Simplex 4100-9934, 4100-9933, 4100-9931, 4100-9932, 4100-9935 User Manual

...
Features
Existing AUTOCALL
7 Module
Equipment Box
4100ES Equipment mounts with 7 module Retrofit Kit, sized to fit existing box
Existing equipment and door assembly are removed
Fire Control Panels
UL, CSFM Listed; FM Approved; Retrofit Kits for Installing 4100ES Equipment into MEA (NYC) Acceptance* Existing AUTOCALL
®
Control Panel Backboxes
Replace existing AUTOCALL fire alarm control panel equipment with Simplex® 4100ES Series products using the existing backbox:
Retrofit kits include either a solid or glass door,
Kits are available to accommodate 1, 2, or 3 bays
of 4100ES equipment
Doors and trim are red See notes on page 2 for installation tool
requirements
With the retrofit kits in place, standard 4100ES equipment can be easily installed:
Existing cabinets accommodate internal battery
mounting up to 33 Ah (ref. battery 2081-9276); 50 Ah or higher battery sizes require external cabinets
Established 4100ES module placement rules apply
Compatible existing backboxes include:
Five module, seven module, or ten module height
boxes
4” (102 mm) or 6” (152 mm) deep boxes Boxes with or without top and bottom mounting
flanges; kit includes adapter brackets for boxes without the flanges
UL Listed to Standard 864
Description
Retrofitting. When existing fire alarm control systems
require capacity or performance increases, it is an opportunity to consider new product solutions. For existing AUTOCALL fire alarm control equipment in need of updating, these retrofit kits allow the installation of 4100ES Series equipment to be mounted in the installed box. By retaining the existing boxes, mechanical and electrical impact is reduced, often significantly.
Typical Applications. Examples for these retrofit kits include backboxes installed on surfaces that would be costly to modify (such as marble, plaster, or concrete) or where installed into a custom enclosure. Whether surface mounted or semi-flush mounted, these retrofit kits can expedite the equipment retrofit process.
Equipment Selection Reminder. Proper retrofitting of existing equipment requires that the desired fire alarm functions be understood in order to specify the necessary 4100ES equipment.
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7170-0026:251 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. This product was not ULC listed as of document revision date. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
Typical Application; 7 Module Box
Retrofitted with Two-Bay 4100ES
S4100-0047-2
Red Retrofit Kits with Glass Door
Model
Existing Box Depth
Existing Box Model No.
Existing Box Capacity
4100ES Module Capacity
4100-9930
4” (102 mm)
8099-512
5 Module
One bay
4100-9931
6” (152 mm)
8099-516
4100-9932
4” (102 mm)
8099-513
7 Module
Two bay
4100-9933
6” (152 mm)
8099-514
4100-9934
6” (152 mm)
8099-515
10 Module
Three bay
Red Retrofit Kits with Solid Door
Model
Existing Box Depth
Existing Box Model No.
Existing Box Capacity
4100ES Module Capacity
4100-9935
4” (102 mm)
8099-512
5 Module
One bay
4100-9936
6” (152 mm)
8099-516
4100-9937
4” (102 mm)
8099-513
7 Module
Two bay
4100-9938
6” (152 mm)
8099-514
4100-9939
6” (152 mm)
8099-515
10 Module
Three bay
Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo and AUTOCALL are trademarks of Tyco International Ltd. and its affiliates and are used under license.
Tyco Safety Products Westminster Westminster, MA 01441-0001 USA
www.tycosafetyproducts-usa-wm.com
© 2011 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
AUTOCALL Retrofit Kit Installation Reference (for details refer to Installation Instructions 579-798)
AUTOCALL Backbox Retrofit Kit Selection
Door assembly,
glass or solid
(glass door shown)
Dress panel for glass doors
Box extension
hardware
Existing box
4100ES bay mounting brackets
Adapter bracket for top of box, if required
Adapter bracket for bottom of box, if required
Installation Notes:
1. Power tools are required.
2. Pilot holes must be drilled in the flanges of the existing box using a
7/64” drill bit. Mark hole locations
using the extension hardware as a template – remove extension hardware before drilling.
3. Self-tapping screws fasten the extension hardware to the box; a medium to heavy duty power screwdriver is recommended; an extra long driver is recommended for 4” deep boxes.
4. Refer to Installation Instructions 579-798 for more information.
S4100-0047-2