Simplex 4010-9601, 4010-9602BA, 4010-9602, 4010-9701, 4010-9604 User Manual

...
Page 1
Fire Control Panels
UL, ULC, CSFM Listed; Addressable Fire Detection and Control FM, NYC Fire Dept Approved* Basic Panel Modules and Accessories
Features
Basic system includes:
Capacity for up to 250 addressable IDNet points, up to
127 VESDA Air Aspiration Systems interface points, and up to 254 addressable notification appliances with up to 2000 points of Annunciation; and up to 20 internal and external card addresses
includes 2 x 40 Super-twist LCD display, 3 programmable control keys and 6 programmable LEDs
CPU assembly includes dedicated compact flash memory
for on-site system information storage and convenient Ethernet service port access
Includes an Enhanced System Supply (ESS) that provides power and battery charging (6 A output):
Dual 3 A on-board IDNAC SLCs (signaling line circuit) IDNAC SLC provides a constant 29 VDC source voltage
during alarm, even during battery operation, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under primary and secondary power
Efficiencies include lower strobe currents, wiring
distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, ability to use smaller gauge wiring
IDNAC SLCs are compatible with both TrueAlert ES
and TrueAlert addressable notification appliances, and remote 4009 IDNAC Repeaters to extend power and wiring distance even farther and extends supervisory capacity by up to 139 additional unit loads or 3 A
Addressable point control is provided by on-board IDNet
2 dual loop SLCs that provide two electrically isolated
channels that support TrueAlarm analog sensors and IDNet communications monitoring and control points with an electrically isolated output channel allowing use with either shielded or unshielded, twisted or untwisted single pair wiring; and providing dual short circuit isolating output loops
Battery charger for up to 110 Ah batteries (UL) or up to
50 Ah batteries (ULC) (33 Ah max in control panel cabinet)
2 A programmable function auxiliary output Remote annunciator module support via RUI (Remote
Unit Interface) communications port, supports either Class B or Class A operation
48 LED panel mount annunciation provides 40 Red and 8
Yellow pluggable LEDs (select models, meets ULC requirements), optional LED kits are available to change individual LED color to Green or Blue to meet specific site requirements
Optional ESS mounted modules, door mounted modules, and other options include:
City Connect (with or without disconnect switches) Alarm Relay Module TrueInsight Remote Gateway Battery brackets for seismic area protection (see page 2)
S4010-0011-5 11/2015
1-Bay Cabinet
1-Bay Cabinet with
LED Annunciation
4010ES Panel Type Reference
Optional block space modules include:
Fire Alarm Physical Bridge and Network Interface Cards
for Peer-to-Peer fire alarm network communications, supports either Class B or Class X operation
Building Network Interface Module (BNIC), SafeLINC
Internet Interface, and BACpac Ethernet Portal
Dual Class A IDNAC Isolator (DCAI) Dual RS-232 Module (for printer, PC annunciator or third
party interface)
VESDA Air Aspiration High Level Interface Serial DACT 8 Zone IDC Modules Class A or B 4 Point Auxiliary Relay Module
Compatible with Simplex
®
remotely located:
4098-9757 QuickConnect2 and legacy 4098-9710
QuickConnect TrueAlarm smoke sensors
4003EC Small Voice Panels 4081 Series, 110 Ah Battery Chargers 4100-7400 Series Graphic Annunciators 4190 Series PC Annunciator, 4190 Series Fiber
Modems and Physical Bridges
4606-9102 Remote LCD Annunciator, 4100-9400
Series Remote InfoAlarm Command Centers, and 4602 Series Status Command Units (SCU) and Remote Command Units (RCU) Annunciators
IP communicator compatibility
* See page 6 for additional listing information. This product has been approved by the
California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0369 for allowable values and/or conditions concerning material presented in this document. NYC Fire Dept COA #6193. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Page 2
Features
4010ES Agency listings:
UL 864, Fire Detection and Control (UOJZ), and
Smoke Control Service (UUKL), and Releasing Service (SYZV)
UL 2017, Process Management Equipment (QVAX) UL 1076, Proprietary Alarm Units-Burglar (APOU) UL 1730, Smoke Detector Monitor (UULH) ULC S527-99, Fire Detection and Control (UOJZC) ULC S559-04, Supervising Station (DAYRC)
Introduction
4010ES Series Fire Detection and Control Panels
provide leading edge installation, operator, and service features for customer applications in the mid-range addressable fire alarm systems market. An on-board Ethernet port provides fast external system communications to expedite installation and service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files to meet NFPA 72 (National Fire Alarm and Signaling Code) requirements.
Modular design. A variety of functional modules are available to meet specific system requirements. Selections allow panels to be configured for either Stand-Alone or Networked fire control operation.
Mechanical Description
Mounting box provides convenient stud markers for
drywall thickness and nail-hole knockouts for quicker mounting
Smooth box surfaces are provided for locally cutting
conduit entrance holes exactly where required
The hinged User Interface panel easily opens for
internal access
Modules are power-limited (except as noted, such as
relay modules)
Doors include tempered glass inserts, boxes and doors
are available in platinum or red
Box and door/retainer assemblies are included with
Basic Panel assemblies
Cabinet assembly is rated NEMA 1 and IP 30 Cabinet assembly design has been seismic tested and
is certified to IBC and CBC standards as well as to ASCE 7 categories A through F, requires battery brackets as detailed on data sheet S2081-0019
Panel Hardware
4010ES Block Space Option Cards mount to the left
of the 4010ES ESS. There are 3 available 4” x 5” blocks for mounting 4010ES hardware options.
Other 4010ES Options: The 4010ES City Connect module or the optional Alarm Relay module mount directly to the ESS. These options are mutually exclusive.
Network Media modules mount directly to the 4010ES Network Interface Card.
The TrueInsight Remote Gateway mounts on the back side of the 4010ES User Interface Panel.
The Battery Compartment located in the bottom of the 4010ES cabinet accepts two batteries, up to 33 Ah, without interfering with expansion module space.
The illustrations at the bottom of this page identify mounting locations available for optional 4010ES modules. (refer to page 7 for additional information)
Software Feature Summary
TrueAlarm individual analog sensing with front panel
information and selection access
“Dirty” TrueAlarm sensor maintenance alerts, service
and status reports including “almost dirty”
TrueAlarm magnet test indication appears as distinct
“test abnormal” message on display when in test mode
TrueAlarm sensor peak value performance report “Install Mode” allows grouping of multiple troubles
for uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with future equipment and devices grouped into a single trouble, operators can more clearly identify events from the commissioned and occupied areas
Module level ground fault searching assists
installation and service by locating and isolating modules with grounded wiring
“Recurring Trouble Filtering” allows the panel to
recognize, process, and log recurring intermittent troubles (such as external wiring ground faults), but only sends a single outbound system trouble to avoid nuisance communications
WALKTEST silent or audible system test performs an
automatic self-resetting test cycle
4" x 5"
3 available 4" x 5"
block spaces for
additional option cards
2 S4010-0011-5 11/2015
Block A
4" x 5"
Block B
Mounting Locations for Optional Modules, One-Bay Cabinet
Enhanced System
Supply
4" x 5"
Block D
TrueInsight Remote Gateway mounts on the back of the 4010ES User Interface Panel
Page 3
Operator Interface Features
Convenient and extensive operator information is
provided using a logical, menu-driven display
Multiple automatic and manual diagnostics for
maintenance reduction
Convenient PC programmer label editing
Password access control
Alarm and Trouble History Logs (up to 2000 total
events) are available for viewing from the LCD, or capable of being printed to a connected printer, or downloaded to a service computer
ULC SYSTEMS
require designating a Ground Fault indicator
3 PROGRAMMABLE LEDs
two selectable as Red or Yellow, one selectable as Green or Yellow
Custom label insert
6 SYSTEM STATUS INDICATOR LEDs provide system status indications, LEDs flash to indicate a change in status and remain on-steady after acknowledged until reset
2 X 40 LCD READOUT, LCD is backlighted during normal conditions, provides up to 40 characters for custom label information
FIRST ALARM DISPLAY operation can be selected for maintained display of first alarm until acknowledged
Convenient Status Information. With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in the illustration below.
LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door provides access to the control switches and allows further inquiry by scrolling the display for additional detail.
The following illustration identifies the primary functions of the operator interface.
FIRE ALARM ACK acknowledges a Fire Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts
PRIORITY 2 ACK acknowledges a Priority 2 Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts
SUPV ACK acknowledges system supervisory conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts
TROUBLE ACK acknowledges system trouble conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts
ALARM SILENCE causes audible notification appliances to be silenced (depending on panel programming) typically after evacuation is complete and while alarm source is being investigated; may allow visible notification to continue (strobes still flashing)
SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal
Waterflow-East
Waterflow-West
Ground Fault
City Disconnect
Elevator Bypass
Ground Fault
Latch
3 PROGRAMMABLE FUNCTION SWITCHES
with yellow LED indicators
3 S4010-0011-5 11/2015
POINT STATUS CONTROL KEYS:
Point Enable and Disable Force On or Arm Force Off or Disarm Return On/Off or Arm/Disarm to Auto Mode
ADDITIONAL FUNCTION KEYS:
Event Time Request More Information Request Lamp Test
LCD NAVIGATION CONTROL:
Menu selection Vertical and Horizontal position selection buttons
NUMERIC KEYPAD for point category and point selection (alphabet characters are not used at this time)
Page 4
IDNet Addressable Device Control
Overview. The 4010ES with ESS provides dual IDNet
(IDNet 2) addressable initiating device Signaling Line Circuits (SLCs) that supervise wiring connections and the individual device communications status on the SLC. With 2-wire IDNet 2 SLCs, initiation, monitoring, and control devices such as manual fire alarm stations, TrueAlarm sensors, control relays, and sprinkler waterflow switches can communicate their identity and status and receive fire alarm system control. Additional addressable interface modules include circuit isolators, conventional IDC zone adapters, and interface to other system circuits such as fans, dampers, and elevator controls.
IDNet 2 Addressable Device Operation
Each addressable point on the IDNet communication
channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Both Class B and Class A operation is available. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuits for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications poll and can be turned on steady from the panel. With addressable devices, the location and status of the connected device is monitored, logged, and displayed on the operator interface LCD with each device having its own 40 character custom label for precise identification.
TrueAlarm Addressable Sensor Operation
Addressable initiating device communications
include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.
TrueAlarm Addressable Sensor Reference
TrueAlarm Photo
Sensor with Base
TrueAlarm Photo/Heat
Sensor in CO Base
Programmable sensitivity of each sensor can be selected at the control panel for different levels of smoke obscuration (shown directly in percent) or for specific heat detection levels. To evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read (or downloaded as a report) and compared to the alarm threshold directly in percent.
CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one system address. The CO sensor can be enabled/disabled, and can be used in LED/Switch modes and custom control. (refer to data sheet S4098-0052 for details)
TrueAlarm heat sensors can be selected for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also available, typically to provide freeze warnings or alert to HVAC system problems. Readings can selected as either Fahrenheit or Celsius.
TrueSense Early Fire Detection. Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 4010ES IDNet address. The panel evaluates smoke activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet S4098-0024.
Diagnostics and Default Device Type
Sensor Status. TrueAlarm operation allows the control
panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor. CO Sensors track their 10 year active life status providing indicators to assist with service planning. Indicators occur at: 1 year, 6 months, and end of life.
Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.
IDNet Device Wiring Reference
IDNet Addressable Channel Capacity. The ESS
provides dual electrically isolated IDNet 2 signaling line circuits (SLCs) that support up to 250 addressable monitor and control points intermixed on the same pair of wires. IDNet 2 SLCs are isolated from other system reference voltages to reduce common mode noise interaction with adjacent system wiring.
IDNet 2 SLC Wiring Specifications
Maximum Distance from Control Panel per Device Load
Total Wire Length Allowed With “T” Taps for Class B Wiring
Maximum Capacitance Between IDNet Channels
Loading per device
Wire Type and Connections
Connections
Compatibility includes: IDNet communicating devices and TrueAlarm sensors including QuickConnect and QuickConnect2 sensors; see data sheet S4090-0011 for additional reference
* Some applications may require shielded wiring. Review your
system with your local Simplex product supplier.
0 to 125 4000 ft (1219 m); 50 ohms
126-250 2500 feet (762 m); 35 ohms
Up to 12,500 ft (3.8 km);
0.60 µF
1 µF
0.8 mA supv., 1 mA alarm; 2 mA per activated device LED
Shielded or unshielded, twisted or untwisted wire*
Terminal blocks for 18 to 12 AWG
4 S4010-0011-5 11/2015
Page 5
IDNAC SLC Control of TrueAlert and TrueAlert ES Addressable Notification
Addressable notification appliance communications
include operation of TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible only (A/O, horn), Audible/Visible (A/V, horn/strobe), and strobes of Speaker/Visible (S/V) notification appliances. (S/V appliances require separate speaker wiring.) IDNAC SLC addressable communications allow each horn and strobe to be individually controlled using a single two-wire circuit, confirms the wiring connections to the individual notification appliance’s electronic circuit, and confirms communications between each appliance and the fire alarm control panel. Addressable communications increases supervision integrity versus conventional notification systems by providing supervision beyond the circuit wiring to each individual appliance and by constantly verifying the ability of each appliance to communicate with the control panel.
Individual Appliance Status and Settings. The fire alarm control panel monitors and records each addressable notification appliance status, type of appliance, and its configured appliance settings. A fault in any individual appliance automatically reports a trouble condition to the control panel.
TrueAlert ES Addressable Appliance Reference
A/O (horn) V/O (strobe) A/V (horn/strobe)
Virtual NACs Provide Control Convenience. For control convenience, IDNAC notification appliances can be grouped into Virtual NACS (VNACs) for group control, grouping that can be made across SLCs, not defined by their wiring connection.
Panel Control Convenience. Applicable operation settings for each appliance can be programmed without having to replace appliances or remove them from the wall or ceiling. An appliance’s VNAC notification zone can be easily changed through programming without having to add additional circuits, conduit, and wiring. Audible and visible appliances for non-Fire Emergency Communications notification can be programmed to operate separately on the same pair of wires as the fire alarm notification appliances. The result is lower installation, retrofit, and overall life-cycle cost of ownership compared with traditional conventional notification systems.
Installation, Retrofit, and Life-Cycle Cost Benefits. With each addressable appliance capable of being controlled separately on the same two-wire IDNAC SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T-tapped” allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency.
Location Information, Diagnostics and Troubleshooting. Each addressable notification appliance
has its own 40 character custom label to identify the location of the appliance and to aid in troubleshooting fault conditions. In conventional notification systems, conventional appliances are not capable of communicating with the control panel. Fault reporting on a conventional system is limited to the circuit wiring and the entire area (zone) covered by appliances on the notification appliance circuit (NAC) making it much more difficult and costly to locate and correct the source of a
5 S4010-0011-5 11/2015
problem. Using the TrueAlert magnet test allows each appliance to individually identify its candela setting and address and to briefly operate if desired, and using the TrueAlert ES
Appliance Self-Test feature provides detailed performance verification per appliance.
TrueAlert ES Appliance Self-Test Operation
On-Board Test Sensors. TrueAlert ES appliances are
equipped with on-board sensors to detect strobe and/or horn output allowing efficient and unobtrusive Self-Testing. When Automatic Self-Test is initiated from the control panel, each appliance within the selected VNAC group will briefly operate and then report its Self-Test status to the control panel, all within several seconds. Silent Self-Test can be selected to test only visible appliance if desired. The control panel is in a trouble condition during testing and in the event of an alarm, Self-Test is automatically terminated. Additionally, Automatic Self-Test can be scheduled to occur at a convenient time on a regular basis.
Automatic Self-Test results are communicated to the control panel with a time and date stamp and are stored in memory. Results are viewable at the front panel display and printed reports can be generated from the panel service port.
Individual Self-Test is selected from the control panel when individual appliances need to be observed to operate. Each appliance in the selected VNAC group will turn on its LED until individually activated by applying a magnet. After performing the individual test, the appliance LED turns off to indicate completion. Results are recorded the same as during the automatic test.
IDNAC SLC Hardware Reference
The Enhanced System Supply provides two, 3 A IDNAC
SLCs for control and power to TrueAlert ES and TrueAlert addressable notification appliances. Both power supplies incorporate an efficient switching design that provides a regulated output of 29 VDC, even during battery operation. With 29 VDC minimum output at the panel, addressable notification SLCs can support wiring distances 2 to 3 times farther than available with conventional notification, or support more appliances per SLC, or work with smaller gauge wiring, or combinations of these benefits. The result is installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.
IDNAC SLC Appliance Wiring Reference
IDNAC SLC Capacity: Up to 127 addresses and up to 139 unit
loads (appliances are typically one unit load, devices such as Isolators may require more than one load, refer to individual device data sheet for specific information)
Recommended Wire Type UTP, unshielded twisted pair
Maximum wire length allowed with “T-Taps” for Class B wiring, per SLC
Maximum wire length per SLC to any appliance
Appliance Supervisory Current
Wiring Connections
10,000 ft (3048 m)
4000 ft (1219 m)
1 unit load = 0.8 mA per appliance
Terminals for 20 to 12 AWG (0.52 mm
2
to 3.31 mm2)
Page 6
Master Controller (CPU)
The 4010ES Master Controller includes dedicated
2GB compact flash Mass Storage memory for on-site system information storage and convenient Ethernet service port access
Convenient front panel accessed Ethernet port for
quick and easy download of site-specific programming
AND, firmware enhancements are made via software
downloads to the on-board flash memory
Every downloaded job is automatically stored to
Compact flash without overwriting earlier versions providing a means for recovering previous configurations
Downtime is reduced because the system stays
running during download
Modifications can be uploaded as well as
downloaded for greater service flexibility
Mass Storage allows job specific files to be stored in
the control panel such as test and inspection reports, record drawings, specifications, and more...
Ethernet connectivity options include Building
Network Interface Module (BNIC) and SafeLINC Internet Interface
RUI (Remote Unit Interface) communications port
supports either Class B or Class A operation for remote annunciation equipment
Basic Panel Model Selection
Basic Panel Description
4010ES panels with ESS include:
An Operator Interface, Master Controller with 2 GB
Compact Flash, IDNet 2 dual loop communications that provides Class B or Class A operation for up to 250 addressable IDNet points, with dual short circuit isolating loop outputs, and 6 A Enhanced System Supply (ESS)
RUI Class B or Class A communications port for
remote annunciation devices
Support for up to 20 internal and external card
addresses
Other standard features may be provided depending
on model (see model selection below for additional details on specific models)
Cabinet and door
6 A Enhanced System Supply details:
Two, 3 A Class B IDNAC SLCs for up to 254
addressable notification appliances; Class A operation is available using the 4010-9930 Dual Class A IDNAC Isolator (DCAI) module
Up to 2 A of auxiliary power 110 Ah (UL)/50 Ah (ULC) battery charger (33 Ah
maximum in the control panel cabinet)
Low Battery Voltage Cutout is selectable when
required (required for ULC listing applications)
2 A for Regulated 24 DC operation; 1 programmable
auxiliary relay rated for 2 A @ 32 VDC
Model
4010-9601 Red
4010-9602(BA)* Platinum
4010-9603 Red
4010-9604 Platinum
* BA model is assembled in the USA.
Current Notes:
1. Basic panel current does not subtract from the 6 A output rating.
2. Supervisory and alarm current specifications are for determining battery standby requirements.
3. Current specifications include an active RUI channel.
4. IDNet channel device current is not included, refer to page 7 for details.
5. IDNAC channel notification appliance current is not included, calculate separately per connected devices.
Panel Color
Language & Voltage
English
120 VAC
English
120 VAC
Listings Features
Basic 1- Bay Panel with 2x40 LCD
Operator Interface, 6 A ESS/battery
UL,
CSFM,
FM
UL, ULC,
CSFM,
FM
charger, (1) Two-loop Isolated IDNet 2 Communications Channel, Class A or Class B, with support for up to 250 addressable IDNet points; and two, 3 A, Class B, IDNAC SLCs with support for 254 addressable notification appliances
Same features as above with 48 LED annunciation; alarm current includes 24 annunciator LEDs activated
Supv.
Current
(see notes below)
256 mA 390 mA
276 mA 455 mA
Alarm
Current
Available
Option Blocks
3
4“x5”
blocks
6 S4010-0011-5 11/2015
Page 7
Addressable Device Load Specifications for Battery Standby
Addressable Channel Loading Reference Device Load
IDNet 2 Communications Channel Output for every 50 Devices 40 mA
Supervisory
Current
Alarm Current
1 mA per device in alarm; 2 mA per activated device LED
IDNAC Communications Channel Output for every 50 Appliances 40 mA calculate per selected appliances
Block Space Option Card Selection
Note: Refer to diagram on page 2 for Option Module availability. Supervisory and Alarm current specifications are for determining
battery standby requirements.
Single Block Option Modules, Select Three (3) Maximum ifNo Dual Block Module is Selected; Select One (1) Maximum if a Dual Block Module or the Module Bracket is Selected
Model Features Option Block Usage
4010-9912
Serial DACT, includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs
4010-9908 4 Point Aux Relay Module 1 Block 15 mA 60 mA
Voltage Regulator Module, 22.8 to 26.4 VDC
4010-9916
(25 VDC nominal); isolated and resettable output; includes earth detection circuit and trouble relay for status monitoring
4010-9918 Dual RS-232 Module 1 Block 60 mA 60 mA
Dual Class A IDNAC Isolator (DCAI); converts a single Class B IDNAC SLC input to two Class A or two Class B SLC outputs; provides short circuit
4010-9930
isolation between each Class A or B output circuit; requires one IDNAC address; the total current remains controlled by the Class B input source SLC at 3 A maximum; select up to 2 per IDNAC SLC
4010-9915
BACpac Ethernet Portal Module; requires 4010-9918 RS-232 Module (no address required)
4010-9901 VESDA HLI 1 Block 60 mA 60 mA
Dual Vertical Block (Flat) Modules, Select One, or Two with 4010-9928 Bracket Kit (except for Media Cards)
Model Features Option Block Usage
Dual Vertical Block Card Mounting Kit, allows
4010-9928
selecting two, dual Vertical Block (flat) modules from the list below
4010-9922
Modular Network Interface Card (requires two media modules, see below)
4010-9818 Network Media Card Wired 4010-9819 Network Media Card Fiber Optic 25 mA 25 mA
4010-9914 Building Network Interface Card 2 Vertical Blocks 236 mA 236 mA
4010-9923* SafeLINC Internet Interface 2 Vertical Blocks 115 mA 115 mA
4010-9924* Modem Physical Bridge Class B
4010-9925* Modem Physical Bridge Class X 246 mA 246 mA
4010-9926** TCP/IP Physical Bridge Class B
4010-9927** TCP/IP Physical Bridge Class X 236 mA 236 mA
Dual Vertical Block (Slot) Modules, Select One if no Dual Vertical (Flat) Modules from Above are Selected
Model Features Option Block Usage
4010-9920 8 Zone Initiating Device Circuit - Class B
4010-9921 8 Zone Initiating Device Circuit - Class A
*UL, ULC, and CSFM listed. ** FM Approved only.
7 S4010-0011-5 11/2015
Supervisory
Current
1 Block
(must mount in block D
30 mA 40 mA
under ESS)
1 Block
3 A maximum
with 2.5 A load
1 Block
Note: One DCAI module can
8.3 mA 18.5 mA
be mounted on the ESS
1 Block 123 mA 123 mA
Supervisory
Current
2 Vertical Blocks NA NA
2 Vertical Blocks 30 mA 30 mA
N/A
55 mA 55 mA
(mounts to 4010-9922)
Requires one of the 2
193 mA 193 mA
Vertical Block spaces on the
4010-9928 Mounting Kit
3 Block “L” Shape, requires
one of the 2 Vertical Block
196 mA 196 mA
spaces on the 4010-9928
Mounting Kit, plus Block D
Supervisory
Current
2 Vertical Blocks
(mother/daughter card)
75 mA 195 mA
Alarm
Current
4.9 A
maximum
with 4 A load
Alarm
Current
Alarm
Current
Page 8
Additional Panel Option Selection (block space is not used)
Model Features
Supervisory
Current
Alarm
Current
Mounting Requirements
4010-9909 City Connect Module w/ disconnect switches 20 mA 36 mA
4010-9910 City Connect Module 20 mA 36 mA
Select one maximum, mounts on ESS
4010-9911 Alarm Relay Module 15 mA 37 mA
4190-6105* TrueInsight Remote Gateway 62 mA 62 mA Mounts on Front Door
4100-5128
Battery Distribution Terminal Block, mounts to side of box, required when battery connection leaves the 4010ES box (also used in the 4100ES fire alarm control panel)
* Refer to data sheet S4100-0063 and contact your local Simplex product representative for more details.
Cabinet Dimension Reference
Miscellaneous Accessories
LED Kits (LEDs are pluggable, use to change color for local application requirements)
Model Description
4100-9843 8 Yellow LED Kit 4100-9844 8 Green LED Kit 4100-9845 8 Red LED Kit 4100-9855 8 Blue LED Kit
End User Programming Tools
Model Description
4100-8802 End User Programming Unit Software 4100-0292 Custom Label Editing (USB Dongle) 4100-0295 Port Vectoring Setup and Control (USB Dongle) 4100-0296 Access Level/Passcode Editing (USB Dongle) 4100-0298 WalkTest Configuration Setup and Control (USB Dongle)
Factory Programming Options
Model Description
4010-8810 Factory Programming (select) 4010-0831 Custom Labels and Programming (requires 4010-8810)
8 S4010-0011-5 11/2015
Page 9
4010ES Card Address Allocation
The 4010ES has a maximum Internal and External Card Address Limit of 20 Card Addresses. Use the Table below to calculate 4010ES card address allocation.
INSTRUCTIONS: Below is a list of 4010ES equipment and the quantity of card addresses they consume
1. For the applicable control panel, write in the Card Address Consumption value in the Card Address Allocation column. (Note: Only select 1 control panel)
2. For the option cards to be installed on the 4010ES, write in the Card Address Consumption value in the Card Address Allocation column.
3. Total the Card Address Allocation column (total must not exceed 20).
Model Description
Control Panels (Select One)
4010-9601 4010-9602
4010-9603 4010-9604 4010-9606
Panel Option Cards (Select As Required)
4010-9901 Flat VESDA HLI Card 1
4010-9922 Flat Network Card 1
4010-9908 4 Point Flat Aux Relay Module 1
4010-9912 Serial DACT 1
4010-9923 SafeLINC Internet Interface Card 1
4010-9914 Building Network Interface Card 1
4010-9918 Dual RS-232 Module 1
4010-9920 8 Zone Initiating Device Circuit - Class B 1
4010-9921 8 Zone Initiating Device Circuit - Class A 1
Remote Annunciation (Select As Required)
4100-9401 Red Cabinet, English
4100-9403 Platinum Cabinet, English 2
4100-9421 Red Cabinet, French 2 for Canada
4100-9423 Platinum Cabinet, French 2 for Canada
4100-9441
4100-9443
4606-9102 4010ES RUI LCD Annunciator, English 1
4606-9102BA 4010ES RUI LCD Annunciator, English 1
4606-9102CF 4010ES RUI LCD Annunciator, French 1 for Canada
4602-9101 Status Command Unit (SCU) LED Annunciator 1
4602-9102 Remote Command Unit (RCU) LED Annunciator w/control 1
4602-9150 Graphic I/O RCU/SCU Assembly for custom annunciator panels 1
4602-7101 Graphic I/O RCU/SCU Assembly for custom annunciator panels 1
4602-7001 RCU for cabinet mount 1
4602-6001 SCU for cabinet mount 1
4100-7401 24 Point I/O Graphic Module for custom annunciator panels 1
4100-7402 64/64 LED Switch Controller for custom annunciator panels 1
4100-7403 32 Point LED Driver Module for custom annunciator panels 1
4100-7404 32 Point Switch Input Module for custom annunciator panels 1
2x40 Display, (1) IDNet 2 Communications Channel, Single Bay Box
2x40 Display, (1) IDNet 2 Communications Channel; 48 Pluggable LED Module
Remote InfoAlarm Command
Red Cabinet, with blank inserts for key labels
Platinum Cabinet, with blank inserts for key labels
Total Card Addresses (Not to Exceed 20) TOTAL
Center
Card Address Consumption
2
3
2
2
2
Card Address
Allocation
Notes
4010-9606 is for
Canada
9 S4010-0011-5 11/2015
Page 10
General Specifications
Input Current
ESS Power Supply Output Ratings
Compatible Special Application Appliances
Battery Charger Rating (sealed lead acid batteries)
Environmental
Additional Technical Reference
IDNAC SLC Ratings
IDNAC SLC Wiring
Auxiliary Power Tap 2 A maximum, rated 19.1 to 31.1 VDC
Battery capacity range
Charger characteristics
and performance
Operating Temperature 32° to 120°F (0° to 49° C)
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Installation Instructions 579-1150
Operating Instructions 579-969
Battery 9 A maximum @ 24 VDC (during battery operation)
Power Supply Output Rating
Additional Compatible Equipment and Reference
Subject Data Sheet Subject Data Sheet
4010ES Agent Release Applications and Accessories
Agent Release Accessories S2080-0010 Multi-Signal Fiber Optics S4100-0049
Building Network Interface S4100-0061 4602 Series SCU/RCU S4602-0001
SafeLINC Internet Interface S4100-0062 PC Annunciator S4190-0013
Interface to VESDA Air Aspiration Detection Systems
Serial DACT (SDACT) S2080-0009 4009 IDNAC Repeater S4009-0004
Fire Alarm Network Overview S4100-0055 4003EC Voice Control Panel S4003-0002
TrueInsight Remote Service S4100-0063 120 VAC Desktop Remote Printer S4190-0011
4606-9102 Remote LCD Annunciator S4606-0002 110 Ah Batteries and Cabinets S2081-0012
Graphic I/O Modules S4100-0005 Remote 110 Ah Battery Chargers and Cabinets S4081-0002
Remote InfoAlarm Command Center S4010-0008 BACpac Ethernet Portal Module S4100-0051
PC Annunciator S4190-0013 Network Physical Bridge S4100-0057
TCP/IP Physical Bridge S4100-0029
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. VESDA is a trademark of Xtralis Pty Ltd. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA). ASHRAE and BACnet are trademarks of ASHRAE, American Society of Heating, Refrigeration, and Air Conditioning Engineers.
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4010-0011-5 11/2015
www.simplex-fire.com
©2015Ty coFireProtectionProducts.Allrightsreserved.Allspecificationsandotherinf ormationshownwerecurrentasofdocumentrevisiondateandaresubjecttochangewithoutnotice.
AC 4 A maximum, 120 VAC @ 60 Hz nominal
6 A output for “Special Application” appliances Note: The 6 A output rating of the ESS was determined
such that optional module currents, and external device and appliance currents can be directly added together, not to exceed 6 A total.
3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit loads; DC-DC converter circuit is >92% efficient over operating range
Output terminals are rated for 20 to 12 AWG with duplicate output terminals rated for two wires each, allowing up to four (4) Class B branch circuit T-taps to be made in the cabinet; additional T-taps may be made in external wiring junction cabinets or boxes
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex product representative for compatible appliances
UL listed for battery charging of 6.2 Ah up to 110 Ah; ULC listed for charging up to 50 Ah batteries; batteries above 33 Ah require separate cabinet
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Output switches to battery backup during mains AC failure or brownout conditions
S4010-0005 Network Communications S4100-0056
S4100-0026
Addressable Device Compatibility, IDNet Communication Sensors and Devices
S4090-0011
Loading...