Simplex 4098 User guide

Page 1
4098 Detectors, Sensors, and Bases Application Manual
574-709 Rev. AP
*0574709AP*
Page 2
This page is intentionally blank
Page 3
Contents
1 Cautions, warnings, and regulatory information...................................................................................... 3
2 Overview.........................................................................................................................................................4
2.1 Special considerations......................................................................................................................................................................... 4
2.1.1 Special considerations for smoke detectors and sensors.......................................................................................................................4
2.1.2 Smoke detector and sensor applications.....................................................................................................................................................4
2.2 Where to place detectors and sensors.............................................................................................................................................. 4
2.2.1 Correct locations for detectors and sensors...............................................................................................................................................4
2.3 Where not to place detectors and sensors....................................................................................................................................... 7
2.3.1 Incorrect locations for detectors and sensors............................................................................................................................................7
2.4 Principles of operation.........................................................................................................................................................................8
2.4.1 Introduction.........................................................................................................................................................................................................8
2.4.2 Heat detector operation...................................................................................................................................................................................8
2.4.3 Photoelectric smoke detectors or sensors..................................................................................................................................................9
2.4.4 Carbon monoxide gas detectors or sensors...............................................................................................................................................9
3 4098 Smoke Detectors, Heat Detectors and Bases................................................................................ 10
3.1 4098 Smoke Detectors.......................................................................................................................................................................10
3.1.1 Smoke detector limitations............................................................................................................................................................................10
3.1.2 Specifications.................................................................................................................................................................................................... 10
3.1.3 Mounting requirements................................................................................................................................................................................. 10
3.2 4098 Heat Detectors.......................................................................................................................................................................... 11
3.2.1 Heat detector types.........................................................................................................................................................................................11
3.2.2 Specifications.................................................................................................................................................................................................... 11
3.3 4098 Bases.......................................................................................................................................................................................... 12
3.3.1 Mounting............................................................................................................................................................................................................12
3.3.2 Wiring..................................................................................................................................................................................................................14
4 TrueAlarm Sensors and Sensor Bases......................................................................................................19
4.1 Introduction........................................................................................................................................................................................ 19
4.2 4098-9733, 4098-9734, and 4098-9778 spacing............................................................................................................................. 19
4.3 4098 TrueAlarm Sensors................................................................................................................................................................... 20
4.3.1 Special applications.........................................................................................................................................................................................20
4.3.2 Mounting............................................................................................................................................................................................................20
4.4 4098 TrueAlarm Sensor Bases..........................................................................................................................................................20
4.4.1 Specifications.................................................................................................................................................................................................... 22
4.4.2 Setting the address of the base................................................................................................................................................................... 23
4.4.3 Address setting for the 2120 CDT System.................................................................................................................................................24
4.4.4 Address Setting for the 4010, 4020, 4100+, 4100U, 4100ES, 4010ES, 4007ES, 4008, or 4120 System....................................24
4.4.5 Wiring..................................................................................................................................................................................................................25
4.4.6 CORC Replacement Instructions..................................................................................................................................................................28
4.5 Setting the Tone for the 4098-9773 CO Sounder Base and the 4098-9772 Sounder Base....................................................... 30
5 Accessories.................................................................................................................................................. 31
5.1 2098-9737 Relay Module wiring....................................................................................................................................................... 31
5.2 4098-9860 Relay Module wiring....................................................................................................................................................... 31
5.3 4098-9822 Relay Module wiring....................................................................................................................................................... 32
5.4 Relay Module installation.................................................................................................................................................................. 32
5.5 Remote LED Module.......................................................................................................................................................................... 33
6 Compatibility and testing........................................................................................................................... 34
6.1 Compatibility for 4098 Detectors and Detector Bases.................................................................................................................. 34
6.2 Compatibility for 4098 Sensors and Sensor Bases........................................................................................................................ 34
6.3 Maintenance and testing...................................................................................................................................................................35
6.3.1 Maintenance..................................................................................................................................................................................................... 35
6.3.2 Testing.................................................................................................................................................................................................................35
6.3.3 Preferred method of testing smoke detectors or sensors....................................................................................................................36
Page 4
4098 Detectors, Sensors, and Bases Application Manual
6.3.4 Test Equipment Available...............................................................................................................................................................................36
6.3.5 Alternate method for testing sensors.........................................................................................................................................................37
6.3.6 Magnetic Test for photoelectric detectors................................................................................................................................................ 38
6.3.7 Maintenance of the CO Sensor.................................................................................................................................................................... 39
6.3.8 End of life service............................................................................................................................................................................................. 39
6.3.9 Standard maintenance...................................................................................................................................................................................39
6.3.10 CO sensor testing flowcharts......................................................................................................................................................................40
6.3.11 Cleaning........................................................................................................................................................................................................... 41
6.3.11.1 Photoelectric smoke detector or sensor cleaning..........................................................................................................................41
6.3.12 Trouble indications........................................................................................................................................................................................41
6.3.12.1 Trouble indications for TrueAlarm sensors...................................................................................................................................... 41
6.3.13 Fire Alarm trouble and maintenance log.................................................................................................................................................42
page ii 574-709 Rev. AP
Page 5
4098 Detectors, Sensors, and Bases Application Manual
1 Cautions, warnings, and regulatory information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
EYE SAFETY HAZARD Under certain fiber optic application conditions, the optical output of this device may exceed eye safety limits. Do not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device.
SULFURIC ACID WARNING Battery contains sulfuric acid, which can cause severe burns to the skin and eyes and can destroy fabric. Replace any leaking or damaged battery while wearing appropriate protective gear. If you come in contact with sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
FCC RULES AND REGULATIONS – PART 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. SYSTEM REACCPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with NFPA-72, after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. NFPA 72® is a registered trademark of the National Fire Protection Association.
page 3 574-709 Rev. AP
Page 6
4098 Detectors, Sensors, and Bases Application Manual
2 Overview
This document provides information about the correct application of both heat and smoke detectors/sensors in conjunction with fire alarm systems.
The information in this publication is intended to be used as a technical guide only. Ensure that the requirements of applicable codes and standards, as well as the directives of Authorities Having Jurisdiction (AHJs) are followed.
2.1 Special considerations
Before installing detectors or sensors, make a survey of the area to be covered in accordance with the information provided in NFPA 72, an excerpt of this is provided in
Proper Use of System Smoke Detectors.
2.1.1 Special considerations for smoke detectors and sensors
Consider the following before installing detectors or sensors:
• Is there human occupancy?
• The contents to be protected.
• The type of construction and use.
• The burning characteristics of contents.
• The air movement - stratification.
• The deflections and obstructions.
• The height of ceilings.
• The surface conditions of ceilings.
• The type of ceiling construction.
• The total area.
• The vent locations: velocities and dilution.
Smoke detector and sensor applications. For additional information, refer to NFPA 72 and the NEMA Guide for
2.1.2 Smoke detector and sensor applications
Each detector/sensor can provide up to 900 square feet, or 84 square meters of coverage, depending on the following:
• The requirements of local codes.
• The results of engineering evaluation.
2.2 Where to place detectors and sensors
2.2.1 Correct locations for detectors and sensors
Important: The guidelines in this section are adapted from standards published by the National Fire Protection Association, Quincy, Massachusetts, U.S.A. These standards include NFPA 72, “National Fire Alarm and Signaling Code”; NFPA 70, “National Electrical Code”, Article 760; and NFPA 90A, “Standard for the Installation of Air Conditioning and Ventilating Systems.”
To provide effective early warning of a developing fire situation, install smoke detectors or sensors in all areas of the protected premises. Total coverage as defined by NFPA 72 includes all rooms, halls, storage areas, basements, attics, lofts, and spaces above suspended ceilings including plenum areas utilized as part of the HVAC system. In addition, this includes all closets, elevator shafts, enclosed stairways, dumbwaiter shafts, chutes, and other subdivisions and accessible spaces.
Fire detection systems installed to meet local codes or ordinances may not be adequate for early warning of the fire. Some codes or ordinances have minimum objectives, such as capturing elevators, or preventing circulation of smoke through HVAC systems instead of early detection of fire.
Weigh the costs against the benefits of installing a complete fire detection system when any detection system is being installed. The location, quantity, and zoning of detectors or sensors is determined by the objectives of the installation, rather than the minimum requirements of any local codes or ordinances.
Detectors or sensors can be omitted from combustible blind spaces when any of the following conditions prevail:
• Where the ceiling is attached directly to the underside of the supporting beams of a combustible roof or floor deck.
• Where the concealed space is entirely filled with noncombustible insulation. In solid joist construction, the insulation need only fill the space from the ceiling to the bottom edge of the joist of the roof or floor deck.
page 4 574-709 Rev. AP
Page 7
4098 Detectors, Sensors, and Bases Application Manual
• Where there are small concealed spaces over rooms, provided the space does not exceed 50 square feet, or 4.6 square meters.
• In spaces formed by sets of facing studs or solid joists in walls, floors, or ceilings where the distance between the facing studs or solid joists does not exceed 6 inches, or 15 centimeters.
page 5 574-709 Rev. AP
Page 8
4098 Detectors, Sensors, and Bases Application Manual
Detectors or sensors can also be omitted from below open grid ceilings where all of the following conditions are met:
• The openings of the grid are at least 1/4 inch, or 6 millimeters in the smallest dimension.
• The thickness of the material does not exceed the smallest of the grid openings.
• The openings constitute at least 70% of the area of the ceiling material.
Detectors or sensors are usually required or recommended underneath open loading docks or platforms and their covers, and in accessible under-floor areas in buildings without basements. Detectors or sensors may be omitted from combustible blind spaces when all of the following conditions prevail:
1. The space is not accessible for storage purposes, it is protected against the entrance of unauthorized persons, and it is protected
against the accumulation of windblown debris.
2. The space contains no equipment or structures, such as steam pipes, electrical wiring, ducts, shafts, or conveyors that could
potentially ignite or conduct the spread of fire.
3. The floor over the space is tight.
4. Non flammable liquids are processed, handled, or stored on the floor above the space.
“Total coverage” as described in NFPA 72, is the definition of a complete fire detection system. In some of the specified areas of coverage, such as attics, closets, under open loading docks or platforms, a heat detector may be more appropriate than a smoke detector. Give careful consideration to the detector manufacturer’s instructions and the following recommendations in this guide.
When only one detector/sensor is required in a room or space, install the detector or sensor as close to the center of the ceiling as possible. Central location of the detector or sensor is best for sensing smoke or fire in any part of the room. If a center location is not possible, place it no closer than 4 inches, or 10 centimeters from the wall, or if it is listed for wall mounting, it can be mounted on the wall. Wall mounted detectors or sensor should be located approximately 4 to 12 inches, or 10 to 30 centimeters from the ceiling to the top of the detector, and at least 4inches, or 10 centimeters from any corner wall junction, see Figure 1.
Figure 1: Wall and ceiling mounted detector or sensor
When an air supply or an air return duct opening is present in a room or space, install the detectors or sensors in the path of the air flow toward the return air duct opening, see Figure 2.
page 6 574-709 Rev. AP
Page 9
4098 Detectors, Sensors, and Bases Application Manual
Figure 2: Detector placement - air supply or return ducts
Smoke tests help determine the correct placement of detectors and sensors. Observe the smoke travel directions and velocity, as these factors can affect detector and sensor performance.
Placement of a detector or sensor near air conditioning or incoming air vents can cause excessive accumulations of dust and dirt on the detector or sensor. This dirt can cause the detector or sensor to malfunction and cause nuisance alarms. Do not locate detectors or sensors closer than 3 feet, or 0.9 meters from an air supply diffuser.
Spot type detectors or sensors in correctly engineered systems, can also be installed in return air ducts, or in approved duct detector housings designed for this application. Although duct detectors are not a substitute for open area detectors, they can provide an effective method of initiating building control functions to prevent smoke being transported from the fire area to other parts of a building.
2.3 Where not to place detectors and sensors
2.3.1 Incorrect locations for detectors and sensors
Installing detectors or sensors in an incorrect location is a major cause of nuisance alarms. To avoid nuisance alarms do not install detectors or sensors in environments that can cause them to malfunction. See the following table and examples:
Table 1: Environmental conditions that influence detector response*
Detection protection
Photo O O X X X Beam O O X X O Air Sampling O O X X O *See Table A-5-3.6.1.1 in NFPA 72 X = May affect detector or sensor responses O = Generally does not affect detector or sensor responses
Do not install detectors or sensors in the following areas:
• In excessively dusty or dirty areas, such as feed rooms, steel mills, etc. Dust and dirt can accumulate on the detector or sensor’s sensing chamber and make it overly sensitive, or block the air entrances to the sensing chamber and make the detector or sensor less sensitive to smoke. Be especially careful to avoid areas where fumigants, fog or mist-producing materials, or sweeping and cleaning compounds are used. These substances can cause nuisance alarms.
• Outdoors, in stables, open storage sheds, or other open structures affected by dust, air currents, or excessive humidity and temperature.
• In damp or excessively humid areas, or next to bathrooms with showers. Water droplets can accumulate inside the sensing chamber and make the detector or sensor overly sensitive. A large amount of humid air is produced during a hot shower. The moisture in this humid air can enter the sensing chamber as water vapor, then cool and condense into droplets causing a nuisance alarm.
• In elevator lobbies over ashtrays or where people smoke while waiting for the elevator.
• In very cold or very hot environments, or in unheated buildings or rooms where the temperature can fall below or exceed the operating temperature range of the detector or sensor. At temperatures below 32°F, or 0°C, ice crystals or condensation can appear inside the sensing chamber and make it overly sensitive or cause a nuisance alarm. At temperatures above the operating range of the detector or sensor greater than 120°F, or 49°C, its internal components may not function correctly.
• In or near areas where combustion particles are normally present, such as in kitchens or other areas with ovens and burners; in garages, where particles of combustion are present in vehicle exhausts; within 15 feet, or 4.5 meters of any type of furnace, hot water heater, or gas space heater; or in welding shops or other types of work areas where some form of combustion is used in the activity
Air velocity >300 ft.
(91.4 m) / min.
Atm. pressure
3000 ft. (914 m)
above sea level
Humidity
>93% RH
Temp. <32°F (0°C) >100°F (38°C)
Color of smoke
page 7 574-709 Rev. AP
Page 10
4098 Detectors, Sensors, and Bases Application Manual
normally conducted in that area. When a detector must be located in, or adjacent to such an area, a fixed temperature heat detector can be appropriate.
• In air streams passing by or through kitchens. Air often enters a residence or a residential unit of an apartment building through cracks around the front or back doors. If the air return is in the bedroom hallway or in the bathroom, and if air from the kitchen easily enters the air stream going from the door to the air return, combustion particles from cooking can cause nuisance alarms. Install detectors or sensors so that they protect the bedrooms but are out of the air stream.
• In or near manufacturing areas, battery rooms, or other areas where substantial quantities of vapors, gases or fumes may be present. Strong vapors, like excessive humidity, can make detectors or sensors overly sensitive or less sensitive than normal. In very large concentrations, gases heavier than air, such as carbon dioxide, may make detectors or sensors more sensitive, while gases lighter than air, such as helium, may make them less sensitive. Aerosol particles may collect on detector or sensor chamber surfaces and cause nuisance alarms.
• In insect-infested areas. If insects enter a detector or sensor’s sensing chamber, they can cause a nuisance alarm. Perform insect eradication procedures before installing detectors or sensors in these locations. If spraying is part of this process, do not allow insect spray to enter the detectors or sensors.
• Near fluorescent light fixtures. Electrical noise generated by fluorescent light fixtures may cause nuisance alarms. Install detectors or sensors at least 1 foot, or 0.3 meters away from these light fixtures.
• When using the CO Base for CO fire detection, do not install in locations that can have potentially high non-fire levels of CO.
Underwriters Laboratories (UL) has three standards for smoke detectors:
• One for duct detectors or sensors, UL 268A.
• One for single and multiple station detectors/sensors, UL 217.
• One for system type detectors or sensors, UL 268.
Only use detectors or sensors in the applications for which they are specifically listed.
The NFPA 101 Life Safety Code states that single station smoke detectors shall sound an alarm only within an individual living unit or similar area and shall not actuate the building fire alarm system. It also states, “All systems and components shall be approved for the purpose for which they are installed.”
In addition to possible code noncompliance, the following deficiencies exist in a series of residential smoke detectors connected in a fire alarm system mode:
• Because the fire alarm system is not supervised, vandals or others can disconnect a detector or the entire system, leaving a building without protection. In this situation the residents are unaware of the serious life threatening condition.
• Residential detectors do not latch in alarm, the detector self-resets. One detector in alarm sounds all the detectors that are connected together. In this situation, after the alarm condition is cleared, it is difficult to identify or locate a specific detector that initially put the system into alarm,.
System detectors or sensors latch in alarm. They do not reset until the power is momentarily disconnected. This makes it easier to identify the location of the detector or sensor that caused the control panel to alarm. In addition, system detectors are specifically designed to connect to a supervised control panel. Two-wire detectors require a UL compatibility review to verify that the detector and panel operate correctly together.
A typical life safety fire alarm system for an apartment complex uses system detectors or sensors and manual fire alarm stations in the hallways and common areas of the complex, and residential single station type detectors and heat detectors in the individual apartments. The system detectors or sensors, manual stations and heat detectors are connected to a supervised control panel, sound a general alarm, and automatically notify the proper authorities that a fire condition exists. The residential detectors located in the apartments are interconnected only within the individual living quarters of each apartment. These residential units sound an alarm only in the apartment unit.
2.4 Principles of operation
2.4.1 Introduction
This section describes how the different types of detectors and sensors work. For additional information about TrueAlarm sensor operation, refer to the TrueAlarm Concepts publication (PER-91-024).
2.4.2 Heat detector operation
The heat detector senses the heat or the Rate-of-Rise (ROR) in the air temperature of the environment in which it is located. The heat detector is comprised of electronic circuitry and a mechanical package that is designed to sense the ROR of the air temperature in an expedient and reliable fashion. Upon detection of an abnormal increase in air temperature, or ROR in air temperature, the electronics indicate an alarm by increasing the amount of current draw from the monitor zone it is connected to. The monitor zone is a supervised
page 8 574-709 Rev. AP
Page 11
4098 Detectors, Sensors, and Bases Application Manual
detection circuit that is connected to a main control panel that takes appropriate action to indicate an alarm has been reported, if the zone current is substantially increased.
Heat detectors are an electronic design, the temperature of the air is sensed using two negative temperature coefficient thermistors. The resistance of the thermistors goes down with an increase in temperature. One thermistor is placed in a position that senses the open air temperature very rapidly (RT1). The second thermistor is positioned in a small cavity that protrudes out from the main body of the detector (RT2). The location of RT2 detects a quick change in the air temperature, but for a slow or medium rate of temperature change, the detector does not signal an alarm due to the ROR feature. For a slower change in temperature, the detector signals an alarm due to a set fixed temperature that is sensed by RT1. For a fast temperature rise, when a difference in temperature is sensed by RT1 and RT2 has reached a predetermined amount, the detector signals an alarm.
2.4.3 Photoelectric smoke detectors or sensors
These devices operate on a light scattering principle. The smoke sensing chamber contains an infrared LED source with a peak spectral emission of 880 nanometers. This source is placed at an angle from a spectrally matched photo-diode receiver. During a NO SMOKE condition, only light reflected from the chamber walls enters the receiver and shows up as a small photo-current. As smoke particles enter the sensing chamber and cross the light beam of the LED, more light reaches the receiver due to scattering. The receiver circuitry converts this photo-current into a signal voltage. In a detector, when this voltage reaches a preset level, an alarm is signaled. In a sensor, this signal voltage goes into an 8-bit, analog to digital (A to D) converter. A digital representation of this signal voltage is then transmitted to the fire alarm panel for further processing.
2.4.4 Carbon monoxide gas detectors or sensors
The CO Sensor and Sounder Bases with a CO Replacement Cartridge (CORC) modules work in conjunction with existing detector heads. The CO Sensor Base enhances fire detection and combines fire and toxic gas leakage detection in a single device. The CO sensor measures the concentration of carbon monoxide gas in the air in part per million (PPM). When toxic gas operation is selected, the FACP panel can generate either a supervisory, utility, or priority 2 alarm. The alarm level is calculated within the panel based on the time integrated CO levels that are measured at the detector.
page 9 574-709 Rev. AP
Page 12
4098 Detectors, Sensors, and Bases Application Manual
3 4098 Smoke Detectors, Heat Detectors and Bases
This chapter contains specification and mounting information for 4098 Smoke Detectors, 4098 Heat Detectors, and 4098 Bases.
3.1 4098 Smoke Detectors
CAUTION: Install the detectors described in this publication in accordance with applicable NFPA standards, local codes, and the Authorities Having Jurisdiction (AHJs). Failure to follow these instructions may result in failure of the detector to initiate an alarm condition. The manufacturer is not responsible for detectors that have been improperly installed, tested, or maintained.
3.1.1 Smoke detector limitations
The smoke detectors used with these bases are designed to activate and initiate emergency action, but do so only when used in conjunction with other equipment. They are designed for installation in accordance with NFPA 72 National Fire Alarm and Signaling Code.
• Smoke detectors do not work without power. AC or DC powered smoke detectors do not work if the power supply is cut off for any reason.
• Smoke detectors do not sense fires when smoke does not reach the detectors. Smoke from fires in chimneys, in walls, on roofs or on the other side of closed doors may not reach the smoke detector and alarm it.
• A detector may not detect a fire developing on another level of a building. For this reason, locate detectors on every level of a building.
• Smoke detectors have sensing limitations. In general, detectors do not provide warning for fires resulting from inadequate fire protection practices, violent explosions, escaping gases, incorrect storage of flammable liquids such as cleaning solvents, other safety hazards, or arson.
• Smoke detectors do not last forever. Smoke detectors contain electronic parts. Even though detectors are made to last for many years, any of these parts can fail at any time. Therefore, test smoke detector systems according to NFPA 72 at least annually. Clean and maintain smoke detectors regularly. See the
Compatibility and testing section of this publication for the cleaning instructions.
3.1.2 Specifications
Table 2: Smoke Detector Specifications
Specifications Smoke Detector Data
Detector PID (4098) 4098-9601, 4098-9605 4098-9602 Type of detector Photoelectric Photoelectric with Heat Working voltage (2-wire) 8.5 – 33 VDC 8.5 – 33 VDC Rated voltage (4-wire) 15 – 32 VDC 15 – 32 VDC Input ripple voltage 25% Max. 25% Max. Max. alarm current 86 mA 86 mA Surge current <200 µA <200 µA Standby current <100 µA <100 µA Heat element rating N/A 135ºF Humidity range (non-condensing) 10-95% RH 10-95% RH Air velocity range 0-2000 FPM 0-2000 FPM
3.1.3 Mounting requirements
All smoke detectors identified in Table 2 mount to a detector base, refer to considerations when mounting smoke detectors.
Important: Smoke must enter the chamber of the detector. Air flow, air stratification, air velocity, air stagnation, and air migration affects detector efficiency.
Note: Where the possibility of positive airflow from the electrical conduit or junction box exists, use 3M Weatherban number 606, or an equivalent, non-flammable sealing compound to seal the conduit openings.
• Do not install detectors in areas where temperatures are likely to exceed 100°F or 38°C or fall below 32°F, or 0°C.
• Because the 4098-9602 detector combines heat sensing, DO NOT install this detector in locations where the ambient temperatures exceed 100°F, or 38°C or where temperature fluctuations above 6°F per minute occur.
• Do not install detectors on a ceiling within 4 inches, or 10 centimeters of a wall.
• Do not install detectors where forced air ventilation can dilute the smoke before it reaches the detector.
• Do not install detectors in areas where smoke is normally present, such as kitchens, furnace rooms, laundry rooms, loading docks, rooms with fireplaces, rooms with candles, soldering rooms, and so on.
4098 Bases for more information. Use the following
page 10 574-709 Rev. AP
Page 13
4098 Detectors, Sensors, and Bases Application Manual
• Do not install detectors in areas where there is likely to be steam, such as in hospital patient rooms with vaporizers, near shower rooms, above large sinks, and so on.
• Do not install detectors above ashtrays in elevator lobbies.
• Wall-mounted detectors should be located 4 to 12 inches, or 10 to 30.5 centimeters from the ceiling to the detector head.
• Protect all detector heads during construction to avoid infiltration of construction debris. Remove any protective covers before activating the system.
• If using an adapter plate, tighten the mounting screws without warping the adapter plate.
• Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
3.2 4098 Heat Detectors
This section contains general notes, specifications, and mounting information about the heat detectors in
WARNING: Heat detectors are NOT life-safety devices: USE HEAT DETECTORS FOR PROPERTY PROTECTION ONLY! For life-safety requirements, use smoke detectors.
Note:
• For all heat detectors, provide electronic supervision with a battery back-up at the fire alarm control panel.
• Where the possibility of positive airflow from the electrical conduit or junction box exists, use 3M Weatherban number 606, or an equivalent, non-flammable sealing compound to seal the conduit openings.
• Refer to NFPA 72 for application, test and maintenance requirements.
3.2.1 Heat detector types
Fixed temperature heat detectors
Electronic fixed temperature heat detectors use a fast response, thermistor based design that senses temperatures quickly and accurately, and consistently identifies when fixed temperatures are exceeded. For this reason, the fixed temperature detectors are recommended for most applications. With a UL spacing distance of 60 X 60 foot, the fixed temperature electronic heat detectors replace both the mechanical fixed and the mechanical ROR heat detectors.
ROR temperature heat detectors
Electronic ROR heat detectors detect fixed temperature alarm thresholds in the same way as the fixed temperature heat detectors, and also detect a ROR alarm with a patented ROR detection design that quickly responds to sudden temperature variations. Due to the nature of the fast response to temperature changes, the correct installation of ROR heat detectors is important. Install ROR heat detectors in stable environmentally controlled areas. Do not install these detectors where hot or cold air can be blown on them, such as near ductwork, industrial equipment, air vents, and so on. Do not install ROR detectors where more than 6ºF per minute temperature changes can normally occur.
Specifications.
3.2.2 Specifications
Features
• Rate-of-Rise and Fixed Temperature, see Table 3.
• Alarm LED.
• Compatible with 2-Wire Initiating Device Circuits (IDCs).
• Current-Limited Alarm State.
Electrical Specifications
• Typical standby current - 80 mA.
• Typical alarm current - 40 mA.
• Maximum current - 80 mA while in an alarm state.
• Operating range - 15-32 VDC.
• Maximum ripple voltage permitted - 30%.
page 11 574-709 Rev. AP
Page 14
4098 Detectors, Sensors, and Bases Application Manual
Table 3: Heat detector models and features
Detector Model Rating or Class* Area / Language Color Code
4098-9612 (UL) 135°F (57°C) FT English — 4098-9613 (UL) 135°F (57°C) FT and RR English — 4098-9614 (UL) 200°F (93°C) FT English White 4098-9615 (UL) 200°F (93°C) FT and RR English White 4098-9616E A1 European Green 4098-9617E C European Red 4098-9618E A Australian White 4098-9619E B Australian Blue 4098-9621E D Australian Red 4098-9622E I Chinese Green 4098-9624E 134°F (56.7°C) FT Korean — 4098-9625E 134°F (56.7°C) FT and RR Korean — 4098-9626E 134°F (56.7°C) FT Taiwanese — 4098-9627E 134°F (56.7°C) FT and RR Taiwanese — 4098-9628E 190°F (87.8°C) FT Korean — 4098-9629E 190°F (87.8°C) FT and RR Korean — 4098-9630E 190°F (87.8°C) FT Taiwanese — 4098-9631E 190°F (87.8°C) FT and RR Taiwanese
* RR abbreviates Rate-of-Rise; FT abbreviates Fixed-Temperature.
All heat detectors identified in the following table mount to a detector base, refer to 4098 Bases for more information. Use the information
Mounting when mounting detector bases.
in
Table 4: Heat detector specifications
Product ID Description Application Max. Spacing
4098-9612 Fixed-Temp. Only, 135°F
(57°C)
4098-9613 Fixed-Temp. and Rate-of-
Rise, 135°F (57°C)
4098-9614 Fixed-Temp. Only, 200°F
(93°C)
4098-9615 Fixed-Temp. and Rate-of-
Rise, 200°F (93°C)
Unusually violent temp. fluctuations and ceiling temperatures not exceeding 100°F (38°C) Normal temp. fluctuations and ceiling temperatures not exceeding 100°F (38°C) Unusually violent temp. fluctuations and ceiling temperatures exceeding 100°F (38°C) but not 150° F (68°C) Normal temp. fluctuations and ceiling temperatures exceeding 100°F (38°C) but not 150°F (68°C)
Allowed (UL)
70 X 70 ft. (21 X 21m)RTI = Quick 20 X 20 ft.
70 X 70 ft (21 X 21m)RTI = Quick 20 X 20 ft
70 X 70 ft.(21 X 21m)RTI = Quick 20 X 20 ft.
70 X 70 ft.(21 X 21m)RTI = Ultra Fast 50 X
FM
(6.1 X 6.1 m)
(6.1 X 6.1 m)
(6.1 X 6.1 m)
50 ft.(15.2 X 15.2 m)
3.3 4098 Bases
The 4098-9788 base is designed for use with the 4098 Series smoke and heat detectors. To use a 4 wire configuration, you must use the 4098-9682 relay base. Heat detectors require the 4098-9684 base when used with a remote LED. This section only covers the information necessary for mounting and wiring these base configurations. Before installing these bases, make a survey of the area to be covered in accordance with the information provided in NFPA 72. For additional information, refer to the NEMA Guide for Proper Use of System Smoke
Detectors.
CAUTION: Install the bases in this section in accordance with applicable NFPA standards, local codes, and Authorities Having Jurisdiction (AHJs). Failure to follow these instructions can result in the detector failing to initiate an alarm condition. The manufacturer is not responsible for detectors that have been incorrectly installed, tested, or maintained.
3.3.1 Mounting
The 4098-9788 base mounts to the following electrical boxes:
• A 4 inch, or 10.16 centimeter octagonal electrical box.
• A 4 inch, or 10.16 centimeter square electrical box.
• A single gang electrical box.
Use the 4098-9832 adapter plate kit when mounting to a 4 inch square or any surface mounted box.
page 12 574-709 Rev. AP
Page 15
4098 Detectors, Sensors, and Bases Application Manual
Figure 3: Typical detector or sensor mounting
Note 1:
To lock and unlock a detector or sensor into a base, complete the following steps:
1. Break off the plastic lock tab to engage the locking mechanism.
2. To lock a detector or sensor into a base, turn the unit until the locking tab clicks into place.
3. To unlock a detector or sensor, insert the blade of a screwdriver into this slot and pull down on the handle. Turn and remove the
detector or sensor, see Figure 3.
Note 2:
Compatibility and testing for detailed information about compatible detectors.
Refer to
Note 3:
Bases with relay modules require that a 1.5 inch, or 38.1 millimeter extension ring, not supplied, is mounted to the 4 inch square or octagonal electrical box to meet the space requirement of the relay cube and its wires. The relay modules cannot be used in single-gang electrical box installations. Ensure the relay cube 4098-9822 is installed in the electrical box directly behind the sensor base.
Note 4:
Use the Adapter Plate Kit, 4098-9832, when mounting the following detectors or sensors to a surface mounted 4 inch, or 10.16 centimeter, square or octagonal box:
4098-9794, 4098-9770 and 4098-9771.
For this installation only, ensure the adapter plates are installed with the textured side towards the electrical box.
Note 5:
4098-9775, 4098-9776, 4098-9780, 4098-9789, 4098-9791, 4098-9792 and all detector bases flush mounted (box to be flush mounted or recessed 1/4” max).
Note 6:
4098-9770, 4098-9771 and 4098-9794 only flush mounted (box with adapter bracket to be flush or recessed 1/4” max).
Note 7:
4098-9772, 4098-9773: Use Adapter plate kit 4098-9863 to mount 4098-9772 or 4098-9773 to 4” square box.
page 13 574-709 Rev. AP
Page 16
4098 Detectors, Sensors, and Bases Application Manual
3.3.2 Wiring
All screw terminals accommodate 14 to 18 American Wire Gauge (AWG) solid or stranded wire. When tightening screws, the range of torque is 8 to 12 inch pounds. Connect the wiring to the terminals shown in the following figure, Figure 4 through Figure 8 show typical wiring applications for the 4098 bases.
CAUTION: Do not loop the wire under the terminals. Break the wire run to provide supervision of the connections.
Figure 4: Wiring and mounting the bases
Note:
1. Break off the plastic tab where indicated to engage the locking mechanism.
2. When the locking mechanism is engaged, insert a flat-head screwdriver in the slot indicated to release the detector from the
base.
3. Use the slotted hole indicated for the first screw when mounting the base.
page 14 574-709 Rev. AP
Page 17
4098 Detectors, Sensors, and Bases Application Manual
Figure 5: 4098-9788 Base connections for Style B or D initiating circuits
Table 5: Figure symbol reference
Symbol Reference
• 2120 Listed Fire Alarm Control Panel
• 4001 Listed Fire Alarm Control Panel
• 4002 Listed Fire Alarm Control Panel
• 4020 Listed Fire Alarm Control Panel
• 4100+ Listed Fire Alarm Control Panel
*
• 4100U Listed Fire Alarm Control Panel
• 4100ES Listed Fire Alarm Control Panel
• 4007ES Listed Fire Alarm Control Panel
• 4007ES hybrid Listed Fire Alarm Control Panel
• 4004 Listed Fire Alarm Control Panel
• 4005 Listed Fire Alarm Control Panel
• 4006 Listed Fire Alarm Control Panel
Note:
1. If used, the 4098-9830 Remote LED is polarized. Refer to Figure 8 to wire the remote LED to the heat detector. Observe color-
coded wiring.
2. Refer to the wiring diagrams provided with the system panel for the correct End-Of-Line (EOL) resistor value.
3. Wire the Primary-1 and the Backup-2 lines separate wire runs, and in compliance with local requirements.
4. For a Style D initiating circuit, wire according to the dotted lines and do not use EOL resistor.
5. Break the wires before connecting to Terminal 4 to maintain supervision. Do not loop the wire underneath Terminal 4.
page 15 574-709 Rev. AP
Page 18
4098 Detectors, Sensors, and Bases Application Manual
Figure 6: 4098-9683 2-Wire Relay Base connections for Style B or D initiating circuits
Note:
1. If used, the 4098-9830 remote LED is polarized. Refer to Figure 8 to wire the remote LED to a heat detector. Observe color-coded
wiring.
2. Only wire one relay base to an initiating circuit.
3. For a Style D initiating circuit, wire according to the dotted lines and do not use an EOL resistor. If it is a Style B initiating circuit,
refer to the wiring diagrams provided with the system panel for the correct EOL resistor value.
4. Wire the Primary-1 and the Backup-2 lines in separate wire runs, and in compliance with local requirements.
5. Aux. Relay contacts, each rated 1 A at 28 VDC / 0.5 A at 125 VAC, resistive.
page 16 574-709 Rev. AP
Page 19
4098 Detectors, Sensors, and Bases Application Manual
Figure 7: 4098-9682 4-Wire Base Connections for Style B Initiating
Circuits, featuring the 24VDC EOL Relay, 2098-9735 or 2098-9739
Note:
1. The figure shows the 4098-9830 remote LED. If used, the 4098-9830 remote LED is polarized. Observe color-coded wiring. Refer
to Figure 8 to wire the remote LED to the heat detector.
2. Aux. Alarm contacts - Form C - each rated 3 A at 28 VDC / 115 VAC, resistive.
3. Refer to the wiring diagrams provided with the system panel for the correct EOL resistor value.
page 17 574-709 Rev. AP
Page 20
4098 Detectors, Sensors, and Bases Application Manual
Figure 8: 4098-9684 Heat Detector LED Base Connections for Style B or D Initiating Circuits
Note:
1. Figure shows 4098-9830 Remote LED. If used, the 4098-9830 remote LED is polarized. Observe color-coded wiring.
2. Wire the Primary-1 and the Backup-2 lines in separate wire runs, and in compliance with local requirements.
3. For a Style D initiating circuit, wire according to the dotted lines and do not use an EOL resistor. If it is a Style B initiating circuit,
refer to the wiring diagrams provided with the system panel for the correct EOL resistor value.
page 18 574-709 Rev. AP
Page 21
4098 Detectors, Sensors, and Bases Application Manual
4 TrueAlarm Sensors and Sensor Bases
4.1 Introduction
This chapter contains general notes, specifications, and mounting information about the TrueAlarm Sensors and Sensor Bases.
WARNING: Ensure that the location of each smoke sensor and each heat sensor has been planned according to local and national fire codes, see NFPA 72.
Smoke sensor sensitivities are set and continuously monitored by the control panel. This functionality complies with NFPA 72. When functional testing of these sensors is required in accordance with NFPA 72, use the test methods described in
Refer to NFPA 72 for application, test and maintenance requirements.
The 4098-9733, 4098-9734, and 4098-9778 heat sensor, and the 4098-9764 multi-sensor provide a ROR function that is software programmed and selectable at 15°F, or 8.3°C, and 20°F, or 11.1°C per minute. The 4098-9733, 4098-9764 and 4098-9778 also provide general temperature monitoring within the range of 32° to 122°F, or 0° to 50°C. The 4098-9734 also provides general temperature monitoring within the range of 32°F to 150°F, or 0°C to 66°C.
Smoke sensors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
Compatibility and testing.
4.2 4098-9733, 4098-9734, and 4098-9778 spacing
Table 6: 4098-9733, 4098-9734, 4098-9778 spacing
Agency Program selection Spacing
UL 135°F / 190°F (57°C / 88°C)* 60 ft. X 60 ft. (18.3 m X 18.3 m) Ceiling
30 ft. X 30 ft. (9.15 m X 9.15 m) Wall
UL 155°F (68°C) 40 ft. X 40 ft. (12.2 m X 12.2 m) Ceiling
20 ft. X 20 ft. (6.1 m X 6.1 m) Wall
FM 135°F / 155°F / 190°F (57°C / 68°C / 88°C)* RTI = Quick
20 X 20 ft. (6.1 X 6.1 m)
FM 135°F / 155°F / 190°F (57°C / 68°C / 88°C)* with 15 or 20°F/min
(8.3 or 11.1°C/min) Rate of Rise
* 190°F (88°C) ratings apply only to the 4098-9734.
RTI = Ultra Fast 50 X 50 ft. (15.2 X 15.2 m)
page 19 574-709 Rev. AP
Page 22
4098 Detectors, Sensors, and Bases Application Manual
4.3 4098 TrueAlarm Sensors
Specifications
Table 7: TrueAlarm sensor specifications
Sensor PID 4098-9714
4098-9774
Type of sensor Photoelectric Heat Heat Gas Photo/heat Photo/heat Average
operating current UL temperature rating*
Humidity range
(non-condensing)
Air velocity range 0 - 4000 FPM — 0 - 1000 FPM 0 - 4000 FPM 0 - 4000 FPM * Fixed temperature functions are software programmed and selectable from the UL temperature rating.
** UL Max. Ambient Ceiling Temp. of 100°F (38°C) at 3600 sq. ft. of Max. Coverage.
† UL Max. Ambient Ceiling Temp. of 100°F (38°C) at 1600 sq. ft. of Max. Coverage.
# UL Max. Ambient Ceiling Temp. of 150°F (66°C) at 3600 sq. ft. of Max. Coverage.
80 µA 6 µA at 68°F (20°C)
135°F (57°C)**
10-95% RH 10-95% RH 10-95% RH 15-95% RH
4.3.1 Special applications
1. The sensitivity range, or setting for the 4098-9714, 4098-9774 and 4098-9764 sensor is 0.2%/FT to 3.7%/FT smoke obscuration.
The sensitivity settings for special applications are configured in the programmer. Sensitivity settings higher than 1.0%/FT are not UL compliant.
2. Special application sensitivities are not for general use and may be more prone to false alarms if used in unsuitable
environments. Potental nuisance sources include steam and particles generated from cooking. Sensors set to a special application sensitivity are not suitable for use in areas where cooking appliances may be used. If cooking appliances are used within the protected space, a normal application mode or configuration must be used for that area. Suitable environments for special application sensitivity settings include data centers, telecommunications, and clean rooms. Unsuitable environments include kitchens and living areas.
3. The 0.2%/FT, 0.5%/FT and 1.0%/FT settings are very sensitive settings: only use the 0.2%/FT setting when a sensor is located
in a totally smoke-free and controlled temperature environment, such as a computer room or telephone switching exchange.
4. To determine if an area is suitable for the 0.2%/FT setting, complete the following steps:
a. Set the sensitivity for the installed sensor at 1.5%/FT. b. Monitor the peak values for 90 days. If you record a peak value of 0.1%/FT or higher during the 90 days, do not use the 0.2%/
FT setting.
5. To determine if an area is suitable for the 0.2%/FT setting, complete the following steps:
a. Set the sensitivity for the installed sensor at 1.5%/FT. b. Monitor the peak values for 90 days. If you record a peak value of 0.25%/FT or higher during the 90 days, do not use the 0.5%/
FT setting.
6. To determine if an area is suitable for the 1.0%/FT setting, complete the following steps:
a. Set the sensitivity for the installed sensor at 1.5%/FT. b. Monitor the peak values for 90 days. If you record a peak value of 0.5%/FT or higher during the 90 days, do not use the 1.0%/FT
setting.
4098-9733 4098-9778
13 µA at 135°F (57°C)
155°F (68°C)†
4098-9734 4098-9746
4098-9747
90 µA 50 µA 90µA 130µA
135°F (57°C)** 155°F (68°C)† 190°F (88°C)#
(15-90% for long term exposure)
4098-9764 4098-9768
135°F (57°C)** 155°F (68°C)†
10-95% RH 10-95% RH
135°F (57°C)** 155°F (68°C)†
4.3.2 Mounting
All sensors identified in Refer to the following information and Figure 3 when mounting TrueAlarm sensors.
4098 TrueAlarm Sensors mount to a sensor base, refer to 4098 TrueAlarm Sensor Bases for more information.
4.4 4098 TrueAlarm Sensor Bases
TrueAlarm smoke or heat sensor bases are connected to a 2120 Multiplex Communicating Device Transponder (CDT), 4020, 4100+, 4100U, 4100ES, 4010ES, 4007ES, 4007ES Hybrid*, 4120, 4008, or 4010 panel by a single wire pair, MAPNET II/IDNet. The 4098-9770, 4098-9775, 4098-9776, 4098-9777, 4098-9780, 4098-9789, 4098-9792, 4098-9793, 4098-9766 (IDNet2 only), and 4098-9767 (IDNet2 only) bases
page 20 574-709 Rev. AP
Page 23
4098 Detectors, Sensors, and Bases Application Manual
and their sensors receive both power and data over MAPNET II/IDNet wiring. The 4098-9791 sensor base requires 24VDC power for relay operation, and the 4098-9771 through 4098-9773 and 4098-9794 sensor bases with sounders require 24 VDC or Notification Appliance Circuit (NAC) power. The 4098-9770 through 4098-9773, 4098-9780, 4098-9791 and 4098-9794 are NOT compatible with the 2120 CDT. The 4098-9793 and 4098-9777 are only compatible with the 4010, 4008, 4100U, 4100ES and 4010ES, 4007ES, except with the 4100-3103 Quad Panel Isolator.
The 4098-9766 and 4098-9767 are only compatible with the 4100ES, 4010ES and 4007ES providing IDNet2.
*From this point on, the 4007ES and the 4007ES Hybrid panels are referred to as 4007ES.
page 21 574-709 Rev. AP
Page 24
4098 Detectors, Sensors, and Bases Application Manual
4.4.1 Specifications
The following table contains specifications for TrueAlarm Sensor Bases.
Table 8: TrueAlarm Sensor Bases specifications
Sensor base PID 4098-9780 2-Wire Relay
Base
Working voltage (MAPNET II/
24 – 40 VDC 24 – 40 VDC 24 – 40 VDC 24 – 40 VDC
IDNet) 24V Working voltage (relay
18 – 32 VDC
or sounder power) MAPNET II/IDNet current,
450 µA 400 µA 400 µA 400 µA
see note 24V standby current (relay or
270 µA
sounder) 24V current (relay or
28 mA
sounder activated) LED output Yes Yes Yes Sounder output Note: MAPNET II/IDNet current with a Photo Sensor plugged into the base
Table 9: TrueAlarm Sensor Bases specifications (continued)
Sensor base PID 4098-9793,
4098-9777 (Isolator Base)
4098-9766, 4098-9767
(IDNet2 only) (Isolator2 base)
Working voltage MAPNET II/IDNet)
24V Working
24 – 40 VDC 30 VDC Normal Standby
35 VDC Alarm
18 – 32 VDC 18 – 32 VDC 16 – 32 VDC
voltage (relay or sounder power) MAPNET II/IDNet current, see note 3 24V standby
500 µA 850 µA Normal Standby
900 µA Alarm
270 µA 270 µA 270 µA
current (relay or sounder) 24V current
17 mA 17 mA 520 Hz: 115mA @ 18
(relay or sounder activated)
LED output Yes Yes Yes Sounder output 88 dBA
Note:
1. 4098-9772 Sounder output - Low Frequency alarm: 86 dBA per UL268; 80 dBA per UL464; Broadband: 87 dBA per UL268; 81
dBA per UL464.
2. 4098-9773 CO Sounder output - Low Frequency alarm: 85.5 dBA per UL268 and UL2034; 79.5 dBA per UL464; Broadband: 87
dBA per UL268 and UL2034; 81 dBA per UL464.
3. MAPNET II/IDNet current with a Photo Sensor plugged into the base
4098-9789, 4098-9775 (w/ Remote LED)
4098-9794 (Sounder Base)
4098-9791 (w/ Relay and Remote LED)
4098-9770 (CO Sensor Base)
4098-9771 (CO Sounder Base)
4098-9792, 4098-9776
4098-9772 (Sounder Base);
4098-9773 (CO Sounder Base)
24 – 40 VDC 24 – 40 VDC 24 – 40 VDC 24 – 40 VDC
400 µA 450 µA 500 µA 400 µA (4098-9772) 500
µA (4098-9773)
VDC 129mA @ 16 VDC Broadband: 125mA @ 18 VDC 139mA @ 16 VDC
minimum
88 dBA
minimum
See Note 1
page 22 574-709 Rev. AP
Page 25
4098 Detectors, Sensors, and Bases Application Manual
4.4.2 Setting the address of the base
Each sensor base has a unique address. This address is associated with a custom label that identifies its physical location within a building. Ensure that the address and location of the base match the address listed in the specification sheets of the following:
• 2120 Job Configuration Report
• Programmer’s Report for the 4020 System
• Programmer’s Report for the 4100+ System
• Programmer’s Report for the 4100U System
• Programmer’s Report for the 4010 System
• Programmer’s Report for the 4008 System
• Programmer’s Report for the 4120 System
• Programmer’s Report for the 4007ES System
• Programmer’s Report for the 4010ES System
• Programmer’s Report for the 4100ES System
See Figure 9 for the DIP Switch location for 4098-9775, 4098-9776, 4098-9777, 4098-9780, 4098-9789, 4098-9791, 4098-9792, 4098-9793, 4098-9766, and 4098-9767 Sensor Bases. See Figure 10 for the DIP Switch locations of 4098-9770, 4098-9771, 4098-9772, 4098-9773 and 4098-9794 Sensor Bases.
Each sensor base has a unique address. This address is associated with a custom label that identifies its physical location within a building. Ensure that the address and location of the base match the address listed in the specification sheets of the 2120 Job Configuration Report or the Programmer’s Report for the FACP.
Figure 9: 4098-9775, 4098-9776, 4098-9777, 4098-9789, 4098-9790, 4098-9791,
4098-9792, 4098-9793, 4098-9766, and 4098-9767 location of the DIP switches
Figure 10: 4098-9770, 4098-9771, 4098-9772, 4098-9773 and 4098-9794 Sensor Bases location of DIP switches
page 23 574-709 Rev. AP
Page 26
4098 Detectors, Sensors, and Bases Application Manual
Note: The 4098-9771, 4098-9772, 4098-9773 and 4098-9794 Sounder Bases have a 9-position DIP Switch. The first eight DIP Switches set the sounder base address. DIP Switch Position 9 is set to OFF or ON depending on the sounder base power source. When the sounder base is connected to a 24 VDC power source, DIP Switch Position 9 is set to “OFF” and the 24 VDC power is supervised by the sounder base. When the sounder base is powered by the panel’s Notification Appliance Circuit (NAC), DIP Switch Position 9 is set to “ON” and the power is supervised by the NAC and not the sounder base. The 4098-9770 base has the same layout, but it does not have sounder functionality. It uses an 8-way DIP switch only.
4.4.3 Address setting for the 2120 CDT System
1. Using the 2120 Job Configuration Report, find the entry for the sensor base, 4098-9775, 4098-9776, 4098-9792 and 4098-9789
only, you are installing. The CUSTOM LABEL column indicates the location while the DEVICE ADDRESS column indicates the switch setting data.
2. Using the switch setting data for the base you are installing, set the address of the base. See
the location of the switches. Use a non-metallic stylus, or the equivalent, to set the switches.
3. Double-check the location and address of the sensor base before proceeding to the electrical installation, see Figure 3.
Setting the address of the base for
4.4.4 Address Setting for the 4010, 4020, 4100+, 4100U, 4100ES, 4010ES, 4007ES, 4008, or 4120 System
1. Using the Programmer’s Report, find the entry for the sensor base you are installing. The device ADDRESS and CUSTOM LABEL are located in the SYSTEM POINT SUMMARY under “M”. For example, Address M1-7, is circled in Figure 12. M1 is the addressable channel and '-7' is the device address on the channel. For a base with Address M1-7, ensure Address 7 is set on the base’s DIP Switches (SW1).
2. Using the example given in Step 1 as guideline, set the address on the base using the information in Figure 13. See
address of the base
3. Mark an address label with the appropriate address for the base by shading a label box for each base DIP Switch in the ON position. Apply the label near the DIP Switch on the base.
4. Double-check the location and address of the sensor base before proceeding to electrical installation.
for the location of the DIP Switches. Use a non-metallic stylus, or the equivalent, to set the switches.
Setting the
Figure 11: 4020 Programmer’s Report
Figure 12: 4100+, 4100U, 4100ES, 4010ES, 4007ES, 4120, 4008, or 4010 Programmer’s Report
The figure below shows the address DIP Switch settings. Refer to FACPs.
Note: The 4020, 4100+, 4100U, 4100ES, and 4120 systems support up to 127 devices on each MAPNET II channels. The 4010, 4100U, 4100ES, 4010ES, and 4007ES support up to 250 devices on the IDNet channel. The 4008 supports up to 200 devices on the IDNet channel.
page 24 574-709 Rev. AP
Compatibility and testing for compatibility information for the various
Page 27
4098 Detectors, Sensors, and Bases Application Manual
Figure 13: MAPNET/IDNet addresses
4.4.5 Wiring
Sensor bases are connected to the fire alarm control panel using a single wire pair for the 4098-9770, 4098-9775, 4098-9776, 4098-9777, 4098-9780, 4098-9789, 4098-9792, 4098-9793, 4098-9766 (IDNet2 only), and 4098-9767 (IDNet2 only) and two pairs of wires for the 4098-9771, 4098-9772 4098-9773, 4098-9791 and 4098-9794.
Using Figure 14 as a reference, connect the bases to the MAPNET II/IDNet wire pair and 24V power, if used.
Important: For additions to existing installations, remove the power from the panel before wiring any bases to avoid damage to the equipment.
Figure 14: Smoke/Heat sensor base connections
page 25 574-709 Rev. AP
Page 28
4098 Detectors, Sensors, and Bases Application Manual
Note:
1. If the 2098-9808 Remote LED or 4098-9822 relay is used, the remote LED and relay wires are not supervised.
2. The maximum quantity of devices on a circuit is 127 for 4020, 4100+, 4100U/4100ES/4010ES (MAPNET), or 4120, 128 for the 2120 CDT panel, 200 for the 4008 panel, and 250 for the 4010 and 4100U/4100ES/4010ES/4007ES (IDNET) panel.
3. If a shield is used, twist the shield wires together and cap with a wire nut. Insulate the shield from the electrical box.
4. Contact A or B: Dry, Form C - each rated 2 A at 24 VDC / 0.5 A at 110 VAC, resistive.
5. 18 to 32 VDC, 0.008 A typical / 0.013 A max.
6. Do not use a remote LED if the 4098-9822 relay module is used.
7. Contact A or B: Dry, Form C - each rated at 3 A at 28 VDC / 115 VAC, resistive.
8. Remove the protective tape over the CO Sensor on the 4098-9770, 4098-9771, 4098-9773 bases only after the sensor head has been installed.
9. The maximum wire length between 4098-9791 sensor base and 2098-9737 relay module is 100 feet, or 30.48 meters.
10. The maximum quantity of sensors with 4098-9771, 4098-9772, 4098-9773, 4098-9794, and 4098-9798 sounder bases is limited to 43 if output is coded, Temporal code, and so on, using MAPNET II/IDNet control. If coding is performed using a 24 VDC or NAC circuit, see note 2.
11. When 4090-9116, 4098-9777, or 4098-9793 isolators are present on the channel, the maximum line resistance between the panel and the isolator, or between two isolators is 10 ohms, 780 feet, or 237.74 meters at 18 AWG.
12. Contacts Dry Form C, rated at 2 A at 30 VDC / 0.5 A at 125 VAC, resistive.
13. The maximum wire length between 4098-9780 sensor base and 4098-9860 relay module is 100 feet, or 30.48 meters.
Figure 15 shows the wiring connections for the isolator sensor base. All screw terminals accept 14 to 18-gauge AWG solid or stranded wire. Ensure the maximum torque does not exceed 12-inch-pounds.
CAUTION: Do not loop the wire under the terminals. Break wire runs to provide supervision.
Figure 15: 4098-9793, 4098-9777, 4098-9766, 4098-9767 Isolator Sensor Base connections
Note:
1. The isolator bases 4098-9777 and 4098-9793 are compatible with the 4010, 4100U, 4100ES, 4010ES, 4007ES, or 4008 panel ONLY.
2. The maximum quantity of devices on a circuit is 250 for 4010, 4100U, 4100ES, 4010ES, and 4007ES panels.
3. If shield is used, twist the shield wires together and cap with a wire nut. Insulate the shield from electrical box.
4. When 4090-9116, 4098-9777, or 4098-9793 isolators are present on the channel, the maximum line resistance between the panel and the isolator, or between two isolators is 10 ohms (780 feet, or 237.74 meters at 18 AWG).
5. The Isolator2 bases 4098-9766 and 4098-9767 are compatible with the 4100ES, 4010ES, or 4007ES providing IDNet2 only.
6. For more detailed information about the use of IDNet Isolator2 bases (4098-9766, 4098-9767) refer to Isolator2 Usage Guidelines (579-1313).
7. When Isolator2 (4090-9122, 4098-9766, or 4098-9767) are present on the channel, the maximum number of isolators (4090-9116, 4090-9122, 4098-9766, 4098-9767, 4098-9777, or 4098-9793) is 50.
page 26 574-709 Rev. AP
Page 29
4098 Detectors, Sensors, and Bases Application Manual
8. When Isolator2 (4090-9122, 4098-9766, or 4098-9767) are present on the channel, the maximum number of units loads between isolators is 50.
9. Fast recovery is only available if all isolators on the IDNet line are of the IDNet Isolator2 type. You can combine an Addressable, such as 4090-9116, IDNet Isolator with an IDNet Isolator2 (4090-9122, 4098-9766, or 4098-9767), but it is not best practice.
10. The IDNet2 channel provides timely loop isolation in case of wiring fault. Depending on local codes, negligible disruption may be achieved by using Isolator2 (4090-9122, 4098-9766, or 4098-9767) close-nippled to the FACU to provide faster fault isolation.
11. Isolator2 work to their full potential when installed on a system that follows 579-1324 IDNet Isolator2 Compatibility Chart.
page 27 574-709 Rev. AP
Page 30
4098 Detectors, Sensors, and Bases Application Manual
4.4.6 CORC Replacement Instructions
This section contains the instructions for the end-of-life replacement of the 4098-9747 CO Replacement Cartridge (CORC), in the CO SSD Bases (Carbon Monoxide Smoke Sensor and Detector Bases). Replacement is necessary due to normal component degradation over time. It is standard maintenance for the CO SSD Bases in order to prolong normal function without requiring base replacement.
WARNING: During installation, you can be exposed to live circuits - attention is required to ensure personal safety and to avoid product damage.
Table 10: Model number reference
Model Name
4098-9747 CORC Replacement 10 yr 4098-9770 CO SSD Sensor Base 10 yr 4098-9771 CO SSD Sounder Base 10 yr
Removing the expired CORC
1. Remove the sensor head, not shown, and set aside for later re-installation.
2. Insert a fine blade screwdriver into the slot, as shown below.
Figure 16: Inserting a Fine Slot Screwdriver
3. Gently free the CORC from the sensor base by pushing straight in. Do not pry. Remove the CORC and dispose
Figure 17: Removing the CORC from the Sensor Base
Installing the replacement CORC, refer to the following photo
1. Remove the replacement CORC from the packaging.
2. Hook the loop of the CORC on the tab in the outer rim of the base, the center of the CORC below the CO sensor cylinder.
3. Gently rotate the CORC inward until it snaps onto the CO SSD Sensor Base.
page 28 574-709 Rev. AP
Page 31
4098 Detectors, Sensors, and Bases Application Manual
4. Re-install the detector head.
5. Remove the dust cover from the CORC, as shown in the following figure.
6. The CORC replacement is complete.
Figure 18: Installing the Replacement CORC
Note: The fire alarm panel must be set to the correct date. Otherwise a false End of Life trouble for the CORC may be annunciated.
page 29 574-709 Rev. AP
Page 32
4098 Detectors, Sensors, and Bases Application Manual
4.5 Setting the Tone for the 4098-9773 CO Sounder Base and the 4098-9772 Sounder Base
These bases can output either a Low Frequency Alarm Tone 520 Hz, or a Broadband Horn Tone. 520 Hz is the factory default, but the tone can be manually selected using a DIP switch near the relay/Remote LED wire pair exit hole.
Figure 19: Setting the Tone for 4098-9772 Sounder Base and 4098-9773 CO Sounder Base
page 30 574-709 Rev. AP
Page 33
4098 Detectors, Sensors, and Bases Application Manual
5 Accessories
This section contains information about relay module accessories.
5.1 2098-9737 Relay Module wiring
The 2098-9737 Relay module is used with the 4098-9791 Sensor Base. Install the relay module using the Figure 14 and Figure 20 as a reference.
Figure 20: 2098-9737 Relay Module Wiring
Note:
1. 18 VDC to 32 VDC 24 mA typical / 35 mA maximum.
2. Contact A or B: dry, Form C, each rated 3 A at 28 VDC / 115 VAC, resistive.
3. The maximum wire length between the 4098-9791 sensor and the relay module is 100 feet, or 30.48 meters.
5.2 4098-9860 Relay Module wiring
The 4098-9860 Relay Module is used with the 4098-9780 Sensor Base. Install the relay module using Figure 14 and Figure 21 as a reference.
Figure 21: 4098-9860 Relay Module wiring
Note:
1. Maximum wire length between sensor 4098-9780 and relay module is 100 ft.
2. Contact Dry Form C, rated at 2 A at 30 VDC / 0.5 A at 125 VAC, resistive.
page 31 574-709 Rev. AP
Page 34
4098 Detectors, Sensors, and Bases Application Manual
5.3 4098-9822 Relay Module wiring
The 4098-9822 Relay Module is used with the 4098-9771 through 4098-9773, 4098-9775, 4098-9780, 4098-9789, 4098-9791 and 4098-9794 Sensor Bases. Install the relay module using Figure 14 and Figure 22 as a reference.
Important:
Do not use a remote LED when using the 4098-9822 relay module. The 4098-9822 relay module is not supervised and can only be used for non-critical supplementary functions. There is a limit of ten control outputs activated on a MAPNET II/IDNet channel. If the channel capacity is exceeded, the relay module can fail to function correctly.
Figure 22: 4098-9822 Relay Module wiring
Note:
1. Do not use a remote LED.
2. 18 VDC to 32 VDC, 0.008 A typical / 0.013 A maximum.
3. Contact A or B: Dry, Form “C” - each rated 2 A resistive at 24 VDC / 0.5 A at 110 VAC, resistive.
4. Contact A from 4098-9771, 4098-9772, 4098-9773, 4098-9775, 4098-9780, 4098-9789, 4098-9791 or 4098-9794 sensor base.
5.4 Relay Module installation
To install the relay module complete the following steps:
1. Mount a 1-1/2 inch, or 3.81 centimeter extension ring, that is not supplied, to an octagonal or square electrical box, also not supplied. The extension ring is required to meet the minimum box volume requirement of 32.3 cubic inches, or 529.4 cubic centimeters for relay module installation.
2. Mount the relay module inside the extension ring directly behind the base and sensor. Do not mount it remotely. See Figure 20 or Figure 22 for the relay module connections.
Note: Use the exact configuration of electrical box, square or octagonal, with an extension to mount the sensor base, when installing the relay module.
page 32 574-709 Rev. AP
Page 35
4098 Detectors, Sensors, and Bases Application Manual
5.5 Remote LED Module
The 2098-9808 Remote LED Module is compatible with the 4098-9772, 4098-9775, 4098-9780, 4098-9789, 4098-9791 and 4098-9794 Sensor Bases.
Use the following figure as a reference when installing the Remote LED Module to a sensor base.
Figure 23: 2098-9808 Remote LED Module wiring
Note: To 4098-9772, 4098-9775, 4098-9780, 4098-9789, 4098-9791 or 4098-9794 Sensor Base
page 33 574-709 Rev. AP
Page 36
4098 Detectors, Sensors, and Bases Application Manual
6 Compatibility and testing
This section covers the compatibility, maintenance, and testing of 4098 Sensors, Detectors, and Bases.
6.1 Compatibility for 4098 Detectors and Detector Bases
This section describes the compatibility between FACPs, detectors, and detector bases.
Table 11: 4098 Detector and Detector Base compatibility
Detectors Compatible 2-Wire
detector base
4098-9601 4098-9602 4098-9605 4098-9612
4098-9788 4098-9684 (LED base for Heat
Detectors Only)
4098-9613 4098-9614 4098-9615
4098-9683 (Relay base not used with 4004 and 4005 Low
Note:
1. The relay operation cannot be guaranteed unless it is the only device on that zone.
2. The panel compatibility identification marker is the model number of the module or panel.
3. The detector compatibility identification marker is the model number found on the detector label.
4. For detailed interconnection data, see the wiring diagrams for the specific panels.
5. For additional compatibility listings, see document 579-832, 2-Wire Detector Compatibility Chart.
System Max. quantity
2120 ET/FADM 25 2120 FABT/VPBT 18 2120/4100+ ZAM 20 4001 18 4002 30 4020 30 4100ES/4010ES/4007ES/4100U/4100+/4120/UT 30 4004/4005 20 4006 30 4004/4005 High Current 30
Current systems)
of bases on an initiating circuit
1 (See note 1)
6.2 Compatibility for 4098 Sensors and Sensor Bases
This section describes the compatibility between FACPs, sensors, and sensor bases.
Table 12: 4098 Sensor and Sensor Base compatibility
Sensors Compatible bases Max. quantity of devices on a circuit
4098-9733 4098-9778
4098-9733 4098-9778
4098-9733 4098-9778
4098-9734
8
4098-9775 4098-9776 4098-9780 4098-9789 4098-9791 4098-9792 4098-9775 4098-9776 4098-9789 4098-9792 4098-9775 4098-9776 4098-9777 4098-9780 4098-9789 4098-9791
4098-9792 4098-9793
4098-9770
4098-9766
4098-9767
MAPNET II:
127 (4020), 127 (4100+), 127 (4120), 127 (4100U), 127 (4100ES), 250 (4010ES/4007ES)
Addresses 1-127
128 (CDT TrueAlarm) Addresses 0-127
IDNET: 250 (4010), 250 (4100U), 250 (4100ES), 250 (4010ES, 4007ES)
7
9
9
Addresses 1-250
page 34 574-709 Rev. AP
Page 37
4098 Detectors, Sensors, and Bases Application Manual
Table 12: 4098 Sensor and Sensor Base compatibility
Sensors Compatible bases Max. quantity of devices on a circuit
4098-9733 4098-9778
4098-9733 4098-9778
4098-9734
8
4098-9775 4098-9776 4098-9777 4098-9780
4098-9772
4098-9794
4098-9771
4098-9773
5
5
5, 7
5, 7
4098-9789 4098-9791 4098-9792 4098-9793
IDNET: 200 (4008) Addresses 1-200
MAPNET II:
127 (4020), 127 (4100+), 127 (4100U), 127 (4100ES), 127 (4120) Addresses 1-127
IDNET:
250 (4010), 250(4100U), 250 (4100ES), 250 (4010ES, 4007ES) Addresses 1-250
4098-9714 4098-9764 4098-9774
6
4098-9775 4098-9776 4098-9780 4098-9792 4098-9789 4098-9791
4098-9772
4098-9794 4098-9770
4098-9771
4098-9773
5
5
IDNET 2:
250 (4100ES), 250 (4010ES, 4007ES) Addresses 1-250
5
5
4098-9777 4098-9793
9
9
IDNET:
250 (4100U), 250 (4100ES), 250 (4010ES, 4007ES) Addresses 1-250
4098-9747 4098-9770
4098-9771
4098-9773
4098-9766
4098-9767
5
5
Note:
1. For detailed interconnection data, see the wiring diagrams for the specific panels.
2. The panel compatibility identification marker is the model number of the module or panel.
3. The sensor compatibility identification marker is the model number found on the sensor label.
4. The 4098-9764 sensor is NOT compatible with bases that have a RED DOT located in the sensor mounting area.
5. The maximum quantity of 4098-9772, 4098-9794 Sounder Bases and 4098-9771 and 4098-9773 CO Sounder bases when the output is coded using MAPNET II/ IDNet control (Temporal Code) is 43. If the coding is performed using 24 VDC or NAC circuit, use the limits specified in Table 12.
6. The 4098-9714 sensor must be used with IDNet 2 Software version 2.02.02 or later.
7. The 4098-9770, 4098-9771, and 4098-9773 CO Bases are compatible with IDNet on the 4100U, 4100ES, 4010ES, and 4007ES only.
8. The 4098-9734 Heat Sensor is compatible with IDNet on the 4100ES, 4010ES, and 4007ES only.
9. Compatible with IDNet2 only.
6.3 Maintenance and testing
6.3.1 Maintenance
The minimal requirement for detector and sensor maintenance requires clearing of surface dust using a vacuum cleaner. Ensure that the cleaning programs comply with the NFPA and local environments. Ensure that cleaning of the internal chamber is only done by a qualified technical representative.
For service, return to your local branch office.
6.3.2 Testing
Smoke sensor sensitivities are set and continuously monitored by the control unit. Dirty or out-of-range sensors are annunciated by the control unit. This functionality complies with NFPA 72.
page 35 574-709 Rev. AP
Page 38
4098 Detectors, Sensors, and Bases Application Manual
Note: When testing detectors or sensors, refer to NFPA 72, or contact your local branch office.
CAUTION: Before functionally testing the detectors or sensors, be sure to disconnect the city connection, releasing devices, and
extinguishing systems. For the 4120, 4006, 4008, 4020, 4010, 4100+, 4100U, 4100ES, 4010ES, or 4007ES panel, put the panel in the Walk Test mode.
6.3.3 Preferred method of testing smoke detectors or sensors
NFPA minimally requires annual functional testing of smoke detectors or sensors at their installed location. To perform this annual test, use the Solo 336 Aerosol Smoke Dispenser.
Important: After testing detectors, reset the fire alarm panel to restore the fire alarm system to a normal status. After testing sensors, ensure you clear the peak values.
6.3.4 Test Equipment Available
The following test equipment is available. Follow the instructions included with the equipment for testing.
• 553-760: Test and Removal Tool, attached to Mr. Longarm 4 foot, or 121.92 centimeter pole (Item number 7508) or 6 foot, or 182.88 centimeter pole (Item number 7512).
• 553-761: Heat Detector or Sensor Removal Adapter, use this with the Test and Removal Tool, 553-760.
• 553-805: Removal Adapter Head Attachment (attaches to the 553-760 tool).
• 553-810: Magnet Tester, attached to Mr. Longarm 4 foot, or 121.92 centimeter pole (Item number 7508) or 6 foot, or 182.88 centimeter pole (Item number 7512).
• Gemini Sensitivity Tester (Model 501 or 502).
• Solo 336 Aerosol Smoke Dispenser –attached to either the Solo 100 (15 ft.) telescopic fiberglass pole or the Solo 101 (4 ft.) fiberglass pole.
• Solo Red Cup (709-024). Use to hold the 553-635 Aerosol Spray Can.
• Solo (708-021) Adapter for Solo Poles. Use to adapt 553-760 Test and Removal Tool to the Solo Pole.
• TrueTest 801, Smoke Detector Sensitivity Test Equipment.
• Smoke 400, Smoke aerosol for TrueTest.
• Testifire 2000-024, Smoke, Heat and CO Detector Tester.
• Testifire 2001-024, Smoke, Heat and CO Detector Test Kit (includes 2 battery batons and
• ac/dc charger).
• TS3-024 Smoke capsule, for use with Testifire Smoke, Heat and CO Detector Tester.
• TC3-024 CO Capsule, for use with Testifier Smoke, Heat and CO Detector Tester.
Note: The TrueTest 801 or the Testifier 2000-024 are the only testers for use with the 4098-9770 and 4098-9771 bases.
Table 13: Available smoke test aerosols
Product name Model Description
PurCheck® HO-30S Smoke alarm tester SmokeCheck® HO-25S Smoke alarm tester CHEKKIT® - Smoke detector tester Solo A4 - Smoke detector tester
page 36 574-709 Rev. AP
Page 39
4098 Detectors, Sensors, and Bases Application Manual
6.3.5 Alternate method for testing sensors
The following test method is suitable for functional checks of sensor bases during installation, however, testing with smoke must be performed to comply with NFPA requirements.
For all sensor bases, position the 553-810 Magnet Tester ½ inch to ¾ inch, or 12 millimeters to 20 millimeters counterclockwise from the visible LED on the sensor base, see Figure 24.
For MAPNET II devices, testing a sensor using a magnet reports a value of 255 for actual/peak. This does not occur for IDNet devices. Clear the peak value after testing.
Figure 24: Magnet Test location for 4098-9775, 4098-9776, 4098-9777, 4098-9780, 4098-9789, 4098-9791,
4098-9792, 4098-9793, 4098-9766, and 4098-9767 Sensor Bases using the 553-810 Magnet Tester
page 37 574-709 Rev. AP
Page 40
4098 Detectors, Sensors, and Bases Application Manual
6.3.6 Magnetic Test for photoelectric detectors
Test the 4098 Photoelectric Detectors by placing a magnet above the location indicated by a “|” mark embossed on the cover for 4 seconds. Use the Magnetic Tester, Part No. 553-810, Table 14, and the following information to test the detectors.
Table 14 describes the LED reaction during Normal and MAG TEST modes to the Normal, More Sensitive, Less Sensitive, and Non­Functional states of the detector.
Figure 25: Magnet Test Location for 4098-9601, 4098-9602 and 4098-9605 Smoke Detectors using the 553-810 Magnet Tester
Table 14: MAG TEST/Normal Modes - states and reactions
State Normal Mode MAG TEST Mode
LED flashes every 4 secs.
Normal X X
More Sensitive X X X
Less Sensitive X X X
Non-Functional X
When placing the magnet at the location indicated by a “|” mark embossed on the cover, the visible LED flashes indicating the condition of the detector.
The following are descriptions of the detector when it is in MAG TEST:
NORMAL - When in MAG TEST, the detector latches into alarm if the detector is within calibration range and the visible LED stays ON.
MORE SENSITIVE - When in MAG TEST, if the detector is more sensitive than the maximum calibration, the visible LED quickly flashes, twice a second. Following the sixth flash, the detector latches into alarm and the visible LED stays ON.
LESS SENSITIVE - When in MAG TEST, if the detector is less sensitive than the minimum calibration, the visible LED slowly flashes four times, once every two seconds. Following the fourth flash, the detector latches into alarm and the visible LED stays ON.
NON-FUNCTIONAL DETECTOR - If the detector is less sensitive than the minimum permitted sensitivity, or if there is a fault in the temperature sensing circuit (4098-9602), the visible LED does not flash normally. When in MAG TEST, the visible LED slowly flashes four times, once every two seconds. After the fourth flash, the detector does NOT latch into alarm, the LED stops flashing and turns OFF.
If the detector is outside the normal operating range, clean it. If after cleaning the detector still indicates an abnormal sensitivity, replace the detector.
LED Flashes Quickly 6 Times
LED Flashes Slowly 4 Times
Latches in Alarm Mode/LED stays “ON”
page 38 574-709 Rev. AP
Page 41
4098 Detectors, Sensors, and Bases Application Manual
6.3.7 Maintenance of the CO Sensor
The CO Sensor is not as susceptible to dirt as the photo or ion sensors, and does not compensate for a loss of sensitivity over the period of its lifetime.
The following two operations to inform a qualified or trained service person that a CO sensor has reached its end of life:
• The FACP panel generates an End of Life trouble notifying the user that a replacement sensor is required.
• Manual standard maintenance testing by a qualified or trained service person checks that the device is fully operational.
6.3.8 End of life service
The end of life of a CO Sensor is based on the manufacture date of the device, not the installation date.The FACP panel daily checks each IDNet CO combination sensor for the End of Life trouble expiration date.The FACP panel generates the following status report based on the condition of the CO Sensor:
None: the CO Sensor has not reached the expiration date.
Almost Expired 6M: the CO Sensor is within 6 months of the expiration date.
Almost Expired 12M: the CO Sensor is within 12 months of the expiration date.
Expired (End of Life): the CO Sensor’s date has expired.
To clear the trouble at the panel:
1. Install a new CRS with a valid date.
2. Perform a hardware reset of the FACP.
Note: For the panel to annunciate these warnings, enable the logging of the Almost Expired trouble, with the exception being the Expired trouble condition which does not require any activation.
The TrueAlarm CO report can also be used to list all End of Life dates of CO sensors in the panel. The report is a quick and easy way to check if any sensors will expire before the next visit to the site.
6.3.9 Standard maintenance
To verify that the sensors are operating correctly, standard maintenance of the CO sensors is required. The standard maintenance process is as follows:
1. The FACP panel is put into the service test mode using either the diagnostic function menu item on the front panel or the system
diagnostic computer port command.
2. A trouble displays at the panel indicating that the panel is in the Device Test Mode.
3. A tester introduces CO gas, heat and smoke simultaneously into the detector.
4. The device LED on the base turns ON steady if any, but not all of the sensors on the device cross an alarm threshold.
5. The device LED on the base flashes slowly if all of the sensors cross an alarm threshold.
6. The appropriate action based on the point type of the CO sensor is taken at the panel.
7. Device Test Mode shall is entered if a faster response time is needed during Walktest.
Note: There is a 20 device LED maximum that can be ON/Flashed at any given time. This limit applies during testing, and during alarm operation. Reset the panel before this limit is reached during testing so that the LED can be used as an indication of a successful test.
page 39 574-709 Rev. AP
Page 42
6.3.10 CO sensor testing flowcharts
4098 Detectors, Sensors, and Bases Application Manual
Figure 26: Testing a single CO sensor
Figure 27: Simultaneous testing of multiple sensor technologies
Note: The LED on the base can turn ON prior to slow flashing depending on when the individual sensors alarm. Only the last LED requested to flash will slow flash. All others will turn to steady ON. Flashing of the LED will only be performed when the IDNet CO algorithms are disabled for testing. During Walktest, a reset timer is activated so that the LED is reset to the OFF state without need­ing a reset at the panel. This reset is user programmable and can be as short as 15 seconds long. This automatic reset may cause the LED on the base to turn OFF before the test is complete. For example, it's possible that depending on the test tool, the LED (if all of the sensors are good) could turn ON then reset to OFF, turn ON then reset to OFF then finally slow flash then reset to OFF.
Note:
The following describes the LED states:
LED OFF - No sensors have exceeded their thresholds
LED ON - At least one sensor exceeded its threshold
LED FLASHING - All sensors for this device have exceeded their thresholds (Note: This could be 2 or 3 sensors depending on what type of CO combination device is configured)
Flashing will only be performed when in testing (IDNet CO algorithms are disabled).
page 40 574-709 Rev. AP
Page 43
4098 Detectors, Sensors, and Bases Application Manual
6.3.11 Cleaning
Introduction
If the sensitivity of the device does not match what is marked on the device’s label, clean the device using a source of oil-free, filtered, compressed air such as Dust-Off, or Tech Duster, and so on.
CAUTION: Notify the appropriate building personnel prior to removing any detectors or sensors from service.
6.3.11.1 Photoelectric smoke detector or sensor cleaning
Blow the compressed air through the open vents around the device so that air enters and cleans the black chamber cover and insect screen assembly, Part No. 677-224, located under the white protective cover.
If the sensitivity of the device does not match what is marked on the device’s label after cleaning, replace the device.
6.3.12 Trouble indications
6.3.12.1 Trouble indications for TrueAlarm sensors
The TrueAlarm smoke sensor is a measuring device that sends data regarding smoke density to the 2120, 4008, 4010, 4020, 4100, 4100+, 4100U, 4100ES, 4010ES, and 4007ES FACPs. The TrueAlarm heat sensor operation is similar, but sends temperature data instead of smoke density data. The FACP uses this data to determine whether a trouble has occurred.
The TrueAlarm sensor has two automatic trouble indications:
• Dirty
• Excessively Dirty
A “Smoke Sensor Dirty” trouble condition is reported when the average value on an individual sensor reaches a set threshold value. At this time, the FACP is still compensating for environmental factors and is holding the set sensitivity level.
A “Smoke Sensor is Excessively Dirty” trouble condition is reported when the average value of an individual sensor reaches a slightly higher set threshold level. At this point, the FACP no longer compensates for environmental factors, and the sensitivity level drifts. Although an “Excessively Dirty” trouble is reported, the sensor continues to operate and reports an alarm condition when one is detected.
In addition to the two automatic trouble conditions, the FACPs have digital pseudo points that must be turned ON so that a TrueAlarm sensor that is close to being a dirty sensor reports as if it is “almost dirty”. This is useful when scheduling maintenance for dirty sensors, it provides a means of checking if other sensors are approaching a dirty state.
The following table shows appropriate action to take when certain trouble indications occur:
Table 15: TrueAlarm troubles and descriptions
Trouble Indication Description
Almost Dirty Using the front panel keys, it is possible for a technical representative to turn ON a digital pseudo
Dirty A “dirty” indication means that the sensor is holding its sensitivity level, schedule maintenance for
Excessively Dirty The “excessively dirty” indication means that the sensor is no longer compensating for dirt and
Self-Test Abnormal All FACP system sensors are automatically tested once every minute. When a sensor fails to report
Expired The FACP panel generates an Expired trouble to notify the user that a replacement sensor is
The panel automatically indicates when a sensor is outside the sensitivity calibration. If the sensor has an analog value below what is listed in the table, the sensor is within its sensitivity setting.
Type Almost Dirty Dirty Excessively Dirty Photo 115 120 135 To view the analog value of a sensor, refer to the operating instructions of the FACP.
point in the FACP so that an “almost dirty” sensor to reports a trouble. Although the “almost dirty” sensor is holding its sensitivity level, you can schedule maintenance for the sensor before the dirty sensor trouble occurs.
the sensor. Clean the sensor as required and, when necessary, call your local branch office for service.
dust. Because nuisance alarms are possible with this condition, clean or replace the sensors immediately. When necessary, call your local branch office for service.
properly to the FACP, a “Self-Test Abnormal” condition occurs. Because the sensor is not working properly, it must be replaced. Replace it, or call your local branch office for service.
required. To clear the trouble, install a new CORC with a valid date must, and perform a hardware reset of the FACP.
Table 16: Analog value of the sensor
page 41 574-709 Rev. AP
Page 44
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
6.3.13 Fire Alarm trouble and maintenance log
Date Time Event/Description Initials
Loading...