This product is compatible with 4100U and 4100ES Fire Alarm Control Panels (FACP).
IMPORTANT: Verify FACP System Programmer, Executive, and Slave Software
compatibility when installing, or replacing system components. Refer to
the Technical Support Information and Downloads website for
compatibility information..
Inspecting Contents
of Shipment
In this Publication
Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify Simplex.
Specifications and other information shown were current as of publication and are subject to change without notice.
Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license.
574-800
Rev. D
Page 2
Cautions, Warnings, and Regulatory Information
Cautions and
Warnings
READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
manual. These instructions must be followed to avoid damage to this product and associated
equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon
unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify an authorized
Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjust-
ments or repairs. All repairs should be performed by a representative or authorized agent of
your local Simplex product supplier.
STATIC HAZARD - Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to
comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGESTo ensure proper system
operation, this product must be tested in accordance with NFPA 72® after any programming
operation or change in site-specific software. Reacceptance testing is required after any
change, addition or deletion of system components, or after any modification, repair or
adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions, known to be affected by a
change, must be 100% tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that are not directly affected by the
change, up to a maximum of 50 devices, must also be tested and proper system operation
verified.
NFPA 72® is a registered trademark of the National Fire Protection Association.
2
Page 3
Introduction to the IDNet Card
Overview
The 4100-series IDNet Card allows the system CPU to communicate with up to 250 IDNet
peripherals, such as smoke detectors and pull stations.
The IDNet card is a flat, 4” by 5” option card that plugs into the power distribution interface
(hereafter referred to as PDI).
Figure 1 depicts the IDNet card.
IDNET LINE TERMINAL BLOCK
(TB1)
SHIELD JUMPER
(P1)
COMM TROUBLE
LED (LED1)
IDNET TROUBLE
LED (LED2)
ADDRESS
DIP SWITCH
(SW1)
LEDs
PDI CONNECTOR
(P2) (on reverse
side)
Figure 1. The IDNet Card
The IDNet card has the following LEDs:
LED1. Normally off. Turns on steady if the IDNet card is not communicating with the 4100
CPU.
LED2. Normally off. Illuminates to indicate a problem with the IDNet lines.
• Steady on indicates channel failure.
• One repetitive blink indicates a line short.
• Two repetitive blinks indicate a Class A failure or an open line.
Continued on next page
3
Page 4
Introduction to the IDNet Card, Continued
Requirements
and Limitations
Refer to Table 1 for general system specifications.
Table 1. System Specifications
Electrical Specifications
Voltage 24 VDC from FACP
Comm/Power
Voltage to
IDNet Slaves
Comm Wiring
Distance
Environmental Specifications
Operating
Temperature
Humidity
Note: Voltage output to IDNet slaves is normally 30 VDC. Output is increased to
36 VDC when it is necessary to activate large numbers of output devices on
IDNet peripherals, such as piezo sounders. The system CPU will set the output
to 36 VDC when LEDs, piezos, or other outputs are activated, usually in an
alarm state.
•Up to 250 IDNet devices are supported by one IDNet channel.
30 VDC (nominal) or 36 VDC @ 350 mA (See note)
40 Ohms line resistance
0.60 µF capacitance (line to line and shield to line)
10,000 feet
32° to 120° F (0° to 49° C)
Up to 93% relative humidity at 94° F (38° C)
IMPORTANT: You must use the 4100-3106 IDNet card when installing Quick Connect
devices.
•The IDNet card keeps track of which LEDs should be on at all times, and displays up to
20 at any given time.
•Up to 43 coded piezo sounders are supported by one IDNet channel.
4
Page 5
Step 1: Installing the IDNet Card into the PDI
Overview
IDNet CARD
#6 SCREWS
The 4100-series IDNet card is designed to be mounted on the PDI in an FACP expansion cabinet.
The card can be mounted on any of the PDI connectors.
Use connector P2, labeled on the back side of the IDNet card, to connect to any of the eight PDI
connectors as shown in Figure 2, below.
WASHERS
STANDOFFS
SCREW
RETAINERS
PDI CONNECTOR
(reverse side)
PDI
Figure 2. Mounting onto the Power Distribution Interface
5
Page 6
Step 2. Configuring the Card
Overview
Setting the Shield
Tie Point
Setting the Address
Configuring the card consists of selecting the shield tie point, and setting the device address. This
section covers both topics.
If a shield is used, use jumper port (P1) to select where the shield will be tied.
• Positions 1 and 2 connect the shield to 0 V.
• Positions 2 and 3 connect the shield to Earth.
The device address is set via DIP switch SW1, which is a bank of eight switches. From left to right
(see Figure 3, below) these switches are designated as SW1-1 through SW1-8. The function of
these switches is as follows:
•SW1-1. This switch sets the baud rate for the internal 4100 communications line running
between the card and the 4100 CPU. Set this switch to ON.
•SW1-2 through SW1-8. These switches set the card’s address within the 4100 FACP.
Refer to Table 2 for a complete list of the switch settings for all of the possible card addresses.
Note: You must set these switches to the value assigned to the card by the
Programmer.
4100 Comm. Baud Rate.
Switch (SW1-1)
Must Be Set to ON
ON
Dip Switches SW1-2 through
SW1-8 set the Card Address.
Figure shows an Address of 3.
Up to 250 IDNet slave devices, such as smoke detectors and pull stations, can be connected to the
IDNet card. Class A or Class B wiring can be used to connect the IDNet card to peripherals.
IMPORTANT: You must use the 4100-3106 IDNet card when installing Quick Connect
devices.
Class A wiring allows IDNet appliances to communicate with the IDNet card even in the event of
an open circuit somewhere in the loop. Class A wiring requires that two wires are routed from the
IDNet card to each IDNet appliance, and then back again to the IDNet card.
Class B wiring allows “T” tapping, and therefore requires less wiring distance per installation than
Class A. IDNet wiring does not require end-of-line resistors, because each IDNet device
communicates directly to the IDNet card.
Review these guidelines before wiring the IDNet card.
• Refer to 4100 Field Wiring Specification Document 900-242 for further information.
• All wiring is shielded, 18 AWG (minimum) to 12 AWG (maximum). Refer to Table 3,
below, for specifications on each type of wire.
Table 3. IDNet Card Wiring Lengths
Wire Gauge Maximum Distance
18 AWG 7.14 Ohms/10,000 ft
Figure 4.
The Ferrite Bead
16 AWG 4.59 Ohms/10,000 ft
14 AWG 2.82 Ohms/10,000 ft
12 AWG 1.77 Ohms/10,000 ft
• All wiring is supervised and power-limited.
• IDNet communications power is 36.25 V (maximum) at 0.5 A, 3333 BPS.
• All wiring that leaves the building requires overvoltage protection. Install module
2081-9044 wherever wire enters or exits the building. A maximum of four 2081-9044
Modules may be connected to one channel. The maximum line distance with two
suppressors is 2500 feet. With an additional two suppressors, the maximum line distance
is 1500 feet.
•For Style 4 operation:
- The maximum distance to any device is 10,000 feet or 40 Ohms.
- “T” taps are allowed.
- The total distance for one IDNet line is 10,000 feet.
- Maximum allowed line-to-line capacitance (“+” to “-” terminals) is 0.60 µF. For
applications with shielded wire, be sure that the total capacitance from line to line plus
the shield to either line is no more than 0.60 µF.
• For Style 6 operation, the maximum loop distance is 2500 feet. “T” taps are not allowed.
• Loop wires once through the supplied ferrite bead(s) as shown in Figure 3.
Continued on next page
8
Page 9
Step 3. Wiring to IDNet Peripherals, Continued
Class A Wiring
To connect the IDNet card to devices using Class A wiring, read the following instructions and
refer to Figure 5, below.
1. Route wire between 12 and 18 AWG from the IDNetB+, IDNetB-, and SHIELD outputs
on TB1 of the IDNet card to the appropriate inputs on a peripheral IDNet appliance.
Note: Use ferrite beads as shown.
2. Route wire from the first IDNet appliance to the next one. Repeat for each appliance.
3. Route wire from the last IDNet appliance to the IDNetA+ and IDNetA- inputs on TB1 of
the IDNet card.
IDNET DEVICES
12 to 18 AWG
FERRITE BEAD
(required)
IDNET CARD
1212
SHIELD
1
2
+
SHIELD
FERRITE BEAD
(required)
Figure 5. Class A Wiring
Continued on next page
9
Page 10
Step 3. Wiring to IDNet Peripherals, Continued
Class B Wiring
To connect the IDNet card to appliances using Class B wiring, read the following instructions.
1. On TB1, jumper IDNetB+ to IDNet A+, and jumper IDNetB- to IDNetA-. If the jumper
is absent, a Class A Trouble will be indicated on LED 2.
Note: Use ferrite bead as shown.
2. Route wire between 12 and 18 AWG from the IDNetA+, IDNetA-, and SHIELD outputs
on TB1 of the IDNet card to a junction box. Begin “T” tapping at the junction box. The
maximum wiring distance for any IDNet circuit is 10,000 feet or 0.60 µF.
The illustration below shows Class B wiring.
IDNET DEVICES
121212
12 to 18 AWG
FERRITE BEAD (required)
IDNET CARD
1
2
+
Figure 6. Class B Wiring
Note: Maintain correct polarity on terminal connections. Do not loop wires under
terminals.
10
Page 11
Troubleshooting
Overview
IDNet Power
Monitor Trouble
Extra Device
Class A Trouble
Earth Fault Search
Short Circuit
Channel Fail
This section describes the messages that may appear on the 4100 display when using the IDNet
card. Trouble messages appear on the left as titles, and possible causes are listed to the right in the
text.
There is no output voltage from the IDNet power supply. Replace the IDNet card.
Appears if one or more extra devices (i.e., devices that have not been configured for the IDNet
channel) are found on the system, or if a device is at an incorrect address. Only one message
appears, regardless of the number of extra devices found. Viewing the trouble log will reveal the
extra device address.
There is an open on the IDNet channel. After fixing the wiring fault, a hardware reset is required
to reset the trouble.
Appears while the IDNet card is searching for earth faults on the IDNet line. When this message is
displayed, the IDNet card cannot show any alarms or other statuses.
Appears when a short is detected on the IDNet channel. This status clears automatically when the
short circuit is removed.
Appears when devices have been configured, but none of the devices are communicating on the
channel. This message does not appear if there are no configured devices on the IDNet channel.
No Answer
Bad Answer
Output Abnormal
Appears when a device is missing.
Appears when there is a faulty device or a noisy communications channel.
Occurs during any of these conditions:
• 24 V is not present on TrueAlarm devices.
• TrueAlarm sensor bases with relay driver outputs are not properly supervised.
• Isolator devices are in isolation mode.
11
Page 12
574-800
Rev. D
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.