Simplex 4100 Operation User guide

Page 1
i
4100 Fire Alarm
Front Panel Operation
Version 9.X Addendum
579-126 Rev. B
Page 2
Page 3
iii
Copyright  Simplex Time Recorder Co., 2000. All rights reserved. Printed in the United States of America.
Copyright  2000 Simplex International Time Equipment Co., Ltd., Mississauga, Ontario L4V 1H3 Canada.
All specifications and other information shown were current as of publication, and are subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written consent of Simplex Time Recorder Company.
The suffix “C” following an eight-digit Product ID number denotes a ULC-listed product.
MAPNET II
communications is protected by U.S. Patent No.4,796,025.
TrueAlarm Analog Detection is protected by U.S. Patent No. 5,155,468.
TrueAlarm
Detector Base is protected by U.S. Patent No. 5,173, 683.
TrueAlert
and IDNet are trademarks of the Simplex Time Recorder Company.
Copyrights and Trademarks
Copyrights
Trademarks
Page 4
iv
Page 5
v
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be tested in accordance with NFPA72-1999, Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating appliances that are not directly affected by the change (up to a maximum of 50 appliances) must also be tested and proper system operation verified.
Follow the instructions in the installation, operating and programming manuals. These instructions must be followed to avoid damage to the Fire Alarm Control Panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED.
Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs. Servicing should be performed by qualified Simplex Representatives.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing appliance pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.
Cautions and Warnings
Page 6
vi
Page 7
vii
Table of Contents........................................................................................... vii
List of Figures................................................................................................. ix
How to Use this Publication............................................................................ xi
Conventions Used ....................................................................................... xi
Key Name Conventions .............................................................................. xi
About this Document ..................................................................................... xii
Introduction................................................................................................ xii
Related Documents .................................................................................... xii
Chapter 1. Version 9.X Overview
Introduction................................................................................................... 1-1
In this Chapter........................................................................................... 1-1
Version 9.X System Description................................................................... 1-2
4100/4020 Version 9.X Compatibility...................................................... 1-2
TrueAlert Addressable Controller............................................................. 1-2
Virtual NACs ............................................................................................ 1-3
TrueAlert Appliances................................................................................ 1-4
VNAC Status ............................................................................................1-4
TrueAlert Controller ................................................................................. 1-4
Effects on the Operator Interface.............................................................. 1-5
Operational Characteristics........................................................................... 1-6
Status Reporting........................................................................................ 1-6
Appliance Control with VNACs ............................................................... 1-7
TrueAlert Disabling/Enabling................................................................... 1-7
Computer Port/SDACT............................................................................. 1-8
Operator Interface......................................................................................... 1-9
TrueAlert Appliances................................................................................ 1-9
Function Key Display ............................................................................... 1-9
Virtual NACs .......................................................................................... 1-10
Display First Alarm................................................................................. 1-11
Chapter 2. System Operations
Introduction................................................................................................... 2-1
In this Chapter........................................................................................... 2-1
Handling Abnormal Conditions .................................................................... 2-2
Read the Display....................................................................................... 2-2
How to Identify a TrueAlert Appliance ....................................................2-2
How to Identify a Version Mismatch Condition ....................................... 2-3
Handling Disabled Conditions...................................................................... 2-5
Introduction............................................................................................... 2-5
How to Disable a VNAC...........................................................................2-5
How to Enable a VNAC............................................................................ 2-6
Chapter 3. TrueAlert Diagnostics
Introduction................................................................................................... 3-1
Contents
Page 8
viii
In this Chapter........................................................................................... 3-1
About TrueAlert Diagnostics........................................................................ 3-2
Diagnostics Trouble.................................................................................. 3-2
Activate all Appliance LEDs on all TrueAlert Controller Channels......... 3-2
Single Appliance Test Mode (Manual Real Appliance Test).................... 3-2
Global Silent Appliance Test .................................................................... 3-3
Manual Silent Appliance Test................................................................... 3-3
4100/4020 WalkTest................................................................................. 3-3
Appliance LED Activation............................................................................ 3-4
Procedure .................................................................................................. 3-4
Manual Real Appliance Test......................................................................... 3-5
Procedure .................................................................................................. 3-5
Global Silent Appliance Test Mode.............................................................. 3-6
Procedure .................................................................................................. 3-6
Manual Silent Appliance Test Mode............................................................. 3-7
Procedure .................................................................................................. 3-7
TrueAlert Appliance WalkTest..................................................................... 3-8
Procedure .................................................................................................. 3-8
Page 9
ix
Figure 1-1. Graphical Representation of Virtual NACs................................... 1-3
Figure 1-2. Device Address Field .................................................................... 1-9
Figures
Page 10
x
Page 11
xi
Before you start using the 4100 Fire Alarm Front Panel Operation Version 9.X Addendum, it's important to understand the conventions used in this publication.
The following conventions are used in this publication to identify special names or text.
Italic type indicates important terms or titles of publications, such as
the 4100 Fire Alarm Front Panel Operation Version 9.X Addendum.
Text enclosed in quotation marks indicates the title of a chapter or section of
the manual, such as “How to Use this Publication.”
Bulleted lists, such as this one, provide you with information. They are also
used to indicate alternatives in numbered procedural steps.
Numbered lists indicate procedures with steps that you must carry out
sequentially.
The following convention is used to describe keys on the Front Panel (Operator Interface Panel).
Operator Interface Panel Auxiliary Keypad names appear in bold type and
in capital letters and are referred to by their names only, without the word “key.” For example, “press ENTER” means press the ‘ENTER’ key on the Auxiliary Keypad.
When an annunciator membrane key is referenced in this manual, it is normally shown bracketed and in capital letters. Examples are <ALARM SILENCE> and < SYSTEM RESET>.
How to Use this Publication
Conventions Used
Key Name Conventions
Page 12
xii
This publication has been created as an addendum to the 4100/4100+ Fire Alarm Operating Instructions (574-018), to document the operation of the TrueAlert features specific to Version 9.X of the 4100/4020 firmware.
Applications may vary due to custom programming and local code requirements.
Refer to the following documents for additional information.
Title Document
TrueAlert Addressable Controller Installation Guide 574-762
TrueAlert Addressable Controller Application Guide 574-796
4100 Fire Alarm Front Panel Operation Instructions Rev. 8.01 Addendum
574-121
About this Document
Introduction
Related Documents
Page 13
1-1
This chapter gives an overview of Version 9.X functionality and describes the operational characteristics and the operator interface of the 4100/4020 Fire Alarm Control Panel (FACP) with Version 9.X firmware installed.
This chapter discusses the topics listed in the following table. Refer to the page number listed after the topic for information on that topic.
Topic See Page #
Version 9.X System Description 1-2
Operational Characteristics 1-6
Operator Interface 1-9
Chapter 1
Version 9.X Overview
Introduction
In this Chapter
Page 14
1-2
To use TrueAlert functionality, Version 9.X (or higher) of the 4100/4020 firmware is required. In addition, the 4100/4020 requires the use of a TrueAlert Addressable Controller connected to the 4100/4020 (via an RUI card) as an external slave.
The 4100/4020 Version 9.X firmware maintains compatibility with all systems that are currently compatible with Version 8 of the 4100/4020 firmware.
Version 9.X of the 4100/4020 firmware requires no changes to other systems, and will operate alongside other 4100s or 4020s on a 4120 Network running Version 8 or higher (i.e., FACPs on a network not using TrueAlert do not have to be upgraded if they are already at Version 8).
The TrueAlert appliances are interfaced to the 4100/4020 FACP through the use of the TrueAlert Addressable Controller. The TrueAlert Addressable Controller is an intelligent slave that uses an RUI interface and consumes one card address.
The number of TrueAlert Controllers in a system is limited by the total number of cards allowed where each TrueAlert Controller is one card address. The TrueAlert Addressable Controller supports the use of up to 189 appliances distributed over three TrueAlert Signaling Line Circuit (SLC) channels (with a maximum of 63 appliances on any channel). It uses slot and appliance addressing to uniquely identify each appliance.
Continued on next page
Version 9.X System Description
4100/4020 Version 9.X Compatibility
TrueAlert Addressable Controller
Page 15
1-3
A Virtual NAC (or VNAC) is a collection of TrueAlert appliances grouped together to allow control functions. Each 4100/4020 system can support up to 64 Virtual NACs (8 default VNACs plus 56 user-defined VNACs). A VNAC can be made up of TrueAlert appliances from any or all of the TrueAlert Controller channels. (A VNAC may cross channel or controller boundaries.)
The 4100/4020 supports custom labels for VNACs, and treats VNACs as notification appliance circuits that can be controlled as system points. An example of this might be a high rise, where every floor wires a single A/V unit in the stairwell. All of the stairwell A/Vs could belong to a single VNAC, although they are distributed across many TrueAlert channels.
Figure 1-1 shows a graphical representation of VNACs. Any appliance may be assigned to up to three groups (in addition to its default group). A TrueAlert Addressable Controller can then control the appliances via VNAC addressing. This means that it can tell all the appliances in a VNAC to turn on or off with a single command that is VNAC-addressed. An appliance maintains internal status for each of its VNACs. With the exception of the default VNACs, the appliance will be on whenever any of its members are on.
Figure 1-1. Graphical Representation of Virtual NACs
Continued on next page
Version 9.X System Description,
Continued
Virtual NACs
FACP
TrueAlert Slave Card
Group 5
Channel 1
Channel 3
Group 6
Group 6 Group 7Group 5
Virtual NAC 6
VNAC 1
(Default – All Appliance Outputs)
RUI Communications
VNAC 12
VNAC 14
VNAC 13
VNAC 9 VNAC 10
VNAC 11
To/From
4100/4020
FACP
TrueAlert
Addressable
Controller
Channel 2
Page 16
1-4
TrueAlert Appliances can have one of the following status conditions:
Normal
Missing (trouble)
Wrong appliance (trouble)
Short (trouble – isolator only)
VNACs have the following status information:
On/off
Disabled (trouble)
Manual override (trouble)
Priority (2-15)
The TrueAlert Controller can have one of the following card-level status conditions:
Card Missing Trouble
Wrong Card Trouble
Channel 1 Class A Trouble
Channel 2 Class A Trouble
Channel 3 Class A Trouble
Channel 1 Communications Failure
Channel 2 Communications Failure
Channel 3 Communications Failure
Positive Earth
Negative Earth
AC Fail
Battery Low/Disconnected
Running on Depleted Battery
Channel 1 Short Circuit Trouble
Channel 2 Short Circuit Trouble
Channel 3 Short Circuit Trouble
Hardware Configuration Mismatch Trouble
Battery Charger Trouble
TrueAlert Channel Controller Trouble
Common Class A Trouble
Continued on next page
Version 9.X System Description,
Continued
TrueAlert Appliances
VNAC Status
TrueAlert Controller
Page 17
1-5
The Version 9.X TrueAlert modifications have the following effects on the 4100/4020 Operator Interface:
TrueAlert appliances are visible as points with custom labels. However, appliances cannot be individually controlled and there is no “ON/OFF” status.
TrueAlert appliances only have trouble status associated with them.
TrueAlert channels are visible and behave in a similar fashion to MAPNET
channels in terms of status reporting.
Turning on all of the LEDs on a TrueAlert Controller is accomplished through the TrueAlert appliance address.
VNACs are visible as signal circuits. They appear after the last conventional signal circuit in the FACP.
VNACs only have on/off, disable, and manual override status associated with them.
Version 9.X System Description,
Continued
Effects on the Operator Interface
Page 18
1-6
The TrueAlert controller gathers a roster of appliances on each of its TrueAlert channels. This roster is then compared to the appliance download information sent by the 4100/4020 Master. If any extra appliances are found, the “Extra Appliance Trouble” status (one status report per TrueAlert Controller) is sent to the 4100/4020. Any extra appliances reported are simply logged in the 4100/4020’s Trouble Log by the Master (similar to MAPNET operation). Once the extra appliance trouble has been reported, it is cleared when the trouble is fixed. Any missing or wrong appliances are also reported at this point (and at any time they change state) as individual troubles in the system. Although only one ‘extra appliance’ trouble will be reported per TrueAlert controller, each extra appliance reported will be logged as such (similar to MAPNET extra appliance operation).
Like all other card status points, the TrueAlert card statuses cannot be made public on the 4120 Network. Card status troubles are all lumped together in the Common Trouble Card Status count.
Only trouble status information is displayed for the appliances (the actual on/off state of individual appliances is unknown to the 4100/4020 system). The possible trouble messages are shown below:
NO ANSWER (appliance missing)
WRONG DEVICE
SHORT CKT TROUBLE (Isolator only)
Individual TrueAlert appliances cannot be made public on the 4120 Network. Therefore, individual appliance troubles are grouped into the 4100/4020 Common Trouble’s Miscellaneous Trouble count. Each TrueAlert appliance that goes into trouble will increment the Common Trouble’s Miscellaneous count. As the trouble clears, the Miscellaneous count will decrement.
Continued on next page
Operational Characteristics
Status Reporting
Page 19
1-7
Appliance control may be performed in the 4100/4020 with the following methods (note that all methods apply to a VNAC):
Manual ON/OFF control with the 4100/4020 keypad (will cause a manual
override trouble on the VNAC)
Switch mode activation (using ONOFF, TOF, PBT modes) if programmed
Computer Port commands (SET, TRACK)
The same rules applied to standard 4100/4020 Signal Circuits apply to the VNACs. A point is only turned on if the requested priority is ‘higher’ than the point’s current priority and if the point is not in manual override trouble. If the point is in manual override trouble, any command other than another manual operation is ignored until the point is restored to automatic operation.
Only the TrueAlert VNACs may be enabled or disabled like other 4100/4020 Signal Circuits. This may be performed through:
Disable /Enable key on 4100/4020 keypad
Switch activation (DE, TDE if programmed)
Computer Port command (DISABLE ON, DISABLE OFF)
Continued on next page
Operational Characteristics,
Continued
Appliance Control with VNACs
TrueAlert Disabling/Enabling
Page 20
1-8
Both TrueAlert appliances and the Virtual NACs will report their statuses on the 4100/4020’s Computer Port. In addition, the SHOW command is expanded to display the Virtual NAC and appliance ‘function screen’ data. The information in the Unsolicited Output section also applies to the 4100/4020 SDACT.
The TrueAlert VNACs will also report unsolicited trouble status changes. They report to the computer port in either address or symbolic format (SIG9 or 3-2-
44) or both ways depending on the terminal settings. VNACs also report their
control status (C0 for OFF, C1 for ON) as they change state.
CLIST and LIST Commands
The CLIST and LIST commands will operate exactly as on the current 4100/4020 except that TrueAlert appliances and VNACs may now be included in the possible response.
SET Command
The SET command allows the control of TrueAlert VNACs. All operations performed with the SET command on standard 4100/4020 Signal Circuits also apply to the VNACs. Individual TrueAlert appliances cannot be controlled with the SET command. If you attempt to do so, you will receive an appropriate error message.
SHOW Command
The SHOW command will be expanded to display the “function screen” information for both TrueAlert appliances and VNACs.
The SHOW screen format for various TrueAlert appliances is shown below:
40 CHARACTER CUSTOM LABEL HORN NORMAL
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ­CARD: 5 CHANNEL: 3 APPLIANCE: 31 AUDIBLE GROUP CONFIG: 11 22 33 VISUAL GROUP CONFIG: 00 00 00 CODING OPERATION: MARCH TIME
The SHOW screen format for Virtual NACs is shown below:
40 CHARACTER CUSTOM LABEL SIGNAL CIRCUIT NORMAL
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ­POINT ADDRESS: 175-2-0 SIGNAL CIRCUIT: SIG10 ENABLED RELAY STATUS IS OFF PRIORITY 15 AUTOMATIC CONTROL
Operational Characteristics,
Continued
Computer Port/SDACT
Page 21
1-9
Individual TrueAlert appliances are called-up on the 4100/4020 Operator Interface Panel via the ‘address’ key. The card number, channel number, and appliance number must be known in order to select the point for viewing from the Operator Interface Panel.
Figure 1-2. Device Address Field
If the point in question is active on the trouble list, it may be viewed by using the Trouble Acknowledge or scroll keys. A TrueAlert appliance has the following high-level screen:
40 CHARACTER CUSTOM LABEL HORN NORMAL
If you press FUNCTION when an individual TrueAlert appliance is on the display, the following screen is displayed to indicate the appliance’s card, channel number, and address:
40 CHARACTER CUSTOM LABEL CARD: 5 CHANNEL: 3 DEVICE: 62
If you press NEXT, the following screen is displayed to indicate the appliance’s group configuration:
AUDIBLE GROUP CONFIG: 11 22 33 VISUAL GROUP CONFIG: 44 55 64
Notes:
1. Default groups are not displayed (only the user-configured groups are shown).
2. The “00” designation means “no user group.”
Continued on next page
Operator Interface
TrueAlert Appliances
Function Key Display
CARD NUMBER
CHANNEL NUMBER
APPLIANCE NUMBER
Page 22
1-10
Press NEXT again. The appliance’s coding operation screen is displayed:
40 CHARACTER CUSTOM LABEL CODING OPERATION: TEMPORAL
Note: If an A/V appliance is being reported, “TEMPORAL” refers to the
audible appliance’s coding operation.
If you press NEXT again, the TrueAlert diagnostic features display one feature at a time. See Chapter 3 for an explanation of the TrueAlert Diagnostics.
VNACs may be called-up on demand from the Operator Interface Panel in two ways:
1. Address key (for example, Card Address 175-1-0)
2. ‘SIG’ key followed by SIG number
If a VNAC is in trouble and on the active trouble list, it may also be called up simply by using the Trouble Acknowledge key. VNACs have the following high-level status screen:
40 CHARACTER CUSTOM LABEL SIGNAL CIRCUIT OFF
If the VNAC is in the ‘normal’ state, its control status (ON/OFF) is displayed. Otherwise, an appropriate trouble indication is displayed in the bottom right of the LCD. The possible troubles and the actual text displayed is shown below:
MANUAL OVERRIDE TBL
DISABLE TROUBLE
The remaining VNAC function screens are consistent with standard NACs (with the exception of the physical & raw states which do not apply for VNACs).
POINT ADDRESS: 175-1-0 SIGNAL CIRCUIT: SIG9
40 CHARACTER CUSTOM LABEL SIGNAL CIRCUIT ENABLED
40 CHARACTER CUSTOM LABEL SIGNAL CIRCUIT RELAY STATUS IS OFF
40 CHARACTER CUSTOM LABEL SIGNAL CIRCUIT PRIORITY 9
40 CHARACTER CUSTOM LABEL SIGNAL CIRCUIT AUTOMATIC CONTROL
Continued on next page
Operator Interface,
Continued
Function Key Display
(Continued)
Virtual NACs
Page 23
1-11
The Display First Alarm alarm list feature (which enables the automatic display of the first alarm) is configurable via the Programmer (disabled by default). If this option has been programmed for your panel, the Operator Interface Panel shows the first (oldest) alarm whenever a single or multiple alarm conditions is reported. The panel LCD display displays the first alarm instead of the “alarm totals” screen display. The following figures demonstrate how a display might appear during an alarm sequence if the Display First Alarm option is selected.
General Point Information Layout
The following screens shows a layout of the fields when displaying the first alarm point information.
40 CHARACTER CUSTOM LABEL POINT TYPE BANNER POINT STATUS
Single Event Unacked Alarm Point
EAST WING, THIRD FLOOR, HEAT
Shows unacked
Heat Detector FIRE ALARM
alarm point and
(Second line alternates once a second)
EAST WING, THIRD FLOOR, HEAT
alternates second line
Press <Alarm Ack> to acknowledge
with ack message
Single Event Acked Alarm Point
EAST WING, THIRD FLOOR, HEAT
Shows acked
Heat Detector FIRE ALARM
alarm point and
(Screen alternates once a second)
**FIRE** Press <Ack> to review.
alternates screen with
FIRE=1 PRI2=0 SUPV=0 TRBL=0
tally screen
Continued on next page
Operator Interface,
Continued
Display First Alarm
Page 24
1-12
Multiple Event Unacked Alarm Points
EAST WING, THIRD FLOOR, HEAT
Show first unacked alarm
Heat Detector FIRE ALARM
event point information and
(Second line alternates once a second)
EAST WING, THIRD FLOOR, HEAT
alternate second line with
Press <Alarm Ack> to acknowledge
ack message
Multiple Event Display After Acking First Alarm Point
EAST WING, FOURTH FLOOR, SMOKE
First alarm acked;
Smoke Detector FIRE ALARM
show next alarm and
(Second line alternates once a second)
EAST WING, FOURTH FLOOR, SMOKE
alternate second line with
Press <Alarm Ack> to acknowledge
ack message.
Multiple Event Display After Acking Second (Last) Alarm
EAST WING, THIRD FLOOR, SMOKE
All alarms acked; alternate
Heat Detector FIRE ALARM
between first alarm point
(Screen alternates once a second)
**FIRE** Press <Ack> to review.
and the main tally screen.
FIRE=2 PRI2=0 SUPV=0 TRBL=0
Operator Interface,
Continued
Display First Alarm
(Continued)
Page 25
2-1
This chapter shows how to handle abnormal system operations for a typical 4100/4020 FACP running Version 9.X firmware. Your system operation may vary due to custom programming and local code requirements.
This chapter discusses the topics listed in the following table. Refer to the page number listed after the topic for information on that topic.
Topic See Page #
Handling Abnormal Conditions 2-2
Read the Display 2-2
How to Identify a TrueAlert appliance 2-2
How to Identify a Version Mismatch Condition 2-3
Handling Disabled Conditions 2-5
How to Disable a VNAC 2-5
How to Enable a VNAC 2-6
Chapter 2
System Operations
Introduction
In this Chapter
Page 26
2-2
When the Operator Interface Panel has an abnormal condition, at least one of the interface panel LEDs (FIRE ALARM, PRIORITY 2 ALARM, SYSTEM SUPERVISORY, or SYSTEM TROUBLE) begins to flash, and the tone-alert sounds. The alphanumeric display on the interface panel shows the total number of abnormal conditions present in the system. At a glance, you know how serious the situation is by reading the number of abnormal conditions displayed, such as the TrueAlert appliance in trouble as shown below.
CUSTOM LABEL FOR CHANNEL 1 APPLIANCE 4 AUDIBLE/VISUAL NO ANSWER
Suppose that you want to disable this appliance. Since this is a TrueAlert appliance, you can’t directly. You must disable the Virtual NAC (or Virtual NACs) to which it belongs.
The TrueAlert appliance in trouble is located on the TrueAlert Addressable Controller which is regarded by the 4100/4020 as a ‘slave’ card. The 4100 Programming Unit Programmer Report lists the card address for the TrueAlert Addressable Controller as Card Address 4 on this system. The Appliance Custom Label thoughtfully provided the Channel and Appliance Number, so we have the appliance address: 4-1-4. Just press ADDR on the auxiliary keypad, enter the address, and press ENTER. The Operator Interface displays the following screen.
CUSTOM LABEL FOR CHANNEL 1 APPLIANCE 4 AUDIBLE/VISUAL NO ANSWER
Go to the DISPLAY/ACTION keypad and press FUNCTION twice. The following information appears.
AUDIBLE GROUP CONFIG: 10 11 0 VISUAL GROUP CONFIG: 10 0 0
This data tells you that the appliance is a member of two VNACs: VNAC 10 and VNAC 11. To disable this appliance, we must disable both VNACs.
Notes:
1. A 4100 System Report showing VNAC locations and membership is very helpful for this procedure.
2. Disabling a VNAC may disable other appliances in that VNAC.
Continued on next page
Handling Abnormal Conditions
Read the Display
How to Identify a TrueAlert Appliance
Page 27
2-3
A Version Mismatch condition is reported as a ‘trouble’ and can be found by accessing the System Trouble Log in the usual manner.
Runtime Viewing of Node Pair Version Numbers
From a 4100 node’s network node identification screen, you have the ability to see the communication version number between the node and all other nodes on the network. (The same feature is available in the GCC.) This provides useful information which, when used in conjunction with the Build Report, helps in troubleshooting whether the expected configuration is running at a node.
Version Checking
Use the following procedure to display the Network Node version number.
1. Press the MENU key on the Display/Action Keypad.
2. Press NEXT or PREVIOUS on the Display/Action Keypad until the
Operator Interface displays the following screen.
Press <NEXT> or <PREVIOUS> to scroll Display Network Node Identification?
3. Press ENTER to select. Node 1 is displayed. Note that the Version
Number is ‘2.’ This means that there have been two builds of this panel since the initial build.
NODE 1 VER#2 Node 1: GRAPHIC COMMAND CENTER (GCC)
4. Press NEXT. Node 2 is displayed. Note that the Version Number is ‘0.’
This means that the version at this panel is at the baseline (or initial build) of the job.
NODE 2 VER#0 Node 2: 4100 SYSTEM (ENHANCED)
5. Press NEXT. Node 3 is displayed. Note that the Version Number is
also ‘0’ indicating that the version at this panel is also at the baseline.
NODE 3 VER#0 Node 3: 4100 SYSTEM (ENHANCED)
Continued on next page
Handling Abnormal Conditions,
Continued
How to Identify a Version Mismatch Condition
Page 28
2-4
6. Press NEXT. Node 4 is displayed. Since this is the panel being used to gather the information, the display shows an asterisk (*).
NODE 4 VER#* *Node 4: 4100 SYSTEM (ENHANCED)
The Version Checking example shows that at least two of the Network Nodes are mismatched and require a build.
Handling Abnormal Conditions,
Continued
How to Identify a Version Mismatch Condition
(Continued)
Page 29
2-5
As the operator of a 4100/4020 FACP, you must use the Operator Interface keypad to disable a zone, outputs to fault warning routing equipment, controls for automatic fire protection equipment, outputs to fire alarm appliances, or outputs to fire alarm routing equipment. Disablements will inhibit all alarm and fault indications. A disablement causes the Operator Interface SYSTEM TROUBLE LED to flash and the piezo sounds. When the trouble condition is acknowledged (ACKed), the LED is illuminated steady ON.
Note: To perform this procedure, you must be at the correct Access
Level or higher.
To disable a VNAC, press SIG on the ENTRY Menu. Then, do the following:
1. Enter the SIG number of the VNAC (VNAC 10 is SIG12 in this example)
2. Press ENTER to select.
VIRTUAL NAC 10 – ALL A/V DEVICES SIGNAL CIRCUIT OFF
3. Press DISABLE.
PRESS <ENTER> TO DISABLE SIGNAL CIRCUIT: SIG12
4. Press ENTER on the ENTRY keypad. The display acknowledges the action.
ACTION TAKEN
The SYSTEM TROUBLE LED begins to flash and the Piezo sounds.
5. Press <TBL ACK> and read the display.
VIRTUAL NAC 10 – ALL A/V DEVICES SIGNAL CIRCUIT DISABLE TROUBLE
Disable the remaining VNAC in a similar manner.
Continued on next page
Handling Disabled Conditions
Introduction
How to Disable a VNAC
Page 30
2-6
Note: To perform this procedure, you must be at the correct Access
Level or higher.
Use the following procedure to enable a VNAC:
1. Press <TBL ACK> until the VNAC signal number is displayed.
VIRTUAL NAC 10 – ALL A/V DEVICES SIGNAL CIRCUIT DISABLE TROUBLE
2. Press ENABLE.
PRESS <ENTER> TO ENABLE SIGNAL CIRCUIT: SIG12
3. Press ENTER on the ENTRY keypad. The display acknowledges the action.
ACTION TAKEN
The trouble count should decrease by one.
4. After a few seconds, a message appears. (For this example, the signal circuit is “OFF.”)
VIRTUAL NAC 10 – ALL A/V DEVICES SIGNAL CIRCUIT OFF
Enable the remaining VNAC in a similar manner.
Handling Disabled Conditions,
Continued
How to Enable a VNAC
Page 31
3-1
There are many diagnostic capabilities available with a TrueAlert Addressable Controller SLC channel that are not available on a traditional NAC. This chapter describes the diagnostic operations that can be used with the TrueAlert Addressable Controller.
This chapter discusses the topics listed in the following table. Refer to the page number listed after the topic for information on that topic.
Topic See Page #
About TrueAlert Diagnostics 3-2
Appliance LED Activation 3-4
Manual Real Appliance Test 3-5
Global Silent Appliance Test Mode 3-6
Manual Silent Appliance Test Mode 3-7
TrueAlert Appliance WalkTest 3-8
Chapter 3
TrueAlert Diagnostics
Introduction
In this Chapter
Page 32
3-2
Note: All TrueAlert Addressable Controller channels are reported as
failed while the diagnostics are being run.
Whenever a TrueAlert channel is in a diagnostics mode, a diagnostics trouble is displayed on the Operator Interface Panel. A TrueAlert channel will be in such a diagnostics mode any time it has an LED lit for diagnostics reasons or any time the channel is in a silent test or individual appliance test mode.
Note: This feature only works when “LEDs flash when polled” is NOT
selected as an option in the Programmer.
The TrueAlert channel supervises appliances by polling them. In the event of a appliance not responding, the system reports an appliance missing trouble. The 4100 provides the capability of identifying the channel, the appliance address, and the labels for the appliance at the operator interface. To aid in finding the appliance, the 4100/4020 has the capability of turning on all of the LEDs on a TrueAlert Addressable Controller via the Operator Interface Panel. This allows the technician to go out into the building and look for the appliance without a lit LED. The operation to turn on the LEDs does not require you to hold a button down. However, it will not allow you to leave the screen that activates the LEDs until they are restored to normal mode.
To activate
all Appliance LEDs on all TrueAlert Controller Channels, log on the 4100/4020 at the appropriate Access Level. On the Operator Interface Panel, go to the TrueAlert appliance function screen and turn on the appliance LEDs on the TrueAlert Addressable Controller. Verify that all of the appliance LEDs assigned to the TrueAlert Addressable Controller turn on. (The 4100/4020 display will remained locked onto this screen for eight hours or until you turn off the LEDs.) From the Operator Interface Panel display under the TrueAlert appliance function screen enable turn off the appliance LED’s on the TrueAlert Addressable Controller. If more than one TrueAlert Addressable Controller is connected to the system repeat the above procedure on the remaining Addressable Controllers.
It is often disruptive to test NACs in an occupied building. To minimize this disruption, the TrueAlert peripherals support a single appliance test mode (also known as the Manual Real Appliance Test) that makes a given notification appliance report its address and emits an alarm.
To initiate the Manual Real Appliance Test, place a magnet on the appropriate area of the notification appliance. The appliance LED emits one long flash denoting the test acknowledge signal, and then another long flash denoting the first digit (always zero) of the appliance address. The LED then flashes one to six times to denote the second digit of the address, pauses, and flashes one to nine times to indicate the third digit of the address. A zero is always indicated by one long flash. After the LED flashes, the appliance goes into alarm for two to three seconds (the audible sounds and the visual flashes). During the test Trouble Pseudo P230 indicates a trouble: “Device Test Active.”
Continued on next page
About TrueAlert Diagnostics
Diagnostics Trouble
Activate all Appliance LEDs on all TrueAlert Controller Channels
Single Appliance Test Mode (Manual Real Appliance Test)
Page 33
3-3
Another test capability that minimizes noise and disruption in a building is Global Silent Appliance Test. This test sets all TrueAlert notification appliances so that alarms are silent. If the system goes into alarm, appliances illuminate their LEDs in a Steady On state without audibles or strobes. You can put the system into this test mode from the Operator Interface. During the test Trouble Pseudo P229 indicates a trouble.
The Manual Silent Appliance Test allows given notification appliances to be manually tested without emitting an alarm. At the Operator Interface Panel, enter the address of a TrueAlert appliance assigned to a particular TrueAlert Addressable Controller. Wait a minimum of one to two minutes before testing appliances to ensure that the diagnostics are active. Place a magnet on the appropriate area of the appliance to initiate the test. The LED emits one long flash denoting the test acknowledge signal, and then another long flash denoting the first digit (always zero) of the appliance address. The LED then flashes one to six times to denote the second digit of the address, pauses, and flashes one to nine times to indicate the third digit of the address. A zero is always indicated by one long flash. Verify that troubles are reported by Pseudo Point P230 (Device Test Mode) and Pseudo Point P229 (Silent Test Mode). When the address is done, the LED illuminates once more for two to three seconds.
Note: TrueAlert horn and strobe appliances will not operate if the 4100
is configured for voice.
The 4100/4020 system with a TrueAlert Addressable Controller supports Non-Voice WalkTest in the same manner as a 4100/4020 system without a controller. VNACs can be put into WalkTest groups, and the appliances will sound out the address of the activated peripheral although the TrueAlert strobes will not flash. (Note that in both silent test and WalkTest, the 4100/4020 displays a trouble at the Operator Interface Panel.) After eight hours of inactivity, the panel returns to normal operation.
About TrueAlert Diagnostics,
Continued
Global Silent Appliance Test
Manual Silent Appliance Test
4100/4020 WalkTest
Page 34
3-4
Note: In order for Diagnostics to operate properly all appliances must
be inactive prior to diagnostic activation.
Use the following procedure to activate all of the TrueAlert Appliance LEDs assigned to a particular TrueAlert Addressable Controller.
1. Log on the 4100/4020 at the appropriate Access Level.
2. On the Operator Interface Panel, go to the TrueAlert appliance function
screen and turn on the appliance LEDs on the TrueAlert Addressable Controller. Verify that all of the appliance LEDs assigned to the TrueAlert Addressable Controller turn on. (The 4100/4020 display will remained locked onto this screen for eight hours or until you turn off the LEDs.)
3. From the Operator Interface Panel display under the TrueAlert appliance
function screen, turn off the appliance LED’s on the TrueAlert Addressable Controller.
If more than one TrueAlert Addressable Controller is connected to the system repeat the above procedure on the remaining Addressable Controllers.
Appliance LED Activation
Procedure
Page 35
3-5
Note: In order for Diagnostics to operate properly all appliances must
be inactive prior to diagnostic activation.
1. Use the following procedure to place the system in the Single Appliance
Test Mode to run the Manual Real Appliance Test.
2. Go to the Operator Interface Panel and enter the address of a TrueAlert
appliance assigned to a particular TrueAlert Addressable Controller.
3. Under the TrueAlert appliance’s FUNCTION screen, put the appliance into
Device Test Mode and verify that a TRUEALERT APPLIANCE TEST MODE ACTIVE trouble is generated at the Operator Interface Panel (and reported by Pseudo P230).
4. Wait a minimum of one to two minutes before testing appliances to ensure
that the diagnostics are active.
5. Activate the magnetic reed switch on the appliance and verify that the horn
appliances sound and that the strobe appliances blink at least once.
6. Under a TrueAlert appliance’s FUNCTION screen, take the TrueAlert
Addressable Controller out of Device Test Mode and verify the trouble clears. (The trouble will clear automatically in eight hours.)
If more than one TrueAlert Addressable Controller is connected to the system repeat the above procedure on the remaining controllers.
Manual Real Appliance Test
Procedure
Page 36
3-6
The Global Silent Appliance Test is a system-wide option to minimize noise and disruption in a building during test. When this test is active, every TrueAlert Controller is active. TrueAlert appliances activate their appliance LEDs instead of activating the appliances.
Use the following procedure to place the system in the Global Silent Appliance Test Mode to run the TrueAlert Silent Test.
1. Log on the 4100/4020 at the appropriate Access Level.
2. At the Operator Interface Panel, enter the address of a TrueAlert appliance
assigned to a particular TrueAlert Addressable Controller.
3. Enable Silent Test Mode from the TrueAlert Appliance Function Screen.
Verify a trouble is reported by Pseudo P229.
4. Wait a minimum of one to two minutes before testing appliances to ensure
that the diagnostics are active.
5. Initiate an alarm on the 4100/4020 and verify that the LED on each A/V
appliance turns on steady without audibles or strobes.
6. Under the TrueAlert appliance’s FUNCTION screen, take the TrueAlert
Addressable Controller out of Silent Test Mode and verify that the troubles clear. (The trouble will clear automatically in eight hours.)
Note: LED operation is dependent on the priority of associated VNACs,
default programming and/or Custom Control programming.
Global Silent Appliance Test Mode
Procedure
Page 37
3-7
The Manual Silent Appliance Test makes a given notification appliance report its address without emitting an alarm. Use the following procedure to initiate the test.
1. At the 4100/4020 Operator Interface Panel, enter the address of a TrueAlert
appliance assigned to a particular TrueAlert Addressable Controller.
2. Go to the TrueAlert Appliance Function Screen and enable Device Test
Mode and Silent Test Mode at the same time. Verify that troubles are reported by Pseudos P229 and P230.
3. Wait a minimum of one to two minutes before testing appliances to ensure
that the diagnostics are active.
4. Place a magnet on the appropriate area of the appliance.
5. Verify that the LED emits one long flash denoting the test
acknowledge signal.
6. Verify that the LED emits another long flash denoting the first digit
(always zero) of the appliance address.
7. Verify that the LED then flashes one to six times to denote the second
digit of the address, pauses, and flashes one to nine times to indicate the third digit of the address. A zero is always indicated by one long flash.
8. When the address is done, the LED illuminates once more for two to
three seconds.
Notes:
1. If more than one TrueAlert Addressable Controller is connected to the system repeat the above procedure for the remaining controllers.
2. Remember to activate Device Test Mode for every TrueAlarm Addressable Controller.
3. Silent Test only needs to be done once for the entire system.
4. The trouble will clear automatically in eight hours.
Manual Silent Appliance Test Mode
Procedure
Page 38
3-8
Notes:
1. In order for the TrueAlert Appliance WalkTest to work properly, only one VNAC is allowed per WalkTest group.
2. The TrueAlert strobes will not flash during this test.
The TrueAlert Addressable Controller will fully support the Non-Voice Simplex WalkTest. Use the following procedure to initiate the TrueAlert WalkTest.
1. Put the 4100/4020 Operator Interface Panel into WalkTest and verify the
WalkTest trouble reports.
2. Initiate a monitor point from each WalkTest group and verify that the
correct code is generated on the appropriate appliance.
BLANK
BLANK PAGE
TrueAlert Appliance WalkTest
Procedure
Page 39
B-1
Page 40
Simplex Time Recorder Co. Simplex Plaza Gardner, Massachusetts 01441-0001 U.S.A.
Ed 11 96
SEC-31-503
(574-637)
Rev. B
Simplex Time Recorder Company Westminster, Massachusetts 01441-0001 U.S.A.
579-126
Loading...