DO NOT INSTALL ANY SIMPLEX
DAMAGED. Upon unpacking your Simplex product, inspect the contents of the
carton for shipping damage. If damage is apparent, immediately file a claim with
the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any
internal adjustments or repairs. All repairs should be performed by a
representative or authorized agent of your local Simplex product supplier.
STATIC HAZARD - Static electricity can damage components. Handle as
follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep uninstalled component wrapped in anti-static
material at all times.
The 4090-9118 Relay IAM with T-Sense provides the 4100U FACP output control
of one Form-C contact set and input status from a T-Sense monitoring zone. The
Relay IAM with T-sense provides the 4100U FACP with the status/state of the
monitored zone. The 4 states that it can indicate are: OPEN, NORMAL,
LIMITED, and SHORT. The LIMITED state occurs when a normally-open
device, electrically located between the series resistor and the EOL resistor,
activates. The FACP can then annunciate the status of closed devices depending
on whether they are before or after the series resistor.
The IDNet channel provides the communication link between the Relay IAM with
T-Sense and 4100U FACP while powering the entire circuit.
The range of possible temperatures under which the 4090-9118 Relay IAM with TSense can function is between 32° F (0° C) and 120° F (49° C). This Relay IAM
operates normally under non-condensing humidity conditions up to 93% relative
humidity at 90° F (32° C).
Relay IAM with T-Sense installation consists of the following:
• Setting the address of the Relay IAM with T-Sense
• Making electrical connections to the Relay IAM with T-Sense
• Mechanically installing the Relay IAM with T-Sense
Mounting
Bracket
Installation Instructions
®
PRODUCT THAT APPEARS
Assembly
PID Label
T-Sense Input
Terminals
IDNet
Terminals
DIP Switch
(Under Re-sealable
Label)
Note: The LED flashes approximately once every three seconds to indicate
valid communications with the 4100U FACP.
Specifications and other information shown were current as of publication and are subject to change without notice.
Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license.
Note: The IDNet channel supports address codes 1 through 250.
Each Relay IAM with T-Sense has a unique address. The address of the Relay
IAM with T-Sense is set via an eight position dip switch (Figure 1). DIP switch
position 1 is the least significant bit (LSB) and position 8 is the most significant
bit (MSB). Set the address using Figure 2 as reference. Use a small screwdriver
or pen to set the switches. The device address for the Relay IAM with T-Sense
should be written on the re-sealable label; this information provides an aid in
troubleshooting the system.
Note: DIP switch in “1” position is “ON” while DIP switch in “0” position is “OFF”.
Configure the Relay IAM with T-Sense to the 4100U panel using the 4100U
Fire Alarm – Programmer’s Manual (574-849).
2
Page 3
Making Electrical Connections
to the Relay IAM with T-Sense
Terminal connections for the Relay IAM with T-Sense are illustrated
in Figure 3.
CAUTION: Do not loop wire under terminals. Break wire runs to
provide supervision.
733-886
(4.7K 1/2 W)
FROM
PREVIOUS
DEVICE
OR F.A.C.P
IF STYLE 4:
TO NEXT
DEVICE
(IF USED)
IF STYLE 6:
TO NEXT
DEVICE
OR F.A.C.P
IDNet +
IDNet -RB
IDNet +
IDNet -RB
733-984
(1.8K 1/2W)
SEE NOTES 1, 2, & 3
OPTIONAL
SHIELD
SEE NOTE 6
S
S
1
2
3
4
N.C.
5
COMMON
6
N.O.
7
8
NOT USED
Notes:
1. Maximum allowable run from FACP to farthest device is not to exceed 2,500 feet
(762 meters). Maximum total wire (including all T-Taps) from FACP is 10,000 feet
(3,048 meters). IDNet lines are 18 AWG (0.823 mm/squared) twisted pair (shield
recommended). When using shield, wire nut, splice, or solder the shield wires. Also
insulate shield from the electrical box.
2. The Relay IAM with T-Sense counts as a one-unit load.
3. IDNet wiring is supervised and Power-Limited. An IDNet circuit has a
communications power rating of 36.25 volts (maximum) at .5 A, 3333 Baud.
4. Contractor wiring to relay contacts is unsupervised. Wire to local code (14 AWG
[2.081 mm/squared] recommended with 12 AWG [3.309 mm/squared] maximum).
Relay contacts are rated for 2 A (1 A for inductive load), 30 VDC and .5 A (0.25 A
for inductive load), 120 VAC (non-power-limited). Inductive loads must be
suppressed with a suitable suppression device. If switching 120VAC, the power
source to the contacts should be externally fused by the user with a 1 Amp 250V
quick blow fuse, UL listed to Guide #JDYX – Littlefuse AGC1 or equivalent. For
power-limited operation, power must be provided from a power-limited auxiliary
power output from the FACP or from a power-limited output of a power supply
listed for fire protective signaling use. When both power-limited and non-powerlimited sources are present, use Type FPL, FPLR, or FPLP power-limited cable for
power-limited circuits. If the relay is used to control a fire safety function, it must be
wired within 3 feet (91.44 cm) of the control circuit. Provisions to conform to NEC
760 power-limited and non-power-limited wiring separation must be made in the
field wiring if non-power-limited wiring is used on the relay output.
5. If AC is used on relay terminals, you must add Label 526-831 to electrical box cover
to indicate high voltage, ground electrical box and bracket to safety ground, and
wire input circuit with twisted-shielded wire (shield connected to grounded bracket).
6. T-Sense input circuits are not to exceed 500 feet (152.4 meters). Only Normally
Open (N/O) dry contacts are allowed on the input circuits. T-Sense lines are 18
AWG (0.823 mm/squared) wire. T-Sense inputs are pulled up to 5 VDC by a 17.4 K
resistor, which can source up to 287 uA (supervised and power-limited). T-Sense
inputs may be tested using ¼ watt, 1% resistors as follows: 6.81 K (normal), 16.9 K
(open), 1.65 K (current-limited), & 845 Ohms (shorted).
7. Relay function is programmable.
Figure 3. Relay IAM with T-Sense Connections
SEE
NOTES
4, 5 & 7
3
Page 4
Mechanically Installing the
Relay IAM with T-Sense
Cover
(Not Supplied)
Install the Relay IAM with T-Sense into a grounded, 4-inch (10.16 cm)
UL-Listed back box (not supplied) using Figure 4 as a reference. Mount the
Relay IAM with T-Sense to the back box as follows:
1. Loosen the two screws on the square back box.
2. Mount the Relay IAM with T-Sense to the back box using the teardrop holes on
the mounting bracket.
3. Secure the Relay IAM with T-Sense to the back box using the two #8/32
panhead screws.
#8/32 Panhead Screw
(Not Supplied)
UL-Listed
4-Inch (10.16 cm)
Square
(2-Inch [5.08 cm]
Deep)
Back Box
(Not Supplied)
#6/32 Flathead Screw
(Not Supplied)
4090-9118
Relay IAM with T-Sense
Note: Simplex offers semi-flush and surface covers (ordered separately) with
a light pipe. The cover(s) with light pipe allow viewing of the
communications LED without taking the cover off. Installation of the
4090-9801 semi-flush cover and 4090-9802 surface cov e r are detailed
in publication 4090 IDNet
Bracket Installation Instruction (574-796).
™
Semi-Flush/Surface Covers and IAM
Figure 4. Relay IAM with T-Sense Back Box Installation
574-874
Rev. C
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.