![](/html/7f/7f9a/7f9afc07153fd601fdbaed8879054ada0ff28d2e63e019372a94e4aaef6a0400/bg1.png)
4007ES Fire Control Panels
UL, ULC, CSFM Listed; Fire Detection and Control with Addressable
FM, NYC Fire Dept Approved* Initiation and Addressable Notification
Features
Flexible standard combination of addressable
initiation and addressable notification
4.3” (109 mm) Diagonal color touchscreen display:
Convenient and intuitive user interface provides detailed
system status and individual point information
Supports dual language selection, including unicode
character languages
A custom background display appears when operation is
normal (see page 7 for details)
Includes a 3 A IDNAC SLC (signaling line circuit)
output power supply that provides enhanced power
delivery to addressable notification appliances:
A constant 29 VDC source voltage is maintained during
alarm, even during battery operation, allowing strobes to
operate at higher voltage with lower current and ensuring
a consistent current draw and voltage drop margin under
both primary power and secondary battery standby
Efficiencies include lower strobe currents, wiring
distances up to 2 to 3 times farther than with conventional
notification, support for more appliances per IDNAC SLC,
and smaller gauge wiring. This provides installation and
maintenance savings. with high assurance that appliances
will operate as normal during worst case alarm conditions
IDNAC SLCs are compatible with both TrueAlert ES and
TrueAlert addressable notification appliances, and remote
4009 IDNAC Repeaters to extend power and wiring
distance even farther and provide for up to 127 addressable
notification appliances
Power supply provides battery backup charging of up to
33 Ah; up to 18 Ah for cabinet mounted batteries and up
to 33 Ah batteries for mounting in close-nippled remote
battery cabinet
Electrically isolated IDNet+ addressable initiating
device SLC:
Provides built-in short circuit isolation for monitoring
and control of TrueAlarm analog sensors and IDNet
communications monitoring and control devices; for use
with either shielded or unshielded, twisted or untwisted
single pair wiring; outputs are Class A or Class B
Standard panel SLC provides up to 100 addressable
points; optional additional loop expansion modules
provide an additional isolated loop with short circuit
isolation for the IDNet+ channel; each loop expansion
module also provides an additional 75 addressable points
to the IDNet+ channel capacity for a total of up to 250
addressable points
Software Feature Summary:
Current and previous panel configuration are both
maintained in on-board memory to allow easy selection
of desired revision
An internal Ethernet service port and an internal serial
service port are available for service computer
connections to perform configuration updates,
downloads and uploads; report downloads, and system
software updates (Ethernet port only); the serial port
provides the connection for the optional TrueInsight
Module
S4007-0002-6 11/2015
4007ES Panel Front View
Software Feature Summary (Continued):
An internal USB interface allows a compatible portable
memory device (memory stick/thumb drive) to store job
revisions, update revised jobs and panel software, and
save detailed system reports from the panel without
requiring a service computer
Optional modules and connections include:
Point or Event DACT assembly that is compatible with
IP Communicators
Up to two additional IDNet+ addressable device output
loop connections with short circuit fault protection and
with 75 additional point capacity each
Front mounted 48 LED annunciator with custom label
inserts provides 24 Yellow LEDs, 20 Red LEDs, and
4 Red/Green LEDs; LEDs are programmable for up to
24 IDC zones of alarm and trouble annunciation or as
required for custom annunciation requirements
Dual Class A IDNAC Isolator (DCAI)
Remote LED annunciator support via RUI (remote unit
interface) communications port for use with unshielded,
twisted pair wiring (UTP)
Eight Point Zone/Relay Modules individually selectable
as IDC or relay rated 2 A @ 30 VDC (resistive)
Alarm relays and auxiliary relays
City connections, with or without disconnect switch
4003EC Voice Control Panels
4009 Series IDNAC Repeaters
Battery brackets for seismic area protection (see page 2)
General Mechanical:
Compact red or platinum cabinet for convenient surface
or semi-flush mounting; rated NEMA 1 and IP30
4007ES Listings reference:
UL 864, Fire Detection and Control (UOJZ)
ULC S527, Control Units for Fire Alarm Systems
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7165-0026:0378 for allowable values and/or conditions concerning material presented in this
document. NYC Fire Dept COA #6151. Additional listings may be applicable; contact your
local Simplex product supplier for the latest status. Listings and approvals under Simplex
Time Recorder Co. are the property of Tyco Fire Protection Products.
![](/html/7f/7f9a/7f9afc07153fd601fdbaed8879054ada0ff28d2e63e019372a94e4aaef6a0400/bg2.png)
Introduction
4007ES Series Fire Detection and Control Panels
provide extensive installation, operator, and service features
with point and module capacities suitable for a wide range of
system applications. The convenient and intuitive color
touchscreen provides easy access for typical system response
actions and for detailed system review or configuration
updates with password control to limit user access.
IDNet+ addressable initiation communications and IDNAC
addressable notification communications are standard
features. (Refer to data sheet S4007-0001 for 4007ES panels
providing conventional notification.)
Operator Interface
Convenient Status Information. With the locking door
closed, the glass window allows viewing of the display
status LEDs. The user interface is a 4.3” diagonal color
touchscreen LCD with separate status LEDs as shown
below.
LED indicators describe the general category of activity
being displayed with the LCD providing more detail. For the
authorized user, unlocking the door provides access to the
control functions and allows further inquiry by scrolling the
display for additional detail.
Operator Interface and Software Features
Convenient and detailed operator information is easily
accessed using a logical, menu-driven touchscreen
display with password access control
Multiple automatic and manual diagnostics for
maintenance reduction
Operator Interface Features (Continued)
Alarm and Trouble History Logs (up to 1000 entries for
each, 2000 total events) are available for viewing from
the display or to be downloaded to a service computer or
to the USB drive
Module level ground fault searching assists installation
and service by locating and isolating modules with
grounded wiring
WALKTEST silent or audible system test performs an
automatic self-resetting test cycle and supports up to 8
WALKTEST groups
Install Mode allows grouping of multiple troubles for
uninstalled modules and devices into a single trouble
condition (typical with future phased expansion); with
future equipment and devices grouped into a single
trouble, operators can more clearly identify events
from the commissioned and occupied areas
Mechanical Description
Locking door with polycarbonate window
Latching front panel assembly swings forward for
convenient internal access
Smooth box surfaces are provided for locally cutting
conduit entrance holes exactly where required
Modules are power-limited (except as noted, such as
relay modules)
Battery compartment (bottom) accepts two batteries,
up to 18 Ah, to be mounted within the cabinet without
interfering with module space; charger capacity is up
to 33 Ah; for batteries greater than 18 Ah, refer to
page 7 for external battery cabinet details
Cabinet assembly design has been seismic tested and
is certified to IBC and CBC standards as well as to
ASCE 7 categories A through F, requires battery
brackets as detailed on data sheet S2081-0019
Touchscreen Display with LED Status Indicators (approximately full size)
Alarm Indicator
red LED
Priority 2 Indicator
red LED
2 S4007-0002-6 11/2015
Supervisory
Indicator yellow LED
Alarm Silenced
Trouble Indicator
yellow LED
yellow LED
AC Power
green LED
Color Touchscreen LCD with
sample Fire Alarm List showing
3 Programmable LEDs with Custom
Label Insert; top two selectable as
Red or Yellow, bottom selectable as
Green or Yellow
![](/html/7f/7f9a/7f9afc07153fd601fdbaed8879054ada0ff28d2e63e019372a94e4aaef6a0400/bg3.png)
Operator Screen Reference
Main Menu Screen provides easy navigation to the function
required. Buttons A, B, and C have programmable functions.
Main Menu
May 27, 2015
12:24 PM
System Trouble Screen identifies active troubles with
custom labels displayed, arrows allow navigation through
the list
System Alarm Screen identifies active alarms with custom
labels displayed, arrows allow navigation through the list
Trouble Log Screen allows review of past troubles with
time stamp and point details shown.
Point Information Screen allows review of point details,
arrows allow navigation through the information.
User Access Login Screen controls access to panel
operations as determined per panel.
3 S4007-0002-6 11/2015