All specifications and other information shown were current as of publication, and are subject to change without notice.
FA4-31-401 (574-062)
Ed695
www.BevanSecurity.Com
+m-
www.BevanSecurity.Com
B
CAUTION
ELECTRICAL HAZARD
Disconnect electrical power when making any internal
adjustments or repairs. Installation and servicing
should be performed by qualified Simplex Representatives.
CAUTION
POWERING REQUIREMENT
When removing power from this system, disconnect
batteries FIRST and AC power last. When connecting
power to this system, connect AC power FIRST and
batteries last.
I
CAUTION
Improper programming of this system can
result in improper system operation. Carefully
test the system after programming is
completed.
I
This equipment generates, uses, and can radiate radio
frequency energy and if not installed and used in
accordance with the instructions manual, may cause
interference to radio communications. It has been
tested and found to comply with the limits for a Class A
computing device pursuant to Subpart J of Part 15 of
FCC Rules, which are designed to provide reasonable
protection against such interference when operated in
a commercial environment.
Walk Test’” by Group
Zone Coding Option
Silent Walk Test’”
Entering Walk Test’” Mode
Walk Test’” Operation
Walk Test’” Features
Abort Audible and Delay On Reactivation
Active/Not Active
Auto Abort
Auto Abort On Time-out
Control List ........................................................................................................................................................
Delay Before Reset ...........................................................................................................................................
Zone Code/Zero Code ......................................................................................................................................
Walk Test’” Procedures ............................................................................................................................................
How to Enter a Walk Test’” Passcode
How to Enter Walk Test’” Mode
How to Exit Walk Test’” Mode ............................................................................................................................
How to
How to Turn a Point ON ....................................................................................................................................
How to Return a Point to Auto ...........................................................................................................................
How to Enable a Disabled Point
What to Do in Case of System Malfunction
Viewing a List
Viewing the Status of Any System Point
Controlling System
Viewing the Sensitivity
Logging and Clearing
Viewing the Historical Alarm
Clearing the Historical
Viewing Abnormal
Clearing the Alarm Verification Tally.
Viewing Power Supply/Charger Voltage and
Generating TrueAlarm”
Figure
1
Interface Panel
2
Interface Panel Showing Fire Alarm Condition
Interface
3
4
Interface Panel Showing System Supervisory Condition
CRT Main Menu Screen
5
CRT Acknowledge
6
7
CRT Log In Screen
CRT Alarm
8
9
CRT Status Screen
40-Character
10
80-Character Line Width Printout
11
12
Typical TrueAlarm” Status Report Screen
Typical TrueAlarm”
The Simplex 4020 is a microprocessor-based Fire Alarm System.
It is UL-listed, power-limited, electrically-
supervised, and protected against loss of primary AC power and brown-out conditions.
The standard 4020 can control up to 127 MAPNET II@ points. Depending on options, the 4020 can control a
maximum of 254 addressable points. Since all points in a system may not be addressable, the 4020 also offers up
to 20 hardwired points (with 4 points standard) that can be used to interface with detector zones, bell or horn circuits,
and auxiliary relay control. Each hardwired point is individually configurable as either a monitor point, a signal circuit,
or as an auxiliary relay output, with up to 8 different points on a single card.
The 4020 offers a variety of ways to provide remote annunciation. It can communicate with the LCD annunciator,
the SCWRCU, or the graphic SCWRCU. The RS-232 interface can be used to output to a printer or CRT.
An alphanumeric display on the 4020 Operator Interface Panel (Figure 1) indicates the condition of the system. The
alphanumeric display shows various prompts and labels which guide the user through a sequenced operation for
each abnormal condition. Audible and visual indications are provided to indicate abnormal conditions when they
exist within the system.
The 4020 capacities are as follows:
l
Up to two MAPNET II@ channels with up to 127 addressable devices each for a total of 254 addressable
devices
l
Up to 20 hardwired points, configurable as monitor, signal, or auxiliary relay points
l
An RS-232 interface
l
Up to 31 remote annunciator locations, which can accommodate SCWRCU, graphic SCU/RCU, and LCD
annunciators
l
An 8-Amp switching power supply, with a battery charger capable of charging batteries with up to 50 Ah
capacity.
The default hardware for a 4020 includes a master controller with a display, master trouble points, city circuit, and
tone-alert. The standard slave module uses three card addresses. “Card (address) 1 W functions like an 8-point multifunction I/O card, but only the first 4 points are available. “Card 2” is the power supply card. “Card 3” is the built-in
MAPNET@ channel.
The following optional hardware is allowed:
l
An additional MAPNET II@ card
l
Two eight-point multifunctional I/O cards
l
An RS-232 interface card configured with two isolated ports, with the ability for one port to be dedicated to
communications with a 2120 Multiplex System.
l
Serial annunciators including the LCD display, the SCWRCU, or the graphic SCWRCU
l
4120 Network Interface
l
25.5 Volt Limiter Module for Agent Release.
NOTE: This document covers operating procedures for a typical 4020 system. Applications will vary due to optional
hardware installed, custom programming, and local code requirements.
SYSTEM OPERATING DESCRIPTION
www.BevanSecurity.Com
The 4020 Operator Interface Panel, hereinafter called the interface panel, shows the following under normal
conditions:
l
Green “POWER ON” LED ON (indicating that AC power is applied)
l
All other interface panel indications OFF
l
Alphanumeric LCD display states that the system is normal, as shown below.
SYSTEM IS NORMAL
08:23:43
I
Abnormal conditions are indicated on the interface panel by flashing the alarm, supervisory, or trouble LED and
sounding the tone-alert. The alphanumeric display provides information as to the point status (alarm, supervisory,
and trouble), type of alarm (smoke detector, pull station etc.), number of abnormal conditions in the system, and a
custom label. Alarm, supervisory, and trouble conditions each have their respective acknowledge key. Pressing the
appropriate acknowledge key will silence the tone-alert. However, the LED indicating the abnormal condition
remains illuminated until all initiating devices are restored to normal.
MON 04-APR-94
I
If your system is configured with the CRT or printer option, point status is also displayed on these devices. The CRT
option controls various system functions. It can acknowledge system status changes, silence alarm signals, and
perform system reset procedures.
When an initiating device (monitor point) senses a Fire Alarm Condition (heat, smoke, manual activation, etc.),
notification appliances (signals) and the tone-alert sounds, and the FIRE ALARM LED turns ON and flashes,
indicating that a Fire Alarm condition is present. In addition, depending on the nature of the alarm condition, relays
trip, the city circuit activates, and various programmed events occur. The tone-alert continues sounding until the
alarm is acknowledged.
Figure 1
Interface Panel
(Access Door Closed)
2
When an initiating device senses a System Supervisory Condition (tamper valve off normal, generator status, etc.),
www.BevanSecurity.Com
programmed notification appliances and the tone-alert sounds, the SYSTEM SUPERVISORY LED on the interface
panel turns ON and flashes, the city circuit may be activated (if required by local codes), and various programmed
events occur. The tone-alert continues sounding until the condition is acknowledged or cleared.
When the 4020 senses a malfunction within the system (loss of power, hardware failure, etc.), a Trouble Condition
is announced by the interface panel. The tone-alert sounds steady, the SYSTEM TROUBLE LED flashes and
various programmed events occur. The tone-alert continues sounding until the condition is acknowledged or
cleared.
NOTE: When an operator interface panel key is referenced within this manual, it is normally shown between left
and right arrows. Examples are cACK> and <ALARM SILENCE>.
All abnormal conditions must be acknowledged by pressing the cACK> key under the appropriate flashing LED.
Notification appliances are silenced by pressing the <ALARM SILENCE> key.
NOTE: When you press the <ALARM SILENCE> key, the ALARM SILENCED LED turns ON steady.
Depressing the <SYSTEM RESET> key restores the system to the normal operating mode if Fire Alarm Conditions
have been acknowledged and restored. Depressing the <PRIORITY 2 ALARM RESET> key on the CONTROL Key
Panel restores the system to normal operation if Priority 2 Alarm Conditions have been acknowledged and restored.
(All keys on the CONTROL Key Panel must be programmed for function.)
The tone-alert may be programmed to sound at specified time intervals to serve as a reminder that a trouble still
exists within the system (System Trouble Reminder).
The system has “re-sound” capability. If, after silencing the signals, the system detects another abnormal condition,
the zone with the abnormal condition is indicated on the interface panel alphanumeric display, the appropriate
indicator again flashes, and the signals again sound.
To provide maximum efficiency in performing primary fire alarm functions, an interface panel access door, shown in
Figure 1, covers all keys except those required for indication and interaction for emergency situations. (The access
door must be opened to reset Priority 2 Alarm Conditions.)
LOG IN PROCEDURE
NOTE: Various functions may be passcode protected to prevent access by unauthorized personnel. Passcodes
are provided to the user during system installation. To change or receive additional information concerning
your passcodes, contact your local Simplex Branch Office.
To Log In, perform the following procedure.
1. Obtain the appropriate passcode information.
2. Open the interface panel access door.
3. Press the <MENU> key on the Display/Action keypad on the right side of the interface panel. The
alphanumeric display shows the following message.
Press <NEXT> or <PREVIOUS> to scroll
Change Access Level?
I
4. Press the <ENTER> key on the Display/Action keypad. The following message is displayed.
Fl=Login F2=Logout
CURRENT ACCESS LEVEL = 1
I
5. Press the <Fl> key (above the alphanumeric display). The display shows the following message.
www.BevanSecurity.Com
Enter a Passcode followed by <ENTER>
I
6. Enter the passcode (up to 10 numbers). Press the <ENTER> key on the ENTRY keypad. For security
reasons, an “X” is displayed for each digit of your passcode, as shown below.
Enter a Passcode followed by <ENTER>
xxx
I
If the passcode is correct, the following message is shown.
Enter a Passcode followed by <ENTER>
ACCESS GRANTED
I
After a brief pause, the display shows the granted access level, such as the level 2 access message shown
below.
Fl=Login F2=Logout
CURRENT ACCESS LEVEL = 2
I
7. Press the <CLR> key twice. The display shows system status, as shown below.
SYSTEM IS NORMAL
08:24:44 MON 04-APR-94
LOG OUT PROCEDURE
IMPORTANT
FAILURE TO LOG OUT ALLOWS UNAUTHORIZED PERSONNEL ACCESS TO THE VARIOUS
PASSCODE PROTECTED FUNCTIONS. IF NO KEYPAD ACTIVITY IS DETECTED FOR TEN MINUTES,
THE SYSTEM WILL RETURN TO LEVEL 1 ACCESS.
I
Perform the following procedure to Log Out and return the operator access level to LEVEL 1 status.
1. Press the <MENU> key. The following message is displayed.
www.BevanSecurity.Com
Press <NEXT> or <PREVIOUS> to scroll
Change Access Level?
2. Press the <ENTER> key. The following message is displayed.
Fl=Login F2=Logout
CURRENT ACCESS LEVEL = 2
I
3. Press the cF2> key. After a brief pause, the display shows a message similar to the one below.
Fl=Login F2=Logout
ACCESS LEVEL REDUCED TO LEVEL 1
I
4. Press the cCLR> key to exit. The display will show a message similar to one of the following messages.
I
I
SYSTEM IS NORMAL
9:27:40 MON 04-APR-94
**TROUBLE** Press <ACK>
FIRE = 0 PR12 = 0 SUPV = 0
I
HANDLING ABNORMAL CONDITIONS
When an abnormal condition occurs, at least one of the interface panel LEDs (FIRE ALARM, PRIORITY 2 ALARM,
SYSTEM SUPERVISORY, or SYSTEM TROUBLE) flashes, and the tone-alert sounds. The alphanumeric display
on the interface panel shows the total number of abnormal conditions present in the system. At a glance, you know
how serious the situation is by reading the number of abnormal conditions displayed, such as the single alarm
- condition shown below.
**FIRE**
FIRE = 1 PR12 = 0 SUPV = 0
I
Press <ACK> to review.
TRBL = 0
I
The system also creates a “List” when abnormal conditions exist. The list contains the number of abnormal
conditions present in the system. The cACK> keys are pushed to view the abnormal condition list, and review each
condition, if required.
When an Alarm Condition is detected by the system, the appropriate ALARM LED flashes and the tone-alert pulses.
For supervisory and trouble conditions, the appropriate interface panel LED flashes, and the tone-alert sounds
steady.
Pressing the appropriate cACK> key (under the flashing LED) displays the first acknowledged condition in the
www.BevanSecurity.Com
appropriate list. Note that the cACK> function may be passcode protected. If you have insufficient privilege to
acknowledge the condition, a message will indicate the problem, and will allow you to view the points without
acknowledging them. If you have sufficient privilege to acknowledge the condition, a message is displayed informing
you that the condition has been acknowledged. (See Operator Access Levels, Section 8, and Log In Procedure,
Section 1, for details.)
The 4020 system can be configured with either Global or Individual Acknowledge. When Global Acknowledge is
used in the system, one press of an <ACK> key globally acknowledges every abnormal point in the system in that
category. If all the points are acknowledged in this manner, an appropriate message is displayed. When Global
Acknowledge is used in a system, and the supervisory service or trouble conditions clears, the abnormal condition
automatically clears. Alarm conditions must be acknowledged. If Individual Acknowledge is used in the system, the
appropriate <ACK> key must be pressed for each condition change.
Note that the acknowledge function imposes a delay of at least one second between point acknowledgments. This
minimum delay allows you to view the information displayed on the alphanumeric display for each point that is being
acknowledged by the cACK> key.
When a point is acknowledged, the interface panel status LED glows steady, and the tone-alert silences. The total
number of alarm, supervisory, and trouble conditions show on the alphanumeric display along with a prompt to press
the cACK> key for point review. Pressing the cACK> key scrolls through the selected list in chronological order.
Each list is different and contains information concerning a particular abnormal condition.
After 30 seconds of keypad inactivity, the total number of abnormal conditions is again shown on the alphanumeric
display. Pressing the cACK> key selects a list for review. The first point to be displayed is either the first
acknowledged point in the list, or the first point in the list if all are acknowledged.
Alarm, supervisory, and trouble lists are displayed in chronological order. A message will indicate when the end of
a list has been reached.
The last message contains the total number of abnormal conditions, such as the single alarm message shown
below.
**FIRE**
FIRE = 1 PRIZ = 0 SUPV = 0 TRBL = 0
I
The <DISPLAY TIME> Key
The <DISPLAY TIME> key is used to view the time of day when the abnormal condition occurred. By viewing the
time for each abnormal condition occurrence, fire department personnel can determine the path and possible cause
for each abnormal condition.
Note that the <DISPLAY TIME> key only displays time for existing abnormal conditions.
Using the <DISPLAY TIME* Key
The red <DISPLAY TIME> key works for any point currently in an alarm, supervisory, or trouble condition. The alarm
list information is obtained from the historical log and is shown on the alphanumeric display, in order of occurrence.
In situations where multiple conditions are present, you can simply push one key to review the time that each
abnormal condition occurred. An example of an alarm condition is shown below.
Press <ACK> to review.
REVERE BUILDING 3RD FLOOR
SMOKE DETECTOR FIRE ALARM
I
I
If the <DISPLAY TIME> key is pressed and held down, the display shows the alarm list information as shown below.
www.BevanSecurity.Com
This information is only displayed while the <DISPLAY TIME> key is held down.
REVERE BUILDING 3RD FLOOR
FIRE ALARM AT: 19:56:32
I
When the <DISPLAY TIME> key is released, the display reverts back to its original label and status.
To display alarm list information, perform the following steps.
1. Ensure that the point to be checked is shown on the alphanumeric display by pressing the appropriate
cACK> key.
2. Press and hold in the <DISPLAY TIME> key. Information concerning the abnormal condition (alarm,
supervisory or trouble) is displayed.
NOTE: If the point is not found in the log due to log overflow, the message “NO TIME FOUND IN LOG”
, displays.
3. Press the appropriate cACK> key to display the next condition change.
4. Repeat steps 2 and 3 above, as required.
MON 04-APR-94
I
NOTE: This key will not work for points directly entered into the system via the keypad (e.g., I/O Points, etc.).
www.BevanSecurity.Com
SECTION 2
www.BevanSecurity.Com
ALARM CONDITIONS
INTRODUCTION
CAUTION
FOLLOW LOCAL OPERATING PROCEDURES WHEN INVESTIGATING ALARM CONDITIONS.
NOTE: Refer to Figure 2 for locations of interface panel LEDs and Keys.
When an Alarm Condition is detected by the 4020, the condition is indicated by the following:
l
Red “FIRE ALARM” or “PRIORITY 2 ALARM” LED is flashing
l
Tone-alert is pulsing
l
LEDs on annunciators may illuminate
l
The alphanumeric display on the interface panel indicates an alarm condition, such as the Fire Alarm condition
shown below.
**FIRE**
FIRE = 1 PR12 = 0
I
Press <ACK> to review.
SUPV = 0
TRBL = 0
I
The interface panel has two red LEDs which are used to indicate alarm conditions. When a Fire Alarm condition or
a Priority 2 Alarm Condition occurs, the appropriate red LED flashes, the tone-alert pulses, and an alarm message
appears on the alphanumeric display. When the appropriate <ALARM ACK> key is pressed, the red LED stops
flashing and glows steady, and the tone-alert silences. When the <ALARM SILENCE> key is pressed, the system
signals are silenced. When the appropriate <SYSTEM RESET> key is pressed, the alarm condition clears and the
red ALARM LED turns off.
GLOBAL ACKNOWLEDGE PANEL OPERATION DURING ALARM CONDITIONS
/ ALPHANUMERIC DISPLAY
J
/ ALARM SILENCED LED
, SYSTEM RESET KEY
RED ALARM LED (FLASHING)
ALARM ACKNOWLEDGE KEY
‘*FIRE** Press <ACb to review.
I
I
--% 0
FIRE z 1 PRl2 I 0 SUPV : 0
FlRE PRIORITY 2
ALARM ALARM SUPERVISORY TROUBLE SILENCED
TRBL I 0
-ON-
Interface Panel Showing Fire Alarm Condition
I ALARM SILENCE KEY
Figure 2
A GLOBAL ACKNOWLEDGE of an Alarm Condition is accomplished in the following manner.
www.BevanSecurity.Com
1. Unlock and open the enclosure door. Read the alphanumeric display on the interface panel. It reports the
number and type of alarm conditions, as shown below.
**FIRE**
FIRE = 1
I
2. Press the <ALARM ACK> key under the flashing red LED. The following items should occur:
a. The tone-alert silences and the display shows pertinent report information, such as shown below.
FIRST FLOOR EAST WING ROOM 31
PULL STATION FIRE ALARM
I
b. The ALARM LED changes from flashing to steady ON, and all alarm conditions are acknowledged.
c. Pressing the cACK> key scrolls through all alarms in chronological order.
HOW TO SILENCE THE ALARM SIGNALS
+
Press the <ALARM SILENCE> key and read the display. The alphanumeric display will show signal status (as
shown below), and the ALARM SILENCED LED turns ON steady.
PR12 = 0
Press <ACK> to review.
SUPV = 0 TRBL = 0
I
I
ALARM SILENCE IN PROGRESS...
I
HOW TO RESET THE SYSTEM
When the alarm condition has been cleared, restore or replace all affected devices (pull stations, smoke detectors
etc.) in accordance with the instructions provided with each device.
Since the system reset procedure for a Fire Alarm Condition differs from the system reset procedure for a Priority 2
Alarm Condition, the system reset procedure you use will depend on the nature of the alarm condition. Use one of
the following procedures to reset the system:
l
To reset a FIRE ALARM Condition: Press the <SYSTEM RESET> key.
l
To reset a PRIORITY 2 ALARM Condition: Open the interface panel door and press the <PRIORITY 2
ALARM RESET> key on the CONTROL panel. Then, after the ALARM LED flashes and the tone-alert pulses,
press the <ALARM ACK> key twice. (After a delay, the system returns to normal and the display reads:)
SYSTEM IS NORMAL
8:23:55 MON 04-APR-94
I
INDIVIDUAL ACKNOWLEDGE PANEL OPERATION DURING ALARM CONDITIONS
www.BevanSecurity.Com
An INDIVIDUAL ACKNOWLEDGE of an Alarm Condition is accomplished in the following manner.
1. Unlock and open the enclosure door. The alphanumeric display on the interface panel reports the number,
and type of alarm conditions, as shown below.
**FIRE**
FIRE = 1 PR12 = 0 SUPV = 0
2. Press the <ALARM ACK> key. Read and follow the instructions on the alphanumeric display. Pertinent
report data is given as shown below.
Press <ACK> to review.
TRBL = 0
FIRST FLOOR EAST WING
Press ACK key to acknowledge ALARM
PULL STATION
3. Press <ALARM ACK> key again. Readthe report data. Repeat this procedure to review all reports. Reports
are displayed in chronological order. Note that the following items have occurred:
a. Tone-alert is silenced
b. ALARM LED is ON, but is no longer flashing.
HOW TO SILENCE THE ALARM SIGNALS
Press the <ALARM SILENCE> key and read the display. The alphanumeric display will show signal status (as
shown below), and the ALARM SILENCED LED turns ON steady.
,FIRE ALARM
ALARM SILENCE IN PROGRESS...
I
HOW TO RESET THE SYSTEM
When the alarm condition has been cleared, restore or replace all affected devices (pull stations, smoke detectors,
etc.) in accordance with the instructions provided with each device. Then do the following:
l
To reset a FIRE ALARM Condition: Press the <SYSTEM RESET> key.
l
To reset a PRIORITY 2 ALARM Condition: Open the interface panel door and press the <PRIORITY 2
ALARM RESET> key on the CONTROL panel. Then, after the ALARM LED flashes and the tone-alert pulses,
press the <ALARM ACK> key twice. (After a delay, the system returns to normal and the display reads:)
I
SYSTEM IS NORMAL
8:27:34
MON 04-APR-94
ESSENTIAL ALARM CONDITION KEYS
www.BevanSecurity.Com
The essential keys for alarm conditions are the <ALARM ACK> (Alarm Acknowledge), <ALARM SILENCE>, and the
<SYSTEM RESET> keys. The remaining keys are concealed by the interface panel access door and are associated
with advanced system functions. (See Section 8, Advanced Functions.)
ALARM ACKNOWLEDGE KEYS
The <ALARM ACK> keys are located directly under the FIRE ALARM LED and the PRIORITY 2 ALARM LED.
Pressing the <ALARM ACK> key (twice for Individual Acknowledge or once for Global Acknowledge) causes the
ALARM LED to change from flashing to steady ON and silences the tone-alert. Pressing the <ALARM ACK> key
does the following:
l
Selects the next unacknowledged alarm point in the list for display (Individual Acknowledge)
l
Acknowledges the displayed point or acknowledges all points on the list (Global Acknowledge)
l
Scrolls the points chronologically after all points have been acknowledged.
If the <ALARM ACK> key is passcode protected, you cannot use this key to acknowledge alarms unless you have
the required access level. (See Operator Access Levels, Section 8, and Log In Procedure, Section 1.)
There are two types of acknowledges for the 4020 system: Global Acknowledge and Individual Acknowledge. Each
acknowledge type operates with the System Alarm Condition in the following manner.
l
Global Acknowledge - When Global Acknowledge is used on the 4020 system, a single key press of the
<ALARM ACK> key acknowledges all alarm status changes in the system. If status change information is
required, you may review this data by pressing the <ALARM ACK> key and reading the alphanumeric display.
l
Individual Acknowledge (For NFPA 72 Proprietary Receiver Requirements) - If an alarm condition has
been acknowledged with the <ALARM ACK> key and further unacknowledged conditions remain in the
system, the tone-alert continues sounding and the next status change shows on the alphanumeric display.
This process repeats until all changes are acknowledged. When this occurs, the tone-alert silences, and the
highest priority acknowledge change appears on the display.
ALARM SILENCE KEY
CAUTION
PRESSING THE ALARM SILENCE KEY CAUSES FIRE ALARM EVACUATION SIGNALS TO TURN
OFF: FOLLOW LOCAL PROCEDURES TO SILENCE ALARM EVACUATION SIGNALS.
When an alarm condition exists, various signals, auxiliary relays, the city connection, and the tone-alert may activate
(depending on the type of alarm condition, the system configuration, and the stage of the alarm condition). The
<ALARM SILENCE> key, when pressed, turns OFF all circuits programmed to follow the Alarm Silence key. The
<ALARM SILENCE> key press will:
l
Turn OFF signal circuits
l
Turn ON the ALARM SILENCED LED
l
Display a message, such as the one shown below.
ALARM SILENCE IN PROGRESS...
Alarm Silence Software Considerations
www.BevanSecurity.Com
The following software functions affect ALARM SILENCE operation.
l
If a Coded Input Device is activated, the <ALARM SILENCE> key press may be ignored until this function
has completed coding. Notification appliances cannot be silenced when a coded station is in alarm. However,
the flashing LED will change from flashing ON to steady ON when the <ALARM ACK> key is pushed. The
notification appliances silence automatically upon coding completion.
l
If the Alarm Silence Inhibit Function is activated but not completed, the <ALARM SILENCE> key press is
ignored. The message, “ALARM SILENCE INHIBITED”, displays for a short time to indicate the action was not
taken. The message “ALARM SILENCE NO LONGER INHIBITED” displays when the inhibit function times
out. If selected, the alarm silence inhibit may be programmed from 1 to 99 minutes. When selected, signals
cannot be silenced until the programmed time has elapsed.’
l
If Waterflow/Sprinkler Devices are activated, notification appliances may or may not be silenced (depending
on local code requirements). Usually, a dedicated bell will continue to sound to indicate water flow.
l
Some visual notification appliances may continue to flash until the system is reset.
SYSTEM RESET KEY
The <SYSTEM RESET> key is used to return the system to its normal state after a Fire Alarm Condition has been
cleared. When the <SYSTEM RESET> key is pushed, it causes any latched circuits to reset automatically. Also reset
are initiating devices, relays (including the city relay), notification appliances, and all LEDs and indicators which are
programmed to reset with the <SYSTEM RESET> key. The message, “SYSTEM RESET IN PROGRESS”, displays
when the <SYSTEM RESET> key is pressed. When the Fire Alarm Condition has reset, the FIRE ALARM LED
flashes, and the system requires that the <ALARM ACK> key be pressed.
When the <ALARM ACK> key is pressed, a message should be displayed that is similar to the one shown below.
SYSTEM IS NORMAL
8:37:13 MON 04-APR-94
If a zone stays in alarm during the reset period, the message “SYSTEM RESET IN PROGRESS” is followed by the
message shown below.
ALARM PRESENT, SYSTEM RESET ABORTED
I
When the “SYSTEM RESET ABORTED” message displays, the system remains in an alarm state. The display
indicates the total number of alarms present in the system along with a prompt to use the <ALARM ACK> key to
review the points. These points do not require acknowledgment. The ALARM LED remains ON to indicate that a
device is still in an alarm condition.
If the system does not reset, and the display still shows an alarm although no alarm condition exists, read the
alphanumeric display on the interface panel to determine the type of device and the location of the device in alarm.
Follow local procedures to investigate the area of the building with the alarm. Look for devices still in alarm (pull
stations, smoke detectors, etc.). Most devices latch until they are reset, either by the system or manually.
IF THE ALARM POINT DOES NOT RESET
If a device does not reset, you may choose to perform the Disable Procedure given in the following paragraphs.
13
HOW TO DISABLE A POINT
www.BevanSecurity.Com
CAUTION
DISABLING A POINT CAUSES THAT POINT TO NOT REPORT ALARM CONDITIONS OR OTHER
STATUS CHANGES. A POINT SHOULD NOT BE DISABLED UNLESS IT IS CLEARLY UNDERSTOOD
THAT FIRE DETECTION OR SECURITY FOR THE AREA OF THE BUILDING COVERED BY THAT
POINT WILL BE LOST. APPROPRIATE STEPS MUST BE TAKEN TO PROVIDE ALTERNATE MEANS
OF PROTECTION FOR THAT AREA OF THE BUILDING WHILE THE POINT IS DISABLED.
If a device does not reset, you may disconnect the device/point causing the alarm condition. However, this point
must first be identified. Press the <ALARM ACK> key, and read the alphanumeric display on the interface panel.
Then disable the identified alarm point with the <DISABLE> key. If the <DISABLE> key is passcode protected,
perform the Log In Procedure before performing the Disable Procedure.
The <DISABLE> key press removes power to any displayed monitor point. Thus, disabling a point causes a trouble
condition on the individual zone.
To disable a point, perform the following procedure.
1. Open the interface panel access door.
2. Press the <ACK> key until the point to be disabled is shown on the alphanumeric display, as shown below.
SECOND FLOOR EAST WING ROOM 16
PULL STATION
I
3. Press the <DISABLE> key. The alphanumeric display shows the following message.
Press <ENTER> to DISABLE
I/O:
I
NOTE: XX = the point to be disabled.
4. Press the CENTER> key. The alphanumeric display shows the action taken.
ACTION TAKEN
NOTE: The system indicates a trouble condition each time a point is disabled. Press the cTBL ACK> key
as required. To clear the alarm condition, follow System Reset Procedures.
IOXX
FIRE ALARM
I
5. Repeat steps 2 through 4 above to disable additional points.
REPAIR/REPLACE THE FAILED CIRCUIT/DEVICE AS SOON AS POSSIBLE. ONCE REPAIRED, THE
DISABLED POINT SHOULD BE ENABLED AS SOON AS POSSIBLE. (See Section 9, How to Enable a
Disabled Point.)
IMPORTANT
14
SECTION 3
www.BevanSecurity.Com
TROUBLE CONDITIONS
INTRODUCTION
NOTE: Refer to Figure 3 for locations of interface panel LEDs and keys.
When a System Trouble Condition is detected by the 4020, the condition is indicated by the following:
l
Yellow ‘SYSTEM TROUBLE” LED on the interface panel flashes
l
Tone-alert sounds steady
l
Annunciator LEDs may be illuminated
l
Alphanumeric display on the interface panel shows the following message.
**TROUBLE**
FIRE = 0 PRI2 = 0 SUPV = 0
Press <ACK> to review.
TRBL = 1
The interface panel has a yellow SYSTEM TROUBLE LED which lights whenever a trouble is present in the system.
When a trouble occurs, the LED flashes, the tone-alert sounds steady, and a trouble message appears on the
alphanumeric display. The trouble LED glows steady and the tone-alert silences when the cTBL ACK> key is
pressed.
When Global Acknowledge is used, and the trouble clears, the system automatically clears without user intervention.
After approximately 30 seconds, the system alphanumeric display should indicate a normal system, as shown
below.
SYSTEM IS NORMAL
8:32:45
When Individual Acknowledge is used, the tone-alert “re-sounds” when the condition clears. The cTBL ACK> key
must be pressed twice (once to change from Alarm Summary to actual point, and once to acknowledge the
condition). After a delay, the system alphanumeric display should indicate a normal system.
MON 04-APR-94
GLOBAL ACKNOWLEDGE PANEL OPERATION DURING TROUBLE CONDITIONS
, @j[Gg Ia] [-iq~][~]
“TROUBLE”
I
FIRE I 0 PR12 = 0 SUPV = 0 TRBL = 1
FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER
00 0
Press cACK> to review points.
%b.,o,,D ?it ALARM ALARM SUPERVISORYTROUB
AA/\&n
- ACKNOWLEDGE
Figure 3
Interface Panel Showing Trouble Condition
. /
4--
ALPHANUMERIC DISPLAY
YELLOW SYSTEM TROUBLE LED
(FLASHING)
ACKNOWLEDGE KEY
A GLOBAL ACKNOWLEDGE of a System Trouble Condition is accomplished in the following manner.
www.BevanSecurity.Com
1. Unlock and open the enclosure door. The alphanumeric display on the interface panel shows the trouble
condition:
**TROUBLE** Press <ACK> to review.
FIRE = 0
I
2. Press the cTBL ACK> Key under the flashing yellow LED. The alphanumeric display shows the area and
type of trouble. The tone-alert silences and the yellow LED glows steady.
FIRST FLOOR EAST WING ROOM 24
FIRE MONITOR ZONE OPEN CIRCUIT TROUBLE
I
3. Read the alphanumeric display. Then investigate the problem to determine its cause.
a. Restore or replace the defective device (switch, wire, notification appliance, etc.) in accordance with
device instructions, or call Simplex to repair the system.
b. The trouble automatically clears when the problem has been corrected.
PR12 = 0
SUPV = 0
TRBL = 1
I
c. After a delay, the alphanumeric display reads:
SYSTEM IS NORMAL
8:36:24 MON 04-APR-94
INDIVIDUAL ACKNOWLEDGE PANEL OPERATION DURING TROUBLE CONDITIONS
An INDIVIDUAL ACKNOWLEDGE of a System Trouble Condition is accomplished in the following manner.
1. Unlock and open the enclosure door. The alphanumeric display on the interface panel shows a trouble
condition, such as shown below.
**TROUBLE**
FIRE = 0
I
2. Press the <TBL ACK> key. Repeat this step and read the reports.
a. The tone-alert silences and the LED glows steady.
PR12 = 0
Press <ACK> to review.
SUPV = 0
TRBL = 1
I
b. The alphanumeric display shows the area and type of problem, as shown below.
FIRE MONITOR ZONE OPEN CIRCUIT TROUBLE
FIRST FLOOR EAST WING
Press ACK key to acknowledge
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.