THESE DEVICES ARE DUCT SMOKE DETECTOR/SENSORS. THEY ARE DESIGNED TO
SAMPLE THE AIR FLOW PASSING BY IT IN THE AIR DUCT TO DETERMINE WHETHER IT
CONTAINS UNACCEPTABLE LEVELS OF SMOKE.
THE EFFECTIVENESS OF A DUCT SMOKE DETECTOR/SENSOR IS HIGHLY DEPENDENT
UPON:
• THE DESIGN AND OPERATING CONDITIONS OF THE AIR HANDLING SYSTEM IN
WHICH IT IS INSTALLED;
• VARIABLES SUCH AS SMOKE DILUTION AND STRATIFICATION
THE BEST DESIGNED SYSTEMS HAVE NO CONTROL; AND,
• PROPER PLACEMENT AND POSITIONING OF THE DUCT SMOKE DETECTOR/SENSOR,
WHICH IS OFTEN COMPROMISED FOR PRACTICAL REASONS.
FOR THE REASONS STATED ABOVE, THE EFFECTIVENESS OF THIS DUCT SMOKE
DETECTOR/SENSOR CANNOT BE WARRANTEED OR GUARANTEED. UNDER NO
CIRCUMSTANCES SHOULD THIS DUCT SMOKE DETECTOR/SENSOR BE USED AS OR
REGARDED TO BE A SUBSTITUTE FOR THE BUILDING’S REGULAR FIRE ALARM AND
DETECTION SYSTEM, TO WHICH THIS DEVICE IS ATTACHED AS A SECONDARY DETECTION
DEVICE.
THE NFPA STATES THAT DUCT SMOKE DETECTORS/SENSORS MUST NOT
SUBSTITUTES FOR OPEN AREA PROTECTION. THE DUCT SMOKE DETECTORS/SENSORS
ARE INTENDED FOR USE IN THE CONTROL OF AIR HANDLING EQUIPMENT FOR THE
PURPOSES OF CLOSING DAMPERS OR SHUTTING DOWN AIR HANDLING UNITS.
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS
DAMAGED. Upon unpacking your Simplex product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a
claim with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any
internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle
as follows:
1. Ground yourself before ope ning or installing components.
2. Keep uninstalled component wrapped in anti-static material at all times.
NOTICE
OVER WHICH EVEN
BE USED AS
NOTE FOR CANADIAN APPLICATION
THE DUCT SMOKE DETECTORS AND SENSORS DESCRIBED IN THIS INSTALLATION
INSTRUCTIONS CAN ONLY BE CONNECTED TO THE 2120 SYSTEMS THAT WERE LABLED PRIOR
TO THE EFFECTIVE DATE OF THE CURRENT ULC STANDARD FOR CONTROL UNITS, MARCH 31,
1989, AND SUBJECT TO ACCEPTANCE BY THE AHJ.
Table of Contents .............................................................................................................................................iii
General Description .......................................................................................................................................... 1
Setting the Duct Sensor’s Address ................................................................................................................... 3
Addressable Duct Sensors 4098-9755 or 4098-9756 (MAPNET II/IDNet)....................................................... 3
General ............................................................................................................................................................. 3
Address Setting for the 2120 CDT System (use with 4098-9755 only) ............................................................ 3
Address Setting for the 4010, 4020, 4100+, or 4120........................................................................................ 3
Rules to Follow ............................................................................................................................................... 15
DC Operation Detector Testing ......................................................................................................................20
Periodic Air Test ............................................................................................................................................. 20
Magnetic Test for Detectors and Sensors ...................................................................................................... 21
Preferred Method of Testing Smoke Detectors/Sensors................................................................................ 22
DC Operation Detector/Sensor Testing .......................................................................................................... 23
Air Differential Pressure Test.......................................................................................................................... 24
The 4098 Duct Detector/Sensors (see Figure 1) are designed to sample air and
detect smoke in air ducts. The 4098 Duct Detector/Sensors are available in the
following configura t ions:
• 4098-9685 Two-Wire Duct Detector supplied with the 4098-9601
Photoelectric Detector
• 4098-9686 Four-Wire Duct Detector supplied with the 4098-9601
Photoelectric Detector
• 4098-9688 Two-Wire Duct Detector with Relay Drive supplied with the
4098-9601 Photoelectric Detector
• 4098-9755 Two-Wire Duct Sensor supplied with the 4098-9714 Photo
Smoke Sensor
• 4098-9756 Four-Wire Duct Sensor supplied with the 4098-9714 Photo
Smoke Sensor
The 4098-9685, 4098-9686, and 4098-9688 Duct Detectors have a red LED on
the detector for “POWER ON” indication (red LED flashing) or for “ALARM”
indication (red LED “ON” steady).
The 4098-9755 and 4098-9756 Duct Sensors have a red LED on the PCB
assembly for “POWER ON” indication (red LED flashing) or for “ALARM” or
“TROUBLE” indication (red LED “ON” Steady).
The 4098-9686 Four-Wire Duct Detector and 4098-9756 Four-Wire Duct
Sensor have a yellow LED that indicates an short or open condition on the
supervised control zone (yellow LED “ON” steady), a trouble is also reported to
the panel during a short or open condition.
The 4098-9686 and 4098-9756 provide a supervised control circuit to drive up
to fifteen (15) remote 4098-9843 relays for alarm, supervisory, and control
functions. The 4098-9688 Two-Wire Duct Detector provides a supervised relay
control output that can drive one (1) 4098-9841 remote relay.
For detailed information on using smoke detectors/sensors in air distribution
systems, see NFPA 90A.
Two 3/4" conduit entries are provided for field wiring
General Description, Continued
COVER GASKET
STATUS LED
HOUSING BASE
BASE GASKET
CAP PLUG
SHIP GROUP 748-518
SEE NOTE
#8 CAPTIVE PANHEAD
SCREW
QTY: 4
HOUSING COVER
DETECTOR MAGNETIC
TEST LOCATION
SENSOR MAGNETIC
TEST LOCATION
DETECTOR
or
SENSOR
SMOKE PORT/AIR FLOW
TEST HOLES
DETECTOR/SENSOR
BASE
(4098-9755, -9756 ONLY)
Note:
connections (#12-18 AWG) to the PCB assembly.
The unused co nduit entry is sealed off using the cap
plug (ship group 748-518). Apply even pressure on
the plastic cap plug to secure it against the conduit
plate. The cap plug seals and removes easily with
moderate pressure.
Addressable Duct Sensors
4098-9755 or 4098-9756
(MAPNET II/IDNet)
The procedures that follow are used to install the 4098-9755 or 4098-9756
addressable duct sensors. See Figure 1 for the location of the duct sensor DIP
switches. The instructions provided show how to set the address at each sensor
and also how to make electrical connections. Addressable smoke duct sensors are
connected to a 2120 Multiplex Communicating Device Transponder (CDT), 4010
Fire Alarm Panel, 4020 Fire Alarm Panel, 4100+ Fire Alarm Panel, or 4120 Fire
Alarm Panel by a single twisted-shielded wire pair (MAPNET II/IDNet).
General
Address Setting for the 2120
CDT System (use with
4098-9755 only)
Duct sensor addressing is critical since the 2120 Communicating Device
Transponder (CDT), 4010, 4020, 4100+, and 4120 Systems report alarms and
troubles per duct sensor rather than per zone. Each duct sensor has a unique
address. This address is associated with a custom label which identifies its
physical location within a building. The duct sensor’s address and location must
match up with the address listed in the specification sheets of the 2120 Job
Configuration Report or P rogrammer’s Report for the 4010, 4020, 4100+, or
4120 System. You should have the appropriate specification sheets with you
during this part of the installation.
1. Using the 2120 Job Configuration Report, find the entry for the duct sensor
you are about to install. The CUSTOM LABEL column provides the
location while the DEVICE ADDRESS column provides the switch setting
data.
2. Using the switch setting data for the duct sensor you are installing set the
duct sensor’s address using Figure 3. Loose n t he four screws securing the
clear plastic cover to the housing base. Locate the DIP switch on the duct
sensor’s PCB assembly in the wiring compartment (see Figure 1). Use a
small screwdriver or pen to set the switches.
For the switch setting data in the DEVICE ADDRESS column, “1” is switch
ON while “0” is switch OFF.
3. Recheck the location of the sensor and its address before electrical
installation. Mark an address label with the appropriate address for your
duct sensor by shading a label box for each sensor DIP switch in the ON
position. Then apply the label to the sensor near the sensor’s DIP switches.
4. Secure the duct sensor’s clear plastic cover to the housing using the four
screws (Torque screw to 8-10 inch-pounds).
Address Setting for the 4010,
4020, 4100+, or 4120
1. Using the System Point Summary for the 4010, 4020, 4100+, or 4120, find
the entry for the duct sensor you are about to install. The ZONE NAME
(with a “M” prefix) and CUSTOM LABEL are located in the SYSTEM
POINT SUMMARY.
For example, Address M1-7 (for the 4010, 4100+, or 4120 System) is
shaded in Figure 2. M1 is the addressable channel while -7 is the device
address on the channel. For a duct sensor with Address M1-7, address 7
must be set on the duct sensor’s DIP switches. Address 7 is illustrated in
Figure 3.
DOCUMENTATION SYSTEM POINT SUMMARY Page 4
9304100A node: 1 rev: 1 10:50:20, WED, 15-JAN-97
---------------------------------------------------------------------------System Point Summary (ascending by zone name) : Point Summary
Zone
Device Point PNIS
Zone Name Custom Label Type Type Code
---------------------------------------------------------------------------IO1 MULTI IO CARD 1 POINT IO1 PULL MONA
IO2 MULTI IO CARD 1 POINT IO2 PULL MONA
IO3 MULTI IO CARD 1 POINT IO3 SSIGNAL SIGA
IO4 MULTI IO CARD 1 POINT IO4 SSIGNAL SIGA
M1-1 COMPUTER LAB BLDG 21 VSMOKE ION
M1-2 3RD FLOOR EAST WING ROOM 18 SMOKE GENIAM
M2-1 2ND FLOOR WEST WING ROOM 12 SMOKE ADRDET
IO9 BASEMENT EAST WING ROOM 3 IO9 SFPUMP MONA
DEVICE ADDRESS
---------------------------------------------------------------------------DOCUMENTATION SYSTEM POINT SUMMARY Page 2
9304100A node: 1 rev: 1 16:32:47, WED, 15-JAN-98
---------------------------------------------------------------------------System Point Summary (ascending by zone name) : Point Summary
Zone
Device Point PNIS
Zone Name Custom Label Type Type Code
---------------------------------------------------------------------------M1-1 FIRST FLOOR MICROWAVE ROOM M1-1 ADRPUL PULL
M1-2 FIRST FLOOR DINING ROOM M1-2 ADRPUL PULL
M1-3 FIRST FLOOR LOBBY M1- ADRPUL PULL
M1-4 FIRST FLOOR MECHANICAL ROOM 2 M1-4 ADRPUL PULL
M1-5 FIRST FLOOR LOADING DOCK M1-5 ADRPUL PULL
M1-6 1ST FLR MECH RM 1 M1-6 PHOTO VSMOKE
M1-7 1ST FLR MECH RM 1 M1-7 DUCT PHOTO
DEVICE ADDRESS
Figure 2. System Point Summaries with MAPNET II/IDNet Address
2. Using the example given in Step 1 as a guideline, set the duct sensor’s
address using Figure 3. Loosen the four screws securing the clear plastic
cover to the housing base. Locate the DIP switch on the duct sensor’s PCB
assembly in the wiring compartment (see Figure 1). Use a small screwdriver
or pen to set the switches.
3. Recheck the location of the sensor and its address before electrical
connection. Mark an address label with the appropriate address for your
duct sensor by shading a label box for each sensor DIP switch in the ON
position. Then apply the label to the sensor near the sensor’s DIP switch.
4. Secure the duct sensor’s clear plastic cover to the housing using the four screws
(Torque screw to 8-10 inch-pounds).
Addressable duct sensors are connected to a 2120 CDT (4098-9755 only), 4010, 4020,
4100+, or 4120 Fire Alarm System by twisted pair-wire (MAPNET II/IDNet). The
duct sensor obtains both power and data over this wire pair. (Shielded twisted pairwire for the MAPNET II/IDNet circuit is recommended; if not shielded or twisted,
consult Simplex Sales Engineering.) For relay operation (4098-9756 only), a separate
24VDC source of power is required in addition to the MAPNET II/IDNet lines. Refer
to Table 1 for duct sensor compatibility.
Note: The 24VDC power source must originate from a fused power supply listed for
fire protection signaling use, or from the Fire Alarm Control Panel (FACP)
power supply.
Figure 5. 4098-9756 Four-Wire Duct Sensor MAPNET II/IDNet Operation with
24VDC Power for Relay Control
Continued on next page
Notes:
1. Duct Sensor wiring is 12 to 18 AWG.
2. Maximum quantity of devices per circuit is 127 for 4020, 4100+, or 4120, and 250 for the 4010 panel.
3. The 2098-9806 and 2098-9808 are polarized, observe color-coded wiring.
4. Maximum wire length to test terminals and remote LED is 250 feet.
5. 4098-9843 PAM-SD Relay (Air Products & Controls Limited) are rated at 7 amps 28VDC/10 amps @ 115VAC. Maximum wire length to PAM-SD Relays is 500
feet (Fifteen PAM-SD Relays maximum). Wiring from the relay to the device it is controlling should be no more than 3 feet (per NFPA 72).
Note: Refer to Table 2 for 4098-9685 and 4098-9688 duct detector compatibility.
4098-9685 Duct Detector Electrical Specifications - Two-Wire DC
Operation (Figure 6, Page 12)
• Input Voltage - 15 to 32VDC, polarized
• Standby Current - 100uA at 24VDC maximum
• Alarm Current - 40mA at 24VDC maximum
4098-9688 Duct Detector Electrical Specifications - Two-Wire DC
Operation with Remote Relay Control (Figure 7, Page 13)
Caution: Connect only one Duct Detector to a two-wire circuit. Cannot be
used with the 4004 and 4005 Low current Initiating Device
Circuits (IDCs).
Relay control activates upon alarm initiating control functions.
• Input Voltage - 15 to 32VDC, polarized
• Standby Current – 2.0mA at 24VDC maximum
• Alarm Current - 40mA at 24VDC maximum
• Compatible Remote Relay: 4098-9841 Remote Relay
• Remote Relay coil connections supervised, 100 feet maximum
• Remote relay contacts rated 1 amp at 28VDC; or ½ amp at 120VAC
resistive, non-power-limited.
Note: Removing detector from the housing, failure of the 24VDC supply
power, or an open or short circuit on the relay control output causes the
Duct Interface Board to open its IDC connection resulting in a trouble
condition at the control panel.
4098-9686 Duct Detector Electrical Specifications - Four-Wire DC
Operation with Remote Relay Control (Figure 8, Page 14)
The 4098-9686 Four-Wire Duct Detector has a supervised zone to control up to
fifteen 4098-9843 Remote Relays (PAM-SD Relay – Manufacturer “Air
Products & Controls Ltd.) for initiating or control functions.
• Input Voltage - 21 to 29VDC (absolute rating of 18 to 32VDC), polarized
• Remote Relay coil connections supervised, 500 feet maximum
• Remote Relay contacts rated 7 amps at 28VDC/10 amps at 115VAC
resistive, non-power limited
• Add 20mA to standby and alarm current if 4098-9835 Remote Alarm/Power
Indicator/Key Switch is used
Notes:
1. Removing detector from the housing, failure of the 24VDC supply power, or
an open or short circuit on the relay control output causes the Duct Interface
Board to open its IDC connection resulting in a trouble condition at the
control panel.
2. The 24VDC power source must originate from a fused power supply listed for fire
protection signaling use, or from the Fire Alarm Control Panel (FACP) power supply.
Accessory installation instructions are provided on Page 19 of this publication.
Remote Alarm Indicator - Model 2098-9808 (Use with 4098-9755 or
4098-9756) or Model 4098-9830 (Use with 4098-9685, 4098-9688, or
4098-9686)
• Red LED indicator ON when detector/sensor is in alarm
• LED Alarm Current - 1.2mA Nominal
ALARM
Remote Alarm Indicator/Key Switch - Model 2098-9806 (Use with
4098-9755 or 4098-9756) or Model 4098-9834 (Use with 4098-9685,
4098-9688, or 4098-9686)
• Red LED indicator ON when detector/sensor is in
alarm. Key switch activates alarm relay 4098-9756,
4098-9688, or 4098-9686 only), remote LED, and puts
NORMAL
ALARM
TEST
the detector/sensor into alarm
• LED Alarm Current - 1.2mA Nominal
Remote Power/Alarm Indicator/Key Switch - Model 4098-9835 (Use
with four-wire 4098-9686)
• Green LED indicator glows with power ON
POWER
ALARM
• Red LED indicator ON when detector is in alarm
NORMAL
• Key Switch activates alarm relay, remote LED, and
TEST
puts the detector into alarm
• Standby Current - 20mA (green LED) at
24VDC Nominal
• LED Alarm Current - 1.2mA (red LED) Nominal
Maximum wire length to test terminals and remote LED is 250 feet.
Figure 6. 4098-9685 Two-Wire Duct Detector DC Operation
Continued on next page
Notes:
1. For Style D initiating device circuit, wire per dotted lines and do not use EOL resistor. If Style B initiating device circuit, refer to
drawings provided with the system panel for proper EOL resistor value.
2. It is recommended that the primary 1 and backup 2 lines be in separate wire runs and in compliance with local requirements.
3. Duct Detector wiring is 12 to 18 AWG. For additional wiring information, refer to wiring diagrams supplied with the system panel.
4. The 4098-9834 and 4098-9830 are polarized; observe color coded wiring.
5. Maximum wire length to test terminals and remote LED is 250 feet.
It is recommended that the primary 1 and backup 2 lines be in separate wire runs and in compliance wit
2-WIREDETECTORWITHRELAY
PRIMARY1
UL-LISTED
CONTROLPANEL
SIMPLEX2120,
4001,4002,4004,4005,
4020,4100+OR4120
INITIATING
DEVICECIRCUIT
VIO
N/C
BLU
C
GRY
N/O
YEL
N/C
ORN
C
GRN
N/O
OPTIONAL
(SEEACCESSORIES)
SEE
NOTES
4,5
REDBLK
+
-
+
-
SEENOTES2,3
BACKUP2
EOLRESISTOR
(IFUSED,SEENOTE1)
TB1
1
2345678
INOUT
+Z
+-
LED
4098-9841
REMOTERELAY
BLK
BLK
SEE
NOTE6
RED
RED
ALARM
LED
OPTIONAL4098-9830WIREDTHESAMEAS
"TEST"CONNECTION
4098-9834
REMOTEALARM
INDICATOR/
KEYSWITCH
TEST
4098-9834LESS
910
+-
TEST-Z
RELAY
Notes:
1. For Style D initiating device circuit, wire per dotted lines and do not use EOL resistor. If Style B
initiating circuit, refer to drawings provided with the system panel for proper EOL resistor value.
2.
local requirements.
3. Duct Detector wiring is 12 to 18 AWG. For additional wiring information, refer to wiring diagrams
supplied with the system panel.
4. The 4098-9834 or 4098-9830 are polarized; observe color coded wiring.
5. Maximum wire length to test terminals and remote LED is 250 feet.
6. 4098-9841 Remote Relay contacts are rated at 1 amp at 28VDC/0.5 amp at 125VAC, resistive, nonpower limited. Wiring from the relay to the device it is controlling should be no more
NFPA 72).
Figure 7. 4098-9688 Two-Wire Duct Detector DC Operation with Remote Relay Control
1. For Style D initiating device circuit, wire per dotted lines and do not use EOL resistor. If Style B initiating device circuit, refer to
drawings provided with the system panel for proper EOL resistor value.
2. It is recommended that the primary 1 and backup 2 lines be in separate wire runs and in compliance with local requirements. Duct
Detector wiring is 12 to 18 AWG. For additional wiring information, refer to wiring diagrams supplied with the system panel.
3. The 4098-9830, 4098-9834, and 4098-9835 are polarized; observe color coded wiring.
4. Maximum wire length to test terminals and remote LED is 250 feet.
5. 4098-9843 PAM-SD Relay (Air Products & Controls Limited) are rated at 7 amps 28VDC/10 amps @ 115VAC. Maximum wire
length to PAM-SD Relays is 500 feet (Fifteen PAM-SD Relays maximum). Wiring from the relay to the device it is controlling
should be no more than 3 feet (per NFPA 72).
Figure 8. 4098-9686 Four-Wire Duct Detector DC Operation with Remote Relay Control
The 4098-9685, 4098-9686, 4098-9688, 4098-9755 or 4098-9756 Duct
Detector/Sensor should be installed in a location of relatively nonturbulent air
flow and within the intended operating velocity range of 300-4000 feet-perminute (91 to 1220 M/min.).
Simplex recommends measurements of air flow and examination of engineering
specifications that define expected duct air velocities under all conditions. This
is done to determine if a location is suitable for duct detector/sensor operation.
An Alnor Instrument Co. (Chicago) Model 6000P Velometer or equivalent (not
supplied) may be used to check the duct air velocity.
Rules to Follow
1. It is recommended to locate detectors/sensors a minimum of six duct widths
downstream from bends or inlets. Such locations ensure that air flow is nonturbulent and that smoke is properly mixed with air in the duct for maximum
detector/sensor efficiency. See Figures 9 and 10.
Note: Installation of a duct detector/sensor to a round duct is the same as
shown in Figures 9 and 10 as long as the round duct is 18 inches or
larger (45.7 cm) in diameter.
BEND OR OTHER
OBSTRUCTION
6 DUCT WIDTHS
MINIMUM
Figure 9. Duct Housing Placement - Location of Bends or Inlets
RETURN AIR
INLET
Figure 10. Duct Housing Placement - Location of Air Return Inlet
2. Locate duct housings so that dampers do not restrict air flow at the
detector/sensor location. See Figure 11.
3. Locate air duct detectors/sensors on the return or supply duct of the
equipment’s air handling system. However, detectors/sensors should NOT
be installed in the return air damper branch. See Figure 11.
4. Locate air duct detectors/sensors on branch lines if close identification of
the alarm source is required.
5. Locate air duct detectors/sensors on the downstream side of filters to sense fire
in filters. However, should the filters block, sufficient air flow may not be
available for proper air duct detector/sensor operation. See Figure 11.
DETECTOR/SEN
EXHAUST
DAMPER
O.K.
RETURN
AIR
SUPPLY
AIR
EXHAUST
FRESH
AIR
INTAKE
DO NOT LOCATE
DETECTOR/SENSOR HERE
FILTER
BANK
DO NOT LOCATE
DETECTOR/
SENSOR HERE
RETURN AIR
DAMPER
DETECTOR/SENSOR
Figure 11. Duct Housing Placement - Location of Dampers
6. Whenever possible, locate air duct detectors/sensors where they can be
conveniently observed and readily serviced.
7. Locate the air duct detectors/sensors in return air ducts ahead of mixing
areas.
8. Do not locate air duct detectors/sensors next to outside air inlets unless you
want to monitor smoke entry to the handling system from an adjacent area.
9. Locate air duct detectors/sensors upstream of air humidifiers and cooling
coils.
Duct Detector/Sensor
Installation
1. Tape the template (Figure 18) on the duct surface as shown in Figure 12.
Note: Do not position the Template with edges angled with respect to air flow
direction (Figure 12) .
2. Drill two 1 1/4 inch (31.75 mm) holes (marked “A” in Figure 18) as located
by the template. Remove template after holes have been drilled.
3. If the duct is more than 3 feet (0.9 m) wide, then punch a 1-inch (25.4 mm)
hole in the duct wall directly opposite the upstream 1 1/4 inch (31.75 mm)
hole. See Figure 13. This hole is used to support the inlet tube.
4. Inlet tubes should be selected and cut to length as specified in Table 3.
After trimming the inlet tube opposite the slot, tap rubber plug (supplied)
into the trimmed end. See Figure 13.
INSERT RUBBER PLUG
THIS END OF
INLET TUBE
EXPECTED
AIR FLOW
DIRECTION
INLET TUBE HOLES
FACE UPSTREAM
AIR FLOW
DIRECTION
OF AIR FLOW
12"
DO NOT INSERT RUBBER PLUG
CUT EXHAUST TUBE TO 1/2 OF
DUCT WIDTH WHEN WIDTH
IS LESS THAN 24"
EXHAUST TUBE
Figure 13. Inlet Tube Orientation (Mounting Position 2 – See Figure 18)
SEE NOTE 1
INLET TUBE RETAINER
BRACKET
TAB
FOR DUCT WIDTHS
3 FEET TO 95 INCHES
SEE NOTE 2
FOR DUCT WIDTHS
12 INCHES TO 3 FEET
Notes:
1. The tab on the inlet tube retainer bracket indicates the
inlet hole side of the pipe.
2. The inlet tube must be installed through the hole in the
housing corner next to the smoke port/air flow test holes.
5. Insert the inlet and exhaust tube receptors of the housing base into the two
holes previously cut in the duct.
6. Using the four # 8 self-tapping sheet metal screws provided in the accessory
kit, locate the four mounting hole locations that are marked inside on the
duct housing plastic (Detector Chamber marked “MTG”). Drill the four
self-tapping scr ews through the housing plas tic and duct shee t metal to
secure the duct housing (no pre-drilling is required). Torque screws 10-12
inch-pounds.
Inlet Tube Installation (See Figures 13 and 14)
7. Install the inlet tube by inserting the rubber plug end of the tube into the
upstream tube receptor located in the rear of the duct housing. The inlet
tube must be installed through the hole i n t he housing corner next to the
smoke port/air flow test holes. Place the tube retainer (supplied) over the
inlet tube so that the tab on the tube retainer goes into the slot on the inlet
tube. Make sure the tube retainer is in the proper orientation so that the
holes in the inlet tube face upstream into the airflow. The tab on the inlet
tube retainer bracket indicates the inlet hole side of the pipe.
Note: If a support hole is being used, be sure to insert the inlet tube through
the hole on the far side of the duct.
8. Fasten the tube retainer using two #8 machine screws.
Notes:
1. Be sure to securely tighten the #8 machine screws to prevent accidental
turning of the tube within the receptor. Torque screws 16-18 inch-pounds.
2. If the inlet protrudes thr ough the far side of the duct, seal t he opening around the
tube (on the outside of the duct) with duct sealant.
Exhaust Tube Installation (See Figures 13 and 14)
9. Install the exhaust tube into the downstream receptor of the duct housing
base. Place the inlet tube retainer bracket (supplied) over the exhaust tube
so that the tab on the tube retainer goes into the slot on the exhaust tube.
10. Fasten the tube retainer using two #8 machine screws.
Note: Be sure to securely tighten the #8 machine screws. Torque screws
If conduit is required, route conduit to the most convenient knockout and secure
to the assembly using suitable fittings.
Note: The unuse d conduit entry is sealed off using the cap plug (incl uded with
ship group 748-518). Apply even pressure on the plastic cap plug to
secure it against the conduit plate. The cap plug seals and removes
easily with moderate pressure.
Connect wires to the appropriate terminals within the duct housing in accordance
with the system wiring diagram and the appropriate typical installation diagram.
Perform all wiring in accordance with the requirements of the National Electric
Code
and local codes.
Connect the optional accessory as specified in the following paragraph and the
associated installation and wiring diagrams.
Note: Only one remote indicator may be connected to each 4098-9685, 4098-9686,
4098-9688, 4098-9755, or 4098-9756.
The 2098-9806, 2098-9808, 4098-9830, 4098-9834, and 4098-9835 accessories
are intended for installation to a standard 2-inch x 3-inch outlet box having a
depth of at least two inches. See Figure 15 for details. Make wiring connections
in accordance with the installation wiring diagram prior to attaching accessory to
the box.
Note: Maximum wire length to test terminals and remote LED is 250 feet.
4098-9835
ALARM/POWER
INDICATOR/KEY SWITCH
ALARM
POWER
NORMAL
TEST
4098-9834
OR
2098-9806
ALARM INDICATOR/
KEY SWITCH
ACTUAL ACCESSORY MAY VARY
SLIGHTLY FROM PICTURE SHOWN
Page 26
Installation, Continued
Detector/Sensor Replacement
To properly remove and replace the detector/sensor to the base (see Figure 1):
1. Remove power from the Duct Detector/Sensor.
2. Loosen the four screws that secure the clear plastic cover to the housing base.
3. Insert a small blade screwdriver into the lock release slot in the base. Rotate
the detector/sensor counterclockwise to remove it from the base.
4. Remove dust cover from the replacement detector/sensor.
5. Insert the detector/sensor into the base and rotate until fully seated, continue
rotation until lock has been engaged.
6. Secure the clear plastic cover to the housing using the four screws (Torque screws to 8-10 inch-pounds).
Note: An audible “snap” indicates proper contact engagement.
WARNING: System will not operate with dust cover in place.
DC Operation Detector
Testing
Periodic Air Test
Basic Unit Test
With power applied to the Duct Detector, introduce aerosol using the 553-673 Smoke
Detector Aerosol Tester i nt o the Duct Detector through the test port holes (Figure 1).
Or, place the 553-810 Magnet Tester next to the test location on the clear Housing
Cover (Figure 16). Observe “ALARM” LED operation on the detector or the
“ALARM” LED on the interface PCB for DUCT Sensors. Restore normal operation
to detector by doing a system reset at the panel, or by momentarily removing power,
or by removing and replacing the detector head. Restore normal operation to sensor
by doing a system reset at the panel.
With the air handling unit turned on, and all filters and dampers in place, open one of
the test port holes (Figure 1) by removing one of the red covers marked “Test” on the
Duct Detector/Sensor. Measure the airspeed velocity inside the duct housing using
the Alnor Instrument Co. Air Velocity Meter (Model 8500) or equivalent (not
supplied).
Note: Refer to manufacturer instructions when performing this test.
Insert the probe in the test opening and measure the airspeed directly in front of the
sampling tube. Airspeed measured at this point should be 200 fpm or greater.
Airspeed measured at the inlet is typically 40% – 60% of the actual airspeed in the
duct housing. Any deviation from the recommended installation rules described
previously can cause this measurement to be unreliable.
If the airspeed measurement is less than 200 fpm, then a direct airspeed measurement
should be taken inside the duct. Airspeed inside the duct should be between 300 fpm
and 4000 fpm (91 to 1220m/min) for proper operation of the smoke detector/sensor.
Airspeed below 200 fpm measured inside of the duct detector/sensor may indicate a
sampling or exhaust tube obstructed by debris. Tubes should be inspected and
cleaned as required.
IMPORTANT: Make sure the test port covers are replaced after testing.
Note: Refer to the 4098 Detectors, Sensors, and Bases Application Manual
(574-709) for detailed information on Detectors and Sensors.
Sensor Magnet Test
The following test method is suitable for functional checks of sensor bases
during installation; however, testing with aerosol must be performed to comply
with NFPA requirements.
Position the 553-810 Magnet Tester on the cover side, below either of the arrow
marks (see Figure 16), not between the two arrow marks. Testing a sensor
with a magnet reports a value of 255 for actual / peak (exception 4010 panel).
Clear the peak value after testing.
Detector Magnet Test
The 4098-9601 photoelectric detector may be tested by placing a magnet at the
location indicated by a “TEST” mark embossed on the cover for four (4) seconds (see Figure 16). Use the Simplex Magnet Tester (Part No. 553-810),
Table 4, and the following information to test detectors.
TEST MARK
ON COVER
PLACE MAGNET TESTER FL AT FOR
(DETECTOR MAGNET T EST LOCATION
DETECTOR TEST
INDICATED BY DASHED LINES)
Table 4 describes the Detector LED reaction during Normal and MAG TEST
modes to the Normal, More Sensitive, Less Sensitive, and Non-Functional states
of the detector.
Table 4. MAG TEST/Normal Modes - States and Reactions
Preferred Method of Testing
Smoke Detectors/Sensors
When placing the magnet near the location (see Figure 16) indicated by a
“TEST” mark embossed on the cover, the visible LED flashes indicating the
detector's condition. The following are descriptions of what you should see
when using the MAG TEST.
• NORMAL - When in MAG TEST, the detector latches into alarm if the
detector is within calibration range and the visible LED stays ON.
• MORE SENSITIVE - When in MAG TEST, if the detector is more
sensitive than the maximum calibration, the visible LED quickly flashes,
twice a second. Following the sixth flash, the detector latches into alarm
and the visible LED stays ON.
• LESS SENSITIVE - When in MAG TEST, if the detector is less sensitive
than the minimum calibration, the visible LED slowly flashes four times,
once every two seconds. Following the fourth flash, the detector latches
into alarm and the visible LED stays ON.
• NON-FUNCTIONAL - If the detector is less sensitive than the minimum
allowable sensitivity, the visible LED does not flash normally. When in
MAG TEST, the visible LED slowly flashes four times, once every two
seconds. After the fourth flash, the detector does NOT latch into alarm and
the LED stops flashing and turns OFF.
If the detector is out of the normal operating range, it should be cleaned. If the
detector still indicates as other than normal sensitivity, replace the detector.
NFPA requires annual testing of the det ectors/sensors a t their installed location
using smoke or aerosol. With the air handling unit turned on, open one of test
port holes (Figure 1) by removing the red cover on the duct detector/sensor
housing. Using an extended nozzle on the smoke detector aerosol tester
(553-673) spray a 4-second burst of aerosol through the test port but not dire ctly
at the detector/sensor head. The nozzle of the smoke detector aerosol tester
should not extend beyond the inlet tube (see Figure 17). Aerosol is sprayed into
the stream of incoming air and not directly into detector/sensor.
IMPORTANT: Make sure the test port covers are replaced after testing.
With the air handling unit OFF and power applied to the air duct detector/sensor,
introduce aerosol into the detector/sensor or activate the built-in test feature as
described in the 4098 Detectors, Sensors, and Bases Application Manual 574-709.
Observe alarm LED operation. Restore normal operation to the detector by doing
a system reset at the pane l , or by momentarily removing power, or by removing
and replacing the detector head after aerosol has been cleared from its chamber.
Restore normal operation to the sensor by doing a system reset at the panel.
Basic Unit Test with 4098-9830 or 2098-9808 Option
Perform the basic unit test above and observe both alarm LED operation of the
detector/sensor and remote alarm indicator. Restore normal operation to the
detector by doing a system reset at the panel, or by momentarily removing power,
or by removing and replacing the detector head after aerosol has been cleared from
its chamber. Restore normal operation to the sensor by doing a system reset at the
panel.
Basic Unit Test with 4098-9834 or 2098-9806 Option
Perform the basic unit test above and observe both alarm LED operation of
detector/sensor and remote alarm indicator. Restore normal operation to detector by
doing a system reset at the panel, or b y momentari l y removing power, or by re movi ng
and replacing the detector head after aerosol has been cleared from its chamber.
Restore normal operation to the sensor by doing a system reset at the panel.
An alternate test method is to insert the key into the keyswitch and turn the key
clockwise to test. Observe alarm LED operation of the detector/sensor and remote
alarm indicator. Restore normal operation to the detector by doing a system reset at the
panel, or by momentarily removing power, or by removing and replacing the detector
head. Restore normal operation to the sensor by doing a system reset at the panel.
Basic Unit Test with 4098-9835 Option
Perform the basic unit test above, the green LED indicator glows when power is
ON. Use with 4098-9686 only.
An alternate test method is to insert the key into the keyswitch and turn the key
clockwise to test. Observe alarm LED operation of the detector and remote
alarm indicator. Restore normal operation to the detector by doing a system
reset at the panel, or by momentarily removing power, or by removing and
replacing the detector head.
With the air handling unit turned on and all filters and dampers in place, measure
the air differential pressure using a Dwyer Instrument Co. (Michigan City, Ind.)
No. 20026 0 to 2” H
Take measurements from inside of the detector/sensor housing before the cover is
installed. Measure the difference in pressure between the intake tube and the
exhaust tube. The pressure differential for all duct velocities between 300 and
4000 feet per minute (91 to 1220 M/min.) shall not be less than 0.015 inches (.381
mm) of water nor greater than 1.55 inches (39.370 mm) of water.
After testing is completed, secure the clear plastic cover to the housing using the four
screws (Torque screws to 8-10 inch-pounds).
The duct housing sampling tube holes should be checked periodically for
cleanliness, thus assuring easy air entry. Any dust or debris should be removed
from tube or tube holes.
The maintenance program of the particular detector/sensor used should be
carried out in accordance with the detector/sensor installation instructions.
Vacuuming the detector/sensor air entry areas should be performed annually, or
as required.