Simplex 4090-9006, 4090-9005 Application And Installation Manual

4090-9005, -9006
Rev. N
4010
- SRP is compatible with 4010 IDNet and NACs
- Master software is at revision 4.01* or higher
- SFIO software is at revision 4.01* or higher
4009
- SRP is compatible with 4009 IDNet and NACs
4100U
- SRP is compatible with 4100 IDNet and NACs on the following: SPS,RPS, XPS and XNAC (not XSIG)
- Master software is at revision 11.11* or higher SPS is at revision 3.07* or higher
- IDNET and IDNET+ are at revision 3.07* or higher
4007ES and 4007ES Hybrid
- Software Revision 3.03 or higher
4010ES
- All revisions
- SRP is compatible with IDNet or IDNet2 and MSS(I) or ESS
4100ES
- All revisions
- SRP is compatible with IDNet or IDNet2 and SPS, or EPS, or RPS, or XPS, or XNAC (all software revisions).
- SRP is not compatible with XSIG
* These revisions incorporate the capability to interpret the additional line condition, which is the
16.2 k supervisory resistor.
Cautions and Warnings
Important Compatibility Information
Introduction
Suppression Release Peripheral
Application and Installation Instructions
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this
installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD. Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or authorized agent of your local Simplex product supplier.
STATIC HAZARD. Static electricity can damage components. Handle as follows:
Ground yourself before opening or installing components. Prior to installation, keep components wrapped in anti-static material at all times.
When the Suppression Release Peripheral (SRP) is used for field replacement, no action is necessary. In a new installation, the software limitations in Table 1 must be adhered to. This is because revision E and earlier SRPs sensed only normal (10 k EOL) and trouble (open-circuit) conditions, and revision F and later SRPs sense normal (10 k EOL), trouble (open-circuits), and supervisory (16.2 k disconnect switch) conditions. When adding a SRP to an existing (pre-revision F) installation, it is necessary to either upgrade the software or clip the 16.2 k resistor from the maintenance switches
Table 1. SRP Compatibility Information
This publication describes the installation procedure for the 4090-9005 and 4090-9006 SRP. The SRP controls the actuator that activates the suppression release systems (such as CO2 or INERGEN), single or double interlock preaction sprinkler systems, and deluge sprinkler systems.
With the SRP, you can upgrade the FACP to enable it to become an agent release system, see Figure 1. Appropriate software is required.
2008-2017 Tyco Fire Protection Products. All rights reserved.
Specifications and other information shown were current as of publication and are subject to change without notice. TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
Continued on next page
Suppression Release Peripheral Application and Installation Instructions
2
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000
0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240
1000
1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241
0100
2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242
1100
3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243
0010
4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244
1010
5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245
0110
6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
1110
7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247
0001
8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
1001
9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249
0101
10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
1101
11 27 43 59 75 91 107 123 139 155 171 187 203 219 235
0011
12 28 44 60 76 92 108 124 140 156 172 188 204 220 236
1011
13 29 45 61 77 93 109 125 141 157 173 189 205 221 237
0111
14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239
LSB
MSB
1 2 3 4 5 6 7 8
1111
DIP SWITCHES 5 THRU 8
ON
OFF
1 = ON 0 = OFF
251 252 253 254 255
DIPSWITCH IS SHOWN SET AT ADDRESS 7.
Introduction
Setting the SRP Address
ADDRESS SWITCH
(SW1)
BRACKET
ASSEMBLY
SUPPRESSION
RELEASE MODULE
RAC OUTPUT
(TB2)
NAC INPUT
(TB1)
LED HARNESS
PLUG (P1)
IDNet INPUT
(TB3)
Figure 1. Suppression Release Peripheral
Note: The IDNet channel supports address codes 1 through 250.
Each SRP has a unique address. The address of the SRP is set with an eight position dip switch (Figure 1), DIP switch position 1 is the least significant bit (LSB) and position 8 is the most significant bit (MSB). Set the address using Figure 2 as reference. Use a small screwdriver or pen to set the switches. Write the device address for the SRP on the re ­sealable label, this information aids in troubleshooting the system.
Note: DIP switch in 1 position is ON while DIP switch in 0 position is OFF.
FigureTag FD9-385-01
Figure 2. Suppression Release Peripheral Address Chart
Suppression Release Peripheral Application and Installation Instructions
3
Mounting the SRP
2975-9227 RED ENCLOSURE BOX
4090-9005, -9006 SUPPRESSION RELEASE PERIPHERAL & MOUNTING BRACKET ASSEMBLY
NUTS QTY: 4
(SUPPLIED with ENCLOSURE)
MOUNTING STUDS (4) FOR SRP MOUNTING
Refer to the 2975-9227 enclosure installation instructions (579-403) for mounting the enclosure box.
Follow the directions below to mount the 4090-9005 and 4090-9006 SRP to a 2975-9227 Enclosure (See Figure 3).
Note: The 4090-9006 ULC-listed SRP is shipped with the peripheral already mounted to the
1. Secure the SRP with bracket assembly to the four enclosure, threaded mounting studs
2. The SRP has an optional communications LED option kit (4090-9812) that mounts to
3. Perform all SRP field wiring and optional LED wiring using the wiring information in
4. Secure the cover to the enclosure box by tightening the captive flat head screw on the
enclosure, skip step 1 for the 4090-9006. The 4090-9005 SRP mounting orientation must be with the NAC and IDNet terminals on the
left as illustrated in the figure below.
using the four supplied nuts (do not over tighten).
the cover. If using the LED option kit, remove the plastic snap-in plug on the enclosure box cover. The LED snaps into the hole on the sheet metal cover. Connect the LED harness to connector P1 on the SRP and ensure red goes on top.
Tables 2 and 3. Use Figure 4 and Figure 5 as a reference.
cover (do not over tighten).
Figure 3. SRP 2975-9227 Enclosure Mounting
Loading...
+ 7 hidden pages