON .............................................. 5-26
Equation 66: Manual Control Main Supply Fan OFF ............................................. 5-26
Equation 67: Manual Control Main RET Air Damper Open ................................... 5-27
Equation 68: Manual Control Main RET Air Damper Close .................................. 5-27
Equation 69: Manual Control Main Exhaust Fan ON ............................................ 5-27
Equation 70: Manual Control Main Exhaust Fan OFF ........................................... 5-27
Equation 71: Manual Control Main SUP Air Damper Open ................................... 5-28
Equation 72: Manual Control Main Sup Air Damper Close ................................... 5-28
Equation 73: Manual Control Main EXH Air Damper Open ................................... 5-28
Equation 74: Manual Control Main EXH Air Damper Close .................................. 5-28
Equation 75: Manual Control Clear Faults ............................................................. 5-29
Equation 76: Master Key-Switch ........................................................................... 5-29
Equation 77: Turn SONALERT ON ....................................................................... 5-30
Equation 78: Turn SONALERT OFF ..................................................................... 5-30
Chapter 6 Glossary of Terms 6-1
Introduction .............................................................................................................. 6-1
In this Chapter ......................................................................................................... 6-1
Glossary of Terms ....................................................................................................... 6-2
Glossary ................................................................................................................... 6-2
Index ............................................................................................................................ 6-1
vi
Page 11
Page 12
Page 13
Page 14
Page 15
Page 16
Page 17
Controlling Smoke Movement, Continued
A
Basic Concept
3. Turn OFF the air inlets and air returns of the areas that are neither being pressurized nor depressurized (i.e., areas far away from the fire). Turning OFF the air return prevents the smoke that is being vented into the return air system from coming into the smoke-free area. In cases where there are large openings (such as an open doorway) between the area on fire and an adjacent area, smoke can be confined by a large volume of air. Pumping large amounts of air through the adjacent space creates a constant draft through the opening into the smoke zone (as shown below).
IR
A
CENTRIFUGAL FAN
Figure 1-3. Confining Smoke with a Large Volume of Air
The draft through the open space keeps back the smoke, confining it to the smoke zone. The amount of air required to keep the smoke from penetrating the open space is quite large. Avoid this type of situation when possible.
I R
AIR
SMOKE
Creating Smoke Zones
To contain smoke by using pressure, you must divide the building into “Smoke Control Zones.” A floor or several floors of the building can be considered a single zone or a single floor can be broken into a number of zones. A zone must be separated from other zones by smoke dampers, airtight doors, and smoke-proof barriers.
When a fire occurs, the smoke control system can then pressurize all of the zones around the zone where the fire initiated (called the “Fire Zone”), isolating the smoke to that single zone.
If the smoke control system is non-dedicated, the layout of the smoke control zones should take into consideration the layout of the HVAC system. You should place multiple areas served by the same HVAC controls in the same smoke control zone. Also, the smoke control zones must conform to any fire control zones that have been established, because the smoke detectors are tied into the fire detection system. Also, keeping the smoke control zones and the fire control zones the same makes it easier to coordinate the two systems.
1-5
Page 18
Page 19
Page 20
Page 21
Smoke Control and Fire Control System Differences
Separate System for Separate Goals
The smoke control system is usually separate from the fire control system, since they have different goals. The goal of the fire control system is to contain and extinguish the fire as fast as possible. These systems, which halt the fire but not the smoke, are often triggered automatically, relying on the heat of the fire to activate the system. Although smoke control systems are also automatic, you must have manual overrides for the automatic controls.
A smoke control system may also be required to work with gas-based fire extinguishers, such as gaseous agent systems installed in many computer rooms. If the smoke control system tries to vent a room with such a system, it may vent the fire suppressing gas as well. Removing the gas lets the fire continue burning. Also, pressurizing the areas surrounding an extinguisher equipped room reduces the effectiveness of the system. Air forced into the room from the outside by pressure can provide the fire with the oxygen it needs to continue burning. Therefore, gas-based fire
extinguishers and smoke control systems should not be active at the same time in the same area.
The smoke control system receives the location of the fire from the fire panel. The fire panel uses a combination of smoke and heat sensors to determine where the fire is located. As defined in NFPA 92A: In the event that signals are received from more than one smoke zone, the smoke control system will operate in the mode determined by the first signal received.
Specific, zoned smoke control strategies should never be triggered by manual pull boxes. The risk of someone pulling a box someplace other than the fire zone is too high for you to trust your smoke control system to this form of activation.
All smoke control systems installed in buildings must be in accordance with the standards adopted by local codes. You can find additional information regarding fire alarm control units in
Underwriters Laboratories Standard UL 864 and the National Fire Protection Association (NFPA®).
1-9
Page 22
Page 23
Page 24
Designing a Smoke Control System, Continued
Selecting the Proper Fans and Duct Work
Choosing the Proper Dampers
Fans must be capable of reaching the required pressure setting within 60 seconds. Each fan must also have a pressure monitor so that the smoke control system can receive feedback on the status of the fan to determine whether it is actually working. It is the responsibility of the system designer to select duct work that meets the temperature and fire ratings for the specific application.
In some climates, the outside air can be so cold that drawing it directly inside the building for pressurization can damage the building's interior fixtures or equipment (e.g., freeze pipes or damage temperature-sensitive equipment). In these cases, some sort of pre-heater needs to be installed on the air inlet. The smoke control system does not need to control this air intake heater as closely as one on an HVAC system, since maintaining comfort levels is not an issue. It simply has to make sure the air sent into an area is warm enough to not damage the building's equipment.
The dampers used to isolate the smoke zone must be smoke dampers. Smoke dampers are dampers that meet the requirements given in UL 555S, Standard for Leakage Rated Dampers for Use in Smoke Control Systems. Following this standard ensures that the dampers are able to block the smoke when they are fully closed. These dampers may be different from those you might use in an HVAC system that does not perform smoke control.
In a smoke control system, the dampers must be able to travel to their desired setting in a maximum time of 75 seconds (see note below). All dampers must be fitted with end-position switches to provide feedback to the smoke control system. These switches let the control system know the position of the dampers, since smoke dampers are usually either fully-closed or fully-open.
Note: Local codes may specify a shorter maximum time.
Dampers sometimes function as both smoke dampers and fire dampers. Fire dampers are dampers that block a fire from penetrating a fire-rated partition via a duct. These dampers are normally open, held in place by a fusible link. The fusible link is a heat-sensitive device that releases the dampers when it is heated to a certain temperature. Once the fusible link releases, the dampers close by the force of gravity. This is required so that fire dampers operate even if the local electric service has failed. The specifications for fire dampers appear in UL 555, Standard for Fire Dampers.
If you want a damper to function as both a smoke damper and a fire damper, it must meet the requirements for both devices. A damper can be operated by an electric motor or pneumatics. However, it must have a fusible link or some other means of automatic closure (like a regular fire damper). Since the control system can override the damper closure if the temperature warrants, the damper needs the fusible link in case the damper’s automatic control is interrupted.
Placing Air Inlets and Outlets
You need to carefully consider the placement of the air inlets and outlets on your building. If you place an outlet that vents smoke too close to an air inlet, the air intake can draw the smoke back into the building. Since smoke rises, the exhausts that vent smoke should be placed well above air inlets. The exhausts should be placed several feet above the roof level to allow space for the smoke to rise and disperse.
Keeping smoke outlets far away from air inlets does not guarantee that the air brought into the building is always smoke free. You may want to place smoke detectors in air inlets that operate during a smoke emergency.
Note: In some cases, smoke detection in the air inlet is required to have the capability of being
overridden by the responding authority after the situation has been investigated.
If the detector finds smoke in the incoming air, it alerts the control system. The control system must then decide whether or not to shut down the air inlet.
1-12
Page 25
Page 26
Designing a Dedicated Smoke Control System, Continued
Designing the Ideal Stairtower System
The ideal stairtower smoke control system must pressurize the stairway enough to keep the smoke out, but it must not pressurize it so much that the doors cannot be opened. An example of a dedicated smoke control system for a stairtower is shown in the figure below.
Exhaust Fan
Air Supply Duct
Air Flow
Fire Rated
Doors
Pressure Vents
Air Flow
Supply Fan
Ensuring Doors Can Open
Figure 1-5. Stairtower Pressurization by Multiple Injections
The figure above shows stairtower pressurization by multiple injections with a supply fan located at ground level and an exhaust fan located on the building roof.
The table below shows the maximum allowable pressure differential across a door in inches water gauge (in.) based on how wide the door is and how much force the automatic door closing mechanism exerts as defined in NFPA 92A. At the pressures shown in the table, the door requires 30 lbf (pounds of force) to open, the maximum limit suggested by the NFPA Life Safety Code (NFPA
101).
Table 1-2. Pressure Differential For Various Door Widths
.
Door Closer
Force (lbf)
6
8 10 12 14
32 in. 36 in. 40 in. 44 in. 48 in.
0.45 0.40 0.37 0.34 0.31
0.41 0.37 0.34 0.31 0.28
0.37 0.34 0.30 0.28 0.26
0.34 0.30 0.27 0.25 0.23
0.30 0.27 0.24 0.22 0.21
Pressure Differential
Continued on next page
1-14
Page 27
Designing a Dedicated Smoke Control System, Continued
Ensuring Doors Can Open
Controlling Pressure in a Stairtower
Table 1-2 assumes a door height of seven feet and a distance from the doorknob to the knob side of the door of three inches. If your door does not meet these requirements, or has opening hardware other than a doorknob, such as panic hardware, then refer to the ASHRAE publication Design of Smoke Control Systems for Buildings for a formula to calculate the proper opening force. The door widths in Table 1-2 are only valid for doors that are hinged at one end. For other types of doors, see the ASHRAE document.
Many door closers vary the amount of force as the door opens. They provide less resistance in the early stages of opening the door than they do later, when the door is almost fully open. The force to open the door shown in Table 1-2 represents the force needed to open the door only enough to let air flow through the opening. Once air is able to flow, the force exerted by the difference in air pressure on the door lessens. Therefore, when calculating the force required to open the door, you may need to lower the door closer force.
Stairtower smoke control systems are divided into two categories: “non-compensated” and “compensated.” These categories are illustrated in the figure below, which shows stairtower pressurization by top injection. Non-compensated systems simply turn on a fan to pressurize the stairtower, as shown below in Stairtower A. The fan speed does not change to compensate for doors opening and closing. The more doors that are open, the more the pressure differential between the stairtower and the building drops.
Constant Fan Speed
Variable
Fan Speed
Stairtower A
Stairtower B
Figure 1-6. Non-Compensated and Compensated Stairtower Systems
Continued on next page
1-15
Vent
Page 28
Page 29
Page 30
Page 31
Page 32
Detecting Smoke, Continued
Firefighter Smoke Control Station (FSCS)
The FSCS must not override such safety controls as:
Electrical overload protection.
Electrical disconnects as required by NFPA 70.
Other controls in accordance with UL 864.
Any fire/smoke damper thermal control as required by UL 33, Standard for Heat Responsive Links for
Fire Protection Service or UL 555S, Standard for Leakage Rated Dampers for Use in Smoke Control Systems.
In non-dedicated systems, local motor controller hand/off/auto switches can remain in-circuit with the FSCS panel. But, they can remain in-circuit only if the switches are in a locked room accessible only to authorized personnel. Also, if such a switch is thrown, a trouble condition must sound in the building main control center. The indicator lights on the FSCS provide information about the functioning of the system. The following colors for example are used for FSCS indicators:
Green - Smoke-control fans and other critical-operation devices are running or the dampers are open.
Yellow - Dampers are in the closed position.
Orange or Amber - The equipment has failed.
Red - A fire has been detected in the area.
The FSCS has a lamp test button that turns ON all the panel lights. Use this button regularly to make sure none of the lights has burned out. The FSCS gets information on the status of the smoke control system equipment from proof monitors on the equipment itself. Each fan that has a capacity of over 2,000 cfm should be equipped with an airflow monitor. A proof sensor is required to monitor airflow and the position of the blade or vane in a damper is also required to be monitored. Smoke dampers should be fitted with end­range switches to indicate that they are fully-opened or fully-closed.
All of the failure lights on the FSCS represent the state of the equipment as determined by the proof sensors. The failure light comes on if the piece of equipment is not in the state its control is set for within its trouble indication time. This time is a maximum of 60 seconds for a fan (see note) and a maximum 75 seconds for a damper. If, within that time, the proof sensors do not report that the piece of equipment has responded to the control system command, the FSCS indicates that the piece of equipment has failed.
Note: Local codes may require shorter maximum times. The 60 second maximum time for the fan must
also account for ramp down time.
Testing the System
Related Documentation
During the installation, you should perform “operational tests” that make sure the components and subsystems of the smoke control system are installed correctly. After the installation is done, you must perform “acceptance tests,” to prove that the smoke control system is capable of doing what it was designed to do. The testing procedures are covered in a later chapter of this document.
The following is a list of additional documentation that may aid you in understanding and designing Smoke Control Systems.
Underwriters Laboratories, Inc., UL 864, Control Units and Accessories for Fire Alarm Systems.
The National Fire Protection Association. NFPA 92A, Recommended Practices for Smoke Control
Systems.
American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE).
Society of Fire Protection Engineers. Design of Smoke Management Systems.
The National Fire Protection Association. NFPA 90A, Standard for the Installation of Air Conditioning
and Ventilating Systems.
Underwriters Laboratories, Inc., UL 555S, Standard for Leakage Rated Dampers for Use in Smoke
Control Systems.
Underwriters Laboratories, Inc., UL 555, Fire Dampers.
1-20
Page 33
Page 34
Page 35
Page 36
Page 37
Chapter 3
Smoke Control System Components
Introduction
In this Chapter
This chapter presents a general overview of the Simplex Smoke Control System. It describes the UL-listed components used, the features of each component, and the role of these components within the system.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Smoke Control System 3-2
4100U/4100ES Panel 3-3
4190 TrueSiteTM Workstation System and 24 Point I/O Graphic Interface 3-4
Optional and Peripheral System Components 3-5
Firefighter’s Smoke Control Station 3-7
3-1
Page 38
Page 39
4100U/4100ES Panels
4100U/4100ES Panel
FigureTag FD4-465­02
A B C
D E F G H I
ZONE1SIG2AUX
3
SYSTEM IS NORMAL
J K L M N O P Q R
08:23:43 am MON 11-DEC-00
FB4IO5IDNet
6
AC Power
ALARMS
SYSTEM WARNINGS
S T U V W X Y Z /
Fire AlarmPriority 2 Alarm
Supervisory Trouble
Alarm Silenced
P7A8L
9
'SP' ( ) , 0 :
Fire Alarm
Priority 2
Supv
Trouble
Alarm
System
NET ADDR
Ack
Ack
Ack
Ack
Silence
Reset
DEL
0
Enter C/Exit
Event
More
Previous
Time
Info
Menu
On
Next
Enable
Arm
Off
Lamp
Disable
Auto
Disarm
Test
Emergency Operating Instructions
Alarm or Warning Condition
How to Silence Building Signals
System indicator flashing . To ne On . Press Alarm Silence.
How to Acknowledge / View Events
How to Reset System
Press ACK located under flashing indicator.
Press System Reset.
Repeat operation until all events are acknowledged.
Press Ack to silence tone device.
Local tone will silence.
Fire Control
(4100U Panel)
The 4100U or 4100ES panel serves as the system controller for the Simplex Smoke Control System. It controls the communications between the other system components within the smoke control system. This panel can be used in a dedicated or a non-dedicated smoke control application. The 4100U/4100ES connects to other panels in the following ways:
The panel can connect to other Simplex Fire Alarm Control Panels via network communications.
The can also connect to the FSCS using Remote Unit Interface (RUI) serial supervised communications
channel connections.
The Master Controller provides system control, synchronization, and supervision of all modules, continuously scanning each module for status changes. Features include:
Operator Panel with LCD and operator keys.
Battery Charger for up to 125 Ah Batteries.
– Batteries up to 50 Ah may be mounted in the bottom of the control cabinet
– Batteries larger than 50 Ah mount external to main control cabinet
Compatible with Lead Acid or NiCad Batteries
System Power Supply (SPS), Power Limited:
Supplies 9 A of alarm current and 5 A of standby current.
Two Class A or Class B NACs rated at 3 A each. Supports TrueAlert non-addressable
A/V operation without synch cube.
One 24 V auxiliary power tap, under software control.
Charges 125 Ah batteries per UL 864; 55 Ah batteries per ULC S527.
LCD readout of system voltage and current, battery voltage and current, and NAC current.
Integral 250 point IDNet™ channel.
AC input is 4A @ 120 VAC, 60 Hz; 2A @ 220/230/240 VAC, 60 Hz.
Includes one relay, DPDT, 2A @ 32 VDC
Landing point and control interface for optional two circuit City Card or three circuit
Relay Card. City Card is Reverse Polarity or Local Energy, configurable for alarm, trouble, and supervisory.
General Operating Specifications
Humidity: Up to 93% RH, Non-Condensing @ 90° F (32° C) Maximum
Temperature: 32° F to 120° F (0° C to 49° C)
3-3
Page 40
4190 TrueSite Workstation System and 24 Point I/O Graphic Interface
4190 TrueSite Workstation (TSW)
4190 TrueSite
Workstation TSW
The 4190 TrueSite Workstation (TSW) provides a graphical user workstation within the Simplex Smoke System. You can interact with the smoke control system by entering input through a keyboard, mouse, or touch-screen.
Note: If a TSW is used in the system, a Firefighter’s Smoke Control Station must be provided
and this station must initiate smoke control commands at the highest priority.
Graphic Screens:
TSW graphic screens can provide easily recognizable site plan and floor plan information. The level of detail can be customized for the specific facility to easily and accurately direct the operator to the immediate area of interest.
Icons can be optionally added to identify the exact device of interest and the operator can utilize TSW Pan and Zoom capabilities to move to a specific screen location for more detail.
When a system status change occurs, the screen displays the type and location of the activity. The operator then touches the appropriate screen area (or uses the mouse control) to access a more detailed view of the zone or device.
For example, the figure below shows some of the information available when viewing a point that represents a VESDA® early warning air aspiration smoke detector.
24-Point I/O Graphic Interface (4100-7401)
®
Figure 3-2. TSW Screen Showing VESDA
Information
The 24-Point I/O Graphic Interface (4100-7401) has the following features:
Each of the 24 points can be individually configured as either an input (e.g., switch) or output (e.g., lamp
or relay).
150 mA output (+24 VDC supervised for LED, incandescent, or relay operation).
Outputs can be steady, slow pulse, or fast pulse.
Switch inputs can monitor two position or three position switches.
Lamp test input.
Provides supervised monitoring and/or control for smoke control applications.
3-4
Page 41
Page 42
Page 43
Page 44
Page 45
Page 46
Page 47
Page 48
General Smoke Control Interconnections
Overview
A Simplex Smoke Control System is usually part of a larger Simplex Fire Alarm System. The Simplex Smoke Control System ties into the building air handling equipment, either dedicated, non-dedicated, or both, to form the overall Smoke Management system for the building.
Since Simplex equipment is not the primary control equipment for a building's non-dedicated air handling equipment, the interconnection between the Simplex Smoke Control System and the non-dedicated air handling equipment is critical. This interconnection must be done in such a manner to guarantee that the Smoke Control System takes priority, and that Smoke Control System commands cannot be overridden by other building systems.
Although every application is different, the sections that follow describe some typical methods for interconnecting to air handling elements to insure that Smoke Control System commands take precedence and that accurate monitoring of the air handling system is fed back into the Smoke Control System. Fan and damper control are shown in some detail to illustrate principles that can be extrapolated to other more special purpose applications. These principles should be generally applied to the detailed design of specific engineered smoke control solutions.
Smoke Control System operation is dependent both on the hardware and the control software. The wiring diagrams shown in this chapter, must be used with appropriate programming to create an operational control system.
4-2
Page 49
®
General Smoke Control Interconnections, Continued
UUKL Addressable Monitor/Control Devices for 4100U and 4100ES
Model Description IDNet™ MAPNET II® See Doc #
4090-9001
4090-9002
4090-9101 Class B monitor ZAM.
4090-9106 Class A monitor ZAM.
4090-9118*
4090-9119*
4090-9120* Six point module; four T sense inputs, 2 relays; one address.
4100-7401 24 Point I/O Graphic Module. –– ––
4100-7402 64/64 LED/Switch Controller. –– ––
4100-7403 32 Point LED Module –– ––
4100-7404 32 Point Switch Module. –– ––
4602-7101
The following table lists the UUKL addressable monitor/control devices for the 4100U or 4100ES system.
Table 4-1. UUKL Addressable Monitor/Control Device List for 4100U/4100ES
Supervised IAM, single address, single point; IDNet and 4100U/4100ES provide “T” sense (current limited monitoring); MAPNET II and 4100U/4100ES provide simple N.O. Class B monitoring.
Relay IAM, single address, single point; Form “C” with relay status tracking.
Relay IAM with T sense input, single address, dual point, relay and input.
Relay IAM with unsupervised input, single address, dual point, relay and input.
Graphic I/O, RCU/SCU (Remote Control Unit/Status Control Unit, selectable operation).
–– –– ––
–– 574-184
–– 574-874
–– 574-875
–– 574-876
574-331
574-183
841-802
S4100-0005
841-802
S4100-0005
841-802
S4100-0005
841-802
S4100-0005
Table 4-2. MAPNET II UUKL Addressable Monitor/Control Device List for 4100U/4100ES
Model Description IDNet™ MAPNET II
2190-9153 Class A Monitor ZAM, surface mount. ––
2190-9154 Class A Monitor ZAM, flush mount. ––
2190-9155 Class B Monitor ZAM, surface mount. ––
2190-9156 Class B Monitor ZAM, flush mount. ––
2190-9159 Class A Signal ZAM, surface mount. ––
2190-9160 Class A Signal ZAM, flush mount. ––
2190-9161 Class B Signal ZAM, surface mount. ––
2190-9162 Class B Signal ZAM, flush mount. ––
2190-9163 Control Relay ZAM, surface mount. ––
2190-9164 Control Relay ZAM, flush mount. ––
2190-9173*
* Devices designed specifically for Smoke Control Applications.
Note: These are common smoke control system components and do not include other commonly used fire detection
components such as pull stations, heat detectors, and initiation and notification appliances.
2-Point I/O Module supervised input and relay output; two sequential addresses.
––
See Doc #
574-668
575-279
574-995
Continued on next page
4-3
Page 50
Page 51
General Smoke Control Interconnections, Continued
Four Story Building Smoke Control Example
The figure below shows an application diagram for a four-story building. This figure illustrates how the elements of the Smoke Control System are architecturally related, how they fit within the overall Simplex Fire Alarm System, and how they relate to the building air handling systems.
Figure Legend Description
FACP Fire Alarm Control Panel (e.g., Model 4100U as described in Chapter 3).
FSCS Firefighter’s Smoke Control Station (as described in Chapter 3).
TSW TrueSite Workstation System (e.g., Model 4190 as described in Chapter 3).
C Relay IAM with Feedback (e.g., Model 4090-9118).
M Supervised IAM (e.g., Model 4090-9001).
D HVAC damper, supply or return (as described in Chapter 3).
DPS Damper position switch (as described in Chapter 3)
FAN Stairtower or elevator shaft pressurization fan.
S Other signaling line circuit devices (e.g., smoke detector, pull station, etc.)
ASW Air flow sensing switch (as described in Chapter 3).
Figure 4-1. Four-Story Building Smoke Control Example
4-5
Page 52
Page 53
Page 54
Page 55
Page 56
Page 57
Page 58
Page 59
Page 60
Page 61
Page 62
Page 63
Page 64
Dedicated Smoke Control System Weekly Self-Test, Continued
Equation 3: Test Stairwell Air Pressure
Equation 4: Reset Stair Pressure Fan to OFF
La be l: TEST STAIRWELL AIR PRESSURE Eq ua tio n 3
C O MMENTS: INPUTS: The O N state o f: P281 UTILITY START SELF TEST PRO G RAM AND the O N state o f: M1-9 C PRESS STAIR PRESS FAN DELAY fo r 10 se c s, running time r is A283 AND NOT the ON sta te o f: M1-42 UTILITY MO NITO R STAIR PRESS FA N O N O UTPUTS: HO LD p o ints ON p ri=9,9 P280 UTILITY STAIR PRESS FAN FAIL END:
La be l: RESET STAIR PRESSURE FAN TO O FF Eq ua tio n 4
C O MMENTS: INPUTS: The O N state o f: P281 UTILITY START SELF TEST PRO G RAM AND the O N state o f: M1-9 C PRESS STAIR PRESS FAN DELAY fo r 60 se c s, running time r is A284 O UTPUTS: HO LD p o ints OFF p ri=9,9 M1-9 C PRESS STAIR PRESS FAN P281 UTILITY START SELF TEST PRO G RAM PRINT to All po rts/ lo g s/ disp lays "SELF TEST PRO G RAM IS C OMPLETE" END:
Equation 5: End of Program
La be l: [END-OF-PRO G RAM] Eq ua tion 5
5-4
Page 65
Page 66
Page 67
Page 68
Page 69
Page 70
Page 71
Page 72
Page 73
Page 74
Page 75
Page 76
Page 77
Page 78
Page 79
Page 80
Page 81
Page 82
Page 83
Page 84
Page 85
Page 86
Page 87
Page 88
Page 89
Page 90
Smoke Control System Custom Control Equations, Continued
Equation 77: Turn SONALERT ON
Equation 78: Turn SONALERT OFF
La be l: TURN SONALERT O N Eq ua tio n 77
C O MMENTS: INPUTS: O R the O N sta te o f: P260 UTILITY FL1 SUPPLY AIR DAMPER FA IL P261 UTILITY FL2 SUPPLY AIR DAMPER FA IL P262 UTILITY FL3 SUPPLY AIR DAMPER FA IL P263 UTILITY FL4 SUPPLY AIR DAMPER FA IL P264 UTILITY FL1 EXHAUST AIR DAMPER FAIL P265 UTILITY FL2 EXHAUST AIR DAMPER FAIL P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL P268 UTILITY MAIN SUPPLY FA N FAIL P269 UTILITY MAIN EXHA UST FAN FA IL P270 UTILITY MAIN RETURN AIR DAMPER FAIL P271 UTILITY MAIN SUPPLY AIR DAMPER FAIL P272 UTILITY MAIN EXHA UST AIR DAMPER FAIL P280 UTILITY STAIR PRESS FAN FAIL AND NOT the ON sta te o f: P290 UTILITY SET NO RMAL C ONDITIO NS A T RESET O UTPUTS: HO LD p o ints ON p ri=9,9 P293 UTILITY PIEZO AC TIVATE END:
La be l: TURN SONALERT O FF Eq ua tio n 78
C O MMENTS: INPUTS: The UP sta te o f: 8-82 SWITC H SILENCE SWITC H And the O N state o f: P273 UTILITY MASTER KEY SWITC H ENABLE O UTPUTS: HO LD p o ints OFF p ri=8,9 P293 UTILITY PIEZO AC TIVATE END:
La be l: [END-O F-PRO GRAM]
5-30
Page 91
Page 92
Page 93
Page 94
Page 95
Page 96
Page 97
Page 98
Page 99
Index
2
24-Point I/O Graphic Interface, 3-4
4
4010 Fire Alarm Control Panel (FACP), 3-5 4020 FACP, 3-5 4190 TrueSite Workstation, 3-4
A
acceptance tests, 1-20 additional documentation, 1-20 air inlets and outlets, 1-12 air pressure, 1-1, 1-11 air pressure differential, 1-3 air pressure, differences in, 1-3 amber/orange indicators, 3-8 ASHRAE, 1-15 audible signal, 3-9 automatic door closing mechanism, 1-14 automatic fire suppression systems, 1-2
B
bypass duct dampers, 1-17 bypass pressure control system, 1-17
C
causes of smoke movement, 1-6
buoyancy, 1-6 expansion, 1-6 HVAC system, 1-6 stack effect, 1-6
wind, 1-6 Cautions and Warnings, 1-3 clear faults button, 3-9 compensated, 1-15 compensated stairtower smoke control
system, 1-17
D
dampers, 3-8 dedicated damper control, 4-6 dedicated fan control, 4-8 dedicated smoke control, 2-3 dedicated smoke control system, 1-8 Dedicated Smoke Control System Weekly
Self-Test, 5-2, 5-3 dedicated smoke control system wiring, 4-6 dedicated system, 1-13 duct smoke detector with relay, 3-6
E
elevator shafts, 1-18 Emergency Operation, 5-2 end-range switches, 1-20 Equation 1
Start Self Test, 5-3
Equation 2
Turn ON Stair Pressure Fan, 5-3
Equation 3
Test Stairwell Air Pressure, 5-4
Equation 4
End of Program, 5-4 Test Stairwell Air Pressure, 5-4
F
fans, 3-8 fans and duct work, 1-11 fire control system, 1-9 fire damper, 1-12 fire detection system, 1-19 fire extinguishers, gas-based, 1-9 fire suppression systems, 1-2 fire zone, 1-5 Firefighter Smoke Control Station, 3-7 Firefighter's Smoke Control Station (FSCS),
1-19 fire-rated ceiling, 1-11 fire-rated partition, 1-11 FSCS graphic, 3-8 FSCS indicators, 1-20
G
gaseous agent fire suppression system, 1-2 ground-level stairtower, 1-17
H
HVAC system, 1-11
I
IAM, 3-6 ideal stairtower, 1-14 indicator lights, 1-20
L
lamp test button, 1-20, 3-9 LCD Annunciator, 3-5
M
managing smoke movement, 1-7
barriers, 1-7
smoke vents and smoke shafts, 1-7
Page 100
manual control panel, 1-19 manual fire alarm pull boxes, 2-4 manual pull boxes, 1-9 manual pull stations, 1-19 manually-operated damper, 1-17 master key-switch, 3-8 monitored switches, 2-3
N
National Fire Protection Association, 1-9 negative air pressure technique, 1-4 Network Display Unit (NDU), 3-5 NFPA 101, 1-14 NFPA 90A, 1-11 NFPA 92A, 1-9, 1-11, 1-14, 2-4 non-compensated, 1-15 non-dedicated damper control, 4-10 non-dedicated fan control, 4-13 non-dedicated smoke control, 2-3 non-dedicated smoke control system, 1-8 non-dedicated systems, 1-20
O
operational tests, 1-20
P
piston effect, 1-18 positive air pressure, zones, 1-4 pressure buildup, 1-11 pressure differential, 1-14 pressure monitor, 1-20 pressurizing an elevator, 1-18 proof sensors, 1-20, 2-3
S
smoke barriers, 1-11
smoke control interconnections, 4-2 Smoke Control Program Requirements, 5-2 smoke control system, 1-9 Smoke Control System Custom Control
Equations, 5-5 smoke control systems, 1-1 smoke control zones, 1-5 smoke damper, 1-11 smoke dampers, 1-12 smoke management, 3-8 smoke migration, 1-18 smoke zones, 3-8 stack effect, 1-3 stairtower, 1-13 stairtower pressurization by multiple
injection, 1-14 Stairtower smoke control systems, 1-15 status indicators, 3-8 System Accessories, 3-6
T
tenable environment, 1-8, 1-10 transient pressures, 1-18
U
UL 555, 1-12 UL 555S, 1-12 UL 864, 1-9
V
vane or pressure differential switches, 2-3
Z
ZAM, 3-6
Loading...