Tyco Safety Products – Westminster, gratefully acknowledges the contributions of the following
organizations to this publication:
•American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
(ASHRAE), Atlanta, GA.
• Andover Controls Corporation, Andover, MA.
• Center for Fire Research, National Engineering Laboratory, National Bureau of Standards,
U.S. Department of Commerce, Washington, DC.
• Integrated Systems, Inc., Brunswick, MD.
• National Fire Protection Association, Inc. (NFPA), Quincy, MA.
• U.S. Veterans Administration, Office of Construction, Washington, DC.
Page 4
Cautions and Warnings
Cautions and
Warnings
READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
manual. These instructions must be followed to avoid damage to this product and associated
equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY PRODUCT THAT APPEARS DAMAGED.
Upon unpacking your product, inspect the contents of the carton for shipping damage.
If damage is apparent, immediately file a claim with the carrier and notify your distributor.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal
adjustments or repairs. All repairs should be performed by a representative or authorized agent of
your local Simplex® product supplier.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
1. Ground yourself before opening or installing components.
2. Prior to installation, keep components wrapped in anti-static material at all times.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to
comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
To further the science of Smoke Management, Tyco Safety Products hereby grants permission to
reproduce or transmit this reference document in any form or by any means, electronic or
mechanical, for the purpose of obtaining information on the science of Smoke Management.
We retain the rights of our respective trademarks.
Simplex, the Simplex logo, TrueSite, TrueAlarm, and IDNet are either trademarks or registered
trademarks of Tyco International Ltd and its affiliates and are used under license. NFPA 72 and
National Fire Alarm Code are registered trademarks of the National Fire Protection Association
(NFPA).
Walk Test™ is protected by US Patent No. 4,725,818.
MAPNET II® addressable communications is protected by U.S. Patent No. 4,796,025.
IDNet™ is patent pending.
TrueAlarm® Analog Detection is protected by U.S. Patent No. 5,155,468.
TrueAlarm® Detector Base is protected by U.S. Patent No. 5,173,683.
Windows® is a registered trademark of the Microsoft Corporation.
VESDA Scanner™ and MiniVESDA™-50 are trademarks and the name VESDA® and
VESDA® E70-D are registered trademarks of Vision Systems.
All other logos are trademarks or registered trademarks of their respective companies.
Index ............................................................................................................................ 6-1
vi
Page 11
About This Guide
Conventions Used
Before you start using the Smoke Management Application Guide, it is important to understand the
conventions used in this publication.
The following conventions are used to identify special names or text.
• Italic type indicates titles of publications, such as the Smoke Management Application Guide.
• Text enclosed in quotation marks indicates important terms or titles of chapters and sections
of the manual, such as “How to Use this Publication.”
•Bulleted lists, such as this one, provide you with information. They are also used to indicate
alternatives in numbered procedural steps.
•Numbered lists indicate procedures with steps that you must carry out sequentially.
vi
Page 12
Page 13
Chapter 1
How Smoke Control Systems Work
Purpose
Introduction
The information in this guide serves to define the intended function of Smoke Control System
Equipment and also explain what operational and performance requirements are necessary for
equipment listed under the UL listing category of UUKL.
IMPORTANT: Smoke control systems must be designed to meet the custom
needs of a particular building and its occupants. This document
This product is subject to change without notice. This document does not constitute any warranty,
express or implied. Tyco Safety Products reserves the right to alter capabilities, performance, and
presentation of this product at any time.
Many people are not aware that smoke is the major killer in fires. Smoke can travel to places in
buildings that are quite distant from the scene of the fire, threatening life and property. It can fill
stairwells and elevator shafts, blocking both evacuation and firefighting. Smoke control systems
reduce the number of smoke-related injuries and deaths. In addition, these systems reduce property
loss and damage caused by smoke.
Smoke control makes use of powered fans to produce air pressure that can control smoke
movement. Air pressure has been used in laboratories for over fifty years to prevent airborne
bacteria and poison gases from migrating from one area to another. It has also been used to control
the entrance of dust and other contaminants into computer rooms; and used in hospitals to prevent
the migration of harmful bacteria into sterile areas.
This chapter gives you an overview of smoke-control systems, including a discussion of the
driving forces of smoke movement, the principles of smoke control, and the concepts of smoke
control system design.
illustrates some basic, common smoke control applications, but is
not in lieu of a properly engineered smoke control system,
designed by a qualified Fire Protection Engineer.
In this Chapter
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Introduction 1-2
Controlling Smoke Movement 1-3
Principles of Smoke Control Systems 1-8
Smoke Control and Fire Control Systems Differences 1-9
Designing a Smoke Control System 1-10
Designing a Dedicated Smoke Control System 1-13
Detecting Smoke 1-19
1-1
Page 14
Introduction
Design Parameters
Design Concepts
A smoke control system can be designed to provide an escape route and/or safe zone.
However, all smoke control systems have the following design parameters:
• Air-flow paths through a building and leakage areas.
• Pressure differences across smoke control system boundaries.
• Door or vent openings in the boundary of a smoke control system.
• Airflow through openings in smoke control system boundaries.
The following factors can affect the design of a smoke control system:
System Flexibility:
System flexibility means using features that allow for easy adjustment of a particular system to
meet the demands of a given situation. For example, during the design and construction of a
building, leakage paths can be estimated. Thus, a smoke control system can only be designed to
provide theoretical protection from smoke. After the building is completed, the system must be
tuned to the actual pressure values. System flexibility is also useful when retrofitting smoke
control systems in existing buildings.
System Control:
A smoke control system should be designed to automatically activate, preferably by an alarm from
a smoke detection system in the fire zone. The advantage of this type of activation is that the
system is activated in the earliest stages of a fire. Smoke control systems should be activated after
the receipt of alarms from a properly designed smoke detection system.
Energy Conservation Management:
Energy conservation methods must be considered when designing a smoke control system.
A smoke control system must be designed to override the local heating, ventilation, and air
conditioning (HVAC) system, or energy management system in order to implement the desired
smoke control operations.
Use of Fire Suppression Systems:
Many fire protection schemes use automatic fire suppression systems. However, while the
functions of fire suppression and smoke control are both desirable, they are not intended to
substitute for each other.
Fire suppression systems are intended to limit the growth rate of a fire. Smoke control systems can
provide safe zones and tolerable conditions along exit routes, but can do little to control fire. In
addition to the obvious differences between the two systems, the way the systems interact must be
considered. For example, pressure differences and air flows are different in the various buildings
within a complex that is protected by a fire suppression system. A water spray from a sprinkler
might interfere with air flow to a smoke exhaust or an outside air pressure system or a smoke
control system could interfere with the performance of a gaseous agent (e.g., Carbon Dioxide or
Nitrogen) fire suppression system.
A general guideline is that the gaseous agent fire suppression system takes precedence over the
smoke control system. It is also desirable that the smoke control system be able to purge the
residual gases and smoke after the fire is extinguished, and replace them with fresh air. This is an
important life-safety consideration, since some fire-suppression gases are asphyxiates.
1-2
Page 15
Controlling Smoke Movement
Basic Concept
Second Floor
Regardless of the method, the basic concept behind controlling smoke is to use differences in air
pressure to minimize the spread of smoke and, if possible, vent it from the building.
You cannot confine smoke by simply closing all access ways (such as doors and vents) to the
room that has the fire in it. Even with these passages closed off, smoke can disperse throughout a
building via cracks, holes made for pipes and electrical wires, and spaces around doors and
windows. Smoke is driven through these small openings by the expanding gases from the fire.
Smoke can also be driven onto other floors by the “stack effect,” which causes air to rise in
buildings. The stack effect is caused by the difference in the interior and exterior temperature of
the building. The figure below shows how smoke can disperse throughout a building:
Adjacent Room
Adjacent Room
Adjacent Room
SM OK E
First Floor
Adjacent Room
Area On Fire
Adjacent Room
Figure 1-1. Smoke Infiltrating Rooms Adjacent to the Fire
Continued on next page
1-3
Page 16
Controlling Smoke Movement, Continued
Basic Concept
Since smoke is carried by the movement of air, you can stop the spread of smoke throughout the
building by lowering the air pressure in the area containing the fire and by raising the air pressure
in the surrounding areas and floors. The difference in air pressure (also called the “Air Pressure
Differential”) between the smoke-filled area and the surrounding areas acts as a barrier to the
smoke, pushing it back into the smoke-filled area. The figure below shows how this works.
FigureTag FD4-465-01
POSITIVE
AIR PRESSURE
POSITIVE
AIR
PRESSURE
POSITIVE
AIR PRESSURE
NEGATIVE
PRESSURE
POSITIVE
AIR PRESSURE
POSITIVE
AIR
PRESSURE
POSITIVE
AIR PRESSURE
Figure 1-2. Applying Positive Air Pressure to Control Smoke
1. Lower the air pressure in a smoke-filled area by controlling the air flow into it and turning
ON the exhaust fans from the area to full capacity. This “Negative Air Pressure” technique
pulls the smoke out of the area and vents it outside of the building.
2. Pressurize the areas and floors surrounding the fire by turning OFF all exhaust systems
(including closing any exhaust dampers) and forcing supply air to those areas at full capacity,
creating zones of “Positive Air Pressure.” The air in the pressurized areas tends to leak into
the smoke zone, using the same cracks and holes that the smoke would use to get out. This
positive pressure airflow into the burning room keeps the smoke from spreading.
POSITIVE
AIR PRESSURE
POSITIVE
AIR PRESSURE
Continued on next page
1-4
Page 17
Controlling Smoke Movement, Continued
A
Basic Concept
3. Turn OFF the air inlets and air returns of the areas that are neither being pressurized nor
depressurized (i.e., areas far away from the fire). Turning OFF the air return prevents the
smoke that is being vented into the return air system from coming into the smoke-free area.
In cases where there are large openings (such as an open doorway) between the area on fire
and an adjacent area, smoke can be confined by a large volume of air. Pumping large
amounts of air through the adjacent space creates a constant draft through the opening into the
smoke zone (as shown below).
IR
A
CENTRIFUGAL FAN
Figure 1-3. Confining Smoke with a Large Volume of Air
The draft through the open space keeps back the smoke, confining it to the smoke zone. The
amount of air required to keep the smoke from penetrating the open space is quite large. Avoid
this type of situation when possible.
I
R
AIR
SMOKE
Creating
Smoke Zones
To contain smoke by using pressure, you must divide the building into “Smoke Control Zones.” A
floor or several floors of the building can be considered a single zone or a single floor can be
broken into a number of zones. A zone must be separated from other zones by smoke dampers,
airtight doors, and smoke-proof barriers.
When a fire occurs, the smoke control system can then pressurize all of the zones around the zone
where the fire initiated (called the “Fire Zone”), isolating the smoke to that single zone.
If the smoke control system is non-dedicated, the layout of the smoke control zones should take
into consideration the layout of the HVAC system. You should place multiple areas served by the
same HVAC controls in the same smoke control zone. Also, the smoke control zones must
conform to any fire control zones that have been established, because the smoke detectors are tied
into the fire detection system. Also, keeping the smoke control zones and the fire control zones the
same makes it easier to coordinate the two systems.
1-5
Page 18
Controlling Smoke Movement, Continued
Causes of
Smoke Movement
The following forces affect smoke movement:
Stack Effect:
When the outside air temperature is colder than the temperature inside a building, there is often an
upward movement of air within the building. This air movement is most noticeable in stairwells,
elevator shafts, electrical risers, or mail chutes, and is referred to as “Normal Stack Effect.” This
phenomenon is most noticeable in tall buildings during winter, but can occur in a single story
building as well.
When the outside air temperature is warmer than the temperature inside a building, there is often a
downward movement of air within the building. This air movement is referred to as “Reverse
Stack Effect.”
In a building with normal stack effect, the existing air currents can move smoke a considerable
distance from the fire origin. If the fire is below the neutral plane of the shaft (i.e., an elevation
where the hydrostatic pressure inside the shaft equals the hydrostatic pressure outside the shaft),
smoke moves with the building air into and up the shaft. Once above the neutral plane, smoke
flows out of the shaft into the upper floors of the building.
Buoyancy:
Smoke from a high temperature fire has buoyancy due to its reduced density. In a building with
leakage in the ceiling of the fire room, this buoyancy-induced pressure can produce smoke
movement. In a fire room with only one opening to the building, air flows into the room while hot
smoke flows out of the room. If the fire room has open doors or windows, the pressure difference
across these openings is negligible because of the large flow areas involved. However, for a
tightly-sealed room, the pressure differences due to expansion may be important.
Wind:
Wind can also have a pronounced influence on smoke movement within a building. The effect of
wind velocity on the air movement within a well-constructed building is minimal. However, the
effects of wind can become important for loosely-constructed buildings or buildings with open
doors or windows.
Frequently in fires, a window breaks. If the window breaks on the side of the building away from
the wind (the leeward side), the negative pressure caused by the wind vents the smoke from the
fire room. This can greatly reduce smoke movement within the building. However, if the broken
window is on the windward side of the building, the positive pressure of the wind can force the
smoke throughout the fire floor, and possibly to other floors as well. This event can endanger lives
and hamper firefighters as well. Wind induced pressures can be quite large and can easily
dominate building air movement.
Continued on next page
1-6
Page 19
Controlling Smoke Movement, Continued
Causes of
Smoke Movement
Managing
Smoke Movement
HVAC System:
Before the development of smoke control systems, HVAC systems were shut down when a fire
occurred. This is because an HVAC system frequently transported smoke during building fires.
In the early stages of a fire, HVAC smoke transport can be a good thing. When a fire starts, the
HVAC system can transport the smoke to a location where people can smell it and be alerted to
the fire (although they may not know where the smoke is coming from). However, as the fire
progresses, the HVAC system transports the smoke to every area that it serves, endangering life in
all those places. To make matters worse, the HVAC system also supplies air to the fire, which aids
combustion.
Although shutting down the HVAC system prevents it from supplying air to the fire, this action
does not prevent the movement of smoke through the supply and return air ducts, air shafts, and
other building openings due to stack effect, buoyancy, or wind effect.
“Smoke Movement Management” includes all of the methods that can be used to modify and
control smoke movement for the benefit of the building occupants, firefighters, and for the
reduction of property damage. The use of barriers, smoke vents, and smoke shafts are traditional
methods of smoke management.
Barriers:
The effectiveness of barriers in limiting smoke movement depends on the leakage paths in the
barrier and on the pressure differential across the barrier. Holes where pipes penetrate floors or
walls, cracks around doors, and cracks in walls or between walls and floors are a few of the places
where smoke can leak through a barrier. The pressure differential across these barriers depends on
wind, buoyancy, stack effect, and the HVAC system.
Smoke Vents and Smoke Shafts:
The effectiveness of smoke vents and smoke shafts depends on their distance from the fire, the
buoyancy of the smoke, and the presence of other driving forces. In addition, when smoke is
sprinkler-cooled the effectiveness of smoke vents and smoke shafts is greatly reduced.
Elevator shafts in buildings have often been used as smoke shafts. The obvious problem with this
is that it prevents the elevator from being used for fire evacuation (because of the “piston effect”
of an elevator), and frequently allows the smoke to travel between floors. Specially designed
smoke shafts which have no leakage can be used to prevent the distribution of smoke to fire-free
floors.
In summary, the effectiveness of barriers in a traditional smoke management system is limited to
the extent that the barriers are free of leakage paths. Smoke vents and smoke shafts are limited by
the fact that the smoke must have sufficient buoyancy to overcome other forces that may be
present.
In the last few years, motorized fans have been used to overcome the limitations of the traditional
systems. The systems that employ these motorized fans are called “Smoke Control Systems.”
These Smoke Control Systems rely on creating air pressure differences and positive or negative
airflows to limit and control the movement of smoke and other noxious gases.
1-7
Page 20
Principles of Smoke Control Systems
System Types
Maintaining
System Integrity
Two types of smoke-control systems exist – Dedicated and Non-dedicated.
•Dedicated Smoke Control System: Is installed in a building for the sole purpose of
controlling smoke.
•Non-dedicated Smoke Control System: Uses parts of the building HVAC system to control
smoke.
In some cases, a building has both non-dedicated and dedicated systems. Non-dedicated systems
are used throughout the building for normal areas such as offices and manufacturing facilities.
Dedicated systems are used for special areas, such as elevator shafts, stairwells, stairtowers, and
other areas that need special smoke-handling techniques.
Smoke Control System products connect to HVAC equipment to form a system for controlling the
flow of smoke during a fire condition. Smoke-control systems are designed, installed, and
maintained so that a system remains effective and provides a “Tenable Environment” during
evacuation of the protected areas. A “Tenable Environment” as defined in NFPA 92A, is an
environment in which the quantity and location of smoke is limited or otherwise restricted to allow
for ready evacuation through the space.
A major concern with any emergency signaling system, whether burglary, fire, or smoke control,
is maintaining system integrity. This task is traditionally accomplished by electrical supervision of
wiring. However because the proper operation of the fans and dampers connected to the output
circuits may involve mechanical controls and pneumatic controls, as well as electrically-actuated
parts, end-process verification is provided. The end-process verification is provided to alert the
firefighter/operator that the fan or damper has operated in response to an automatic or manual
command issued during an emergency condition. While end-process verification confirms
operation during an emergency condition, system integrity during a non-emergency
(normal supervision) conditions is checked differently depending on whether the equipment is
non-dedicated or dedicated.
The operability of the non-dedicated smoke-control equipment is verified by the "comfort level" in
the areas that are served by the equipment. In other words, if the HVAC equipment is not
functioning properly, the building occupants are soon made aware of this and the problem can be
solved.
The operability of the dedicated smoke control equipment is verified by an automatic self-test that
is performed on a weekly basis.
1-8
Page 21
Smoke Control and Fire Control System Differences
Separate System
for Separate Goals
The smoke control system is usually separate from the fire control system, since they have
different goals. The goal of the fire control system is to contain and extinguish the fire as fast as
possible. These systems, which halt the fire but not the smoke, are often triggered automatically,
relying on the heat of the fire to activate the system. Although smoke control systems are also
automatic, you must have manual overrides for the automatic controls.
A smoke control system may also be required to work with gas-based fire extinguishers, such as
gaseous agent systems installed in many computer rooms. If the smoke control system tries to vent
a room with such a system, it may vent the fire suppressing gas as well. Removing the gas lets the
fire continue burning. Also, pressurizing the areas surrounding an extinguisher equipped room
reduces the effectiveness of the system. Air forced into the room from the outside by pressure can
provide the fire with the oxygen it needs to continue burning. Therefore, gas-based fire
extinguishers and smoke control systems should not be active at the same time in the same
area.
The smoke control system receives the location of the fire from the fire panel. The fire panel uses
a combination of smoke and heat sensors to determine where the fire is located. As defined in
NFPA 92A: In the event that signals are received from more than one smoke zone, the smoke
control system will operate in the mode determined by the first signal received.
Specific, zoned smoke control strategies should never be triggered by manual pull boxes. The
risk of someone pulling a box someplace other than the fire zone is too high for you to trust your
smoke control system to this form of activation.
All smoke control systems installed in buildings must be in accordance with the standards
adopted by local codes. You can find additional information regarding fire alarm control units in
Underwriters Laboratories Standard UL 864 and the National Fire Protection Association (NFPA®).
1-9
Page 22
Designing a Smoke Control System
Basic Goal
How to Begin
Engineering
Responsibility
The basic goal of the smoke control system is to maintain a tenable environment. A tenable
environment allows:
• The building occupants to evacuate safely from the building.
• The firefighters to get quickly to the fire zone.
The first step to take in designing a smoke control system is to lay out the smoke control zones,
as previously explained. After the smoke zones are established, address the following design
factors:
• The zone-by-zone smoke control plan.
• The amount of pressure needed to contain smoke.
• Proper separation between zones.
• The fans and duct work used in the smoke control system.
• Dampers required for smoke control.
• The air inlets and outlets used in the smoke control system.
Smoke control systems must be engineered by qualified personnel. Complete calculations of
system designs are the responsibilities of the Engineer of Record and go beyond the scope of this
publication. A high level of coordination is required between the engineers, Authority Having
Jurisdiction (AHJ), and system designers who are involved in the process.
Creating the
Zone-By-Zone
Smoke Control Plan
You must create a smoke control plan for each zone in your building. Each smoke control zone
plan consists of the number of steps the smoke control system must take to contain the smoke in
the building zone. For each zone, you must decide:
• Whether you should depressurize the zone if a fire occurs.
• If the zone is to be depressurized, by how much you should depressurize it.
• Which adjacent zones should be pressurized and how much pressure is required.
Some zones in a building may need special consideration. As mentioned earlier, zones that have
gas fire extinguisher systems should not be vented (depressurized) and the zones surrounding the
fire zone with such a system should not be pressurized. You may not be able to pressurize other
areas, such as hospital labs or biological research labs, due to the risk of contaminating
surrounding areas with germs or toxins from these facilities.
Consider the number of zones surrounding the fire zone that should be pressurized. While, in
theory, all you need to do is to pressurize all of the zones immediately surrounding the fire zone, it
is possible that smoke can find a way around the pressurized areas and infiltrate distant zones.
Thus, depending on the size of the building and the capacity of the smoke control system, you may
decide to pressurize more zones.
Note: An increase in the number of zones to be pressurized means a corresponding increase in
the size of the air supply system.
Make certain to write down the state that all fans, dampers, and other smoke control equipment
should be in to control smoke in each zone. Then program this information into the smoke control
system.
1-10
Page 23
Designing a Smoke Control System, Continued
Determining the
Smoke Containment
Pressure
Since air pressure is what keeps smoke from spreading, the primary design factors are the amount
of pressure needed to confine the smoke, and the size of the system used to create this pressure.
For the smoke control system to create a barrier of air pressure between the smoke zone and
surrounding zones, the amount of pressure required varies with the height of the ceiling and
whether or not the building has a sprinkler system. The table below gives examples of the
minimum pressure differential needed to keep smoke out of rooms surrounding the fire site as
defined in NFPA 92A.
Table 1-1. Examples of Fire Zone Minimum Pressure Differential
Sprinkler System Ceiling Height
Minimum Pressure
Differential (in.)*
Yes Any 0.05 in.
No 9 ft. 0.10 in.
No 15 ft. 0.14 in.
No 21 ft. 0.18 in.
* in. = Inches, Water Gauge
Pressure buildup in an area depends on the amount of leakage. Leakage occurs through joints,
cracks, openings for pipes and wires, gaps between doors and their door jams, and so forth.
The better the zone is sealed off from neighboring zones, the easier it is to maintain the required
pressure. Since larger openings, like normally-open doorways, require large amounts of air to
maintain pressurization, you should avoid this type of situation.
Separating Smoke
Zones Properly
Selecting the Proper
Fans and Duct Work
You must separate smoke zones from one another by “smoke barriers,” which prevent smoke from
passing through them. Smoke barriers can be a wall, a floor, or a ceiling. Any openings in the
smoke barrier must be closed with a smoke-proof fitting. For example, any duct work going
through a smoke barrier must have “smoke dampers” installed. A smoke damper is a damper that
prevents smoke from passing through it when fully closed. During a smoke emergency all of the
fittings should seal themselves, so that smoke cannot penetrate the barrier.
Since the smoke control zones should be the same as the fire control zones, you usually separate
your zones with a “fire-rated partition.” A fire-rated partition is a wall that is built of fire resistant
materials and that reaches from floor to ceiling. Different floors should be separated by a “firerated ceiling,” a ceiling made of fire-resistant materials. Both fire-rated partitions and fire-rated
ceilings are rated for the amount of time they can withstand a fire. Any openings in a fire-rated
partition or ceiling must be capable of being sealed with a fire-rated closure, such as a fire-rated
door or fire damper.
The fans and duct work used in the smoke control system must be capable of providing the
amount of pressure you calculated earlier. In a non-dedicated system, this may mean that you
need to install fans that have a higher capacity than the HVAC system normally requires. The
ducts must be capable of taking the pressurization (or the depressurization, for the fire zone's
return duct) that the smoke control system demands. Both the fans and the ducts should meet local
requirements such as those stated in NFPA 90A, Standard for the Installation of Air Conditioning
and Ventilating Systems.
Continued on next page
1-11
Page 24
Designing a Smoke Control System, Continued
Selecting the Proper
Fans and Duct Work
Choosing the
Proper Dampers
Fans must be capable of reaching the required pressure setting within 60 seconds. Each fan must
also have a pressure monitor so that the smoke control system can receive feedback on the status
of the fan to determine whether it is actually working. It is the responsibility of the system
designer to select duct work that meets the temperature and fire ratings for the specific application.
In some climates, the outside air can be so cold that drawing it directly inside the building for
pressurization can damage the building's interior fixtures or equipment (e.g., freeze pipes or
damage temperature-sensitive equipment). In these cases, some sort of pre-heater needs to be
installed on the air inlet. The smoke control system does not need to control this air intake heater
as closely as one on an HVAC system, since maintaining comfort levels is not an issue. It simply
has to make sure the air sent into an area is warm enough to not damage the building's equipment.
The dampers used to isolate the smoke zone must be smoke dampers. Smoke dampers are dampers
that meet the requirements given in UL 555S, Standard for Leakage Rated Dampers for Use in Smoke Control Systems. Following this standard ensures that the dampers are able to block the
smoke when they are fully closed. These dampers may be different from those you might use in an
HVAC system that does not perform smoke control.
In a smoke control system, the dampers must be able to travel to their desired setting in a maximum
time of 75 seconds (see note below). All dampers must be fitted with end-position switches to
provide feedback to the smoke control system. These switches let the control system know the
position of the dampers, since smoke dampers are usually either fully-closed or fully-open.
Note: Local codes may specify a shorter maximum time.
Dampers sometimes function as both smoke dampers and fire dampers. Fire dampers are dampers
that block a fire from penetrating a fire-rated partition via a duct. These dampers are normally
open, held in place by a fusible link. The fusible link is a heat-sensitive device that releases the
dampers when it is heated to a certain temperature. Once the fusible link releases, the dampers
close by the force of gravity. This is required so that fire dampers operate even if the local electric
service has failed. The specifications for fire dampers appear in UL 555, Standard for Fire Dampers.
If you want a damper to function as both a smoke damper and a fire damper, it must meet the
requirements for both devices. A damper can be operated by an electric motor or pneumatics.
However, it must have a fusible link or some other means of automatic closure (like a regular fire
damper). Since the control system can override the damper closure if the temperature warrants, the
damper needs the fusible link in case the damper’s automatic control is interrupted.
Placing Air Inlets
and Outlets
You need to carefully consider the placement of the air inlets and outlets on your building. If you
place an outlet that vents smoke too close to an air inlet, the air intake can draw the smoke back
into the building. Since smoke rises, the exhausts that vent smoke should be placed well above air
inlets. The exhausts should be placed several feet above the roof level to allow space for the
smoke to rise and disperse.
Keeping smoke outlets far away from air inlets does not guarantee that the air brought into the
building is always smoke free. You may want to place smoke detectors in air inlets that operate
during a smoke emergency.
Note: In some cases, smoke detection in the air inlet is required to have the capability of being
overridden by the responding authority after the situation has been investigated.
If the detector finds smoke in the incoming air, it alerts the control system. The control system
must then decide whether or not to shut down the air inlet.
1-12
Page 25
Designing a Dedicated Smoke Control System
Introduction
About Stairtowers
Most of the systems discussed so far have been non-dedicated systems. Even in a building where
the primary smoke control system is non-dedicated, special zones or functions may exist that
require a “dedicated” system. The most common example of a dedicated system is a dedicated
smoke control system for a stairtower.
A “stairtower” is a stairwell with a ventilation system that is isolated from the main building.
The only connection between the building and the stairtower are fire-rated doors on each floor.
Since the building occupants should use the stairtower to leave during an evacuation, keeping the
stairtower smoke-free is vital.
A stairtower has its own dedicated system that pressurizes the stairtower to keep smoke out.
This dedicated system can take several forms, from a fan mounted in the roof of the stairtower, to
a duct system that delivers air to each level.
You must pressurize a stairtower enough to keep smoke out. However, if the pressure in the
stairtower is too great, then opening the doors leading into the stairtower can be difficult.
(See the figure below.)
Too Much Pressure
Building
Too Little Pressure
Building
Stairtower
Stairtower
Figure 1-4. The Effects of Too Much or Too Little Pressure
1-13
Page 26
Designing a Dedicated Smoke Control System, Continued
Designing the Ideal
Stairtower System
The ideal stairtower smoke control system must pressurize the stairway enough to keep the smoke
out, but it must not pressurize it so much that the doors cannot be opened. An example of a
dedicated smoke control system for a stairtower is shown in the figure below.
Exhaust Fan
Air Supply Duct
Air Flow
Fire Rated
Doors
Pressure Vents
Air Flow
Supply Fan
Ensuring Doors
Can Open
Figure 1-5. Stairtower Pressurization by Multiple Injections
The figure above shows stairtower pressurization by multiple injections with a supply fan located
at ground level and an exhaust fan located on the building roof.
The table below shows the maximum allowable pressure differential across a door in inches water
gauge (in.) based on how wide the door is and how much force the automatic door closing
mechanism exerts as defined in NFPA 92A. At the pressures shown in the table, the door requires 30
lbf (pounds of force) to open, the maximum limit suggested by the NFPA Life Safety Code (NFPA
101).
Table 1-2. Pressure Differential For Various Door Widths
.
Door Closer
Force (lbf)
6
8
10
12
14
32 in. 36 in. 40 in. 44 in. 48 in.
0.45 0.40 0.37 0.34 0.31
0.41 0.37 0.34 0.31 0.28
0.37 0.34 0.30 0.28 0.26
0.34 0.30 0.27 0.25 0.23
0.30 0.27 0.24 0.22 0.21
Pressure Differential
Continued on next page
1-14
Page 27
Designing a Dedicated Smoke Control System, Continued
Ensuring Doors
Can Open
Controlling Pressure
in a Stairtower
Table 1-2 assumes a door height of seven feet and a distance from the doorknob to the knob side
of the door of three inches. If your door does not meet these requirements, or has opening
hardware other than a doorknob, such as panic hardware, then refer to the ASHRAE publication
Design of Smoke Control Systems for Buildings for a formula to calculate the proper opening
force. The door widths in Table 1-2 are only valid for doors that are hinged at one end. For other
types of doors, see the ASHRAE document.
Many door closers vary the amount of force as the door opens. They provide less resistance in the
early stages of opening the door than they do later, when the door is almost fully open. The force
to open the door shown in Table 1-2 represents the force needed to open the door only enough to
let air flow through the opening. Once air is able to flow, the force exerted by the difference in air
pressure on the door lessens. Therefore, when calculating the force required to open the door, you
may need to lower the door closer force.
Stairtower smoke control systems are divided into two categories: “non-compensated” and
“compensated.” These categories are illustrated in the figure below, which shows stairtower
pressurization by top injection. Non-compensated systems simply turn on a fan to pressurize the
stairtower, as shown below in Stairtower A. The fan speed does not change to compensate for
doors opening and closing. The more doors that are open, the more the pressure differential
between the stairtower and the building drops.
Constant
Fan Speed
Variable
Fan Speed
Stairtower A
Stairtower B
Figure 1-6. Non-Compensated and Compensated Stairtower Systems
Continued on next page
1-15
Vent
Page 28
Designing a Dedicated Smoke Control System, Continued
Controlling Pressure
in a Stairtower
The building shown in Figure 1-6, Stairtower A has no vent to the outside. Compensated systems
adjust the airflow to make up for pressure lost through open doors. A compensated system
(Figure 1-6, Stairtower B) can use dampers (or vents) to relieve excess pressure in the stairtower
to ensure that the pressure does not go over the maximum limit.
There are a number of ways compensated stairtower smoke control systems can control
pressurization. In a basic system with a roof-mounted fan blowing air into the stairtower, pressure
can be regulated by varying the speed of the fan, the pitch of the fan blade, the inlet vanes, or the
number of fans operating (assuming there is more than one).
More sophisticated systems use ducts to deliver air to several points in the stairtower. The
dampers can be controlled to maintain the appropriate pressure in their zone. Duct systems can
also use bypass dampers and ducts to control the amount of air flowing from the fan to the outlets.
The bypass dampers are opened when the stairtower is at the proper pressure, so that excess air
flows into the bypass duct, then back to the air inlet not into the duct system.
The figure below shows a stairtower pressurization system that uses multiple pressure injection
dampers mounted in an air pressure duct. In this example, the vents to the building have
barometric dampers. While a roof-mounted fan is shown in the figure, the fan can be located at
any level. A manually-operated damper may be located at the top of the stairtower to aid the fire
department in purging smoke from the building during a fire.
Pressurization Fan
Air Pressure Duct
Dampers
Figure 1-7. Stairtower Pressurization by Multiple Injections (Roof-Mounted Fan)
Continued on next page
1-16
Page 29
Designing a Dedicated Smoke Control System, Continued
Controlling Pressure
in a Stairtower
The figure below shows a bypass pressure control system for stairtower pressurization with the
bypass-around supply fan located at ground level. Although a ground-level fan is shown, the fan
can actually be placed at any level. The bypass duct dampers are controlled by one or more static
pressure sensors located between the stairtower and the building. In addition, a manually-operated
damper may be located at the top of the stairtower for smoke purging by the fire department.
Bypass Duct Dampers
Bypass Duct
Air Intake
Figure 1-8. A Bypass Pressure Control System
There are several ways for a compensated stairtower smoke control system to get rid of excess air
pressure to ensure that the stairtower doors can open properly. One or more vents to the building
exterior (with dampers) can be used in the stairtower to release excess pressure. These dampers
can be barometrically controlled (being forced open by the excess air pressure) or controlled by
electric motors or pneumatics as in conventional HVAC systems. In both cases, the dampers must
be placed far enough away from the air supply to prevent venting of air that has not yet been able
to disperse through the stairtower. Vents can also lead into the building, but you should consider
carefully the impact of venting extra pressure into the building before using this type of vent.
You can also use an exhaust fan to vent the excess pressure from the stairtower. Such a fan should
be designed to operate only when the stairtower is over-pressurized. It should never be on when
the pressure differential between the building and the stairtower is below the lowest limit.
1-17
Page 30
Designing a Dedicated Smoke Control System, Continued
Elevator Smoke
Control
Most elevators do not have smoke protection, fire protection, or other features necessary for them
to be considered as a means for fire evacuation. Elevator systems not specifically designed and
built for fire evacuation should not be used in fire situations.
The elevator smoke control system is intended to prevent smoke flow to other floors by way of the
elevator shaft. Elevator shafts present a special menace with regards to smoke control. An elevator
shaft makes a perfect chimney to draw smoke into the upper levels of a building. Since elevators
usually have openings on each floor, and the seals on the elevator doors are often poor, the
elevator shaft can become a mechanism to spread smoke throughout a building. Smoke control in
an elevator shaft is an important consideration in the overall smoke control plan.
The problems resulting from smoke migration through elevator shafts are illustrated by the
MGM Grand Hotel fire. Although the fire occurred on the ground floor, the smoke from that fire
migrated through the elevator shafts to the upper floors resulting in a number of fatalities.
An obvious solution to this problem is to pressurize the elevator shafts, as shown in the figure
below. However, pressurizing an elevator shaft presents a number of problems. While the elevator
doors can be fitted with improved seals and rubber sweeps, these systems will not totally eliminate
air leakage. Also, most elevator shafts are not designed to be pressurized. They often have large
openings at the top where the cables feed into the winding room. Shafts are often constructed of
porous material that cannot contain the air pressure. And since most shafts are not designed to be
inspected after the elevators are installed, finding and repairing cracks that would let smoke
infiltrate or pressure escape is difficult.
Special Smoke-Proof
Elevator Doors
Elevator
Smoke
Low Pressure
Area Created by
Elevator Door
Figure 1-9. Pressurizing an Elevator Shaft to Prevent Smoke Migration
Even if the shaft is pressurized, another primary problem is caused by the transient pressures
produced when an elevator car moves inside the shaft during a smoke emergency. This “piston
effect” can pull smoke into a normally pressurized elevator lobby or elevator shaft. For example,
an elevator car moving down from the top of the shaft may create a small low air pressure zone
near the top of the shaft, which can pull smoke from the fire zone into the shaft.
At the present time, these issues have not been resolved. Pressurizing the elevator shafts so that
the elevators can operate during a smoke emergency is still being studied.
IMPORTANT: In general, elevators should not be used as an escape route during
an evacuation.
1-18
Page 31
Detecting Smoke
Introduction
Configuring and
Monitoring a Smoke
Control System
The fire detection system is the system that is connected to the smoke or heat detectors. Every
smoke zone should have a Listed smoke or heat detector installed in it. The detectors should be
located so that they can detect the presence of smoke or fire before it spreads beyond the zone.
Once the fire control system detects the fire, it relays to the smoke control system the zone and the
type of alarm that was triggered. The smoke control system then takes action.
Never use manual pull stations to initiate specific zoned smoke control. There is no guarantee that
the person pulling the alarm is in the same smoke zone as the fire. The automatic smoke control
system should take only those actions that are common to all smoke strategies when a manual pull
station is activated. For example, the stairtower can be pressurized in response to a manual pull
box alarm. Implementing a specific smoke control strategy must wait until the smoke detectors
locate the fire zone.
The smoke control system should be able to act on its own in response to detecting smoke.
When it detects smoke, the system enacts the planned strategy of the designer. The automatic
smoke control should maintain the strategy to control smoke in the first zone that smoke is
detected in. It would be difficult for you to create strategies for controlling smoke in all possible
combination of zones.
The automatic smoke control system must have the highest priority over all other automatic
control systems in the building. It must override energy management, occupancy schedules, or
other controls. The only systems that should be able to automatically override the smoke control
system are such safety systems as high pressure limiters.
Considering how unpredictable smoke is, you must have a manual control panel from which the
smoke control system can be monitored and overridden. This panel, called a “Firefighter's Smoke
Control Station” (FSCS), allows fire-fighting personnel to take manual control of the smoke
control system.
Firefighter Smoke
Control Station
(FSCS)
The FSCS is a graphic annunciating control panel that gives firefighters information about the
state of the smoke control system, as well as manual control over all of its components. The FSCS
should be located in a secure room or cabinet to prevent unauthorized personnel from tampering
with it. The room or cabinet should be clearly marked so that firefighters can quickly locate the
FSCS.
The FSCS panel has a diagram of the building showing the entire smoke control system, along
with status lights and override switches for all of the system components. The diagram of the
building should include all smoke control zones, all of the ducts leading to and from the zones
with arrows indicating the direction of air flow in the ducts, and a clear indication of which zone
each piece of equipment serves.
The panel must have controls to activate all fans, dampers, and other equipment related to the
smoke control system. These manual controls must be able to override all automatic control of
smoke control equipment. In particular, the FSCS must be able to override:
• Hand/off/auto switches.
• Local start/stop switches on fan motor controllers.
• Freeze detection devices.
• Duct smoke detectors.
Continued on next page
1-19
Page 32
Detecting Smoke, Continued
Firefighter Smoke
Control Station
(FSCS)
The FSCS must not override such safety controls as:
• Electrical overload protection.
• Electrical disconnects as required by NFPA 70.
• Other controls in accordance with UL 864.
• Any fire/smoke damper thermal control as required by UL 33, Standard for Heat Responsive Links for
Fire Protection Service or UL 555S, Standard for Leakage Rated Dampers for Use in Smoke Control
Systems.
In non-dedicated systems, local motor controller hand/off/auto switches can remain in-circuit with the FSCS
panel. But, they can remain in-circuit only if the switches are in a locked room accessible only to authorized
personnel. Also, if such a switch is thrown, a trouble condition must sound in the building main control
center. The indicator lights on the FSCS provide information about the functioning of the system.
The following colors for example are used for FSCS indicators:
• Green - Smoke-control fans and other critical-operation devices are running or the dampers are open.
• Yellow - Dampers are in the closed position.
• Orange or Amber - The equipment has failed.
• Red - A fire has been detected in the area.
The FSCS has a lamp test button that turns ON all the panel lights. Use this button regularly to make sure
none of the lights has burned out. The FSCS gets information on the status of the smoke control system
equipment from proof monitors on the equipment itself. Each fan that has a capacity of over 2,000 cfm
should be equipped with an airflow monitor. A proof sensor is required to monitor airflow and the position of
the blade or vane in a damper is also required to be monitored. Smoke dampers should be fitted with endrange switches to indicate that they are fully-opened or fully-closed.
All of the failure lights on the FSCS represent the state of the equipment as determined by the proof sensors.
The failure light comes on if the piece of equipment is not in the state its control is set for within its trouble
indication time. This time is a maximum of 60 seconds for a fan (see note) and a maximum 75 seconds for a
damper. If, within that time, the proof sensors do not report that the piece of equipment has responded to the
control system command, the FSCS indicates that the piece of equipment has failed.
Note:Local codes may require shorter maximum times. The 60 second maximum time for the fan must
also account for ramp down time.
Testing the System
Related
Documentation
During the installation, you should perform “operational tests” that make sure the components and
subsystems of the smoke control system are installed correctly. After the installation is done, you must
perform “acceptance tests,” to prove that the smoke control system is capable of doing what it was designed
to do. The testing procedures are covered in a later chapter of this document.
The following is a list of additional documentation that may aid you in understanding and designing Smoke
Control Systems.
• Underwriters Laboratories, Inc., UL 864, Control Units and Accessories for Fire Alarm Systems.
• The National Fire Protection Association. NFPA 92A, Recommended Practices for Smoke Control
Systems.
• American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE).
Society of Fire Protection Engineers. Design of Smoke Management Systems.
•The National Fire Protection Association. NFPA 90A, Standard for the Installation of Air Conditioning
and Ventilating Systems.
•Underwriters Laboratories, Inc., UL 555S, Standard for Leakage Rated Dampers for Use in Smoke
Control Systems.
•Underwriters Laboratories, Inc., UL 555, Fire Dampers.
1-20
Page 33
Chapter 2
Smoke Control Design Parameters
Introduction
In this Chapter
This chapter presents the general design parameters for Simplex Smoke Control System
equipment.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
System Requirements 2-2
System Design Parameters 2-3
2-1
Page 34
System Requirements
General
Requirements
Agency
Requirements
The Simplex Smoke Control System has the following general requirements:
• A smoke control system is a complete system engineered for a particular installation.
• Electrical supervision is required up to the input of the trunk-connected devices involved with the
electrical sensing and control of HVAC devices.
• The interconnection of the smoke control equipment to the HVAC equipment, and to other system
equipment, is intended to be in accordance with a specific installation diagram that is generated by either
the smoke control equipment manufacturer or by another responsible party.
Equipment for Smoke Control Systems is to be listed to Underwriters Laboratories category
UUKL per the requirement of UL 864, Control Units and Accessories for Fire Alarm Systems.
Additionally, system equipment must be in accordance with locally adopted codes such as
NFPA 92A and the pertinent building codes.
Some of the smoke control considerations are as follows:
•Standby Power - Standby power for Simplex Smoke Control System Equipment is optional, however if
the equipment also provides fire alarm service then standby power would be required.
•Smoke Control Actuating Input Circuits - The circuits which connect to devices which initiate
automatic smoke control must consist of one of the following:
- A supervised fire alarm initiating circuit of a Fire Alarm Control Unit which is also
providing smoke control.
- A supervised circuit connected to a zone output of a UL Listed Fire Alarm Control Unit.
- An unsupervised circuit connected to a zone output of a Listed Fire Alarm Control Unit
with each unit mounted adjacent (within twenty feet) to the other and the interconnecting
wiring run in conduit.
•Firefighter’s Smoke Control Station - Each system must also provide a Firefighter’s Smoke Control
Station (FSCS) as defined in NFPA 92A. The FSCS provides a complete and easily understood system
status, with provisions for manually overriding any smoke control process.
The contents of this document are derived from Standard NFPA 92A Recommended Practice for Smoke-Control Systems. Additional construction and reliability concerns, not covered in
NFPA 92A, are derived from similar requirements governing Fire Alarm Control Units as found in
UL Standard 864. Detailed engineering design information is contained in the ASHRAE
publication, Design of Smoke Management Systems.
2-2
Page 35
System Design Parameters
Verifying System
Integrity During
Non-Emergency
Conditions
Weekly Self-Test
Verifying System
Integrity During
Emergency
Conditions
The means for verifying system integrity during a non-emergency condition varies depending on
whether the smoke control system is a “dedicated” or a “non-dedicated” system.
•Dedicated Smoke Control Components: Solely used for smoke control functions and are
not operated in a non-emergency condition. Dedicated system equipment is therefore required
to incorporate an automatic weekly self-test of each smoke control function.
•Non-dedicatedSmoke Control Components: HVAC components within a building which
are operated regularly. The normal “comfort” level associated with the proper operation of the
equipment serves as the means of maintaining system integrity.
The weekly self-test consists of the smoke control system automatically commanding the
associated function to operate and expecting, within a specified time, that the associated proof
sensor will operate. A valid proof sensor operation does not have to be annunciated. However, the
lack of an expected proof sensor operation should produce an audible trouble signal and indicate
the specific device which did not operate.
Smoke control system equipment must verify that a fan or damper has achieved its required end
function during emergency conditions. This end-process verification consists of monitoring fans
by vane or pressure differential switches, and dampers by degree-of-opening switches. These
monitored switches are further connected back to an input monitoring circuit of the Smoke
Control System Equipment, programmed to expect a signal within a specified time after an
automatic or manual activation. Annunciation of the end-process verifies that the process operates
as intended; if the proof sensors fail to operate, an audible trouble signal is sounded.
Automatic
Activation
Where equipment used for smoke control is also used for normal building operation, control of
this equipment must be preempted or overridden as required for smoke control. Automatic
activation of systems and equipment for zoned smoke control must have the highest priority over
all other sources of automatic control within the building. This equipment includes air
supply/return fans and dampers subject to automatic control according to building occupancy
schedules, energy management, or other purposes. The following controls should not be automatically overridden:
• Static pressure high limits.
• Duct smoke detectors on supply air systems.
2-3
Page 36
System Design Parameters, Continued
Subsequent
Automatic
Activation
Automatic
Activation By a
Manual Pull Box
Manual Operation
Automatic Override
of Manual Activation
Once an automatic activation has occurred, subsequent alarm signals that would normally result in
the automatic actuation of a smoke control strategy shall be annunciated only. No fans or dampers
should be actuated in response to any subsequent automatic fire alarm signal in order to avoid the
possibility of defeating any smoke control strategies that are in process.
Activation of the smoke control system should be by smoke detectors and any other automatic
devices located within the zone covered by the specific air conditioning and ventilating system.
Manual fire alarm pull boxes should not be used to initiate specific zoned smoke control
strategies because such a pull box in an adjacent smoke zone may be pulled, thereby placing the
system in an incorrect mode.
It is desirable that the smoke control system be independently controlled from a smoke control
center which should have controls capable of overriding all other HVAC systems. A manual
command is capable of overriding either fully or partially any automatic activation that may be in
process. This is based on the assumption that any manual activation is performed by authorized
personnel in response to a known emergency condition.
Since smoke control operation must override any programmed HVAC function, it is considered
acceptable for the “Initial Automatic Activation” to override any manual control, initiated by any
other operator terminal other than the FSCS, which is currently in place.
NFPA Standard 92A requires that manual control initiated by the FSCS take precedence over
automatic control. Therefore, the smoke control system automatic programmed functions do not
override a manual FSCS control when a smoke control operation is initiated.
Example: When a switch at the FSCS is operated, the control point is activated or deactivated
at a priority higher than the automatic smoke control program or any other operator
terminal priority. This prevents the automatic smoke control program or manual
commands from other operator terminals from overriding commands initiated at the
FSCS.
2-4
Page 37
Chapter 3
Smoke Control System Components
Introduction
In this Chapter
This chapter presents a general overview of the Simplex Smoke Control System. It describes the
UL-listed components used, the features of each component, and the role of these components
within the system.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Smoke Control System 3-2
4100U/4100ES Panel 3-3
4190 TrueSiteTM Workstation System and 24 Point I/O Graphic Interface 3-4
Optional and Peripheral System Components 3-5
Firefighter’s Smoke Control Station 3-7
3-1
Page 38
Smoke Control System
Smoke Control
System
A typical Simplex smoke control system is shown below:
Figure 3-1. Typical Network Smoke Control System
The following major components are used in the Simplex Smoke Control System:
• 4100U/4100ES Control Panel (used as the system controller).
• 4190 TrueSite Workstation System (TSW).
• Firefighter’s Smoke Control Station (FSCS).
These components are described in the following sections.
3-2
Page 39
4100U/4100ES Panels
4100U/4100ES Panel
FigureTag FD4-46502
A B C
D E F G H I
ZONE1SIG2AUX
3
SYSTEM IS NORMAL
J K L M N O P Q R
08:23:43 am MON 11-DEC-00
FB4IO5IDNet
6
AC Power
ALARMS
SYSTEM WARNINGS
S T U V W X Y Z /
Fire AlarmPriority 2 Alarm
Supervisory Trouble
Alarm Silenced
P7A8L
9
'SP' ( ) , 0 :
Fire Alarm
Priority 2
Supv
Trouble
Alarm
System
NET ADDR
Ack
Ack
Ack
Ack
Silence
Reset
DEL
0
Enter C/Exit
Event
More
Previous
Time
Info
Menu
On
Next
Enable
Arm
Off
Lamp
Disable
Auto
Disarm
Test
Emergency Operating Instructions
Alarm or Warning Condition
How to Silence Building Signals
System indicator flashing . To ne On . Press Alarm Silence.
How to Acknowledge / View Events
How to Reset System
Press ACK located under flashing indicator.
Press System Reset.
Repeat operation until all events are acknowledged.
Press Ack to silence tone device.
Local tone will silence.
Fire Control
(4100U Panel)
The 4100U or 4100ES panel serves as the system controller for the Simplex Smoke Control
System.
It controls the communications between the other system components within the smoke control
system. This panel can be used in a dedicated or a non-dedicated smoke control application.
The 4100U/4100ES connects to other panels in the following ways:
• The panel can connect to other Simplex Fire Alarm Control Panels via network communications.
• The can also connect to the FSCS using Remote Unit Interface (RUI) serial supervised communications
channel connections.
The Master Controller provides system control, synchronization, and supervision of all modules,
continuously scanning each module for status changes. Features include:
• Operator Panel with LCD and operator keys.
• Battery Charger for up to 125 Ah Batteries.
– Batteries up to 50 Ah may be mounted in the bottom of the control cabinet
– Batteries larger than 50 Ah mount external to main control cabinet
• Compatible with Lead Acid or NiCad Batteries
• System Power Supply (SPS), Power Limited:
− Supplies 9 A of alarm current and 5 A of standby current.
− Two Class A or Class B NACs rated at 3 A each. Supports TrueAlert non-addressable
A/V operation without synch cube.
− One 24 V auxiliary power tap, under software control.
− Charges 125 Ah batteries per UL 864; 55 Ah batteries per ULC S527.
− LCD readout of system voltage and current, battery voltage and current, and NAC current.
− Integral 250 point IDNet™ channel.
− AC input is 4A @ 120 VAC, 60 Hz; 2A @ 220/230/240 VAC, 60 Hz.
− Includes one relay, DPDT, 2A @ 32 VDC
− Landing point and control interface for optional two circuit City Card or three circuit
Relay Card. City Card is Reverse Polarity or Local Energy, configurable for alarm,
trouble, and supervisory.
General Operating Specifications
• Humidity: Up to 93% RH, Non-Condensing @ 90° F (32° C) Maximum
• Temperature: 32° F to 120° F (0° C to 49° C)
3-3
Page 40
4190 TrueSite Workstation System and 24 Point I/O Graphic Interface
4190 TrueSite
Workstation (TSW)
4190 TrueSite
Workstation TSW
The 4190 TrueSite Workstation (TSW) provides a graphical user workstation within the Simplex
Smoke System. You can interact with the smoke control system by entering input through a
keyboard, mouse, or touch-screen.
Note: If a TSW is used in the system, a Firefighter’s Smoke Control Station must be provided
and this station must initiate smoke control commands at the highest priority.
Graphic Screens:
TSW graphic screens can provide easily recognizable site plan and floor plan information. The level
of detail can be customized for the specific facility to easily and accurately direct the operator to the
immediate area of interest.
Icons can be optionally added to identify the exact device of interest and the operator can utilize
TSW Pan and Zoom capabilities to move to a specific screen location for more detail.
When a system status change occurs, the screen displays the type and location of the activity.
The operator then touches the appropriate screen area (or uses the mouse control) to access a more
detailed view of the zone or device.
For example, the figure below shows some of the information available when viewing a point that
represents a VESDA® early warning air aspiration smoke detector.
24-Point I/O Graphic
Interface (4100-7401)
®
Figure 3-2. TSW Screen Showing VESDA
Information
The 24-Point I/O Graphic Interface (4100-7401) has the following features:
• Each of the 24 points can be individually configured as either an input (e.g., switch) or output (e.g., lamp
or relay).
• 150 mA output (+24 VDC supervised for LED, incandescent, or relay operation).
• Outputs can be steady, slow pulse, or fast pulse.
• Switch inputs can monitor two position or three position switches.
• Lamp test input.
• Provides supervised monitoring and/or control for smoke control applications.
3-4
Page 41
Optional and Peripheral System Components
Optional System
Components
The following components may also be used in the Simplex Smoke Control System:
• Network Display Unit (NDU).
• 4010 Fire Alarm Control Panel (FACP).
• LCD Annunciator.
Note: The designated FSCS must initiate smoke control commands at the highest priority.
The figure below shows these optional components:
DISPLAY
TIME
SYSTEM
RESET
4603-9101 LCD
Annunciator
Emergency Operating Instructions
SYSTEM IS NORMAL
08:23:43 am MON 11-DEC-00
ALARMS
SYSTEM WARNINGS
Fire Alarm Priority 2 Alarm
Supervisory Trouble
Fire Alarm
Priority 2
Supv
Ack
Ack
Ack
Event
Time
On
Enable
Arm
Off
Disable
Auto
Disarm
AC Power
Alarm Silenced
Trouble
Alarm
System
Ack
Silence
Reset
More
Previous
Info
Menu
Next
Lamp
Test
Alarm or Warning Condition
System indicator flashing. Tone On.Press Alarm Silence.
How to Acknowledge / View Events
Press ACK located under flashing indicator.
Repeat operation until all events are acknow ledged.
Local tone will silence.
A B C
D E F G H I
ZONE1SIG2AUX
J K L M N O P Q R
FB4IO5IDNet
S T U V W X Y Z /
P7A8L
'SP' ( ) , 0 :
NET ADDR
0
Enter C/Exit
How to Silence Building Signals
How to Reset System
Press System Reset.
Press Ack to silence tone devic e.
FIRE
PRIORITY 2
ALARM
ALARM
ALARM
ALARM
ACK
3
6
9
DEL
Fire Alarm Local Mode Controller
Local
Mode
Control
CONTROL
ENABLE
Alarm
Reset
Silence
See Operating Instruction 579-343
Alarm
Alarm
Silenced
Mode
Active
Power
ALARM
SYSTEM
SYSTEM
POWER
SILENCED
SUPERVISORY
TROUBLE
ON
SUPV
TBL
ALARM
ACK
ACK
ACK
SILENCE
4601 Series Transponder
Local
Local Mode Controller
On
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
Fire Control
4100U Fire Alarm Control Panel or
Network Display Unit (NDU) with Voice
Modules and LED/Switch Modules
Figure 3-3. Optional Smoke Control System Components
3-5
4100U MINIPLEX
Transponder Cabinet
Continued on next page
DISCONNECT
A.C. POWER
N
AND
BATTERY
C
BEFORE
O
SERVICING
A
I
U
T
T
U
I
A
SERVICING
O
BEFORE
C
BATTERY
AND
N
A.C. POWER
DISCONNECT
Page 42
Optional and Peripheral System Components, Continued
Peripheral
Components
In addition to the components previously described, a Simplex Smoke Control System also
contains one or more of the following addressable or conventional components:
• Smoke Detection Device
• Duct Smoke Detection Relay
• Individual Addressable Module (IAM, Single or Multi-point)
• Zone Addressable Module (ZAM, Monitor or Control)
• System Accessories (Printer, PC Annunciator, etc.)
3-6
Page 43
Firefighter Smoke Control Station
Firefighter Smoke
Control Station
(FSCS)
The figure below shows a view of a typical Firefighter’s Smoke Control Station (FSCS) used with
the Simplex Smoke Control System. FSCS panels are custom designed for each building. See the
“FSCS Ordering Information” section later in this chapter.
Figure 3-4. Firefighter’s Smoke Control Station
Continued on next page
3-7
Page 44
Firefighter Smoke Control Station, Continued
Firefighter Smoke
Control Station
(FSCS)
The smoke control panel must work completely in conjunction with the fire alarm control panel.
This is because the FSCS is used by firefighters to activate and deactivate all smoke control
sequences in the event that the fire spreads and for smoke cleanup operations. All switches
override the automatic operation, in the event of a conflict with the operation. The FSCS must be
able to override any other manual or automatic control that is being used in the system, except
when those controls intended to protect against electrical overloads, provide for personal safety,
or prevent major system damage.
The design of the controls and status indications must be as simple as possible for firefighter use.
Smoke control schemes can sometimes incorporate the simultaneous use of multiple (sometimes
over a hundred) air handling units, exhaust fans, and dampers to accomplish the function.
The FSCS graphic must show all fans in excess of 2000 CFM, all dampers or groups of Variable
Air Volume (VAV) boxes, and all major ducts. The FSCS graphic must depict the direction of
airflow in the ducts. The air handling units, fans, and dampers must be grouped into “systems” or
“smoke zones.” These “smoke zones” are determined by the physical layout of the building and
the smoke and fire barriers as structurally and architecturally designed, for firefighting purposes.
It may be advantageous to provide one switch for each “system” or “smoke zone.” With the
appropriate units interlocked to manage smoke in the affected area, there could be potentially
hundreds of H-O-A switches. Fans require a three-position control that provides ON-AUTO-OFF
capabilities. Dampers require a three-position control that provides OPEN-AUTO-CLOSE
capabilities. The AUTO position can be removed if the piece of equipment can only be controlled
by the FSCS.
Smoke Management zones can be provided with a three-position switch, in addition to the
required switches, that provides PRESSURIZE-AUTO-EXHAUST capabilities. Status indications
are required for each system to positively indicate that a smoke control sequence has been
initiated. Fans must have a single green indicator that turns on when the fan proof sensor indicates
that the fan is running.
Dampers have three indicators:
• Yellow: Turns ON when the damper proof sensor confirms that the damper is closed
• Green: Turns ON when the damper proof sensor confirms that the damper is open
• Amber: Turns ON to indicate failure.
These indicators must be OFF when the damper is between the open and closed position.
The FSCS must have a Red indicator for each smoke control zone to signal if the zone is currently
in an alarm condition.
The FSCS must have Amber/Orange indicators to annunciate equipment faults from each piece of
equipment monitored by proof sensors. If fans do not indicate running within 60 seconds, or
dampers do not reach the required position within 75 seconds, a fault indication must be
annunciated on the FSCS.
Note: Confirm actual times with local codes.
The FSCS must have a “master key-switch” to prevent unauthorized personnel from issuing
commands. When the key is inserted and turned, all controls on the FSCS are enabled. Alternate
command control may be performed by being inside a locked enclosure or other access control
means that are accepted by local authority.
Continued on next page
3-8
Page 45
Firefighter Smoke Control Station, Continued
Firefighter Smoke
Control Station
(FSCS)
FSCS Ordering
Information
The FSCS must have an audible signal that sounds when either a smoke control zone is in alarm or
to bring attention to a fault indicator. Operating the key-switch and then pressing the audible
silence button is the only method of silencing the FSCS audible signal.
The FSCS must have an “Audible Silence Button.” This momentary push-button is activated only
when the master key-switch is ON. This button is used to silence the FSCS audible signal that
activated as a result of proof sensors failing to report or annunciation of smoke detection within
the FSCS smoke control zones.
The FSCS must have a means to turn OFF equipment fault indicators that were activated as a
result of proof sensors failing to report within the required time period. If a “Clear Faults Button”
or similar means to clear faults, is used it would be active only when the master key-switch is ON.
An alternate means may be by logging in at an authorized level at the Fire Alarm Control Panel
and then clearing the faults.
The FSCS must have a “Lamp Test Button.” This momentary push-button is active at all times to
turn ON all indicators to allow for visual confirmation of failed indicator LEDs.
Note: Refer to Chapter 4 for a list of Simplex Field Wiring Diagrams and Interconnection
Diagrams that can assist you in installing the Simplex Smoke Control System.
A Firefighter’s Smoke Control Station (FSCS) consists of a site-specific, customized floor plan or
elevation graphic, illuminated status indicators, and switches. The FSCS uses Simplex LED
drivers and switch input modules (Models 4100-7401 through -7404 and 4602-7101) that
communicate with the 4100U/4100ES FACP by means of a supervised RUI communications
channel. The Models 4100-7401 through -7404 and 4602-7101 have been found suitable for use as
components internal to a UL-Listed FSCS manufactured by others.
There are several suppliers of UL-listed FSCS. Below are references to two manufacturers known
to have UL Listed FSCS equipment utilizing Simplex LED drivers and switch modules when this
document was published. Since manufacturer's Listing compliance may change, always verify
smoke control system equipment listing compliance of the FSCS before placing your FSCS order.:
To build an FSCS panel to your project specifications:
• Specify the size requirement of your FSCS.
• Coordinate the FSCS box requirements with the vendor.
• Provide an approved drawing of the desired FSCS graphic.
• Specify the type of Simplex graphic modules to be connected to the FSCS.
Note: Graphic vendors provide mating connectors for the graphic interface modules from a
Simplex controller.
3-9
Page 46
Firefighter Smoke Control Station, Continued
About the Fire Alarm
Control Panel
The Fire Alarm Control Panel connects to all of the smoke detectors, manual pull boxes, fire
alarms, etc. within the building. When one of the FACP sensors detects a problem, the FACP
informs the smoke control panel which sensor is in alarm condition and what the alarm condition
is. The smoke control system receives all alarm information from the FACP. However, the smoke control zones must correspond to the zones of the FACP.
3-10
Page 47
Chapter 4
Installing the Smoke Control System
Introduction
In this Chapter
This chapter contains general guidelines for smoke control installations and interconnections.
Please refer to the applicable installation documents for component installation instructions. These
documents are shipped with the individual components.
All wiring in the Simplex Smoke Control System must comply with the National Electric Code
(NFPA 70), the National Fire Alarm Code (NFPA 72), the appropriate Simplex Field Wiring
diagrams (refer to the “Field Wiring and Interconnection Diagrams” section of this chapter) and
any state or local requirements.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
General Smoke Control Interconnections 4-2
Dedicated Smoke Control System Wiring 4-6
Non-Dedicated Smoke Control System Wiring Diagrams 4-10
4-1
Page 48
General Smoke Control Interconnections
Overview
A Simplex Smoke Control System is usually part of a larger Simplex Fire Alarm System. The
Simplex Smoke Control System ties into the building air handling equipment, either dedicated,
non-dedicated, or both, to form the overall Smoke Management system for the building.
Since Simplex equipment is not the primary control equipment for a building's non-dedicated air
handling equipment, the interconnection between the Simplex Smoke Control System and the
non-dedicated air handling equipment is critical. This interconnection must be done in such a
manner to guarantee that the Smoke Control System takes priority, and that Smoke Control
System commands cannot be overridden by other building systems.
Although every application is different, the sections that follow describe some typical methods for
interconnecting to air handling elements to insure that Smoke Control System commands take
precedence and that accurate monitoring of the air handling system is fed back into the Smoke
Control System. Fan and damper control are shown in some detail to illustrate principles that can
be extrapolated to other more special purpose applications. These principles should be generally
applied to the detailed design of specific engineered smoke control solutions.
Smoke Control System operation is dependent both on the hardware and the control software.
The wiring diagrams shown in this chapter, must be used with appropriate programming to create
an operational control system.
4-2
Page 49
®
General Smoke Control Interconnections, Continued
UUKL Addressable
Monitor/Control
Devices for 4100U
and 4100ES
Model Description IDNet™ MAPNET II® See Doc #
4090-9001
4090-9002
4090-9101 Class B monitor ZAM.
4090-9106 Class A monitor ZAM.
4090-9118*
4090-9119*
4090-9120* Six point module; four T sense inputs, 2 relays; one address.
4100-7401 24 Point I/O Graphic Module. –– ––
4100-7402 64/64 LED/Switch Controller. –– ––
4100-7403 32 Point LED Module –– ––
4100-7404 32 Point Switch Module. –– ––
4602-7101
The following table lists the UUKL addressable monitor/control devices for the 4100U or 4100ES
system.
Table 4-1.UUKL Addressable Monitor/Control Device List for 4100U/4100ES
Supervised IAM, single address, single point; IDNet and
4100U/4100ES provide “T” sense (current limited
monitoring); MAPNET II and 4100U/4100ES provide simple
N.O. Class B monitoring.
Relay IAM, single address, single point; Form “C” with relay
status tracking.
Relay IAM with T sense input, single address, dual point,
relay and input.
Relay IAM with unsupervised input, single address,
dual point, relay and input.
Graphic I/O, RCU/SCU (Remote Control Unit/Status Control
Unit, selectable operation).
–– –– ––
–– 574-184
–– 574-874
–– 574-875
–– 574-876
574-331
574-183
841-802
S4100-0005
841-802
S4100-0005
841-802
S4100-0005
841-802
S4100-0005
Table 4-2. MAPNET II UUKL Addressable Monitor/Control Device List for 4100U/4100ES
Model Description IDNet™ MAPNET II
2190-9153 Class A Monitor ZAM, surface mount. ––
2190-9154 Class A Monitor ZAM, flush mount. ––
2190-9155 Class B Monitor ZAM, surface mount. ––
2190-9156 Class B Monitor ZAM, flush mount. ––
2190-9159 Class A Signal ZAM, surface mount. ––
2190-9160 Class A Signal ZAM, flush mount. ––
2190-9161 Class B Signal ZAM, surface mount. ––
2190-9162 Class B Signal ZAM, flush mount. ––
2190-9163 Control Relay ZAM, surface mount. ––
2190-9164 Control Relay ZAM, flush mount. ––
2190-9173*
* Devices designed specifically for Smoke Control Applications.
Note: These are common smoke control system components and do not include other commonly used fire detection
components such as pull stations, heat detectors, and initiation and notification appliances.
2-Point I/O Module supervised input and relay output;
two sequential addresses.
––
See Doc #
574-668
575-279
574-995
Continued on next page
4-3
Page 50
General Smoke Control Interconnections, Continued
Reference
Information
For wiring details on the devices shown in the following sections, refer to the following reference
information shown below:
• MAPNET II/IDNet Devices Field Wiring Diagram .......................... 841-804
• 4020/4100 Graphic Annunciator Field Wiring Diagram ................. 841-802
• 4100ES Fire Alarm System Installation Instructions ........................ 574-848
4-4
Page 51
General Smoke Control Interconnections, Continued
Four Story
Building Smoke
Control Example
The figure below shows an application diagram for a four-story building. This figure illustrates
how the elements of the Smoke Control System are architecturally related, how they fit within the
overall Simplex Fire Alarm System, and how they relate to the building air handling systems.
Figure Legend Description
FACP Fire Alarm Control Panel (e.g., Model 4100U as described in Chapter 3).
FSCS Firefighter’s Smoke Control Station (as described in Chapter 3).
TSW TrueSite Workstation System (e.g., Model 4190 as described in Chapter 3).
C Relay IAM with Feedback (e.g., Model 4090-9118).
M Supervised IAM (e.g., Model 4090-9001).
D HVAC damper, supply or return (as described in Chapter 3).
DPS Damper position switch (as described in Chapter 3)
FAN Stairtower or elevator shaft pressurization fan.
S Other signaling line circuit devices (e.g., smoke detector, pull station, etc.)
ASW Air flow sensing switch (as described in Chapter 3).
Figure 4-1. Four-Story Building Smoke Control Example
4-5
Page 52
Dedicated Smoke Control System Wiring
Overview
Dedicated
Damper Control
Dedicated Smoke Control System wiring is usually straightforward. The Smoke Control System is
the only source for commands to the fans and dampers, and therefore bypass and cut-off relays are
not needed. The following sections illustrate some examples of dedicated fan and damper control.
Damper control is a basic function of the Simplex Smoke Control System. Interconnections to
motorized dampers are shown in Figures 4-2 and 4-3.
The figure below shows dedicated motorized damper control using a 4090-9120 6-Point I/O
Module. Both relay outputs are used, one to control opening the damper and the other to control
closing it.
The wiring between the 6-Point I/O Module and the control relays is unsupervised, so the module
must be mounted within three feet of the relays/dampers in accordance with NFPA 72.
Note: The wiring to the limit switches is supervised and limited to 500 ft. (152 m).
1/4 A @ 120 VAC
0V
1A @ 30 VDC
or
POWER
SOURCE
LISTED
CONTROL
RELAY
(N/O)
INPUT 1
INPUT 2
IDNet +
IDNet -
COMM
N/O
COMM
N/O
+24V
FROM
FACP
OPEN POSITION
LIMIT SWITCH
N/O
COMM
N/O
COMM
CLOSED POSITION
LIMIT SWITCH
6.8 K 1/2 W EOLR
(Per Installation Instructions, 574-876)
SMOKE DAMPER
DAMPER
CLOSED
POWER
MOTOR
RETURN
DAMPER
OPEN
POWER
Figure 4-2. Dedicated Motorized Damper Control Using a 6-Point I/O Module
Continued on next page
4-6
LISTED
CONTROL
RELAY
(N/O)
Page 53
Dedicated Smoke Control System Wiring, Continued
Dedicated
Damper Control
Dedicated damper control using the 4100-7401 24-Point I/O is similar to control using Relay
IAMs and 6-Point I/O Modules, except that the 4100-7401 module is used for both control and
feedback. This module communicates with the 4100U/4100ES Master over the RUI
communications, and offers the added advantage that all I/O is supervised. The figure below
shows dedicated motorized damper control using the 4100-7401 24-Point I/O:
Figure 4-3. Dedicated Motorized Damper Control Using the 24-Point I/O Module
4-7
Page 54
Dedicated Smoke Control System Wiring, Continued
Dedicated
Fan Control
Like smoke dampers, fan control is a basic function of the Simplex Smoke Control System.
General principles for interconnection to a dedicated fan are shown in Figures 4-4 and 4-5.
In a dedicated fan control application, the 4090-9118 Relay IAM is used to provide inputs to a fan
to turn it ON and monitor the feedback from the controller. The wiring between the Relay IAM
and the fan is unsupervised, so the IAMs must be mounted within three feet of the controller in
accordance with NFPA 72.
1A @ 30 VDC
or
1/4 A @ 120 VAC
POWER
SOURCE
INPUT
COMM
N/O
LISTED
RELAY
(N/O)
IDNet SLC
FROM FACP
SERVICE
DISCONNECT
LISTED
SAIL
FAN
RETURN
SWITCH
N/OCOMM
6.8 K 1/2 W EOLR
(Per Installation Instructions 574-874)
Figure 4-4. Dedicated Fan Control Using a Relay IAM
Continued on next page
4-8
Page 55
Dedicated Smoke Control System Wiring, Continued
Dedicated
Fan Control
Dedicated fan control using the 4100-7401 24-Point I/O is similar to control using Relay IAMs
and 6-Point I/O Modules, except that the 4100-7401 module is used for both control and feedback.
This module communicates with the 4100U/4100ES Master over the RUI communications, and
offers the added advantage that all I/O is supervised. The figure below shows the equivalent
interconnects for applications using a 24-Point I/O Module.
Figure 4-5. Dedicated Fan Control Using the 24-Point I/O Module
4-9
Page 56
Non-Dedicated Smoke Control System Wiring Diagrams
Overview
Non-Dedicated
Damper Control
Non-dedicated Smoke Control System wiring adds a layer of complexity, as the Smoke Control
System must take control of the fans and dampers from the HVAC system. This introduces the use
of bypass and cutoff relays not needed in a Dedicated Smoke Control System. The following
sections illustrate some examples of non-dedicated damper and fan control.
Damper control and overriding the HVAC control of the damper is a basic function of the Simplex
Smoke Control System. Interconnections for dampers are shown in Figures 4-6 through 4-9.
Control of the damper is accomplished using the 4090-9118 Relay IAM. The Relay IAM
communicates with the FACP via the Simplex IDNet Signaling Line Circuit (SLC). When
commanded by the FACP the Relay IAM activates the smoke control override relay and supplies
power to the pressure switch to close the damper.
Continued on next page
4-10
Page 57
Non-Dedicated Smoke Control System Wiring Diagrams, Continued
Non-Dedicated
Damper Control
Feedback of the closure is accomplished using a 4090-9120 6-Point I/O Module to monitor the
closed position limit switch on the damper. The module also communicates with the Simplex
FACP via IDNet. Wiring from the module to the control relay is unsupervised, so it must be
mounted within three feet of the relay/damper in accordance with NFPA 72.
The figure below shows non-dedicated motorized damper control using the 6-Point I/O Module.
LISTED
RELAY
(N/O)
(B)
LISTED
RELAY
(N/O)
POWER
SOURCE
EMS
LISTED
RELAY
(N/C)
LISTED
RELAY
(N/C)
INPUT 1
INPUT 2
IDNet SLC
FROM FACP
1/4 A @ 120 VAC
+24V
FROM
FACP
COMM
COMM
1A @ 30 VDC
or
0V
N/O
N/O
(A)
OPEN POSITION
LIMIT SWITCH
N/O
MOTOR
DAMPER
OPEN
POWER
RETURN
DAMPER
CLOSED
POWER
COMM
N/O
COMM
CLOSED POSITION
6.8 K 1/2 W EOLR
(Per Installation Instructions, 574-876)
LIMIT SWITCH
SMOKE DAMPER
Figure 4-6. Non-Dedicated Motorized Damper Control
The two relay circuits of the 6-Point I/O Module are used, one to control opening the damper and
the other to control closing it. Relays [A] and [B] are activated to close the damper. One output
circuit controls Relay [A] to override the Energy Management System (EMS) and provide power
to the motor to close the damper. Relay [B] insures that no open power is provided to the motor
from the EMS. The other output circuit works in exactly the opposite fashion to control the
opening of the damper. The damper position is monitored by the two supervised inputs of the
6-Point I/O Module.
The wiring between the 6-Point I/O Module output circuits and the relays is unsupervised, so the
6-Point I/O Module must be mounted within three feet of the relays/dampers in accordance with
NFPA 72. The wiring to the limit switches is supervised, so no such restriction exists with the
monitor circuits.
Continued on next page
4-11
Page 58
Non-Dedicated Smoke Control System Wiring Diagrams, Continued
Non-Dedicated
Damper Control
The figure below shows non-dedicated motorized damper control using the 24-Point I/O Module.
Figure 4-7. Non-Dedicated Motorized Damper Control Using the 24-Point I/O Module
4-12
Page 59
Non-Dedicated Smoke Control System Wiring Diagrams, Continued
Non Dedicated
Fan Control
Like smoke dampers, fan control and overriding the HVAC control is a basic function of the
Simplex Smoke Control System. General principles for interconnection to a non-dedicated fan are
shown in Figures 4-8 and 4-9.
In a non-dedicated fan control application, a 4090-9120 6-Point I/O Module is used to provide
inputs to a fan controller for smoke control override and monitor the feedback from the controller.
The wiring between the module and the fan controller is unsupervised, so the module must be
mounted within three feet of the controller in accordance with NFPA 72.
0V
+24V
FROM
FACP
INPUT 1
COMM
N/O
COMM
N/O
1A @ 30 VDC
or
1/4 A @ 120 VAC
POWER
SOURCE
LISTED
RELAY
(N/O)
EMS
LISTED
IDNet SLC
FROM FACP
FA
N
RETURN
RELAY
(N/C)
SERVICE
DISCONNECT
LISTED
SAIL
SWITCH
N/OCOMM
6.8 K 1/2 W EOLR
(Per Installation Instructions, 574-876)
Figure 4-8. Non-Dedicated Fan Control Using a 6-Point I/O Module
Continued on next page
4-13
Page 60
Non-Dedicated Smoke Control System Wiring Diagrams, Continued
Non Dedicated
Fan Control
Non-dedicated fan control using the 24-Point I/O is similar to control using a Relay IAM
or 6-Point I/O Module, except that the 4100-7401 24-Point I/O Module is used for both control
and feedback. This module communicates with the 4100U/4100ES Master over the RUI
communications SLC, and offers the added advantage that all I/O is supervised, so no restrictions
on module placement are required. The figure below shows the equivalent interconnects for
applications using a 24-Point I/O.
Figure 4-9. Non-Dedicated Fan Control Using the 24-Point I/O Module
4-14
Page 61
Chapter 5
Smoke Control System Programs
Introduction
In this Chapter
This chapter provides examples of Simplex Smoke Control System programs. These programs are
presented to illustrate what can be accomplished with this system. Since every system is unique,
your programs will not be identical to these programs. Instead, use these programs as templates
when programming the system.
Keep in mind the following smoke control objectives when programming the system:
•Maintain safe fire-free and smoke-free routes to allow sufficient time for the occupants to exit
the premises or move to designated safe refuge areas.
•Provide a relatively clear approach to the fire area by firefighters so that the fire (the source of
the smoke) can be contained and extinguished as fast as possible.
•If designated safe refuge areas are a part of the life safety design, then the control system must
prevent smoke migration into such areas for a prolonged period of time.
•Reduce the amount of fire and smoke damage to the property.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Smoke Control Program Requirements 5-2
Dedicated Smoke Control System Weekly Self-Test 5-3
Smoke Control System Custom Control Equations 5-5
5-1
Page 62
Smoke Control Program Requirements
Introduction
Emergency
Operation
Automatic Program
Dedicated Smoke
Control System
Weekly Self-Test
The following paragraphs describe the requirements for the various types of programs that can be
implemented using the Simplex Smoke Control System.
Emergency operation programs have the following functions:
• Zoned smoke control to activate from automatic devices only.
• Manual devices may cause any operation that is common to all smoke strategies
(e.g. Stairtower Pressurization).
•
Automatic operation programs have the following functions:
• The first alarm in sets the operation strategy for smoke control. Subsequent alarms do not change the
smoke control strategy operation. The first alarm in sets that zone ON, and the other zones OFF. (See
Equations 9, 11, 13, and 15.)
• The program checks proof sensors and reports equipment operation to the FSCS or, if such proof is not
received within a specified time from activation it reports any failure to the FSCS. The delay time to
allow sensors to operate is set at ten seconds for conversion in testing. This delay time can be increased
to accommodate the time it takes for the equipment to respond. The maximum delay time is 60 seconds
for fans (Equations 19 through 24) and 75 seconds for dampers (Equations 25 through 46).
• Manual operation of the FSCS control switches overrides the automatic program. Manual commands
have a higher priority than automatic operations. (See Equations 47 through 74.)
Dedicated smoke control system weekly self-test programs have the following functions:
• Begins Saturday at 0000 hours if there is no alarm.
• Run once. Any failures sound an audible fault signal and light an indicator on the FSCS showing the
device that failed. In addition, the program displays “Weekly Smoke Control Self-Test Failed (Time &
Date).”
5-2
Page 63
Dedicated Smoke Control System Weekly Self-Test
Custom Control
Programming
Example
Equation 1:
Start Self-Test
The Custom Control equations in this example are written for 4100U/4100ES based smoke control
system, and show how to implement the Dedicated Smoke Control System Weekly Self-Test
requirement described on the previous page.
Note: The points mentioned are representative of any system. Your system uses different points
to provide the Inputs and Outputs. The following equations are provided as reference
material. The syntax may be slightly different than that shown. However, the logic and
content are the same.
The following list gives the Custom Control program (equation) number followed by a title
(or label) for the program.
Eq ua tio n No . La be l
------------- -------------------------------------------------- 1 STA RT SELF TEST
2 TURN O N STAIR PRESSURE FAN
3 TEST STAIRWELL AIR PRESSURE
4 RESET STA IR PRESSURE FAN TO O FF
5 [END-OF-PRO G RAM]
La be l: STA RT SELF TEST Eq ua tio n 1
C O MMENTS:
INPUTS:
Whe n the d a y o f we e k is Sa t
AND If A na lo g : A 6 is g re a te r tha n va lue : 0 (C nts)
AND If Ana lo g : A 6 is le ss tha n o r e q ua l to va lue : 3 (C nts)
AND NOT the ON sta te o f:
A0 A NALO G NUMBER OF SYSTEM FIRE ALARMS
O UTPUTS:
TRAC K p o ints ON p ri=9,9
P281 UTILITY START SELF TEST PRO G RAM
END:
Equation 2: Turn ON
Stair Pressure Fan
La be l: TURN O N STAIR PRESSURE FAN Eq ua tion 2
C O MMENTS:
INPUTS:
The O N state o f:
P281 UTILITY START SELF TEST PRO G RAM
O UTPUTS:
HO LD p o ints ON p ri=9,9
M1-9 C PRESS STAIR PRESS FAN
END:
5-3
Page 64
Dedicated Smoke Control System Weekly Self-Test, Continued
Equation 3:
Test Stairwell
Air Pressure
Equation 4:
Reset Stair Pressure
Fan to OFF
La be l: TEST STAIRWELL AIR PRESSURE Eq ua tio n 3
C O MMENTS:
INPUTS:
The O N state o f:
P281 UTILITY START SELF TEST PRO G RAM
AND the O N state o f:
M1-9 C PRESS STAIR PRESS FAN
DELAY fo r 10 se c s, running time r is A283
AND NOT the ON sta te o f:
M1-42 UTILITY MO NITO R STAIR PRESS FA N O N
O UTPUTS:
HO LD p o ints ON p ri=9,9
P280 UTILITY STAIR PRESS FAN FAIL
END:
La be l: RESET STAIR PRESSURE FAN TO O FF Eq ua tio n 4
C O MMENTS:
INPUTS:
The O N state o f:
P281 UTILITY START SELF TEST PRO G RAM
AND the O N state o f:
M1-9 C PRESS STAIR PRESS FAN
DELAY fo r 60 se c s, running time r is A284
O UTPUTS:
HO LD p o ints OFF p ri=9,9
M1-9 C PRESS STAIR PRESS FAN
P281 UTILITY START SELF TEST PRO G RAM
PRINT to All po rts/ lo g s/ disp lays
"SELF TEST PRO G RAM IS C OMPLETE"
END:
Equation 5:
End of Program
La be l: [END-OF-PRO G RAM] Eq ua tion 5
5-4
Page 65
Smoke Control System Custom Control Equations
Introduction
Smoke Control
System CC Equation
Summary
The following Custom Control (CC) equations are written for a 4100U/4100ES based smoke
control system. Note that the points mentioned are representative of any system. Your system will
use different points to provide the Inputs and Outputs.
The following “Custom Control Equation Summary” gives the CC equation number followed by a
label (title) for the program.
C USTO M C O NTROL EQ UATIO N SUMMARY
Eq ua tio n No . La b el
------------------- --------------------------------------- 1 SET UP NORMAL C ONDITIONS AT STA RTUP
2 C LEAR FAULTS ON STARTUP
3 SET NO RMAL C O NDITIO NS AT RESET
4 REPO RT TROUBLE IF SWITC HES NOT RESET
5 INITIALIZE NO RMAL C ONDITIO NS AT RESET
6 NO RMAL C O NDITIO NS C O MPLETE AFTER RESET
7 SMOKE C O NTROL INITIATE
8 SMOKE C O NTROL RESET
9 INITIATE SMO KE ZO NE 1
10 AC TIVA TE SMO KE C O NTROL ZONE 1
11 INITIATE SMO KE ZONE 2
12 AC TIVA TE SMO KE C O NTROL ZONE 2
13 INITIATE SMO KE ZONE 3
14 AC TIVA TE SMO KE C O NTROL ZONE 3
15 INITIATE SMO KE ZONE 4
16 AC TIVA TE SMO KE C O NTROL ZONE 4
17 SUPPLY FA N DUC T SMO KE ALARM
18 STA IR PRESS FAN DUC T SMOKE ALARM
19 REPO RT TBL IF SUPPLY FA N NOT O N
20 REPO RT TBL IF SUPPLY FA N NOT O FF
21 REPO RT TBL IF EXHAUST FAN NOT O N
22 REPO RT TBL IF EXHAUST FAN NOT O FF
23 REPO RT TBL IF STAIR PRESS FA N NOT O N
24 REPO RT TBL IF STAIR PRESS FA N NOT O FF
25 REPO RT TBL IF MAIN EXH DAMPER NO T O PEN
26 REPO RT TBL IF MAIN EXH DAMPER NO T C LO SED
27 REPO RT TBL IF MAIN SUP DAMPER NO T O PEN
28 REPO RT TBL IF MAIN SUP DAMPER NO T C LO SED
29 REPO RT TBL IF MAIN RET DAMPER NO T O PEN
30 REPO RT TBL IF MAIN RET DAMPER NO T C LO SED
31 REPO RT TBL IF SUP DAMPER 1 NOT O PEN
32 REPO RT TBL IF SUP DAMPER 1 NOT C LO SED
33 REPO RT TBL IF SUP DAMPER 2 NOT O PEN
34 REPO RT TBL IF SUP DAMPER 2 NOT C LO SED
35 REPO RT TBL IF SUP DAMPER 3 NOT O PEN
36 REPO RT TBL IF SUP DAMPER 3 NOT C LO SED
37 REPO RT TBL IF SUP DAMPER 4 NOT O PEN
38 REPO RT TBL IF SUP DAMPER 4 NOT C LO SED
39 REPO RT TBL IF EXH DAMPER 1 NOT O PEN
40 REPO RT TBL IF EXH DAMPER 1 NOT C LO SED
41 REPO RT TBL IF EXH DAMPER 2 NOT O PEN
42 REPO RT TBL IF EXH DAMPER 2 NOT C LO SED
43 REPO RT TBL IF EXH DAMPER 3 NOT O PEN
Continued on next page
5-5
Page 66
Smoke Control System Custom Control Equations, Continued
Smoke Control
System CC Equation
Summary
Eq ua tio n No . La b e l
------------------- ------------------------------------------------------------------ 44 REPO RT TBL IF EXH DAMPER 3 NOT C LO SED
45 REPO RT TBL IF EXH DAMPER 4 NOT O PEN
46 REPO RT TBL IF EXH DAMPER 4 NOT C LO SED
47 MA NUAL C ONTROL SUP AIR DAMPER 1 O PEN
48 MA NUAL C ONTROL SUP AIR DAMPER 1 C LO SE
49 MA NUAL C ONTROL SUP AIR DAMPER 2 O PEN
50 MA NUAL C ONTROL SUP AIR DAMPER 2 C LO SE
51 MA NUAL C ONTROL SUP AIR DAMPER 3 O PEN
52 MA NUAL C ONTROL SUP AIR DAMPER 3 C LO SE
53 MA NUAL C ONTROL SUP AIR DAMPER 4 O PEN
54 MA NUAL C ONTROL SUP AIR DAMPER 4 C LO SE
55 MA NUAL C ONTROL EXH AIR DA MPER 1 O PEN
56 MA NUAL C ONTROL EXH AIR DAMPER 1 CLOSE
57 MA NUAL C ONTROL EXH AIR DA MPER 2 O PEN
58 MA NUAL C ONTROL EXH AIR DAMPER 2 CLOSE
59 MA NUAL C ONTROL EXH AIR DA MPER 3 O PEN
60 MA NUAL C ONTROL EXH AIR DAMPER 3 CLOSE
61 MA NUAL C ONTROL EXH AIR DA MPER 4 O PEN
62 MA NUAL C ONTROL EXH AIR DAMPER 4 CLOSE
63 MA NUAL C ONTROL STAIR PRESS FAN O N
64 MA NUAL C ONTROL STAIR PRESS FAN O FF
65 MA NUAL C ONTROL MA IN SUPPLY FA N O N
66 MA NUAL C ONTROL MA IN SUPPLY FA N O FF
67 MA NUAL C ONTROL MA IN RET AIR DAMPER O PEN
68 MA NUAL C ONTROL MA IN RET AIR DAMPER C LO SE
69 MA NUAL C ONTROL MA IN EXHAUST FA N O N
70 MA NUAL C ONTROL MA IN EXHAUST FA N O FF
71 MA NUAL C ONTROL MA IN SUP AIR DAMPER OPEN
72 MA NUAL C ONTROL MA IN SUP AIR DAMPER CLO SE
73 MA NUAL C ONTROL MA IN EXH AIR DAMPER OPEN
74 MA NUAL C ONTROL MA IN EXH AIR DAMPER C LO SE
75 MA NUAL C O NTROL C LEAR FAULTS
76 MA STER KEY SWITC H
77 TURN SONALERT O N
78 TURN SONALERT O FF
[END-O F-PRO GRA M]
5-6
Page 67
Smoke Control System Custom Control Equations, Continued
Equation 1:
Set Up Normal
Conditions at
Startup
Equation 2:
Clear Faults on
Startup
La be l: SET UP NORMAL C ONDITIO NS A T STA RTUP Eq ua tio n 1
C O MMENTS:
INPUTS:
The O N state o f:
A34 TIMER SYSTEM STARTUP PULSE TIMER
O UTPUTS:
HO LD p o ints ON p ri=9,9
M1-10 C PRESS SUPPLY FAN RELAY
M1-11 C PRESS EXHAUST FA N RELAY
M1-12 C DAMPER MAIN O UTSIDE AIR DAMPER
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
M1-14 C DAMPER MAIN RETURN A IR DAMPER
M1-15 C DAMPER 1ST FLO O R SUPPLY AIR DAMPER
M1-16 C DAMPER 2ND FLO O R SUPPLY AIR DAMPER
M1-17 C DAMPER 3RD FLO OR SUPPLY AIR DAMPER
M1-18 C DAMPER 4TH FLO OR SUPPLY AIR DAMPER
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
M1-21 C DAMPER 3RD FLO OR EXHA UST/ RETURN AIR DAMPER
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
P291 UTILITY SET NORMAL C O NDITIO NS AT STARTUP
HO LD p o ints OFF p ri=9,9
M1-9 C PRESS STAIR PRESS FAN
END:
La be l: C LEAR FAULTS ON STA RTUP Eq ua tio n 2
C O MMENTS:
INPUTS:
The O N state o f:
P291 UTILITY SET NO RMAL C ONDITIO NS A T STARTUP
DELAY fo r 30 se c ., running time r is A293
O UTPUTS:
HO LD p o ints OFF p ri=9,9
P260 UTILITY FL1 SUPPLY AIR DAMPER FA IL
P261 UTILITY FL2 SUPPLY AIR DAMPER FA IL
P262 UTILITY FL3 SUPPLY AIR DAMPER FA IL
P263 UTILITY FL4 SUPPLY AIR DAMPER FA IL
P264 UTILITY FL1 EXHAUST AIR DAMPER FAIL
P265 UTILITY FL2 EXHAUST AIR DAMPER FAIL
P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL
P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL
P268 UTILITY MAIN SUPPLY FA N FAIL
P269 UTILITY MAIN EXHA UST FAN FA IL
P270 UTILITY MAIN RETURN AIR DAMPER FAIL
P271 UTILITY MAIN SUPPLY AIR DAMPER FAIL
P272 UTILITY MAIN EXHA UST AIR DAMPER FAIL
P280 UTILITY STAIR PRESS FAN FAIL
P291 UTILITY SET NO RMAL C ONDITIO NS A T STARTUP
HO LD p o ints ON p ri=9,9
P290 UTILITY SET NO RMAL C ONDITIO NS A T RESET
END:
5-7
Page 68
Smoke Control System Custom Control Equations, Continued
Equation 3:
Set Normal
Conditions at Reset
Equation 4:
Set Normal
Conditions at Reset
La be l: SET NORMAL C O NDITIO NS A T RESET Eq uatio n 3
C O MMENTS:
INPUTS:
The O N state o f:
A21 TIMER SYSTEM RESET PULSE TIMER
O UTPUTS:
HO LD p o ints ON p ri=9,9
P290 UTILITY SET NO RMAL C ONDITIO NS A T RESET
END:
La be l: SET NORMAL C O NDITIO NS A T RESET Eq uatio n 4
C O MMENTS:
INPUTS:
O R the UP sta te o f:
8-65 SWITC H Ann 1 Pt 65 G ra p hic LED/ SW C tlr w/ 32
8-66 SWITC H Ann 1 Pt 66 G ra p hic LED/ SW C tlr w/ 32
8-67 SWITC H Ann 1 Pt 67 G ra p hic LED/ SW C tlr w/ 32
8-68 SWITC H Ann 1 Pt 68 G ra p hic LED/ SW C tlr w/ 32
8-69 SWITC H Ann 1 Pt 69 G ra p hic LED/ SW C tlr w/ 32
8-70 SWITC H Ann 1 Pt 70 G ra p hic LED/ SW C tlr w/ 32
8-71 SWITC H Ann 1 Pt 71 G ra p hic LED/ SW C tlr w/ 32
8-72 SWITC H Ann 1 Pt 72 G ra p hic LED/ SW C tlr w/ 32
8-73 SWITC H Ann 1 Pt 73 G ra p hic LED/ SW C tlr w/ 32
8-74 SWITC H Ann 1 Pt 74 G ra p hic LED/ SW C tlr w/ 32
8-75 SWITC H Ann 1 Pt 75 G ra p hic LED/ SW C tlr w/ 32
8-76 SWITC H Ann 1 Pt 76 G ra p hic LED/ SW C tlr w/ 32
8-77 SWITC H Ann 1 Pt 77 G ra p hic LED/ SW C tlr w/ 32
8-78 SWITC H Ann 1 Pt 78 G ra p hic LED/ SW C tlr w/ 32
8-79 SWITC H Ann 1 Pt 79 G ra p hic LED/ SW C tlr w/ 32
O R the DO WN state o f:
8-65 SWITC H Ann 1 Pt 65 G ra p hic LED/ SW C tlr w/ 32
8-66 SWITC H Ann 1 Pt 66 G ra p hic LED/ SW C tlr w/ 32
8-67 SWITC H Ann 1 Pt 67 G ra p hic LED/ SW C tlr w/ 32
8-68 SWITC H Ann 1 Pt 68 G ra p hic LED/ SW C tlr w/ 32
8-69 SWITC H Ann 1 Pt 69 G ra p hic LED/ SW C tlr w/ 32
8-70 SWITC H Ann 1 Pt 70 G ra p hic LED/ SW C tlr w/ 32
8-71 SWITC H Ann 1 Pt 71 G ra p hic LED/ SW C tlr w/ 32
8-72 SWITC H Ann 1 Pt 72 G ra p hic LED/ SW C tlr w/ 32
8-73 SWITC H Ann 1 Pt 73 G ra p hic LED/ SW C tlr w/ 32
8-74 SWITC H Ann 1 Pt 74 G ra p hic LED/ SW C tlr w/ 32
8-75 SWITC H Ann 1 Pt 75 G ra p hic LED/ SW C tlr w/ 32
8-76 SWITC H Ann 1 Pt 76 G ra p hic LED/ SW C tlr w/ 32
8-77 SWITC H Ann 1 Pt 77 G ra p hic LED/ SW C tlr w/ 32
8-78 SWITC H Ann 1 Pt 78 G ra p hic LED/ SW C tlr w/ 32
8-79 SWITC H Ann 1 Pt 79 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P290 UTILITY SET NO RMAL C O NDITIO NS AT RESET
O UTPUTS:
TRAC K p o ints ON p ri=9,9
P256 TROUBLE FSCS SWITC HES NO T RESET
END:
5-8
Page 69
Smoke Control System Custom Control Equations, Continued
Equation 5:
Initialize Normal
Conditions at Reset
La be l: INITIALIZE NORMAL C O NDITIO NS AT RESET Eq ua tio n 5
C O MMENTS:
INPUTS:
The O N state o f:
P290 UTILITY SET NO RMAL C ONDITIO NS A T RESET
AND NOT the TROUBLE sta te o f:
P256 TROUBLE FSCS SWITC HES NO T RESET
O UTPUTS:
HO LD p o ints OFF p ri=7,9
P275 UTILITY SMO KE C O NTROL ALARM INITIATE
P276 UTILITY SMO KE C O NTROL ZO NE 1 INITIATE
P277 UTILITY SMO KE C O NTROL ZO NE 2 INITIATE
P278 UTILITY SMO KE C O NTROL ZO NE 3 INITIATE
P279 UTILITY SMO KE C O NTROL ZO NE 4 INITIATE
HO LD p o ints ON p ri=9,9
M1-10 C PRESS SUPPLY FAN RELAY
M1-11 C PRESS EXHAUST FA N RELAY
M1-12 C DAMPER MAIN O UTSIDE AIR DAMPER
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
M1-14 C DAMPER MAIN RETURN A IR DAMPER
M1-15 C DAMPER 1ST FLO O R SUPPLY AIR DAMPER
M1-16 C DAMPER 2ND FLO O R SUPPLY AIR DAMPER
M1-17 C DAMPER 3RD FLO OR SUPPLY AIR DAMPER
M1-18 C DAMPER 4TH FLO OR SUPPLY AIR DAMPER
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
M1-21 C DAMPER 3RD FLO OR EXHA UST/ RETURN AIR DAMPER
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
HO LD p o ints OFF p ri=9,9
M1-9 C PRESS STAIR PRESS FAN
END:
Equation 6:
Normal Conditions
Complete After
Reset
La be l: NORMAL C O NDITIO NS C O MPLETE AFTER RESET Eq uatio n 6
C O MMENTS:
INPUTS:
The O N state o f:
P290 UTILITY SET NO RMAL C ONDITIO NS A T RESET
AND NOT the TROUBLE sta te o f:
P256 TROUBLE FSCS SWITC HES NO T RESET
DELAY fo r 10 se c ., running time r is A294
O UTPUTS:
HO LD p o ints OFF p ri=9,9
P290 UTILITY SET NO RMAL C ONDITIO NS A T RESET
END:
5-9
Page 70
Smoke Control System Custom Control Equations, Continued
Equation 7:
Smoke Control
Initiate
Equation 8:
Smoke Control
Reset
La be l: SMOKE C O NTROL INITIA TE Eq ua tio n 7
C O MMENTS:
INPUTS:
The O N state o f:
A0 A NALO G NUMBER OF SYSTEM FIRE ALARMS
O UTPUTS:
TRAC K p o ints ON p ri=9,9
P275 UTILITY SMO KE C ONTROL ALARM INITIATE
PULSE a na lo g : A280, fo r 2 se c .
END:
La be l: SMOKE C O NTROL RESET Eq ua tio n 8
C O MMENTS:
Any Fire a la rm turn O FF a ll Pseud o s tha t ma y b e used in te sting
INPUTS:
The O N state o f:
A280 TIMER CUSTO M C O NTROL - TIMER
O UTPUTS:
HO LD p o ints OFF p ri=9,9
P260 UTILITY FL1 SUPPLY AIR DAMPER FA IL
P261 UTILITY FL2 SUPPLY AIR DAMPER FA IL
P262 UTILITY FL3 SUPPLY AIR DAMPER FA IL
P263 UTILITY FL4 SUPPLY AIR DAMPER FA IL
P264 UTILITY FL1 EXHAUST AIR DAMPER FAIL
P265 UTILITY FL2 EXHAUST AIR DAMPER FAIL
P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL
P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL
P268 UTILITY MAIN SUPPLY FA N FAIL
P269 UTILITY MAIN EXHA UST FAN FA IL
P270 UTILITY MAIN RETURN AIR DAMPER FAIL
P271 UTILITY MAIN SUPPLY AIR DAMPER FAIL
P272 UTILITY MAIN EXHA UST AIR DAMPER FAIL
END:
Equation 9:
Initiate Smoke
Zone 1
La be l: INITIATE SMO KE ZONE 1 Eq ua tio n 9
C O MMENTS:
An a la rm in Zo ne 1 turns O N sm o ke c o ntro l fo r zo ne 1, turns o the rs O FF
INPUTS:
The DETEC T state o f:
M1-1 FIRE 1ST FLO OR SMO KE
O UTPUTS:
HO LD p o ints ON p ri=8,8
P276 UTILITY SMO KE C O NTROL ZO NE 1 INITIA TE
HO LD p o ints OFF p ri=7,7
P277 UTILITY SMO KE C O NTROL ZO NE 2 INITIA TE
P278 UTILITY SMO KE C O NTROL ZO NE 3 INITIA TE
P279 UTILITY SMO KE C O NTROL ZO NE 4 INITIA TE
END:
5-10
Page 71
Smoke Control System Custom Control Equations, Continued
Equation 10:
Activate Smoke
Control Zone 1
Equation 11:
Initiate Smoke
Zone 2
La be l: A C TIVA TE SMO KE C O NTROL ZONE 1 Eq ua tio n 10
C O MMENTS:
The 5 se c o nd d e la y a llo ws p o ints tha t ma y b e ON in te st to b e turne d
O FF p rior to b e ing turne d O N b y this smo ke c o ntro l e qua tio n.
INPUTS:
The O N state o f:
P276 UTILITY SMO KE C O NTROL ZO NE 1 INITIA TE
DELAY fo r 5 se c ., running tim e r is A256
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
M1-21 C DAMPER 3RD FLO OR EXHA UST/ RETURN AIR DAMPER
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
M1-14 C DAMPER MAIN RETURN A IR DAMPER
M1-15 C DAMPER 1ST FLO O R SUPPLY AIR DAMPER
HO LD p o ints ON p ri=9,9
M1-11 C PRESS EXHAUST FAN RELAY
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
M1-15 C DAMPER 1ST FLO O R SUPPLY AIR DAMPER
M1-9 C PRESS STAIR PRESS FAN
END:
La be l: INITIATE SMO KE ZONE 2 Eq ua tio n 11
C O MMENTS:
INPUTS:
The DETEC T state o f:
M1-2 FIRE 2ND FLO O R SMOKE
O UTPUTS:
HO LD p o ints ON p ri=8,8
P277 UTILITY SMO KE C O NTROL ZO NE 2 INITIA TE
HO LD p o ints OFF p ri=7,7
P276 UTILITY SMO KE C O NTROL ZO NE 1 INITIA TE
P278 UTILITY SMO KE C O NTROL ZO NE 3 INITIA TE
P279 UTILITY SMO KE C O NTROL ZO NE 4 INITIA TE
END:
5-11
Page 72
Smoke Control System Custom Control Equations, Continued
Equation 12:
Activate Smoke
Control Zone 2
Equation 13:
Initiate Smoke
Zone 3
La be l: A C TIVA TE SMO KE C O NTROL ZONE 2 Eq ua tio n 12
C O MMENTS:
INPUTS:
The O N state o f:
P277 UTILITY SMO KE C O NTROL ZO NE 2 INITIATE
DELAY fo r 5 se c ., running tim e r is A285
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-14 C DAMPER MAIN RETURN A IR DAMPER
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
M1-21 C DAMPER 3RD FLO OR EXHAUST/ RETURN AIR DAMPER
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
M1-16 C DAMPER 2ND FLO O R SUPPLY AIR DAMPER
HO LD p o ints ON p ri=9,9
M1-11 C PRESS EXHAUST FAN RELAY
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
M1-16 C DAMPER 2ND FLO O R SUPPLY AIR DAMPER
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
M1-9 C PRESS STAIR PRESS FAN
END:
La be l: INITIATE SMO KE ZONE 3 Eq ua tio n 13
C O MMENTS:
INPUTS:
The DETEC T state o f:
M1-3 FIRE 3RD FLO OR SMO KE
O UTPUTS:
HO LD p o ints ON p ri=8,8
P278 UTILITY SMO KE C O NTROL ZO NE 3 INITIA TE
HO LD p o ints OFF p ri=7,7
P276 UTILITY SMO KE C O NTROL ZO NE 1 INITIA TE
P277 UTILITY SMO KE C O NTROL ZO NE 2 INITIA TE
P279 UTILITY SMO KE C O NTROL ZO NE 4 INITIA TE
END:
5-12
Page 73
Smoke Control System Custom Control Equations, Continued
Equation 14:
Activate Smoke
Control Zone 3
Equation 15:
Initiate Smoke
Zone 4
La be l: A C TIVA TE SMO KE C O NTROL ZONE 3 Eq ua tio n 14
C O MMENTS:
INPUTS:
The O N state o f:
P278 UTILITY SMO KE C ONTROL ZONE 3 INITIA TE
DELAY fo r 5 se c ., running tim e r is A286
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-14 C DAMPER MAIN RETURN A IR DAMPER
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
M1-17 C DAMPER 3RD FLO OR SUPPLY AIR DAMPER
HO LD p o ints ON p ri=9,9
M1-11 C PRESS EXHAUST FAN RELAY
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
M1-17 C DAMPER 3RD FLO OR SUPPLY AIR DAMPER
M1-21 C DAMPER 3RD FLO OR EXHAUST/ RETURN AIR DAMPER
M1-9 C PRESS STAIR PRESS FAN
END:
La be l: INITIATE SMO KE ZONE 4 Eq ua tio n 15
C O MMENTS:
INPUTS:
The DETEC T state o f:
M1-4 FIRE 4TH FLO O R SMO KE
O UTPUTS:
HO LD p o ints ON p ri=8,8
P279 UTILITY SMO KE C O NTROL ZO NE 4 INITIA TE
HO LD p o ints OFF p ri=7,7
P276 UTILITY SMO KE C O NTROL ZO NE 1 INITIA TE
P277 UTILITY SMO KE C O NTROL ZO NE 2 INITIA TE
P278 UTILITY SMO KE C O NTROL ZO NE 3 INITIA TE
END:
5-13
Page 74
Smoke Control System Custom Control Equations, Continued
Equation 16:
Activate Smoke
Control Zone 4
Equation 17:
Supply Fan Duct
Smoke Alarm
La be l: A C TIVA TE SMO KE C O NTROL ZONE 4 Eq ua tio n 16
C O MMENTS:
INPUTS:
The O N state o f:
P279 UTILITY SMO KE C ONTROL ZONE 4 INITIA TE
DELAY fo r 5 se c ., running tim e r is A287
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-14 C DAMPER MAIN RETURN A IR DAMPER
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
M1-21 C DAMPER 3RD FLO OR EXHA UST/ RETURN AIR DAMPER
M1-18 C DAMPER 4TH FLO OR SUPPLY AIR DAMPER
HO LD p o ints ON p ri=9,9
M1-11 C PRESS EXHAUST FAN RELAY
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
M1-18 C DAMPER 4TH FLO OR SUPPLY AIR DAMPER
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
M1-9 C PRESS STAIR PRESS FAN
END:
La be l: SUPPLY FA N DUC T SMO KE ALARM Eq ua tio n 17
C O MMENTS:
INPUTS:
The DETEC T state o f:
M1-6 FIRE ROO F TO P SUPPLY DUC T SMO KE DET
O UTPUTS:
HO LD p o ints OFF p ri=9,9
M1-10 C PRESS SUPPLY FA N RELAY
END:
Equation 18:
Stair Press Fan Duct
Smoke Alarm
La be l: STAIR PRESS FAN DUC T SMO KE ALARM Eq ua tio n 18
C O MMENTS:
INPUTS:
The DETEC T state o f:
M1-5 FIRE STAIR SUPPLY DUC T SMO KE DET
O UTPUTS:
HO LD p o ints OFF p ri=9,9
M1-9 C PRESS STAIR PRESS FAN
END:
5-14
Page 75
Smoke Control System Custom Control Equations, Continued
Equation 19:
Report TBL if
Supply Fan Not ON
Equation 20:
Report TBL if
Supply Fan Not OFF
La be l: REPO RT TBL IF SUPPLY FAN NO T O N Eq ua tio n 19
C O MMENTS:
INPUTS:
The O N state o f:
M1-10 C PRESS SUPPLY FA N RELAY
DELAY fo r 10 se c ., running time r is A264
AND NOT the ON sta te o f:
M1-41 UTILITY MO NITO R SUPPLY FAN O N
O UTPUTS:
HO LD p o ints ON p ri=9,9
P268 UTILITY MA IN SUPPLY FA N FAIL
END:
La be l: REPO RT TBL IF SUPPLY FAN NO T O FF Eq ua tion 20
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-10 C PRESS SUPPLY FA N RELAY
DELAY fo r 10 se c ., running time r is A292
AND NOT the ON sta te o f:
M1-50 UTILITY MO NITO R SUPPLY FA N O FF
O UTPUTS:
HO LD p o ints ON p ri=9,9
P268 UTILITY MAIN SUPPLY FA N FAIL
END:
Equation 21:
Report TBL if
Exhaust Fan Not ON
Equation 22:
Report TBL
if Exhaust Fan
Not OFF
La be l: REPO RT TBL IF EXHAUST FAN NO T O N Eq ua tio n 21
C O MMENTS:
INPUTS:
The O N state o f:
M1-11 C PRESS EXHAUST FAN RELAY
DELAY fo r 10 se c ., running time r is A263
AND NOT the ON sta te o f:
M1-43 UTILITY MO NITO R EXHAUST FAN O N
O UTPUTS:
HO LD p o ints ON p ri=9,9
P269 UTILITY MAIN EXHA UST FAN FAIL
END:
La be l: REPO RT TBL IF EXHAUST FAN NO T O FF Eq ua tio n 22
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-11 C PRESS EXHAUST FAN RELAY
DELAY fo r 10 se c ., running time r is A291
AND NOT the ON sta te o f:
M1-44 UTILITY MO NITO R EXHA UST FAN O FF
O UTPUTS:
HO LD p o ints ON p ri=9,9
P269 UTILITY
MA IN EXHAUST FAN FAIL
END:
5-15
Page 76
Smoke Control System Custom Control Equations, Continued
Equation 23:
Report TBL if Stair
Press Fan Not ON
Equation 24:
Report TBL if Stair
Press Fan Not OFF
La be l: REPO RT TBL IF STAIR PRESS FAN NOT O N Eq ua tio n 23
C O MMENTS:
INPUTS:
The O N state o f:
M1-9 C PRESS STAIR PRESS FAN
DELAY fo r 10 se c ., running time r is A265
AND NOT the ON sta te o f:
M1-42 UTILITY MO NITO R STAIR PRESS FA N O N
O UTPUTS:
HO LD p o ints ON p ri=9,9
P280 UTILITY STAIR PRESS FAN FAIL
END:
La be l: REPO RT TBL IF STAIR PRESS FAN NOT O FF Eq uatio n 24
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-9 C PRESS STAIR PRESS FAN
DELAY fo r 10 se c ., running time r is A290
AND NOT the ON sta te o f:
M1-47 UTILITY MO NITO R STAIR PRESS FA N O FF
O UTPUTS:
HO LD p o ints ON p ri=9,9
P280 UTILITY STAIR PRESS FAN FAIL
END:
Equation 25:
Report TBL if
Main EXH Damper
Not Open
Equation 26:
Report TBL if
Main EXH Damper
Not Closed
La be l: REPO RT TBL IF MAIN EXH DAMPER NOT O PEN Eq uatio n 25
C O MMENTS:
INPUTS:
The O N state o f:
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
DELAY fo r 10 se c ., running time r is A262
AND NOT the ON sta te o f:
M1-51 UTILITY MO NITO R MAIN EXHAUST A IR DAMPER OPEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P272 UTILITY MAIN EXHA UST AIR DAMPER FAIL
END:
La b e l: REPORT TBL IF MAIN EXH DA MPER NO T C LO SED Eq ua tio n 26
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
DELAY fo r 10 se c ., running time r is A281
AND NOT the ON sta te o f:
M1-52 UTILITY MO NITO R MAIN EXHAUST A IR DAMPER CLO SED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P272 UTILITY MAIN EXHA UST AIR DAMPER FAIL
END:
5-16
Page 77
Smoke Control System Custom Control Equations, Continued
Equation 27:
Report TBL if
Main SUP Damper
Not Open
Equation 28:
Report TBL if Main
SUP Damper Not
Closed
La be l: REPO RT TBL IF MAIN SUP DAMPER NO T O PEN Eq uatio n 27
C O MMENTS:
INPUTS:
The O N state o f:
M1-12 C DAMPER MAIN O UTSIDE AIR DAMPER
DELAY fo r 10 se c ., running time r is A266
AND NOT the ON sta te o f:
M1-48 UTILITY MO NITO R O UTSIDE AIR DAMPER OPEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P271 UTILITY MAIN SUPPLY AIR DAMPER FAIL
END:
La be l: REPO RT TBL IF MAIN SUP DAMPER NO T C LO SED Eq ua tio n 28
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-12 C DAMPER MAIN O UTSIDE AIR DAMPER
DELAY fo r 10 se c ., running time r is A267
AND NOT the ON sta te o f:
M1-49 UTILITY MO NITO R O UTSIDE A IR DAMPER C LO SED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P271 UTILITY MAIN SUPPLY AIR DAMPER FAIL
END:
Equation 29:
Report TBL if
Main RET Damper
Not Open
Equation 30:
Report TBL if Main
RET Damper Not
Closed
La be l: REPO RT TBL IF MAIN RET DA MPER NO T O PEN Eq uatio n 29
C O MMENTS:
INPUTS:
The O N state o f:
M1-14 C DAMPER MAIN RETURN A IR DAMPER
DELAY fo r 10 se c ., running time r is A268
AND NOT the ON sta te o f:
M1-45 UTILITY MO NITO R MAIN RETURN AIR DAMPER OPEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P270 UTILITY MAIN RETURN AIR DAMPER FAIL
END:
La be l: REPO RT TBL IF MAIN RET DAMPER NO T C LO SED Eq ua tio n 30
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-14 C DAMPER MAIN RETURN A IR DAMPER
DELAY fo r 10 se c ., running time r is A269
AND NOT the ON sta te o f:
M1-46 UTILITY MO NITO R MAIN RETURN AIR DAMPER CLOSED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P270 UTILITY MAIN RETURN AIR DAMPER FAIL
END:
5-17
Page 78
Smoke Control System Custom Control Equations, Continued
Equation 31:
Report TBL If SUP
Damper 1 Not Open
Equation 32:
Report TBL If
SUP Damper 1
Not Closed
La be l: REPO RT TBL IF SUP DAMPER 1 NOT O PEN Eq ua tion 31
C O MMENTS:
INPUTS:
The O N state o f:
M1-15 C DAMPER 1ST FLO O R SUPPLY AIR DAMPER
DELAY fo r 10 se c ., running time r is A257
AND NOT the ON sta te o f:
M1-25 UTILITY MONITO R FLR 1 SUPPLY AIR DAMPER O PEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P260 UTILITY FL1 SUPPLY AIR DAMPER FA IL
END:
La be l: REPO RT TBL IF SUP DAMPER 1 NOT C LO SED Eq ua tio n 32
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-15 C DAMPER 1ST FLO O R SUPPLY AIR DAMPER
DELAY fo r 10 se c ., running time r is A282
AND NOT the ON sta te o f:
M1-29 UTILITY MO NITO R FLR 1 SUPPLY AIR DAMPER C LO SED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P260 UTILITY FL1 SUPPLY AIR DAMPER FA IL
END:
Equation 33:
Report TBL If SUP
Damper 2 Not Open
Equation 34:
Report TBL If
Sup Damper 2
Not Closed
La be l: REPO RT TBL IF SUP DAMPER 2 NOT O PEN Eq ua tion 33
C O MMENTS:
INPUTS:
The O N state o f:
M1-16 C DAMPER 2ND FLO O R SUPPLY AIR DAMPER
DELAY fo r 10 se c ., running time r is A270
AND NOT the ON sta te o f:
M1-26 UTILITY MONITO R FLR 2 SUPPLY AIR DAMPER O PEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P261 UTILITY FL2 SUPPLY AIR DAMPER FA IL
END:
La be l: REPO RT TBL IF SUP DAMPER 2 NOT C LO SED Eq ua tio n 34
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-16 C DAMPER 2ND FLO O R SUPPLY AIR DAMPER
DELAY fo r 10 se c ., running time r is A271
AND NOT the ON sta te o f:
M1-30 UTILITY MO NITO R FLR 2 SUPPLY AIR DAMPER C LO SED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P261 UTILITY FL2 SUPPLY AIR DAMPER FA IL
END:
5-18
Page 79
Smoke Control System Custom Control Equations, Continued
Equation 35:
Report TBL If SUP
Damper 3 Not Open
Equation 36:
Report TBL If
SUP Damper 3
Not Closed
La be l: REPO RT TBL IF SUP DAMPER 3 NOT O PEN Eq ua tion 35
C O MMENTS:
INPUTS:
The O N state o f:
M1-17 C DAMPER 3RD FLO OR SUPPLY AIR DAMPER
DELAY fo r 10 se c ., running time r is A272
AND NOT the ON sta te o f:
M1-27 UTILITY MONITO R FLR 3 SUPPLY AIR DAMPER O PEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P262 UTILITY FL3 SUPPLY AIR DAMPER FA IL
END:
La be l: REPO RT TBL IF SUP DAMPER 3 NOT C LO SED Eq ua tio n 36
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-17 C DAMPER 3RD FLO OR SUPPLY AIR DAMPER
DELAY fo r 10 se c ., running time r is A273
AND NOT the ON sta te o f:
M1-31 UTILITY MO NITO R FLR 3 SUPPLY AIR DAMPER C LO SED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P262 UTILITY FL3 SUPPLY AIR DAMPER FA IL
END:
Equation 37:
Report TBL If SUP
Damper 4 Not Open
Equation 38:
Report TBL If
SUP Damper 4
Not Closed
La be l: REPO RT TBL IF SUP DAMPER 4 NOT O PEN Eq ua tion 37
C O MMENTS:
INPUTS:
The O N state o f:
M1-18 C DAMPER 4TH FLO OR SUPPLY AIR DAMPER
DELAY fo r 10 se c ., running time r is A274
AND NOT the ON sta te o f:
M1-28 UTILITY MONITO R FLR 4 SUPPLY AIR DAMPER O PEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P263 UTILITY FL4 SUPPLY AIR DAMPER FA IL
END:
La be l: REPO RT TBL IF SUP DAMPER 4 NOT C LO SED Eq ua tio n 38
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-18 C DAMPER 4TH FLO OR SUPPLY AIR DAMPER
DELAY fo r 10 se c ., running time r is A275
AND NOT the ON sta te o f:
M1-32 UTILITY MO NITO R FLR 4 SUPPLY AIR DAMPER C LO SED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P263 UTILITY FL4 SUPPLY AIR DAMPER FA IL
END:
5-19
Page 80
Smoke Control System Custom Control Equations, Continued
Equation 39:
Report TBL if EXH
Damper 1 Not Open
Equation 40:
Report TBL If EXH
Damper 1 Not
Closed
La be l: REPO RT TBL IF EXH DAMPER 1 NOT O PEN Eq uatio n 39
C O MMENTS:
INPUTS:
The O N state o f:
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
DELAY fo r 10 se c ., running time r is A258
AND NOT the ON sta te o f:
M1-33 UTILITY MO NITO R FLR 1 EXHAUST AIR DAMPER OPEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P264 UTILITY FL1 EXHAUST AIR DAMPER FAIL
END:
La be l: REPO RT TBL IF EXH DAMPER 1 NOT C LO SED Eq uatio n 40
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
DELAY fo r 10 se c ., running time r is A276
AND NOT the ON sta te o f:
M1-37 UTILITY MO NITO R FLR 1 EXHAUST AIR DAMPER CLOSED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P264 UTILITY FL1 EXHAUST AIR DAMPER FAIL
END:
Equation 41:
Report TBL If EXH
Damper 2 Not Open
Equation 42:
Report TBL If
EXH Damper 2
Not Closed
La be l: REPO RT TBL IF EXH DAMPER 2 NOT O PEN Eq uatio n 41
C O MMENTS:
INPUTS:
The O N state o f:
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
DELAY fo r 10 se c ., running time r is A277
AND NOT the ON sta te o f:
M1-34 UTILITY MO NITO R FLR 2 EXHAUST AIR DAMPER OPEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P265 UTILITY FL2 EXHAUST AIR DAMPER FAIL
END:
La be l: REPO RT TBL IF EXH DAMPER 2 NOT C LO SED Eq uatio n 42
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
DELAY fo r 10 se c ., running time r is A259
AND NOT the ON sta te o f:
M1-38 UTILITY MO NITO R FLR 2 EXHAUST AIR DAMPER CLOSED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P265 UTILITY FL2 EXHAUST AIR DAMPER FAIL
END:
5-20
Page 81
Smoke Control System Custom Control Equations, Continued
Equation 43:
Report TBL If EXH
Damper 3 Not Open
Equation 44:
Report TBL If
EXH Damper 3
Not Closed
La be l: REPO RT TBL IF EXH DAMPER 3 NOT O PEN Eq uatio n 43
C O MMENTS:
INPUTS:
The O N state o f:
M1-21 C DAMPER 3RD FLO OR EXHAUST/ RETURN AIR DAMPER
DELAY fo r 10 se c ., running time r is A278
AND NOT the ON sta te o f:
M1-35 UTILITY MO NITO R FLR 3 EXHAUST AIR DAMPER OPEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL
END:
La be l: REPO RT TBL IF EXH DAMPER 3 NOT C LO SED Eq uatio n 44
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-21 C DAMPER 3RD FLO OR EXHAUST/ RETURN AIR DAMPER
DELAY fo r 10 se c ., running time r is A260
AND NOT the ON sta te o f:
M1-39 UTILITY MO NITO R FLR 3 EXHAUST AIR DAMPER CLOSED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL
END:
Equation 45:
Report TBL If EXH
Damper 4 Not Open
Equation 46:
Report TBL If
EXH Damper 4
Not Closed
La be l: REPO RT TBL IF EXH DAMPER 4 NOT O PEN Eq uatio n 45
C O MMENTS:
INPUTS:
The O N state o f:
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
DELAY fo r 10 se c ., running time r is A279
AND NOT the ON sta te o f:
M1-36 UTILITY MO NITO R FLR 4 EXHAUST AIR DAMPER OPEN
O UTPUTS:
HO LD p o ints ON p ri=9,9
P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL
END:
La be l: REPO RT TBL IF EXH DAMPER 4 NOT C LO SED Eq uatio n 46
C O MMENTS:
INPUTS:
NO T the O N state o f:
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
DELAY fo r 10 se c ., running time r is A261
AND NOT the ON sta te o f:
M1-40 UTILITY MO NITO R FLR 4 EXHAUST AIR DAMPER CLOSED
O UTPUTS:
HO LD p o ints ON p ri=9,9
P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL
END:
5-21
Page 82
Smoke Control System Custom Control Equations, Continued
Equation 47:
Manual Control SUP
AIR Damper 1 Open
Equation 48:
Manual Control SUP
Air Damper 1 Close
La be l: MA NUAL C O NTROL SUP AIR DAMPER 1 OPEN Eq ua tio n 47
C O MMENTS:
INPUTS:
The UP sta te o f:
8-66 SWITC H Ann 1 Pt 66 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=5,9
M1-15 C DAMPER 1ST FLO O R SUPPLY AIR DAMPER
END:
La be l: MA NUAL C O NTROL SUP AIR DAMPER 1 CLO SE Eq ua tio n 48
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-66 SWITC H Ann 1 Pt 66 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=5,9
M1-15 C DAMPER 1ST FLO O R SUPPLY AIR DAMPER
END:
Equation 49:
Manual Control SUP
Air Damper 2 Open
Equation 50:
Manual Control SUP
Air Damper 2 Close
La be l: MA NUAL C O NTROL SUP AIR DAMPER 2 OPEN Eq ua tio n 49
C O MMENTS:
INPUTS:
The UP sta te o f:
8-68 SWITC H Ann 1 Pt 68 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=5,9
M1-16 C DAMPER 2ND FLO O R SUPPLY AIR DAMPER
END:
La be l: MA NUAL C O NTROL SUP AIR DAMPER 2 CLO SE Eq ua tio n 50
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-68 SWITC H Ann 1 Pt 68 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=5,9
M1-16 C DAMPER 2ND FLO O R SUPPLY AIR DAMPER
END:
5-22
Page 83
Smoke Control System Custom Control Equations, Continued
Equation 51:
Manual Control SUP
Air Damper 3 Open
Equation 52:
Manual Control SUP
Air Damper 3 Close
La be l: MA NUAL C O NTROL SUP AIR DAMPER 3 OPEN Eq ua tio n 51
C O MMENTS:
INPUTS:
The UP sta te o f:
8-70 SWITC H Ann 1 Pt 70 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=5,9
M1-17 C DAMPER 3RD FLO OR SUPPLY AIR DAMPER
END:
La be l: MA NUAL C O NTROL SUP AIR DAMPER 3 CLO SE Eq ua tio n 52
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-70 SWITC H Ann 1 Pt 70 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=5,9
M1-17 C DAMPER 3RD FLO OR SUPPLY AIR DAMPER
END:
Equation 53:
Manual Control SUP
Air Damper 4 Open
Equation 54:
Control SUP Air
Damper 4 Close
La be l: MA NUAL C O NTROL SUP AIR DAMPER 4 OPEN Eq ua tio n 53
C O MMENTS:
INPUTS:
The UP sta te o f:
8-72 SWITC H Ann 1 Pt 72 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=5,9
M1-18 C DAMPER 4TH FLO OR SUPPLY AIR DAMPER
END:
La be l: MA NUAL C O NTROL SUP AIR DAMPER 4 CLO SE Eq ua tio n 54
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-72 SWITC H Ann 1 Pt 72 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=5,9
M1-18 C DAMPER 4TH FLO OR SUPPLY AIR DAMPER
END:
5-23
Page 84
Smoke Control System Custom Control Equations, Continued
Equation 55:
Manual Control EXH
Air Damper 1 Open
Equation 56:
Manual Control EXH
Air Damper 1 Close
La be l: MA NUAL C O NTROL EXH A IR DAMPER 1 O PEN Eq uatio n 55
C O MMENTS:
INPUTS:
The UP sta te o f:
8-67 SWITC H Ann 1 Pt 67 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=5,9
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
END:
La b e l: MANUAL C O NTROL EXH A IR DAMPER 1 C LO SE Eq ua tio n 56
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-67 SWITC H Ann 1 Pt 67 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=5,9
M1-19 C DA MPER 1ST FLOO R EXHAUST/ RETURN AIR DAMPER
END:
Equation 57:
Manual Control EXH
Air Damper 2 Open
Equation 58:
Manual Control EXH
Air Damper 2 Close
La be l: MA NUAL C O NTROL EXH A IR DAMPER 2 O PEN Eq uatio n 57
C O MMENTS:
INPUTS:
The UP sta te o f:
8-69 SWITC H Ann 1 Pt 69 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=5,9
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
END:
La b e l: MANUAL C O NTROL EXH A IR DAMPER 2 C LO SE Eq ua tio n 58
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-69 SWITC H Ann 1 Pt 69 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=5,9
M1-20 C DAMPER 2ND FLO O R EXHA UST/ RETURN AIR DAMPER
END:
5-24
Page 85
Smoke Control System Custom Control Equations, Continued
Equation 59:
Control EXH Air
Damper 3 Open
Equation 60:
Manual Control EXH
Air Damper 3 Close
La be l: MA NUAL C O NTROL EXH A IR DAMPER 3 O PEN Eq uatio n 59
C O MMENTS:
INPUTS:
The UP sta te o f:
8-71 SWITC H Ann 1 Pt 71 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=5,9
M1-21 C DAMPER 3RD FLO OR EXHAUST/ RETURN AIR DAMPER
END:
La b e l: MANUAL C O NTROL EXH A IR DAMPER 3 C LO SE Eq ua tio n 60
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-71 SWITC H Ann 1 Pt 71 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=5,9
M1-21 C DAMPER 3RD FLO OR EXHAUST/ RETURN AIR DAMPER
END:
Equation 61:
Manual Control EXH
Air Damper 4 Open
Equation 62:
Manual Control EXH
Air Damper 4 Close
La be l: MA NUAL C O NTROL EXH A IR DAMPER 4 O PEN Eq uatio n 61
C O MMENTS:
INPUTS:
The UP sta te o f:
8-73 SWITC H Ann 1 Pt 73 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=5,9
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
END:
La b e l: MANUAL C O NTROL EXH A IR DAMPER 4 C LO SE Eq ua tio n 62
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-73 SWITC H Ann 1 Pt 73 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=5,9
M1-22 C DAMPER 4TH FLO OR EXHA UST/ RETURN AIR DAMPER
END:
5-25
Page 86
Smoke Control System Custom Control Equations, Continued
Equation 63:
Manual Control Stair
Press Fan ON
Equation 64:
Manual Control Stair
Press Fan OFF
La be l: MA NUAL C O NTROL STAIR PRESS FAN ON Eq ua tio n 63
C O MMENTS:
INPUTS:
The UP sta te o f:
8-65 SWITC H Ann 1 Pt 65 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=8,9
M1-9 C PRESS STAIR PRESS FAN
END:
La be l: MA NUAL C O NTROL STAIR PRESS FAN OFF Eq ua tio n 64
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-65 SWITC H Ann 1 Pt 65 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-9 C PRESS STAIR PRESS FAN
END:
Equation 65:
Manual Control Main
Supply Fan ON
Equation 66:
Manual Control Main
Supply Fan OFF
La be l: MA NUAL C O NTROL MAIN SUPPLY FAN ON Eq ua tio n 65
C O MMENTS:
INPUTS:
The UP sta te o f:
8-74 SWITC H Ann 1 Pt 74 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=8,9
M1-10 C PRESS SUPPLY FA N RELAY
END:
La be l: MA NUAL C O NTROL MAIN SUPPLY FAN OFF Eq ua tio n 66
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-74 SWITC H Ann 1 Pt 74 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-10 C PRESS SUPPLY FA N RELAY
END:
5-26
Page 87
Smoke Control System Custom Control Equations, Continued
Equation 67:
Manual Control
Main RET Air
Damper Open
Equation 68:
Manual Control
Main RET Air
Damper Close
La be l: MA NUAL C O NTROL MAIN RET A IR DAMPER OPEN Eq ua tio n 67
C O MMENTS:
INPUTS:
The UP sta te o f:
8-75 SWITC H Ann 1 Pt 75 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=8,9
M1-14 C DAMPER MAIN RETURN A IR DAMPER
END:
La be l: MANUAL C ONTROL MAIN RET AIR DA MPER C LO SE Eq ua tion 68
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-75 SWITC H Ann 1 Pt 75 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-14 C DAMPER MAIN RETURN A IR DAMPER
END:
Equation 69:
Manual Control Main
Exhaust Fan ON
Equation 70:
Manual Control Main
Exhaust Fan OFF
La be l: MA NUAL C O NTROL MAIN EXHAUST FAN O N Eq ua tio n 69
C O MMENTS:
INPUTS:
The UP sta te o f:
8-76 SWITC H Ann 1 Pt 76 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=8,9
M1-11 C PRESS EXHAUST FAN RELAY
END:
La be l: MA NUAL C O NTROL MAIN EXHAUST FAN O FF Eq uatio n 70
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-76 SWITC H Ann 1 Pt 76 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-11 C PRESS EXHAUST FAN RELAY
END:
5-27
Page 88
Smoke Control System Custom Control Equations, Continued
Equation 71:
Manual Control
Main SUP Air
Damper Open
Equation 72:
Manual Control
Main Sup Air
Damper Close
La be l: MA NUAL C O NTROL MAIN SUP AIR DAMPER O PEN Eq ua tio n 71
C O MMENTS:
INPUTS:
The UP sta te o f:
8-77 SWITC H Ann 1 Pt 77 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=8,9
M1-12 C DAMPER MAIN O UTSIDE AIR DAMPER
END:
La be l: MANUAL C ONTROL MAIN SUP AIR DAMPER C LO SE Eq ua tion 72
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-77 SWITC H Ann 1 Pt 77 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-12 C DAMPER MAIN O UTSIDE AIR DAMPER
END:
Equation 73:
Manual Control
Main EXH Air
Damper Open
Equation 74:
Manual Control
Main EXH Air
Damper Close
La be l: MA NUAL C O NTROL MAIN EXH AIR DAMPER O PEN Eq ua tio n 73
C O MMENTS:
INPUTS:
The UP sta te o f:
8-78 SWITC H Ann 1 Pt 78 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints ON p ri=8,9
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
END:
La b e l: MANUAL C ONTROL MAIN EXH AIR DAMPER CLO SE Eq ua tio n 74
C O MMENTS:
INPUTS:
The DO WN sta te o f:
8-78 SWITC H Ann 1 Pt 78 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=8,9
M1-13 C DAMPER MAIN EXHAUST AIR DAMPER
END:
5-28
Page 89
Smoke Control System Custom Control Equations, Continued
Equation 75:
Manual Control
Clear Faults
Equation 76:
Master Key-Switch
La be l: MA NUAL C O NTROL C LEAR FAULTS Eq uatio n 75
C O MMENTS:
INPUTS:
The UP sta te o f:
8-80 SWITC H Ann 1 Pt 80 G ra p hic LED/ SW C tlr w/ 32
AND the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=9,9
P260 UTILITY FL1 SUPPLY AIR DAMPER FA IL
P261 UTILITY FL2 SUPPLY AIR DAMPER FA IL
P262 UTILITY FL3 SUPPLY AIR DAMPER FA IL
P263 UTILITY FL4 SUPPLY AIR DAMPER FA IL
P264 UTILITY FL1 EXHAUST AIR DAMPER FAIL
P265 UTILITY FL2 EXHAUST AIR DAMPER FAIL
P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL
P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL
P268 UTILITY MAIN SUPPLY FA N FAIL
P269 UTILITY MAIN EXHA UST FAN FA IL
P270 UTILITY MAIN RETURN AIR DAMPER FAIL
P271 UTILITY MAIN SUPPLY AIR DAMPER FAIL
P272 UTILITY MAIN EXHA UST AIR DAMPER FAIL
P280 UTILITY STAIR PRESS FAN FAIL
END:
La be l: MA STER KEY SWITC H Eq ua tio n 76
C O MMENTS:
INPUTS:
The UP sta te o f:
8-81 SWITC H Ann 1 Pt 81 G ra p hic LED/ SW C tlr w/ 32
O UTPUTS:
TRAC K p o ints ON p ri=8,9
P273 UTILITY MASTER KEY SWITC H ENABLE
END:
5-29
Page 90
Smoke Control System Custom Control Equations, Continued
Equation 77:
Turn SONALERT ON
Equation 78:
Turn SONALERT
OFF
La be l: TURN SONALERT O N Eq ua tio n 77
C O MMENTS:
INPUTS:
O R the O N sta te o f:
P260 UTILITY FL1 SUPPLY AIR DAMPER FA IL
P261 UTILITY FL2 SUPPLY AIR DAMPER FA IL
P262 UTILITY FL3 SUPPLY AIR DAMPER FA IL
P263 UTILITY FL4 SUPPLY AIR DAMPER FA IL
P264 UTILITY FL1 EXHAUST AIR DAMPER FAIL
P265 UTILITY FL2 EXHAUST AIR DAMPER FAIL
P266 UTILITY FL3 EXHAUST AIR DAMPER FAIL
P267 UTILITY FL4 EXHAUST AIR DAMPER FAIL
P268 UTILITY MAIN SUPPLY FA N FAIL
P269 UTILITY MAIN EXHA UST FAN FA IL
P270 UTILITY MAIN RETURN AIR DAMPER FAIL
P271 UTILITY MAIN SUPPLY AIR DAMPER FAIL
P272 UTILITY MAIN EXHA UST AIR DAMPER FAIL
P280 UTILITY STAIR PRESS FAN FAIL
AND NOT the ON sta te o f:
P290 UTILITY SET NO RMAL C ONDITIO NS A T RESET
O UTPUTS:
HO LD p o ints ON p ri=9,9
P293 UTILITY PIEZO AC TIVATE
END:
La be l: TURN SONALERT O FF Eq ua tio n 78
C O MMENTS:
INPUTS:
The UP sta te o f:
8-82 SWITC H SILENCE SWITC H
And the O N state o f:
P273 UTILITY MASTER KEY SWITC H ENABLE
O UTPUTS:
HO LD p o ints OFF p ri=8,9
P293 UTILITY PIEZO AC TIVATE
END:
La be l: [END-O F-PRO GRAM]
5-30
Page 91
Chapter 6
Glossary of Terms
Introduction
In this Chapter
This chapter contains a glossary to terms that are used in this publication
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Glossary of Terms 6-2
6-1
Page 92
Glossary of Terms
Glossary
Acceptance Tests – Tests designed to prove a smoke control system is capable of doing what is
designed to do.
AHJ – The “Authority Having Jurisdiction” is the organization, office, or individual responsible
for approving equipment, an installation, or a procedure.
Alarm Service – The service required following the receipt of an alarm signal.
Alarm Signal – A signal indicating an emergency requiring immediate action, as an alarm for fire
from a manual box, a waterflow alarm, an alarm from an automatic fire alarm system, or other
emergency signal.
Alarm System – A combination of compatible initiating devices, control panels, and notification
appliances designed and installed to produce an alarm signal in the event of fire.
Annunciator – A unit containing two or more identified targets or indicator lamps in which each
target or lamp indicates the circuit, condition, or location to be annunciated.
Auxiliarized Local System – A local system that is connected to the municipal alarm facilities.
Auxiliarized Proprietary System – A proprietary system that is connected to the municipal alarm
facilities.
Auxiliary Protective Signaling System – A connection to the municipal fire alarm system to
transmit an alarm of fire to the municipal communications center. Fire alarms from an auxiliary
alarm system are received at the municipal communications center on the same equipment and by
the same alerting methods as alarms transmitted from municipal fire alarm boxes located on
streets.
Auxiliary Trip Relay – A relay used to operate a municipal master box from an auxiliarized
control panel.
Bell, Single Stroke – A bell whose gong is struck only once each time operating energy is applied.
Bell, Vibrating – A bell that rings continuously as long as operating power is applied.
Box (or Station), Fire Alarm – (1) Non-coded. A manually operated device that, when operated,
closes or opens one or more sets of contacts and generally locks the contacts in the operated
position until the box is reset. (2) Coded. A manually operated device in which the act of pulling a
lever causes the transmission of not less than three rounds of coded alarm signals. Similar to the
non-coded type, except that instead of a manually operated switch, a mechanism to rotate a code
wheel is utilized. Rotation of the code wheel, in turn, causes an electrical circuit to be alternately
opened and closed, or closed and opened, thus surrounding a coded alarm that identifies the
location of the box. The code wheel is cut for the individual code to be transmitted by the device
and can operate by clockwork or by an electric motor. Clockwork transmitters can be pre-wound
or can be wound by the pulling of the alarm lever. Usually the box is designed to repeat its code
four times and automatically come to rest. Pre-wound transmitters must sound a trouble signal
when they required rewinding. Solid state electronic coding devices are also used in conjunction
with the fire alarm control unit to produce coded sounding of the audible signaling appliances.
Break-glass Box (or Station) – A break-glass box is one in which it is necessary to break a
special element in order to operate the box.
Continued on next page
6-2
Page 93
Glossary of Terms, Continued
Glossary
Bypass Pressure Control System – The bypass-around supply fan can actually be placed at any
level. The bypass duct dampers are controlled by one or more static pressure sensors located
between the stairtower and the building. In addition, a manually operated damper may be located
at the top of the stairtower for smoke purging by the Fire Department.
CC – Custom Control.
Central Station System – A system, or group of systems, in which the operations of circuits and
devices are signaled automatically to, recorded in, maintained, and supervised from an approved
central station having competent and experienced observers and operators who, upon receipt of a
signal, take the required action. Such systems are controlled and operated by a person, firm, or
corporation whose principal business is the furnishing and maintaining of supervised signaling
service.
Channel – A path for signal transmission between two or more stations or channel terminations.
A channel can consist wire, radio waves, or equivalent means of signal transmission.
Chimes – A single stroke or vibrating-type audible signal appliance that has a xylophone-type
striking bar.
Circuit Interface – A functional assembly that interfaces one or more of its initiating device
circuits with a signaling line circuit in a manner that permits the central supervising station to
indicate the status of each of its individual initiating device circuits.
Circuit – The conductors or radio channel, and associated equipment used to perform a definite
function in connection with an alarm system.
Coded Signal – A signal pulsed in a prescribed code for each round of transmission. A minimum
of three rounds and a minimum of three impulses are required for an alarm signal.
Combination Detector – A device that either (1) responds to more than one of the fire
phenomena such as smoke, heat, flame, and fire gas or (2) employs more than one operating
principle to sense one of these phenomena. Typical examples are (1) a combination of heat
detector with a smoke detector, or (2) a combination rate-of-rise and fixed temperature heat
detector.
Combination System – A local protective signaling system for fire alarm, supervisory, or guard
tour supervisory service whose components may be used in whole or in part in common with a
non-fire signaling system such as a paging system, a burglar alarm system, a musical program
system, or a process monitoring service system, without degradation of or hazard to the protective
signaling system.
Communication Channel – A signaling channel (usually leased from a communication utility
company) having two or more terminal locations and a suitable information handling capacity
depending on the characteristics of the system used. One terminal location is at the central
supervising station and the other terminal location or locations are sources from which are
transmitted alarm signals, supervisory signals, trouble signals, and such other signals as the central
supervising station is prepared to receive and interpret.
Compensated System – Adjust the airflow to make up for pressure lost through open doors.
A compensated system can use dampers (or vents) to relieve excess pressure in the stairtower to
ensure that the pressure does not go over the maximum limit.
Continued on next page
6-3
Page 94
Glossary of Terms, Continued
Glossary
Control Unit – A device with the control circuits necessary to (a) furnish power to a fire alarm
system; (b) receive signals from alarm initiating devices and transmit them to audible alarm
notification appliances and accessory equipment; and (c) electrically supervise the system
installation wiring and primary (main) power. The control unit can be contained in one or more
cabinets in adjacent or remote locations.
Dedicated Smoke Control Components – Solely used for smoke control functions and are not
operated in a non-emergency condition. Dedicated system equipment is therefore required to
incorporate an automatic weekly self-test or each smoke control function.
Dedicated Smoke Control System – Installed in a building for the sole purpose of controlling
smoke.
Delinquency Signals – A signal indicating the need of action in connection with the supervision
of guards or system attendants.
Duct System – Use bypass dampers and ducts to control the amount of air flowing from the fan to
the outlets. The bypass dampers are opened when the stairtower is at the proper pressure, so that
excess air flows not into the duct system, but into the bypass duct and back to the air inlet.
Emergency Voice/Alarm Communication Systems – A system that provides dedicated manual
or automatic, or both, facilities for originating and distributing voice instructions, as well as alert
and evacuating signals pertaining to a fire emergency to the occupants of a building.
EOL Device – End of Line Device. A device used to terminate a supervised circuit.
EOLR – End of Line Resistor.
EP Damper Control – Electrical to Pressure Damper Control. This type of damper control may
not be commonly used due to lack of full damper position sensing.
FACP – Fire Alarm Control Panel.
Fault – An open, ground, or short condition on any line(s) extending from a control unit, which
could prevent normal operation.
FDM – Frequency Division Multiplexing. A signaling method characterized by the simultaneous
transmission of more than one signal in a communication channel. Signals from one or multiple
terminal locations are distinguished from one another by virtue of each signal being assigned to a
separate frequency or combination of frequencies.
Fire Dampers – Dampers that block a fire from penetrating a fire rated partition via a duct.
These dampers are normally-open, held in place by a fusible link. The specifications for fire
dampers appear in UL Standard 555, Standard for Fire Dampers.
Fire Suppression System – Limits the growth rate of a fire, but does not eliminate or limit smoke.
Fire-Rated Ceiling – A ceiling made of fire-resistant materials.
Fire-Rated Partition – A fire partition is a wall that is built of fire resistant materials and that
reaches from floor to ceiling.
Flame Detector – A device that detects infrared, or ultraviolet, or visible radiation produced by a
fire.
FSCS – Firefighter’s Smoke Control Station. A graphic annunciating control panel that gives
firefighters information about the state of the smoke control system as well as manual control over
all of its components.
Ground Fault Detector – Detects the presence of a ground condition on system wiring.
Continued on next page
6-4
Page 95
Glossary of Terms, Continued
Glossary
Ground Fault – A condition in which the resistance between a conductor and ground reaches an
unacceptably low level.
Heat Detector – A device which detects abnormally high temperature or rate-of-temperature rise.
Horns – An audible signal appliance in which energy produces a sound by imparting motion to a
flexible component that vibrates at some nominal frequency.
HVAC system – Heating, ventilation, and air conditioning system.
IDC – Initiating Device Circuit.
Initiating Device – A manually or automatically operated device, the normal intended operation
of which results in a fire alarm or supervisory signal indication from the control unit. Examples of
alarm signal initiating devices are thermostats, manual boxes, smoke detectors, and waterflow
switches. Examples of supervisory signal initiating devices are water level indicators, sprinklersystem valve-position switches, pressure supervisory transmitters, and water temperature switches.
Initiating Device Circuit – A circuit to which automatic or manual signal initiating devices such
as fire alarm boxes, fire detectors, and waterflow alarm devices are connected.
Labeled – Equipment or materials to which has been attached a label, symbol or other identifying
mark of an organization acceptable to the “Authority Having Jurisdiction” and concerned with
product evaluation, that maintains periodic inspection of production of labeled equipment or
materials and by whose labeling the manufacturer indicates compliance with appropriate standards
or performance in a specified manner.
Leg Facility – That part of a signaling line circuit connecting each protected building to the trunk
facility or directly to the central supervising station.
Listed – Equipment or materials included in a list published by an organization acceptable to the
“Authority Having Jurisdiction” and concerned with product evaluation, that maintains periodic
inspection of production of listed equipment or materials periodic inspection of production of
listed equipment or materials and whose listing states either that the equipment or material meets
appropriate standards or has been tested and found suitable for use in a specified manner.
Local Alarm System – A local system sounding an alarm as the result of the manual operation of
a fire alarm box or the operation of protection equipment or systems, such as water flowing in a
sprinkler system, the discharge of carbon dioxide, the detection of smoke, or the detection of heat.
Local Energy Auxiliary Alarm System – An auxiliary alarm system that employs a locally
complete arrangement of parts, initiating devices, relays, power supply, and associated
components to automatically trip a municipal transmitter or master box over electric circuits that
are electrically isolated from the municipal system circuits.
Local Supervisory System – A local system arranged to supervise the performance of guard
tours, or the operative condition of automatic sprinkler systems or other systems for the protection
of life and property against the fire hazard.
Local System – A local system is one that produces a signal at the premises protected.
Maintenance – Repair service, indicating periodic inspections and tests, required to keep the
protective signaling system and its component parts in an operative condition at all times, together
with replacement of the system of its components, when for any reason they become
undependable of inoperative.
Continued on next page
6-5
Page 96
Glossary of Terms, Continued
Glossary
Master Box – A municipal fire alarm box that may also be operated by remote means.
Multiplexing – A signaling method characterized by the simultaneous or sequential transmission,
or both, and reception of multiple signals in a communication channel including means for
positively identifying each signal.
Municipal Communications Center – The building or portion of a building used to house the
central operating part of the fire alarm system; usually the place where the necessary testing,
switching, receiving, retransmitting, and power supply devices are located.
Municipal Fire Alarm Box – A specially manufactured enclosure housing a manually operated
transmitter used to send an alarm to the municipal communications center.
Municipal Transmitter – A specially manufactured enclosure housing a transmitter that can only
be tripped remotely, used to send an alarm to the municipal communications center.
NDU – Network Display Unit.
Negative Air Pressure Technique – Pulls the smoke out of the area and vents it outside of the
building.
Non-coded Signal. – Signal from any notification appliance that is energized continuously.
Non-Compensated System. – Simply turn on a fan to pressurize the stairtower. The fan speed
does not change to compensate for doors opening and closing. The more doors that are open, the
more the pressure differential between the stairtower and the building drops.
Non-Dedicated Smoke Control Components – Consists of HVAC components within a building
which are operated regularly. The normal “comfort” level associated with the proper operation of
the equipment serves as the means of maintaining system integrity.
Non-Dedicated Smoke Control System – Uses parts of the HVAC system to control smoke.
Normal Stack Effect – An upward movement of air within the building.
Notification Appliance – Any audible or visible signal employed to indicate a fire, supervisory,
or trouble condition. Examples of audible signal appliances are bells, horns, sirens, electronic
horns, buzzers, and chimes. A visible indicator consists of a lamp, target, meter deflection, or
equivalent.
Notification Appliance Circuit – A circuit or path directly connected to an notification
appliance(s) such as bell, horns, chimes, or others.
NPU – Networking Processing Unit.
Operational Tests – Test that make sure the components and subsystems of the smoke control
system are installed correctly.
Paging System – A system intended to page one or more persons such as by means of voice over
loudspeaker stations located throughout the premises or by means of coded audible signal or
visual signals similarly distributed, or by means of lamp annunciators located throughout the
premises.
Permanent Visual Record (Recording) – Immediately readable, not easily alterable print, slash,
punch, etc., listing all occurrences of status change.
Piston Effect – Transient pressures produced when an elevator car moves inside the shaft during a
smoke emergency. This “piston effect” can pull smoke into a normally pressurized elevator lobby
or elevator; shaft.
Continued on next page
6-6
Page 97
Glossary of Terms, Continued
Glossary
Proprietary Protective Signaling System– An installation of protective signaling systems that
serve contiguous and noncontiguous properties under one ownership from a central supervising
station located at the protected property, where trained, competent personnel are in constant
attendance. This includes the central supervising station, power supplies, signal-initiating devices,
initiating device circuits, signal notification appliances, equipment for the automatic, permanent
visual recording of signals, and equipment for the operation of emergency building control
services.
Protective Signaling Systems– Electrically operated circuits, instruments, and devices, together
with the necessary electrical energy, designed to transmit alarm, supervisory, and trouble signals
necessary for the protection of life and property.
Rectifier – An electrical device without moving parts that changes alternating current to direct
current.
Remote Station Protective Signaling System – An installation using supervised dedicated
circuits, installed to transmit alarm, supervisory, and trouble signals from one or more protected
premises to a remote location at which appropriate action is taken.
Repeater Facility – Equipment needed to relay signals between the protected premises and the
central supervising action.
Reverse Stack Effect – Downward movement of air within the building.
RUI – Remote Unit Interface communications
SLC – Signaling Line Circuit (Path). A circuit or path (channel or trunk and leg) over which
multiple signals are transmitted and received.
Smoke Barriers – Barriers that prevent smoke from passing through them.
Smoke Control System – A system that employs motorized fans to create air pressure differences
and positive or negative airflows to limit and control the movement of smoke and other noxious
gases. Provides safe zones and tolerable conditions along exit routes but can do little to control
fire.
Smoke Control Zones – A zone must be separated from other zones by smoke dampers, airtight
doors, and smoke-proof barriers.
Smoke Damper – (1)A damper that prevents smoke from passing through when fully closed.
(2) Dampers that meet the requirements given in UL 555S, Standard for Leakage Rated Dampers for Use in Smoke Controls Systems. (3) In a smoke control system, the damper must be fitted with
the end-position switches to provide feedback to the smoke control system.
Smoke Detector – A device that detects visible or invisible particles of combustion.
Spacing – A horizontal measured dimension relating to the allowable coverage of fire detectors.
Stairtower – A stairwell with a ventilation system that is located from the main building.
Supervision Service – The service required to monitor performance of guard patrols and the
operative condition of automatic sprinkler system and of other systems for the protection life and
property.
Supervision – The term supervised refers to monitoring of the circuit, switch, or device in such a
manner that a trouble signal is received when a fault that would prevent normal operation of the
system occurs.
Continued on next page
6-7
Page 98
Glossary of Terms, Continued
Glossary
Supervisory Signal – A signal indicating the need of action in connection with the supervision of
guard tours, sprinkler and other extinguishing system standards and designated as such by the
Authority Having Jurisdiction.
System Flexibility – Using features that allow for easy adjustment of a particular system to meet
the demands of a given situation.
Tenable Environment – As defined by the NFPA, an environment in which the quantity and
location of smoke is limited or otherwise restricted to allow for ready evacuation though the space.
Transmitter – A system component to which initiating devices or groups of initiating devices are
connected. The component transmits signals to the central supervising station indicating the status
of the initiating devices and the initiating device circuits.
Trouble Signal – An audible signal indicating trouble of any nature, such as a circuit break or
ground, occurring in the devices or wiring associated with a protective signaling system.
TSW – TrueSite Workstation System. The 4190 TSW provides a graphical user workstation
within the Simplex Smoke System.
Visible Signal – A visible signal is the response to the operation of an initiating device by one or
more direct or indirect visible notification appliances. For a direct visible signal, the sole means of
notification is by illumination of the area surrounding the visible signaling appliance.
Waterflow Switch – An assembly approved for the service and so constructed and installed that
any flow of water from a sprinkler system equal to or greater than that from a single automatic
sprinkler of the smallest orifice size installed on the system will result in activation of this switch
and subsequently indicate an alarm condition.
Zone – A designed area of a building. Commonly, zones within a building are annunciated to
rapidly locate a fire.
6-8
Page 99
Index
2
24-Point I/O Graphic Interface, 3-4
4
4010 Fire Alarm Control Panel (FACP), 3-5
4020 FACP, 3-5
4190 TrueSite Workstation, 3-4
A
acceptance tests, 1-20
additional documentation, 1-20
air inlets and outlets, 1-12
air pressure, 1-1, 1-11
air pressure differential, 1-3
air pressure, differences in, 1-3
amber/orange indicators, 3-8
ASHRAE, 1-15
audible signal, 3-9
automatic door closing mechanism, 1-14
automatic fire suppression systems, 1-2
B
bypass duct dampers, 1-17
bypass pressure control system, 1-17
End of Program, 5-4
Test Stairwell Air Pressure, 5-4
F
fans, 3-8
fans and duct work, 1-11
fire control system, 1-9
fire damper, 1-12
fire detection system, 1-19
fire extinguishers, gas-based, 1-9
fire suppression systems, 1-2
fire zone, 1-5
Firefighter Smoke Control Station, 3-7
Firefighter's Smoke Control Station (FSCS),