Specifications and other information shown were current as of publication and are subject to
change without notice. TYCO, SIMPLEX, and the product names listed in this material are
marks and/or registered marks. Unauthorized use is strictly prohibited.
READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions must
be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper
installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon unpacking your Simplex
product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier
and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All repairs
should be performed by a representative or authorized agent of your local Simplex product supplier.
STATIC HAZARD - Static electricity can damage components. Handle as follows:
EYE SAFETY HAZARD - Under certain fiber-optic application conditions, the optical output of this device may exceed eye
safety limits. Do not use magnification (such as a microscope or other focusing equipment) when viewing the output of this
device.
SULFURIC ACID WARNING- Battery contains sulfuric acid, which can cause severe burns to the skin and eyes and can
destroy fabric. Replace any leaking or damaged battery while wearing appropriate protective gear. If you come in contact with
sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be tested in
accordance with NFPA-72, after any programming operation or change in site-specific software. Reacceptance testing is required after any change,
addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
Page 3
Table of Contents
Copyrights, Trademarks, Cautions, Warnings, and Regulatory Info......................................i-2
In this chapter ....................................................................................................................................... 1-1
4007ES Product List ............................................................................................................................. 1-1
User Interface ....................................................................................................................................... 1-2
In this chapter ....................................................................................................................................... 2-1
Mounting the 4007ES Panels ............................................................................................................... 2-1
Trim Kit ........................................................................................................................................2-2
Trim Kit Application............................................................................................................................... 2-2
Final Installation .................................................................................................................................... 2-5
Chapter. 3 NAC Power Supply ...................................................................................3-1
In this chapter ....................................................................................................................................... 3-1
NAC Power Supply Specifications............................................................................................3-2
Power Supply Specifications.................................................................................................................3-2
In this Chapter....................................................................................................................................... 4-1
IDNAC Power Supply Specifications ........................................................................................4-2
Power Supply Specifications.................................................................................................................4-2
In this chapter ....................................................................................................................................... 5-1
Power Supplies Specifications.............................................................................................................. 5-1
In this chapter ....................................................................................................................................... 6-1
LED Module .......................................................................................................................................... 6-1
City Circuit............................................................................................................................................. 6-1
TrueInsight Service Gateway................................................................................................................ 6-2
Dual Class A Isolator ............................................................................................................................6-2
Example of Combinations ..................................................................................................................... 6-2
Appendix. A ULC Programming Requirements ...................................................... A-1
iv
Page 5
Chapter 1
Overview
IntroductionThe 4007ES fire alarm control panel provides audible and visible indication of alarms,
troubles, and supervisory conditions. The 4007ES panels supports addressable notification
and initiating devices and the 4007ES Hybrid panels supports non-addressable notification
devices and addressable initiating devices*. The panel can be configured by using a panel
programmer.
*From this point on, the 4007ES and the 4007ES hybrid will be referred to as 4007ES, unless
stated otherwise.
4007ES operator instructions are described in the 4007ES Operator’s Manual, 579-1165.
4007ES programming instructions are described in the 4007ES Programmer’s manual,
579-1167.
In this chapter
4007ES Product List ............................. 1-1Glossary ................................................ 1-2
User Interface........................................ 1-2
4007ES Product
List
Part Number
4007-9101
4007-9201
4007-9102
4007-9202
Part Number
4007-9801
4007-9802
4007-9803
4007-9804
4007-9805
4007-9806
4007-9807
4007-9808
4007-9809
4190-6106
Base Panels
4007ES Hybrid, Red
4007ES, Red
4007ES Hybrid, Platinum
4007ES, Platinum
Optional Modules: Field Installed
Zone/Relay Module579-1103
25V Regulator Module579-812
IDNet+ Loop Expansion Module579-1106
Dual Class A Module579-1029
LED Module579-1105
DACT Module579-954
City Circuit with Disconnect Module579-955
City Circuit without Disconnect Module579-955
Relay Module579-955
TrueInsight Remote Service Gateway and Programming579-953
Manual
1-1
Page 6
Overview, Continued
Chapter 1 Overview
Glossary
TermDefinition
AuxAbbreviation for Auxiliary; typically used to describe Auxiliary Power.
EOLEnd-of-Line (typically in reference to and end-of-line resistor or EOL
resistor).
FACPFire Alarm Control Panel.
HybridIn this document, “Hybrid” the 4007ES Hybrid models that provide both
addressable and conventional initiation with conventional non
addressable Notification Appliance Circuits.
IDCInitiating Device Circuit.
IDNetAddressable SLC for up to 250 addressable devices.
IDNet+IDNet which is electrically isolated from internal panel electronics.
IDNACIndividual Device Notification Appliance Circuit (Addressable).
NACNotification Appliance Circuit (formerly called signal circuit).
Regulated 24 DCNotification appliance operation that meets the minimum listing
requirements; inrush currents typically require power supply and NAC
rating.
RUIRemote Unit Interface; SLC for communications with remote
annunciators.
Simple NACA Reverse Polarity Supervised Notification Appliance Circuit that is
capable of on steady or coded operation. Sync or SmartSync operation
is not supported.
SLCSignaling Line Circuit
SmartSyncA reverse polarity monitored NAC capable of synchronizing and
controlling both horns and strobes on the same circuit via a proprietary
signaling protocol. Used as the protocol for TrueAlert Non-Addressable
Devices.
User Interface The user interface is a 4.3” (109mm) diagonal color LCD with a built-in resistive touch panel
and 12 indicating LEDs. The color LCD provides system status and access to perform system
functions and to change the system configuration.
Figure 1-1 shows an inside view of the 4007ES panel with the optional LED module
(4007-9805) installed.
Figure 1-1. 4007ES Panel Inside View
1-2
Page 7
Chapter 2
Power Supply
Screws
16” (406mm)
16-5/16”
(416mm)
16’ (406mm)
20-7/8” (530mm)
20-3/16”
(512mm)
1-1/2” (38mm)
Mounting Holes
Installation
IntroductionThis chapter describes how to install the 4007ES panel. It can be semi-flush or surface mount.
In this chapter
Mounting the 4007ES Panels ................ 2-1Trim Kit Application .............................2-2
•Due to the danger of metal fragments
falling into electronics when drilling
the holes for the conduits, remove the
electronics in the system:
- To remove the electronics, unscrew
the ten screws. Remove the power
supply and store it in a safe, clean, and
dry location until the panel installation
is completed, see Figure 2-1.
- If installing a 4007ES hybrid panel,
also remove the Zone/Relay card (three
screws).
•Use a suitable punch where conduit
entrance is required. Knockouts are not
provided. Locate and create on-site as
required during installation.
Figure 2-1 Screws location
•For surface or semi-flush mounting to a wooden wall structure, the panel must be attached
with four 1-½-inch-long (38 mm) lag bolts and four ½-inch-diameter (13 mm) washers
(supplied by others).
•For surface mounting, secure the box to the wall using the tear-drop mounting holes on
the back surface. For semi-flush mounting, secure the box (along the sides) to the wall
studs. Note that the front surface of the back box must protrude at least 1-1/2 inch (38mm)
inches from the wall surface for semi-flush installation. A trim kit is supplied for semiflush mounting. Refer to the Trim Kit Application section for more information.
•To install the panel refer to Figure 2-2 for the dimensions and use the holes in the back
box to secure it to the wall.
.
Figure 2-2. Back Box Installation dimensions and Semi-Flush Mounting (Right)
2-1
Page 8
Trim Kit
Top Trim Bands (x2)
Side Trim Bands (x2)
Corner Pieces (x4)
Semi-Flush
Mounted
Back Box
Chapter 2 Installation
Trim Kit
Application
Trim kits are used to cosmetically cover wall openings when boxes are mounted semi-flush
into the wall. The kit includes:
•Two top trim bands (shorter)
•Two side trim bands (longer)
•Four corner pieces.
Figure 2-3 Semi-Flush Trim Kit
After mounting the box semi-flush to the wall, attach the trim per the following procedure:
1. The strips need to be cut before being attached. Carefully
cut them to length using a hacksaw or sharp utility knife.
Cut the strips approximately 1" (25 mm) shorter than the
box dimension. The box is 20-7/8" (530 mm) wide and
20-3/16" (512 mm) high.
2. Attach the strips one at the time. Peel off the adhesive tape
release and center the strip on the box placing the edge of
the strip against the box surface, then press down solidly to
assure adhesion.
3. Each corner piece overlaps the trim strip slightly less than
3/4" (19 mm). Align the corner pieces tight to the box
corner and attach with a drywall or similar screw, suitable
for the wall material (screws are not supplied).
Figure 2-4. Applying the Trim
2-2
Page 9
Chapter 2 Installation
Optional Modules
Keep battery wiring terminals
to the front of the box. If the DACT
or the City/Relay option card is
used, run 734-306 harness
wiring on the back of the box
to maintain separation from
battery wiring.
Keep NPL wiring this
side of the box, strain
relieved to the back
of the box using the
lances shown.
Keep PL wiring in
this area for any
optional cards
mounted on this side
if NPL wiring is run
towards the top of
the box.
NPL conduit entry
NPL Conduit Entry
Side View of Panel
Note:
The 2098-9739 Relay is
used as an example.
Other UL Listed 24VDC
EOL relays can be used,
depending on the application.
TO AUX POWER
RED
BLACK
2098-9739
END OF
LINE RELAY
YELLOW
IDC
LAST IDC
DEVICE
Wiring
Wiring GuidelinesFollow these guidelines when connecting Power-Limited (PL) systems. For more information
about these guidelines, contact your authorized Simplex Product supplier.
•Non-Power Limited (NPL) field wiring (AC power, batteries, City connection, DACT)
must be installed and routed in the shaded areas shown in Figure 2-5.
•A minimum of 0.25 inches space must be maintained between NPL and PL field wiring.
•The AC Harness is pre-wired (tied to back of the box).
Figure 2-5. Field Wiring Guidelines (NAC Power Supply Shown as Reference)
•Conductors must test free of all grounds.
•A system ground must be provided for earth detection and lightning protection devices.
This connection must comply with approved earth detection per NFPA780.
•Splicing is permitted. All spliced connections must either be soldered (resin-core solder),
crimped in metal sleeves, or encapsulated with an epoxy resin. When soldering or crimped
metal sleeves are used, the junction must be insulated with a high-grade electrical tape that is
as sound as the original insulating jacket. Shield continuity must be maintained throughout.
•Excess slack should be kept to a minimum inside the back box enclosure. The wiring
should be neatly dressed and bundled together using wire ties.
•All wiring must be done using copper conductors only, unless noted otherwise.
•For IDNet, shielded wire is not recommended. If
shielded wires are present, cut and tape off the
shield at each end in the panel to prevent it from
coming in contact with other components. Metallic
continuity of the shield must be maintained and
insulated throughout the entire length of the cable.
•If shielded wire is used, the metallic continuity of
the shield must be maintained throughout the entire
cable length and the entire length of the cable must
have a resistance greater than 1 megohm to earth
ground. Underground wiring must be free of all
water.
•In areas of high lightning activity, or in areas that
have large power surges, the 2081-9027 or the
2081-9044 Transient Suppressor should be used on
monitor points.
Figure 2-6. EOL Relay Diagram
2-3
Page 10
Chapter 2 Installation
Wiring
Wiring Guidelines •Wires must not be run through elevator shafts.
•Only system wiring can be run together in the same conduit.
When powering remote units through relay contacts, power for these circuits must be
provided by a PL power supply listed for fire-protective signaling use. An end-of-line
(EOL) relay must be used to supervise the auxiliary power circuit.
•Connect the output of the EOL Relay to cause a trouble. Wire in series with the EOL resistor
on an available Initiating Device Circuit (IDC) or Individual Addressable Module (IAM).
Safety GroundProper operation and protection against transient energy per UL 864 and ULC-S527 requires
connection of safety ground wire to cabinet chassis. Connect safety ground before wiring any
other circuits to the panel.
AC Supply WiringAdhere to the following guidelines when wiring AC Power.
•AC power must be wired from a dedicated circuit breaker or fuse, rated no more than
20 A, per NFPA-72, NEC, and local codes.
•Before handling AC feed, verify that it is not live using a voltmeter. Make sure the circuit
is de-energized and tagged to prevent injury.
•AC supply wiring must be 14 AWG minimum to 12 AWG maximum.
•Connect a 12 AWG copper ground wire from safety ground in the electrical distribution
panel to the panel safety ground stud.
•Input voltage:
- 120 VAC, 50/60 Hz
- 240 VAC, 50/60 Hz
- No configuration settings required to select.
Battery
Guidelines
•A fused harness (harness 734-304 for NAC power supply and 734-303 for IDNAC power
supply) is required to connect the backup batteries. That harness is shipped with the panel.
The mating spade lug on the battery should be 0.250” X 0.032". If another size is needed,
you will need to replace the battery terminal connectors on the supplied battery harness.
•The 4007ES battery charger supports up to 33 Ah batteries (maximum) within UL864 and
ULCS527 guidelines.
- 18 Ah batteries can fit inside the box.
- 25 Ah and 33 Ah batteries use 2081-9282 (red 25 Ah or 33 Ah) or 4009-9801 (beige
25 Ah)
•To minimize the power losses due to wiring from the external battery box to the 4007ES,
use at least a 12 AWG wire. Mount the battery box within 20 feet of the panel in
accordance with the mounting instruction label in the box. All interconnecting wiring must
be enclosed in conduit.
•Seismic battery brackets can be used internal to the 4007ES box (2081-9401 (12.7 Ah
bracket), 2081-9402 (18 Ah bracket)). For more information on how to install the seismic
brackets, refer to Battery Bracket installation instructions 579-944.
2-4
Page 11
Power
Jumper
Negative
Positive
SDACT
SDACT
SDACT
Final InstallationTo finalize the installation:
1. Reinstall the power supply and the electronics.
2. Follow the steps below to
install the batteries:
a. Place the first battery on
the left side of the panel
to avoid interference
with the DACT (if
installed).
Note:
The battery terminals should face
the front of the box.
b. Insert the second battery
and make sure it is
snugly positioned beside
the first battery.
c. Wire the batteries in
series such that you have
24 V. Use the white wire
provided to bridge the
batteries together. (see
Figure 2-7).
Chapter 2 Installation
IMPORTANT:
Verify all field
wiring before
applying any
power to the panel.
Power up the system:
1. Connect the negative lead
to the battery.
2. Apply AC.
3. Connect the positive to the
battery.
Figure 2-7. Power Supply
2-5
Page 12
Page 13
Chapter 3
TB3
B
B
A
A
P2
2
1
B
B
A
A
P1
2
1
P2
P1
AUX/SNAC
LEDs
P6
IDNet
RUI
Zone/
Relay
J5
TB1
NAC 1 NAC2 NAC3 NAC4
BAT- BAT+
City/
Relay
Option
Zone/
Relay
25V
REG
CPU
TB4
IDNet
Loop B
J17
IDNet
Loop C
TB2
P4
P9
J16
P8
P11
J15
LEDs
P10
NAC Power Supply
IntroductionA conventional reverse polarity NAC power supply is used in a 4007ES hybrid panel. It
provides 6A and can support:
•Non-addressable notification devices
•Addressable initiating devices
Refer to Figure 3-1 and Table 3-1for the main components of the NAC power supply.
In this chapter
Figure 3-1. NAC Power Supply
Table 3-1. Main Components Information
P1RUI Class A/B jumpersP2IDNet Class A/B jumper
TB4Battery connectionTB2NAC 1 and NAC 2
P10AC Power ConnectionTB3NAC 3 and NAC 4
J5 and J15 Zone / RelayJ7IDNet Loop B
J16CPU ConnectionJ8IDNet Loop C
J17Option ConnectionP4NAC Power Supply Card On-line
P11City/Relay ConnectionP6Battery Depleted Jumper
P81-2 (default) / IDNet card on line
TB1
IDNet Loop 1, Aux
Power, RUI Connection
P9
25V Regulator Jumpers 1-2, 3-4
default. Power is fed to the zone/
relay card. No jumpers. Using 40079802, 25V Regulator Module.
Power Supply Specifications................. 3-2NAC Section Overview........................ 3-3
The NAC Power Supply can supply 6A of 24V power in addition to the base draw of the CPU/
Power Supply cards. The current draw taken from optional cards, IDNet Devices, Aux Power,
and NACs must be subtracted from 6A.
IMPORTANT: Refer to the 4007-9801 8-Point Zone/Relay Card
Installation Instruction, manual 579-1103, to determine the
draw of the pre-installed Zone/Relay card.
Table 3-2. 4007ES Hybrid System Current Draw
Maximum AC Input
Standby Conditions
No alarms (NACs normal). No IDNet devices connected.145 mA
Add to above for each additional IDNet device in standby. 0.8 mA
Total current for fully loaded IDNet channel in standby.345 mA
Alarm Conditions
4 NACs ON: TBL Relay Activated: IDNet LED On. No
IDNet devices connected.
Add to above for each IDNet device in alarm.1 mA
2 A at 120 VAC, 50/60Hz
1 A at 240 VAC, 50/60Hz
Current
(Battery Standby 24 V)
Current
(Battery Alarm 24 V)
190 mA
Add to above for each IDNet LED On (20 maximum IDNet
devices LEDs On).
Total current for fully loaded IDNet channel in alarm.480 mA
2 mA
3-2
Page 15
NAC Section
NAC1
B+ B- A+ A-
NAC2
B+ B- A+ A-
NAC3
B+ B- A+ A-
NAC4
B+ B- A+ A-
Chapter 3 NAC Power Supply
NAC Section
Overview
Specifications
The NAC power supply allows connection to up to four Class A NAC circuits. Notification
appliances within the 4007ES system are synchronized including any attached 4009 series
NAC extenders. Do not mix Wheelock and Simplex branded devices in the same system, they
will not be synchronized. The following TrueAlert non-addressable appliances are Special
Application compatible with the NAC power supply:
* Each 49CMT series appliance counts as 5 regular appliances for the maximum 70 appliances that
can be supported per NAC. As the earth fault sensitivity with thirteen MT appliances drops from 10
K to 9.6K ohms, no more than thirteen 49CMT series appliances may be placed on one circuit.
Electrical Specifications:
Voltage24 VDC nominal
Alarm CurrentThe maximum alarm current is 3 A per circuit.
Supervisory CurrentRefer to Table 3-4
Special Application Appliances
(TrueAlert Non-Addressable)
Note: When NACs are used for Regulated 24DC appliances, maximum current per NAC is reduced to 2 A
and total power supply notification current rating is reduced to 3 A. Current used by modules powered from the 4007ES power supply must be deducted from the total current.
6 A total
WiringWiring Parameters
The NAC Power Supply is supervised and power-limited. Refer to Table 3-4 for the NACs’
supported EOL resistors and the related supervisory current and to Table 3-3 for the wiring
parameters.
Note: If a shielded wire is used, cut it and tape it at both ends.
Maximum wiring distanceEOLRCurrent
Maximum cable load10,000 ft (3,048m) per channel3.9 k5.7 mA
Maximum wire length from
panel to any device
Maintain correct polarity on terminal connections. Do not loop
wires under terminals.
Table 3-3. Wiring Parameters
4,000ft (762m)4.7 k4.8 mA
3-3
Table 3-4. Supported EOLR
and Supervisory Current
5.1 k4.4 mA
5.6 k4.0 mA
10 k2.2 mA
15 k1.4 mA
Continued on next page
Page 16
NAC Section, Continued
WiringWiring Distances
Table 3-5 lists the maximum distances from the NAC terminal block to the last appliance in a
Class A configuration, depending on wire gauge and current. Use Table 3-5 to calculate wire
distances for your application if you are using Class A wiring. Table 3-6 gives the values for a
Class B configuration.
Table 3-5. Class A Wiring Distances
Chapter 3 NAC Power Supply
Alarm Current
Max Distance
w/ 18 AWG
(0.8231 mm
2
)
Max Distance
w/ 16 AWG
(1.309 mm2)
Max Distance
w/ 14
AWG
(2.081 mm
2
)
Max Distance
w/ 12 AWG
(3.309 mm
2
)
Resistance
0.25 A420 ft (128 m)667 ft (203 m)1,063 ft (324 m)1,691 ft (515 m)6 Ohms
0.50 A210 ft (64 m)334 ft (102 m)532 ft (162 m)845 ft (258 m)3 Ohms
0.75 A140 ft (43 m)222 ft (68 m)354 ft (108 m)564 ft (172 m)2 Ohms
1.00 A105 ft (32m)167 ft (51 m)266 ft (81 m)423 ft (129 m)1.5 Ohms
1.25 A84 ft (26 m)133 ft (41 m)213 ft (65 m)338 ft (103 m)1.2 Ohms
1.50 A70 ft (21 m)111 ft (34 m)177 ft (54 m)282 ft (86 m)1 Ohm
0.25 A840 ft (256 m)1,335 ft (407 m)2,126 ft (648 m)3,382 ft (1,031 m)12 Ohms
0.50 A420 ft (128 m)667 ft (203 m)1,063 ft (324 m)1,691 ft (515 m)6 Ohms
0.75 A280 ft (85 m)445 ft (136 m)709 ft (216 m)1,127 ft (344 m)4 Ohms
1.00 A210 ft (64 m)334 ft (102 m)532 ft (162 m)845 ft (258 m)3 Ohms
1.25 A168 ft (51 m)267 ft (81 m)425 ft (130 m)676 ft (206 m)2.4 Ohms
1.50 A140 ft (43 m)222 ft (68 m)354 ft (108 m)564 ft (172 m)2 Ohms
1.75 A120 ft (37 m)191 ft (58 m)304 ft (93 m)483 ft (147 m)1.71 Ohms
2.00 A105 ft (32 m)167 ft (51 m)266 ft (81 m)423 ft (129 m)1.5 Ohms
2.25 A93 ft (28 m)148 ft (45 m)236 ft (72 m)376 ft (115 m)1.33 Ohms
2.50 A84 ft (26 m)133 ft (41 m)213 ft (65 m)338 ft (103 m)1.2 Ohms
2.75 A76 ft (23 m)121 ft (37 m)193 ft (59 m)307 ft (94 m)1.09 Ohms
3.00 A70 ft (21 m)111 ft (34 m)177 ft (54 m)282 ft (86 m)1 Ohm
Note:
•Max Distance = distance from the power supply to last appliance.
•This table is calculated at 49
higher temperatures, refer to NEC Table 8.
•Distances are based on a 3 V drop, and take into account the worst-case panel output voltage.
•If circuit integrity wire is used instead of housing cable in a fire rated enclosure, reduce wiring distances
by 38 ft (12 m) for every 10 ft (3 m) of potential exposure.
o
Max Distance
w/ 14 AWG
(2.081 mm2)
C (120oF). If you are installing in locations that could be exposed to
Max Distance
w/ 12 AWG
(3.309 mm2)
Resistance
DC
DC
3-4
Continued on next page
Page 17
NAC Section, Continued
TYPICAL
APPLIANCE
RED
RED
RED
TYPICAL
APPLIANCE
BLK
BLK
BLK
12 AWG (3.309 mm 2) to
18 AWG (0.8231 mm
2
)
Leave the 378-030 EOL
Resistor (10 K Ohm, ½ W;
brown/black/orange) on
unused circuits
NAC1
B+ B- A+ A-
NAC2
B+ B- A+ A-
NAC3NAC4
B+ B- A+ A- B+ B- A+ A-
TYPICAL
APPLIANCE
REDBLK
TYPICAL
APPLIANCE
10K 1/2W (133-894)
REDRED
REDRED
12 AWG (3.309 mm
2
) to
18 AWG (0.8231 mm
2
)
BLK
BLK
BLK
4081-9008 EOL Harness
Leave the factory installed
EOL Resistor (10 KOhms,
½ W, brown/black/orange)
on unused circuits
NAC1
B+ B- A+ A-
NAC2
B+ B- A+ A-
NAC3NAC4
B+ B- A+ A- B+ B- A+ A-
WiringClass A Wiring
Note: The Class A wiring style is set up in the programmer. Refer to the 4007ES Programmer’s manual,
579-1167, for more information.
To connect the power
supply to reverse-polarity,
non-addressable
notification appliances
using Class A wiring:
1. Route wire from the
“B+” and “B-” outputs of
the power supply to the
appropriate inputs on a
peripheral notification
appliance. Use NAC1,
NAC2, NAC3 or NAC4
(2.).
2. Route wire from the first
appliance to the next
one. Repeat for each
appliance.
Chapter 3 NAC Power Supply
Figure 3-3. Class A NAC Wiring
3. Route wire from the last appliance to the A+ and A- inputs on the same NAC circuit of the
power supply.
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Leave the 10 KOhms, ½ W, brown/black/orange resistor (378-030) on each unused circuit.
No external end-of-line resistor is needed for circuits in use.
Class B Wiring
Note: The Class B wiring style is set up in the programmer. Refer to the 4007ES Programmer’s
manual, 579-1167, for more information.
To connect the power
supply to appliances using
Class B wiring:
1. Route wire from the B+,
B- outputs on TB2 and
TB3 of the power supply to the appropriate
inputs on a peripheral
notification appliance.
Use NAC1, NAC2,
NAC3, or NAC4.
2. Route wire from the first
appliance to the next
one. “T” tapping is not
allowed. Repeat for
each appliance.
Figure 3-4 Class B NAC Wiring
3. Route wire from the last appliance to the EOLR harness (10KOhms, 1/2 W: P/N 733-894).
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Leave the factory installed EOL Resistor (10 KOhms*, ½ W; brown/black/orange) on each
unused circuit. The circuit must connect “B+” to “B-” terminals.
6. Document EOL value in panel per circuit.
*If using a 4007ES hybrid panel, keep the original value and set the programmer accordingly.
3-5
Page 18
Troubleshooting
LEDs
Aux/SNAC
Comm
Gen Power
NAC1
NAC2
NAC3
NAC4
LEDs
RUI TBL
RUI OC
TroubleshootingTable 3-7 gives the LED definition for the NAC power.
Table 3-7. 4007ES Hybrid Indicator LEDs
Figure 3-5. LEDs on the 4007ES Hybrid Power Supply
LED10AC
LED2RUI Trouble Yellow. On for Class A RUI trouble
LED6RUI OCYellow. Indicates a short (overcurrent)
LED3Comm
LED 4Gen Power
LED5, 7, 8,
and 9
NAC 1, 2, 3,
4
Green. Off on AC failure
Yellow. Indicates that the communication between the NAC power supply and the CPU is lost
Steady On, yellow. Indicates AC power loss, earth fault, overcurrent
and battery trouble
Steady On, yellow. Used to signal overcurrent, short, and open
circuit.
Chapter 3 NAC Power Supply
LED1Aux/SNAC
Steady On, yellow. Use to signal overcurrent, short, and open
circuit.
3-6
Page 19
Chapter 4
B
B
A
A
P2
2
1
B
B
A
A
P1
2
1
P2
IDNAC
AUX RELAY 1 AUX RELAY 2
LEDs
P4
5A Fuse
250VAC
BAT- BAT+
City/
Relay
Option
25V
REG
CPU
P5
TB4
P1
AUX PWR/
SNAC
IDNet
RUI
TB3
TB1
IDNet
Loop B
IDNet
Loop C
TB2
Zone/
Relay
J7
P5
J15
P9
J16
P8
P11
J17
P5
IDNAC Power Supply
IntroductionAn IDNAC power supply is used in the 4007ES (non Hybrid) panel. It provides 4 A and can
support:
•Addressable notification devices
•Addressable initiating devices
Refer to Figure 4-1 and Table 4-1 for the main components of the IDNAC power supply.
In this Chapter
Figure 4-1. IDNAC Power Supply
Table 4-1. Main Components Information
P1RUI Class A/B jumpersP2IDNet Class A/B jumper
TB4Battery connectionTB2IDNAC
P10AC Power ConnectionTB3Aux Relay 1 and 2
J15
DCAI
Zone/Relay Connection
J10IDNet Loop 2
J7Zone/RelayJ11IDNet Loop 3
J16CPU ConnectionP5Battery Depleted Jumper
J17Option ConnectionP81-2 (default) / IDNet card on line
P11City Circuit Connection
Power Supply Specifications ................ 4-2IDNAC Section Overview ....................4-3
TB1
IDNet Loop 1, Aux
Power, RUI Connection
P9
25V Regulator Jumpers 1-2, 3-4
default. Power is fed to the zone/relay
card. No jumpers. Using 4007-9802,
25V Regulator Module
Troubleshooting .................................... 4-9SLC Channel Trouble LED Codes ........ 4-9
System Trouble LED Codes................ 4-10
4-1
Page 20
IDNAC Power Supply Specifications
Chapter 4 IDNAC Power Supply
Power Supply
Specifications
The IDNAC Power Supply can supply 4A of 24V power in addition to the base draw of the
CPU/Power Supply cards. The current draw taken from optional cards, IDNet Devices, Aux
Power, and NACs must be subtracted from 4A.
Table 4-2. 4007ES System Current Draw
Maximum AC Input
Standby Conditions (see Note 1)
No alarms (NACs normal). IDNet devices connected180 mA
Add to above for each additional IDNet or IDNAC device in
standby
Total current for fully loaded IDNet or IDNAC channel in standby431 mA
Alarm Conditions (see Note 1)
IDNAC ON: No IDNet LED On. No IDNet devices connected185 mA
Add to above for each IDNet device in alarm (see note 2)1 mA
Add to above for each IDNet LED On (20 maximum IDNet
devices LEDs On)
2 A at 120 VAC, 50/60 Hz
1 A at 240 VAC, 50/60 Hz
Current (see Note 1)
(Battery Standby 24 V)
0.8 mA
Current (see Note 1)
(Battery Alarm 24 V)
2 mA
Total current for fully loaded IDNet channel in alarm (20 LEDs
On) (see note 2)
Notes:
1. Add an additional 9 mA per active auxiliary relay (Alarm or Standby)
2. IDNAC Alarm current depends on the IDNAC device used. Refer to the device’s manual for more informa-
tion on currents.
475 mA
4-2
Page 21
IDNAC Section
IDNAC
+ - + -
Chapter 4 IDNAC Power Supply
IDNAC Section
Overview
Specifications
The IDNAC power supply has a single SLC
for connecting addressable IDNAC devices.
The power supply is compatible with
TrueAlertES and TrueAlert Addressable
product lines (both multi and fixed candela).
The IDNAC output is Class B only. Class A
operation requires use of optional module
4007-9804, IDNAC dual Class A isolator.
The output is duplicated on the terminal block
to facilitate “T” tapping on the circuit at the
panel. EOL resistors are not required.
All wiring is supervised and power-limited.
Table 4-3. IDNAC Specifications
- Up to 12 4905-9929 remote TrueAlert Addressable Isolators per
IDNAC Circuit.
- Up to 30 devices connected directly to any isolator terminal pair*.
Supports
- Up to six isolators between any appliance and the IDNAC SLC
terminals. All wiring is 20 AWG to 12 AWG.
*For more information on the isolator, refer to the 4905 Isolator+ Installation Instructions, 574-769.
Figure 4-2. IDNAC Terminal
Electrical Specifications:
Channel Voltage29.5 VDC nominal.
Circuit RequirementsThe maximum alarm current is 3 A per circuits.
Isolator
Isolator (DCAI)
WiringWiring Parameters
Table 4-4 identifies the IDNAC wiring parameters that must be considered.
IDNAC Wiring Limits
Channel Loading
Max. wiring distance
Max. cable load10,000 ft (3,048m) per channel.
To wire an IDNAC as a Class A circuit, the DCAI modules (4007-9804)
is required (2 Class A circuits with fault isolation). For more information
on Dual Class A isolator and on how to calculate Class B wiring with
isolation, refer to the
Table 4-4. IDNAC Wiring Parameters
127 devices (IDNAC devices or other compatible devices). Refer
to the Compatible Devices and Appliances section for more
details.
DCAI Installation Instructions 579-1029
.
Max. wire length from
panel to any device
Note: If a shielded wire is used, cut it and tape it.
4,000ft (762m).
4-3
Page 22
IDNAC Section, Continued
WiringIDNAC Class B Wiring Tables
Use the following tables to calculate the wiring distance to farthest appliance.
Maximum wiring distance is the shorter of the distance limits as calculated by alarm current
voltage drop or by reaching the communications distance limit.
Chapter 4 IDNAC Power Supply
Table 4-5. Wiring Limit Based on Alarm
Table 4-6. Wiring Limit Based on Communication
Current
Alarm
Current
0.050
0.1002644 ft
0.1501763 ft 2802 ft
0.2001322 ft 2102 ft 3342
0.2501058 ft 1681 ft 2674 ft
0.300881 ft 1401 ft 2228 ft 3542 ft
0.350755 ft 1201 ft 1910 ft 3036 ft
0.400661 ft 1051 ft 1671 ft 2657 ft
0.450588 ft934 ft 1485 ft 2362 ft 37566.4540568 ft904 ft1437 ft 2285 ft 3634 ft
0.500529 ft 841 ft 1337 ft 2125 ft 33806.0045528 ft840 ft1336 ft 2124 ft 3378 ft
0.750353 ft 560 ft891 ft 1417 ft 2254 ft5.6050493 ft784 ft1247 ft 1982 ft 3152 ft
1.000264 ft 420 ft668 ft 1063 ft 1690 ft5.2455462 ft734 ft1168 ft 1856 ft 2952 ft
1.250212 ft 336 ft535 ft850 ft 1352 ft4.9260434 ft690 ft1097 ft 1744 ft 2774 ft
1.500176 ft 280 ft446 ft708 ft 1127 ft4.7563419 ft665 ft1058 ft 1682 ft 2675 ft
1.750151 ft 240 ft382 ft607 ft 966 ft4.6465409 ft650 ft 1034 ft 1643 ft 2613 ft
2.000132 ft 210 ft334 ft531 ft845 ft4.3870386 ft614 ft 976 ft1552 ft 2468 ft
2.250118 ft 187 ft297 ft472 ft 751 ft4.1575366 ft581 ft 924 ft 1469 ft 2337 ft
2.500106 ft168 ft267 ft425 ft 676 ft3.9480347 ft551 ft 877 ft1394 ft 2217 ft
2.75096 ft 153 ft 243 ft 386 ft 615 ft3.7485330 ft524 ft833 ft1325 ft 2107 ft
3.00088 ft 140 ft 223 ft 354 ft 563 ft3.5690314 ft499 ft794 ft1262 ft 2006 ft
Wiring distance must not exceed 4000 ft
Distance to the Last Appliance
20
AWG
4000 ft 4000 ft 4000 ft 4000 ft 4000 ft14.5411252 ft 2038 ft 3241 ft 4000 ft 4000 ft
18
AWG
4000 ft 4000 ft 4000 ft 4000 ft12.9651142 ft 1815 ft 2887 ft 4000 ft 4000 ft
16
AWG
4000 ft 4000 ft 4000 ft11.38101003 ft 1595 ft 2536 ft 4000 ft 4000 ft
14
12
AWG
4000 ft 4000 ft10.1415893 ft1420 ft2258 ft 3590 ft 4000 ft
4000 ft 4000 ft9.1220804 ft1278 ft 2033 ft3231ft 4000 ft
AWG
4000 ft8.2825730 ft1160 ft 1845 ft 2934 ft 4000 ft
4000 ft7.5830668 ft1061 ft1688 ft 2683 ft 4000 ft
4000 ft6.9735614 ft977 ft1553 ft 2469 ft 3928 ft
Table 4-7. Ohms per 1000 ft
Line
Impedance
(Ohms)
3.4095299 ft476 ft757 ft1203 ft 1913 ft
3.24100286 ft454 ft723 ft1149 ft 1827 ft
3.10105273 ft435 ft691 ft1099 ft 1748 ft
Devices
Distance to the Last Appliance
20
AWG
18
AWG
16
AWG
14
AWG
AWG
12
GageOhms/1000 ft2.97110262 ft416 ft662 ft1052 ft 1673 ft
20 AWG11.3472.85115251 ft399 ft634 ft1009 ft 1604 ft
18 AWG7.1372.73120241 ft383 ft609 ft968 ft1539 ft
16 AWG4.4882.58127228 ft362 ft576 ft915 ft1456 ft
14 AWG2.8230
12 AWG1.7750
Wiring distance must not exceed 4000 ft
4-4
Page 23
IDNAC Section, Continued
IDNAC
Device
IDNAC
Device
IDNAC
Device
IDNAC
Device
IDNAC
Device
IDNAC
Device
T-TAP
T-TAP
IDNAC
+
-
+
-
T-TAP
Wiring IDNAC Class B Wiring
To connect the power supply to
appliances using Class B wiring:
1. Route the wire from the “+” and
the “-” outputs on the IDNAC
terminal block (TB2) to the
appropriate inputs on a
peripheral notification
appliance.
2. Route wire from the first appli-
ance to the next one. “T” tapping is allowed. Repeat for each
appliance.
3. Repeat steps 1 and 2 for each
IDNAC output you want to use.
Notes: 1. Notification appliances are rated per individual nameplate label. Maintain correct polarity on termi-
nal connections.
2. Each IDNAC + and - terminal is rated for 2 identical wires. This allows up to 4 Class B T-TAP cir-
cuits directly from each IDNAC terminal block. See Figure 4-3.
Chapter 4 IDNAC Power Supply
Figure 4-3. Class B Wiring
4-5
Page 24
IDNAC Section, Continued
Chapter 4 IDNAC Power Supply
Compatible
Devices and
Appliances
The devices and appliances listed in Table 4-8 are compatible with the IDNAC power supply.
Notification devices are synchronized within the 4007ES system, including any attached 4009
series NAC extenders.
LED Visible Only High
Candela Wall Mount
Weatherproof
LED Audible/Visible Wall
Mount
59VO-WRFH-BA
59VO-WWFH-BA
59VO-WRFO
59VO-WRFO-BA
59VO-WWFO-BA
59VO-APPLWRH-O
59VO-APPLWWH-O
59AV-WRF
59AV-WRF-BA
59AV-WWF
59VO-WRFABH-BA
59VO-WWFABH-BA
59VO-WRFABO
59VO-WRFABO-BA
59VO-WWWFABO-BA
59AV-WRFAB
59AV-WRFAB-BA
59AV-WWFAB
59VO-APPLWRH
59VO-APPLWWH
59VO-APPLWR-O
59VO-APPLWW-O
59AV-WWFAB-BA
59AV-APPLWR
59AV-APPLWW
59AV-WWF-BA
4906-9229
4906-9230
4906-9203
4906-9204
4906-9254
N/A
N/A
4-6
Page 25
Table 4-8. Compatible Devices and Appliances
Chapter 4 IDNAC Power Supply
LED Audible/Visible Wall
Mount
High Candela
LED Audible/Visible Wall
Mount Weatherproof
LED Audible/Visible Wall
Mount High Candela
Weatherproof
Audible Only Wall Mount
Audible Only Wall Mount
Weatherproof
59AV-WRFH
59AV-WRFH-BA
59AV-WWFH-BA
59AV-WRFO
59AV-WRFO-BA
59AV-WWFO-BA
59AV-APPLWRH-O
59AV-APPLWWH-O
59AO-WRS
59AO-WRS-BA
59AO-WRSO
59AO-WRSO-BA
59AV-WRFABH
59AV-WRFABH-BA
59AV-WWFABH-BA
59AV-WRFABO
59AV-WRFABO-BA
59AV-WWFABO-BA
59AO-WWS
59AO-WWS-BA
59AO-WWSO-BA
59AO-APPLWR-O
Plate59AP-EUROBB
Notes:
1. Maximum thirty-two (32) 49MT appliances per circuit.
2. Maximum twenty-one (21) 49MTV appliances per circuit.
59AV-APPLWRH
59AV-APPLWWH
59AV-APPLWR-O
59AV-APPLWW-O
59AO-APPLWR
59AO-APPLWW
59AO-APPLWW-O
4-7
Page 26
Auxiliary Relays Section
AUX RELAY1
N.O. C N.C
AUX RELAY2
N.O. C N.C
Normally
open
Normally
closed
Common
12 AWG (3.309 mm
2
) to
18 AWG (0.8231 mm
2
)
Auxiliary Relays
Section Overview
Electrical Specifications:
Relay circuit rated to
switch:
Contacts:
Power
When power through auxiliary contacts is provided by the power supply, wiring is powerlimited.
When power through auxiliary contacts is not provided by the power supply, use in-line fuse
holder 208-165 with 208-183, 1A fuse with attached cap (supplied separately). If the power
source is not power-limited to the requirements of UL864, wiring is to be segregated to the
non-power-limited spaces of the cabinet.
Note:
The Aux Relays terminals on
the IDNAC power supply are
controlled by two on-board
programmable relays. The
relay circuits are not
supervised
Chapter 4 IDNAC Power Supply
Table 4-9. Auxiliary Relays Specifications
2 A at 30 VAC or 30 VDC, resistive load.
Relay contacts are Form C dry contacts. Transorbs provide
suppression to Earth. Do not switch voltages greater than rating, or
damage may result.
Figure 4-4. Aux Relay Terminals
4-8
Page 27
Chapter 4 IDNAC Power Supply
A
B
C
D
Comm Loss
IDNAC TBL
LEDs
Scroll push
button (SW1)
Troubleshooting
Troubleshooting The code produced by the lit yellow indicator LEDs corresponds to a trouble that is either
occurring on the System or on the SLC Channels. See Table 4-10 for the 4007ES LED
definitions and Table 4-11 for the LEDs and their codes.
IDNAC Channel troubles are indicated by yellow LEDs labeled IDNAC TBL and letters A to
D. When the IDNAC TBL LED is lit, the IDNAC Channel is experiencing a trouble. Refer to
Table 4-1 for the trouble codes for LEDs A to D. The LED SCROLL pushbutton can be used to
scroll through multiple trouble indicators.
Table 4-10. 4007ES Indicator LEDs.
LED: A, B, C, DSignal various trouble conditions
on the 4007ES and its SLC.
Refer to Table 4-11 and
Table 4-12 for troubles details
IDNAC TBLWhen On steady, refer to Table
4-11 for detailed troubles
indicated by LEDs A-D
LED COMM Loss Indicates that the communica-
tion between the IDNAC power
supply and the CPU is lost
Scroll Push
Button (SW1)
Used to scroll through multiple
troubles, since only one trouble
can be displayed at a time.
SLC Channel
Trouble LED
Codes
Figure 4-5. LEDs on the 4007ES Power Supply
SLC Channel troubles are indicatedby LEDs A to D, as well as IDNAC. Refer to Table 4-11
for the description of the LEDs.
Table 4-11. SLC Channel Trouble LED Codes
IDNACABCD
IDNAC Channel Fail: The channel is not responding.
IDNAC Short Circuit: There is a short circuit on the channel.
IDNAC Duplicate Device: There are 2 devices on the channel
that have the same address.
IDNAC Missing device: There is a device programmed on the
channel that it cannot detect.
IDNAC Extra Device: The channel is detecting the address of
a device that has not been programmed.
IDNAC Wrong Device: The channel is detecting a device that
had been programed as the wrong “type”.
IDNAC Controller Fail: The channel can no longer detect the
controller.
IDNAC Address Out of Range: There is a device with an
unsupported address on the channel.
IDNAC Isolator Trouble: An isolator on the channel is open.
IDNAC Overcurrent: A device on the Channel is drawing too
much current.
IDNAC Earth Trouble: There is a positive or a negative earth
fault on the channel.
Description:
4-9
Page 28
Troubleshooting, Continued
Chapter 4 IDNAC Power Supply
System Trouble
LED Codes
System troubles are indicated by LEDs A to D.
Table 4-12. System Trouble LED Codes
ABCDDescription:
No Trouble: There are no troubles detected on the system.
AC Fail: The AC power is disconnected but the battery is working.
Low Battery: The battery voltage is under 22.8 V.
Battery Cutout: The Battery voltage is below 19.4 V. At this point, if jumper
P16 is set to “battery disconnect when depleted”, the system will shut down.
Depleted/Missing Battery: If jumper P16 is not set to “battery disconnect
when depleted”, this trouble will appear when the battery voltage is below
19.4 V. This code will also appear if the system cannot detect the battery.
Charger Trouble: There is a trouble with the battery charger.
Card Overcurrent: The module is drawing too much current.
Negative Earth: The circuit is shorted to ground on the negative wire.
Positive Earth: The circuit is shorted to ground on the positive wire.
Negative Earth on RUI: The RUI circuit is shorted to ground on the negative
wire.
Positive Earth on RUI: The RUI circuit is shorted to ground on the positive
wire.
City Circuit 1 Trouble: The trouble configured on the City Card’s circuit one
has been triggered.
City Circuit 2 Trouble: The trouble configured on the City Card’s circuit two
has been triggered.
AuxNAC Open: Depending on the chosen configuration, either the Aux circuit
or the NAC circuit is open.
AuxNAC Short: Depending on the chosen configuration, either the Aux circuit
or the NAC circuit is experiencing a short circuit.
AuxNAC Overcurrent: Depending on the chosen configuration, either the
Aux circuit or the NAC circuit is drawing too much current.
4-10
Page 29
Chapter 5
4007ES Power Supplies
IntroductionThis chapter describes the common sections of both the 4007ES Hybrid NAC power supply
and the 4007ES IDNAC power supply.
In this chapter
Power Supplies
Specifications
Wiring GuidelinesClass A wiring allows devices to communicate with the FACP even in the event of a single
Power Supplies Specifications.......................... 5-1Wiring Guidelines ....................... 5-1
open circuit somewhere on the loop. Class A wiring requires that two wires are routed from
the power supply to each device, and then back again to the power supply.
Class B wiring allows “T” tapping, and therefore requires less cable distance per installation
than Class A.
Auxiliary power only: Supervision must be provided if the auxiliary power circuit is to be
wired as a power-limited circuit. In order to connect a circuit using PL wiring, the devices
being powered must all be addressable, or a UL Listed EOL relay must be used to supervise
the circuit.
o
32
F - 120oF (0oC-49oC).
Up to 93% relative humidity at 90
densing.
o
F (32oC), non-con-
5-1
Page 30
IDNet Section
IDNet
B+ B- A+ A-
Chapter 5 4007ES Power Supplies
IDNet Section
Overview
Specifications
The power supply provides an isolated IDNet
channel. This section is compatible with IDNet
communicating initiating devices and allows the
system CPU to communicate with up to 250
peripheral devices, such as smoke detectors and
pull stations.
Figure 5-1. IDNet on the Power Supply
Table 5-1. IDNet Specifications
Up to 250 addressable IDNet devices and up to 43 coded piezo
Supports:
Electrical Specifications:
Channel Voltage
to Remote Devices
Earth Detection
Threshold:
Circuit Requirements:
LEDS:
For detailed information on LEDs troubleshooting, refer to Table 5-7 and Table 5-8 in the
Troubleshooting section.
sounders may be coded by the IDNet channel. Base panel
supports 100 points, with 75 additional points per additional
IDNet+ Loop Expansion Module (refer to manual 579-1106).
30 VDC (normal); 35 VDC Alarm.
Data rate is 3333 bps.
Output circuits are supervised and power-limited.
10k ohms minimum from either positive or negative terminals.
Refer to Table 3-2 for the IDNet current on a NAC power supply.
Refer to Table 4-2 for the IDNet current on a IDNAC power supply.
Device
Addressing
(Class A and
Class B)
The IDNet section can be wired as a Class A circuit or a Class B circuit.
Class A wiring provides an alternate communication path that allows communication to all
devices to be maintained when a single open circuit fault occurs. Class A wiring requires two
wires to be routed from the IDNet Primary Terminals (B+, B-) to each device, and then back to
the IDNet Secondary Terminals (A+, A-). Wiring is in/out, “T” tapping is not allowed.
Class B wiring allows “T” tapping. IDNet wiring is inherently supervised due to individual
device level communications. EOL resistors are not required.
5-2
Page 31
IDNet Section, Continued
XXXX ft maximum to
farthest device from
either end of loop
Device
Device
Device
Control Terminals
(Class A wiring example)
Device
Control Terminals
(Class B wiring example)
Device
Device
Total cable load
must not exceed
12,500ft (3,8km)
Device
Chapter 5 4007ES Power Supplies
Device
Addressing
(Class A and
Class B)
•If no remote isolators or isolator bases are on the loops, device addressing can be assigned
without concern for sequence.
•If remote isolators or isolator bases are on the loops, the required addressing approach
is to start from the “B” side and assign each successive isolator a higher address than the
isolator it precedes.
•For Class B wiring only, the “A” output and “B” output per loop are connected together
in parallel via a jumper.
Wiring Wiring Parameters
Table 5-2 identifies the IDNet wiring parameters that must be considered when installing this
card. For additional wiring information, refer to document 900-408, Simplex Addressable Fire
Alarm Panels Field Wiring Specifications.
Table 5-2. IDNet Wiring Parameters
IDNet Wiring Capacitance Parameters
ParameterValue
Maximum Supported Channel CapacitanceThe sum of line-to-line capacitance, plus the capacitance of
either line-to-shield (if shield is present) = 0.6 µF
IDNet Wiring Class A and Class B Limits
Channel LoadingUp to 125 devices126 to 250 devices
Max. resistance to compatible devices.
(Include the 2081-9044 Overvoltage
Protector resistance when applicable)
•The "maximum wiring distance" is the maximum
distance from both the IDNet control terminals (primary
and return) to the farthest device on the circuit. See
Figure 5-2.
•Maximum wiring distance is determined by either
reaching the maximum resistance, the maximum
capacitance, or the stated maximum distance,
whichever occurs first.
•The total circuit cable load (amount of cable used) must
not exceed 12,500ft (3,8km).
IDNet Wiring Considerations
using 2081-9044 Overvoltage
Protectors
(2081-9044 is UL listed to
Standard 1459, Standard for
Telephone Equipment)
External wiring must be shielded (for lightning suppression) and 2081-9044
Overvoltage Protectors must be installed at building exit and entrance locations.
For more information, refer to the Model 2081-9044 Overvoltage Protector Installation Instructions, 579-832.
Capacitance; each protector adds 0.006 µF across the connected line.
Resistance; each protector adds 3 ohms per line of series resistance; both IDNet wires
are protected; 6 ohms per protector will be added to total loop resistance.
Maximum distance of a single protected wiring run is 3270 ft (1 km).
Refer to document number 574-832, 2081-9044 Overvoltage Protector Installation Instructions, for additional information.
4000 ft (1219 m)2500 ft (762 m)
Figure 5-2. Maximum Wiring Distance
5-3
Page 32
IDNet Section, Continued
+
1
2
1212
IDNet
Devices
18 to 12 AWG
B+ B- A+ A-
B
B
A
A
P2
2
1
Position
3-5
Position
4-6
P2
B+ B- A+ A-
IDNet CIRCUIT A
B+
TB1
1
B- A+ A-
Devices
B+, B-
Terminals
2
1
4
3
Note: For Class B wiring only, up to 4 parallel wiring “T”
taps may be made at the output terminal blocks
B+ B- A+ A-
2
1
2 Circuit Configuration
4 Circuit Configuration
Different Circuit Configurations
B
B
A
A
P2
2
1
Position
1-3
Position
2-4
WiringClass A Wiring
To wire IDNet section as a Class A circuit.
1. Make sure the jumpers on P2 are set to positions 3-5 and 4-6.
2. Route the wiring from the IDNet Circuit Primary Terminals (B+, B-) on TB1 of the IDNet to
the corresponding inputs on the first device.
3. Route wiring from the first device to the next as in/out. See Figure 5-3. Repeat for each
device.
4. Route the wiring from the last device to the terminals A+, A- to the panel, maintaining
polarity.
5. Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield
at each end in the panel to prevent it from coming into contact with other components.
Metallic continuity of the shield must be maintained and insulated throughout the entire
length of the cable.
Chapter 5 4007ES Power Supplies
Figure 5-3. IDNet Class A Wiring
Class B Wiring
When wiring the circuit as Class B, both the B+, B- and A+, A- terminals are available for
parallel connections. Within the IDNet circuitry, A+ is connected to B+, and A- is connected to
B- so circuits can stem from either one. Additionally, two wires can be connected to each screw
terminal.
To wire IDNet as a Class B circuit:
1. Set the jumpers on P2 to positions 1-3 and 2-4.
2. Route wiring from the IDNet Circuit Primary Terminals (B+, B-) to the corresponding inputs
on the first device.
It is possible to add up to 4 circuits on the terminal block when using Class B wiring. See
Figure 5-4 for the diagram.
3. Route wiring from the first device to the next as in/out as shown in Figure 5-4. Repeat for
each device.
4. Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield
at each end (in the panel and at the last device in each run) in the panel to prevent it from
coming into contact with other components. Metallic continuity of the shield must be
maintained and insulated throughout the entire length of the cable.
Figure 5-4. IDNet Class B Wiring
5-4
Page 33
Auxiliary Power Section
AUX PWR/SNAC
+ -
733-894
10K EOLR
TYPICAL AUDIBLE/VISIBLE APPLIANCES
NAC -
NAC+
+ B
- B
IDNET
B+A+A-B-
RUI
B+A+A-B-
AUX PWR / SNAC
+-
Chapter 5 4007ES Power Supplies
AUX PWR/SNAC
Overview
The AUX PWR/SNAC terminal block is located
on the top left corner of the power supply.
Through the ES Panel Programmer, this point
can be configured as either a 24V Auxiliary
(AUX) power or as a simple reverse polarity
Notification Appliance Circuit (NAC). This
circuit does not support TrueAlert addressable
devices nor non-addressable smartsync
appliances.
The AUX PWR/SNAC is rated 2 A maximum.
Current used is deducted from the total available
power supply current.
Figure 5-5. AUX/SNAC Terminal
Table 5-3. AUX/SNAC Wiring Specification
Output rating:29.5 V maximum
Current Rating:2 A, maximum.
Earth Detection
Threshold
Wiring Gauge:18 AWG (min.)
Wiring Notes:
1. All wiring from the AUX/SNAC is power limited.
2. Conductors must test free of all grounds and stray voltages
before connection to appliances and panel.
3. Terminate Class B NACs as shown using 733- 894 EOL.
For Canadian applications, mount end-of-line resistor to
TEPG-US Model 431537 EOL plate in accordance with
ULC-S527.
4. If wiring is routed outside the building, use of a listed secondary protector is required. Use Simplex 2081-9028 (rated 5 A) or 20819044 (rated 0.2 A). A protector must be installed at each building exit/entrance. Each 2081-9028 adds 0.2 ohms wiring resistance.
2081-9044 adds 6 ohms wiring resistance, and will greatly reduce wiring distance.
10K ohms minimum from either
positive or negative terminals.
to 12 AWG (max.).
Figure 5-6. Simple NAC Wiring
Table 5-4. Simple NAC Wiring Limits
Alarm Current20 AWG18 AWG16AWG14 AWG12 AWG
Line Resistance
(Ohms)
0.25617 ft981 ft1560 ft2480 ft3944 ft14.00
0.50308 ft490 ft780 ft1240 ft1972 ft7.00
0.75206 ft327 ft520 ft827 ft1315 ft4.67
1.00154 ft245 ft390 ft620 ft986 ft3.50
1.25123 ft196 ft312 ft496 ft789 ft2.80
1.50103 ft163 ft260 ft413 ft657 ft2.33
1.7588 ft140 ft223 ft354 ft563 ft2.00
2.0077 ft123 ft195 ft310 ft493 ft1.75
Note: This Chart indicates the maximum distance for 1/4 -2A loads. Wiring distance is from the panel terminals to the last
appliance. Use of a 2081-9044 protector reduces wiring distance.
5-5
Page 34
Auxiliary Power Section, Continued
Chapter 5 4007ES Power Supplies
AUX PWR/SNAC
Overview
Output of AUX or NAC is 24V nominal. Minimum voltage is 19.5 @ minimum battery;
maximum is 29.5V. Aux Loads include the compatible 4007ES Annunciators series, 4090
series of IDNet ZAMs and IAMs and any listed device operating within the output limits of the
AUX. Calculate wiring loss for actual devices used. Compatible Appliances include 4904
series of free-run strobes, 4901 series non-smartsync horns, 4098 series TrueAlarm Sounder
Base and 4009 NAC extenders, used in reverse-polarity activation mode.
Maintain correct polarity on terminal connections. Do not loop wires under terminals.
If Class A is not used, configure jumpers P1 accordingly.
Shield wire is not required. Twisted wire is recommended for improved noise immunity.
2,500 feet (762 m) to device from PSU card.
10,000 feet (3,048 m).
Figure 5-8 depicts Class A and Class B wiring.
Figure 5-8. RUI Wiring to the Host Panel
5-7
Page 36
Chapter 5 4007ES Power Supplies
LEDs
Earth Fault+
Loop A Loop B Loop C
Earth Fault -
IDNet
Trouble
Comm
Trouble
Troubleshooting
TroubleshootingThe code produced by the lit indicator LEDs corresponds to a trouble occurring on the system.
See Table 5-7 for the IDNet LED definitions and Table 5-8 the 4007ES trouble messages.
Table 5-7. 4007ES System Indicator LEDs
Comm Trouble
IDNet trouble
Earth fault+Illuminates to indicate a positive earth fault.
Earth fault -Illuminates to indicate a negative earth fault.
IDNet LEDs:
A, B, and C
MessageDefinition
Normally off. Turns on steady if the IDNet is
not communicating with the FACP CPU.
Normally off. Illuminates to indicate a problem
with the IDNet channel:
• Channel failure.
• Line short.
• Class A failure or an open line.
Steady ON: Indicates an open or short condition on indicated loop.
Figure 5-9. LEDs on the 4007ES Power Supplies
Table 5-8. 4007ES System Trouble Messages
AC Fail AC power is not present or is too low for proper system operation.
Low Battery The battery voltage is below the 22.8 V nominal level by 10% or more.
Depleted/Missing
The battery is either below 19.4 V or completely undetected.
Battery
Card OvercurrentThe module is drawing more current than it should. Check for faults on the circuit.
Charger TroubleThe battery charger is either defective or being heavily loaded by batteries. Read charger
current at front panel, if charger current is approximately 1.4 A, batteries are likely loading
the charger. Remove battery connection and measure the output. If the output is 27.6 (or
close, temperature dependent), there is a possibility of depleted batteries or a bad set of
batteries. Allow batteries to charge or replace them if they do not take a charge.
If the current is ~1.4 A with batteries and charger voltage below 20 V, remove the
batteries and recheck the charger voltage. If the voltage is around ~27.3 V, then the
batteries are heavily depleted.
Extra DeviceAppears if one or more extra devices (i.e., devices that have not been configured for the
IDNAC or IDNet channel) are on the system. Only one message appears, regardless of
the number of extra devices found.
Earth Fault SearchComes up during the Earth Fault Search diagnostic function. Once the search is initiated,
the front panel display indicates how far along the search process has progressed (10%,
25%…75%), and then shows the results of the search. The result either identifies the
offending circuit or indicates that the earth fault could not be found. During the search of
circuits (IDNet, NAC,IDNAC, and aux power), system alarm and trouble processing is
suspended.
Positive EarthAppears when a positive earth fault is detected.
Negative EarthAppears when a negative earth fault is detected.
Short Circuit Appears when a short is detected on the IDNAC/NAC channel. This status clears
automatically when the short circuit is removed.
Channel FailAppears when each device on the IDNet channel has been configured, and when none of
the devices are communicating on the channel. This message does not appear if there
are no configured devices on the IDNAC channel.
5-8
Page 37
Chapter 6
Optional Modules and Cards
IntroductionThe 4007ES can be ordered with a variety of optional cards and modules, depending on the
Alarm Relay Card ................................. 6-2TrueInsight Service Gateway................ 6-2
Dual Class A Isolator............................ 6-2Example of Combinations..................... 6-2
The 8-point zone/relay card (4007-9801) mounts in the 4007ES panel. Up to four cards can be
added. Each card allows the monitoring of up to eight Class B or four Class A zones, or eight
relay contacts.
For more information on the 8-point zone/relay card, refer to manual 579-1103.
The 25V regulator module (4007-9802) regulates the panel power supply output received
from the NAC power supply (4007ES) or the IDNAC power supply (4007ES hybrid) to a
25VDC level. The 25VDC regulated output is isolated from the panel and complies with
power-limited requirements.
For more information on the 25V regulator module, refer to manual 579-812.
The IDNet+ loop expansion card (4007-9803) mounts directly on the IDNAC/NAC power
supply.Up to two cards can be added. Each card adds a single Class A/Class B IDNet+ loop
and increases the device capacity by 75 points.
For more information on the IDNet+ loop expansion card, refer to manual 579-1106.
LED ModuleThe LED module (4007-9805) allows the operator to view the simultaneous signaling of an
alarm and trouble conditions on up to 24 zones. All the LEDs have configurable colors, red or
yellow, except the LEDs in the last column, which are configurable as red or green.
For more information on the LED module, refer to manual 579-1105.
SDACT CardThe SDACT card (4007-9806) can be mounted in the 4007ES panel. It is used to notify a
central station when an event occurs, to report changes to a specific point, to be connected to a
transmitter for connection to a central station.
For more information, refer to manual 579-954.
City CircuitThe city circuit card with disconnect switches (4007-8907) and without disconnect switches
(4007-9808) are used to annunciate alarms and other urgent indications to remote facilities.
Each city circuit module has two configurable circuits (alarm, trouble, or supervisory
reporting) and supports Reverse Polarity and Local Energy Master Box Applications. Only
one city card can be installed per system. It is not available when an alarm relay is used.
For more information on city circuits cards, refer to manual 579-955.
6-1
Page 38
Chapter 6 Optional Modules and Cards
IDNet+ Loop
Expansion cards
Power Supply
Relay Module
Zone/Relay
Module
Zone/Relay
Module
DACT
Module
BLOCK E
BLOCK F
BLOCK J
BLOCK K
BLOCK C
BLOCK I
BLOCK G
BLOCK H
BLOCK D
Optional Modules and Cards, Continued
Alarm Relay CardThe Alarm relay card (4007-9809) is used to provide common unsupervised control functions
or indications for devices. Each relay module has three circuits (alarm, trouble, and supervisory
signals). It is not available when a city circuit card is used.
For more information on alarm relay card, refer to manual 579-955.
TrueInsight
Service Gateway
Dual Class A
Isolator
Example of
Combinations
The remote service gateway (4190-6104) sends data to a remote service monitoring facility to
detail troubles in the panel. When the data reaches the monitoring facility, a qualified
technician is notified via e-mail and can then begin diagnostic process remotely.
For more information on the remote service gateway, refer to manual 579-953.
The Dual Class A Isolator (DCAI) (4007-9804) card converts the Class B output of the IDNAC
SLC into two isolated Class A outputs.
For more information on the DCAI, refer to manual 579-1029.
Figure 6-1, Figure 6-2, and Figure 6-3 are examples of some of the combinations that can be
made in a 4007ES with the available optional cards and modules.
Figure 6-1. Example 1
6-2
Page 39
Optional Modules and Cards, Continued
25V Regulator
Module
TrueInsight
Module
IDNet+ Loop
Expansion cards
Power Supply
Zone/Relay
Module
City Circuit
Module
Zone/Relay
Module
Zone/Relay
Module
IDNet+ Loop
Expansion cards
Power Supply
City Circuit
Module
Dual Class A
Isolator Card
Example of
Combinations
Chapter 6 Optional Modules and Cards
Figure 6-2. Example 2
Figure 6-3. Example 3
6-3
Page 40
Page 41
Appendix A
ULC Programming Requirements
Common Earth
Fault Ground and
Common Trouble
Indicator
This application monitors a system pseudo that counts the number of ground faults or troubles
that occur on the system. Each time this counter increments (i.e. a ground fault or trouble
occurs), a yellow LED on the operator interface panel illuminates.
Step 1. Add a Custom Control equation to monitor all ground faults:
1. Click on the Custom Control Tab
2. Add a new Equation
3. Paste the following equation:
[INPUTS]
STATUS ON
A112 | ANALOG | COUNTER | GROUND TROUBLE COUNTER
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY |
[END OUTPUTS]
Note: P535 is shown as an example; use any digital point.
A-1
Page 42
ULC Programming Requirements
Common Earth
Fault Ground and
Common Trouble
Indicator
Step 2. Open Color User Interface Card Properties Dialog
1. Click on the Hardware Tab and expand the Unit 0, Box 1, Bay 1 icons to display the Color
User Interface Card. (Click on the + signs to the left of the Unit 0, Box 1, and Bay 1 icons to
expand them.)
Figure A-1. Selecting the Color User Interface Card
2. Right click on the Color User Interface card icon and select Properties.
3. Click on the Point Editing tab (see figure Figure A-2)
Figure A-2. The Display Tab: Display Checkbox
Step 3. Program the LED
1. Select one of the multicolor LEDs (3-2-1, 3-2-2, or 3-2-3) to program (Figure A-3).
2. Click on the Point Type drop down list box and select LEDYELLOW.
3. Click on the Mode drop down list box and select ON.
4. Enter P535 (or your chosen digital point number from the equation) (no spaces) in the
Reference Address field to program the LED for ground faults. OR
5. Enter A2 (no spaces) in the Reference Address field to program the LED to illuminate