Simplex 4007-9201BA User guide

Page 1
4007ES Fire Control Panels
UL, ULC, CSFM Listed; Fire Detection and Control with Addressable FM, NYC Fire Dept Approved* Initiation and Addressable Notification
Features
Flexible standard combination of addressable initiation and addressable notification
4.3” (109 mm) Diagonal color touchscreen display:
Convenient and intuitive user interface provides detailed
system status and individual point information
Supports dual language selection, including unicode
A custom background display appears when operation is
normal (see page 7 for details)
Includes a 3 A IDNAC SLC (signaling line circuit) output power supply that provides enhanced power delivery to addressable notification appliances:
A constant 29 VDC source voltage is maintained during
alarm, even during battery operation, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby
Efficiencies include lower strobe currents, wiring
distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, and smaller gauge wiring. This provides installation and maintenance savings. with high assurance that appliances will operate as normal during worst case alarm conditions
IDNAC SLCs are compatible with both TrueAlert ES and
TrueAlert addressable notification appliances, and remote 4009 IDNAC Repeaters to extend power and wiring distance even farther and provide for up to 127 addressable notification appliances
Power supply provides battery backup charging of up to
33 Ah; up to 18 Ah for cabinet mounted batteries and up to 33 Ah batteries for mounting in close-nippled remote battery cabinet
Electrically isolated IDNet+ addressable initiating device SLC:
Provides built-in short circuit isolation for monitoring
and control of TrueAlarm analog sensors and IDNet communications monitoring and control devices; for use with either shielded or unshielded, twisted or untwisted single pair wiring; outputs are Class A or Class B
Standard panel SLC provides up to 100 addressable
points; optional additional loop expansion modules provide an additional isolated loop with short circuit isolation for the IDNet+ channel; each loop expansion module also provides an additional 75 addressable points to the IDNet+ channel capacity for a total of up to 250 addressable points
Software Feature Summary:
Current and previous panel configuration are both
maintained in on-board memory to allow easy selection of desired revision
An internal Ethernet service port and an internal serial
service port are available for service computer connections to perform configuration updates, downloads and uploads; report downloads, and system software updates (Ethernet port only); the serial port provides the connection for the optional TrueInsight
4007ES Panel Front View
Software Feature Summary (Continued):
An internal USB interface allows a compatible portable
memory device (memory stick/thumb drive) to store job revisions, update revised jobs and panel software, and save detailed system reports from the panel without requiring a service computer
Optional modules and connections include:
Point or Event DACT assembly that is compatible with
IP Communicators
Up to two additional IDNet+ addressable device output
loop connections with short circuit fault protection and with 75 additional point capacity each
Front mounted 48 LED annunciator with custom label
inserts provides 24 Yellow LEDs, 20 Red LEDs, and 4 Red/Green LEDs; LEDs are programmable for up to 24 IDC zones of alarm and trouble annunciation or as required for custom annunciation requirements
Dual Class A IDNAC Isolator (DCAI) Remote LED annunciator support via RUI (remote unit
interface) communications port for use with unshielded, twisted pair wiring (UTP)
Eight Point Zone/Relay Modules individually selectable
as IDC or relay rated 2 A @ 30 VDC (resistive)
Alarm relays and auxiliary relays City connections, with or without disconnect switch 4003EC Voice Control Panels 4009 Series IDNAC Repeaters Battery brackets for seismic area protection (see page 2)
General Mechanical:
Compact red or platinum cabinet for convenient surface
or semi-flush mounting; rated NEMA 1 and IP30
4007ES Listings reference:
UL 864, Fire Detection and Control (UOJZ) ULC S527, Control Units for Fire Alarm Systems
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0378 for allowable values and/or conditions concerning material presented in this document. NYC Fire Dept COA #6151. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Module
S4007-0002-6 11/2015
Page 2
Introduction
4007ES Series Fire Detection and Control Panels
provide extensive installation, operator, and service features with point and module capacities suitable for a wide range of system applications. The convenient and intuitive color touchscreen provides easy access for typical system response actions and for detailed system review or configuration updates with password control to limit user access.
IDNet+ addressable initiation communications and IDNAC addressable notification communications are standard features. (Refer to data sheet S4007-0001 for 4007ES panels providing conventional notification.)
Operator Interface
Convenient Status Information. With the locking door
closed, the glass window allows viewing of the display status LEDs. The user interface is a 4.3” diagonal color touchscreen LCD with separate status LEDs as shown below.
LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door provides access to the control functions and allows further inquiry by scrolling the display for additional detail.
Operator Interface and Software Features
Convenient and detailed operator information is easily
accessed using a logical, menu-driven touchscreen display with password access control
Multiple automatic and manual diagnostics for
maintenance reduction
Operator Interface Features (Continued)
Alarm and Trouble History Logs (up to 1000 entries for
each, 2000 total events) are available for viewing from the display or to be downloaded to a service computer or to the USB drive
Module level ground fault searching assists installation
and service by locating and isolating modules with grounded wiring
WALKTEST silent or audible system test performs an
automatic self-resetting test cycle and supports up to 8 WALKTEST groups
Install Mode allows grouping of multiple troubles for
uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with future equipment and devices grouped into a single trouble, operators can more clearly identify events from the commissioned and occupied areas
Mechanical Description
Locking door with polycarbonate window Latching front panel assembly swings forward for
convenient internal access
Smooth box surfaces are provided for locally cutting
conduit entrance holes exactly where required
Modules are power-limited (except as noted, such as
relay modules)
Battery compartment (bottom) accepts two batteries,
up to 18 Ah, to be mounted within the cabinet without interfering with module space; charger capacity is up to 33 Ah; for batteries greater than 18 Ah, refer to page 7 for external battery cabinet details
Cabinet assembly design has been seismic tested and
is certified to IBC and CBC standards as well as to ASCE 7 categories A through F, requires battery brackets as detailed on data sheet S2081-0019
Touchscreen Display with LED Status Indicators (approximately full size)
Alarm Indicator
red LED
Priority 2 Indicator
red LED
2 S4007-0002-6 11/2015
Supervisory
Indicator yellow LED
Trouble Indicator
yellow LED
Alarm Silenced
yellow LED
AC Power
green LED
Color Touchscreen LCD with
sample Fire Alarm List showing
3 Programmable LEDs with Custom
Label Insert; top two selectable as
Red or Yellow, bottom selectable as
Green or Yellow
Page 3
Operator Screen Reference
Main Menu Screen provides easy navigation to the function
required. Buttons A, B, and C have programmable functions.
Main Menu
May 27, 2015
12:24 PM
System Trouble Screen identifies active troubles with custom labels displayed, arrows allow navigation through the list
System Alarm Screen identifies active alarms with custom labels displayed, arrows allow navigation through the list
Trouble Log Screen allows review of past troubles with time stamp and point details shown.
Point Information Screen allows review of point details, arrows allow navigation through the information.
User Access Login Screen controls access to panel operations as determined per panel.
3 S4007-0002-6 11/2015
Page 4
IDNet+ Addressable Device Control
Overview. The 4007ES provides an IDNet+ addressable
initiating device Signaling Line Circuit (SLC) that supervises wiring connections and the individual device communications status on the SLC. With 2-wire IDNet+ SLCs, initiation, monitoring, and control devices such as manual fire alarm stations, TrueAlarm sensors, control relays, and sprinkler waterflow switches can communicate their identity and status and receive fire alarm system control. Additional addressable interface modules include circuit isolators, conventional IDC zone adapters, and interface to other system circuits such as fans, dampers, and elevator controls.
TrueAlarm heat sensors can be selected for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also available, typically to provide freeze warnings or alert to HVAC system problems. Readings can selected as either Fahrenheit or Celsius.
TrueSense Early Fire Detection. Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 40070ES IDNet+ address. The panel evaluates smoke activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet
IDNet+ Addressable Device Operation
Each addressable device on the IDNet+
communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Both Class B and Class A operation is available. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuits for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications poll and can be turned on steady from the panel. With addressable devices, the location and status of the connected device is monitored, logged, and displayed on the operator interface LCD with each device having its own 40 character custom label for precise identification.
TrueAlarm Addressable Sensor Operation
Addressable initiating device communications
include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.
TrueAlarm Addressable Sensor Reference
S4098-0024.
Diagnostics and Default Device Type
Sensor Status. TrueAlarm operation allows the control
panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor. CO Sensors track their 10 year active life status providing indicators to assist with service planning. Indicators occur at: 1 year, 6 months, and end of life.
Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.
IDNet+ Device Wiring Reference
IDNet+ Addressable Channel Capacity. The
4007ES provides an isolated output IDNet+ signaling line circuit (SLC) that supports up to 250 addressable monitor and control points intermixed on the same pair of wires. (250 total requires two 4007-9803 IDNet+ Loop Expansion Modules.)
IDNet+ SLC Wiring Specifications
Maximum Distance from Control Panel per Device Load
Total Wire Length Allowed With “T” Taps for Class B Wiring
Maximum Capacitance Between IDNet+ Channels
Loading per device
Wire Type and Connections
Connections
Compatibility includes: IDNet communicating devices and TrueAlarm sensors including QuickConnect and QuickConnect2 sensors; see data sheet S4090-0011 for additional reference
* Some applications may require shielded wiring. Review your
system with your local Simplex product supplier.
0 to 125 4000 ft (1219 m); 50 ohms
126-250 2500 feet (762 m); 35 ohms
Up to 12,500 ft (3.8 km);
0.60 µF
1 µF
0.8 mA supv., 1 mA alarm; 2 mA per activated device LED
Shielded or unshielded, twisted or untwisted wire*
Terminal blocks for 18 to 12 AWG
TrueAlarm Photo
Sensor with Base
TrueAlarm Photo/Heat
Sensor in CO Base
Programmable sensitivity of each sensor can be selected at the control panel for different levels of smoke obscuration (shown directly in percent) or for specific heat detection levels. To evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read (or downloaded as a report) and compared to the alarm threshold directly in percent.
CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one system address. The CO sensor can be enabled/disabled, and can be used in LED/Switch modes and custom control. (refer to data sheet S4098-0052 for details)
4 S4007-0002-6 11/2015
Page 5
IDNAC SLC Control of TrueAlert and TrueAlert ES Addressable Notification
Addressable notification appliance communications
include operation of TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible only (A/O, horn), Audible/Visible (A/V, horn/strobe), and strobes of Speaker/Visible (S/V) notification appliances. (S/V appliances require separate speaker wiring.) IDNAC SLC addressable communications allow each horn and strobe to be individually controlled using a single two-wire circuit, confirms the wiring connections to the individual notification appliance’s electronic circuit, and confirms communications between each appliance and the fire alarm control panel. Addressable communications increases supervision integrity versus conventional notification systems by providing supervision beyond the circuit wiring to each individual appliance and by constantly verifying the ability of each appliance to communicate with the control panel.
Individual Appliance Status and Settings. The fire alarm control panel monitors and records each addressable notification appliance status, type of appliance, and its configured appliance settings. A fault in any individual appliance automatically reports a trouble condition to the control panel.
TrueAlert ES Addressable Appliance Reference
problem. Using the TrueAlert magnet test allows each appliance to individually identify its candela setting and address and to briefly operate if desired, and using the TrueAlert ES
Appliance Self-Test feature provides detailed performance verification per appliance.
TrueAlert ES Appliance Self-Test Operation
On-Board Test Sensors. TrueAlert ES appliances are
equipped with on-board sensors to detect strobe and/or horn output allowing efficient and unobtrusive Self-Testing. When Automatic Self-Test is initiated from the control panel, each appliance within the selected VNAC group will briefly operate and then report its Self-Test status to the control panel, all within several seconds. Silent Self-Test can be selected to test only visible appliance if desired. The control panel is in a trouble condition during testing and in the event of an alarm, Self-Test is automatically terminated.
Automatic Self-Test results are communicated to the control panel with a time and date stamp and are stored in memory. Results are viewable at the front panel display and printed reports are available from the panel USB port. (See sample reports on page 10.)
Individual Self-Test is selected from the control panel when individual appliances need to be observed to operate. Each appliance in the selected VNAC group will turn on its LED until individually activated by applying a magnet. After performing the individual test, the appliance LED turns off to
A/O (horn) V/O (strobe) A/V (horn/strobe)
Virtual NACs Provide Control Convenience. For control convenience, IDNAC notification appliances can be grouped into Virtual NACS (VNACs) for group control.
Panel Control Convenience. Applicable operation settings for each appliance can be programmed without having to replace appliances or remove them from the wall or ceiling. An appliance’s VNAC notification zone can be easily changed through programming without having to add additional circuits, conduit, and wiring. Audible and visible appliances for non-Fire Emergency Communications notification can be programmed to operate separately on the same pair of wires as the fire alarm notification appliances. The result is lower installation, retrofit, and overall life-cycle cost of ownership compared with traditional conventional notification systems.
Installation, Retrofit, and Life-Cycle Cost Benefits. With each addressable appliance capable of being controlled separately on the same two-wire IDNAC SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T-tapped” allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency.
Location Information, Diagnostics and Troubleshooting. Each addressable notification appliance
has its own 40 character custom label to identify the location of the appliance and to aid in troubleshooting fault conditions. In conventional notification systems, conventional appliances are not capable of communicating with the control panel. Fault reporting on a conventional system is limited to the circuit wiring and the entire area (zone) covered by appliances on the notification appliance circuit (NAC) making it much more difficult and costly to locate and correct the source of a
5 S4007-0002-6 11/2015
indicate completion. Results are recorded the same as during the automatic test.
IDNAC SLC Hardware Reference
The 4007ES provides a 3 A IDNAC SLC for control and
power to TrueAlert ES and TrueAlert addressable notification appliances. The power supply incorporates an efficient switching design that provides a regulated output of 29 VDC, even during battery operation. With 29 VDC minimum output at the panel, addressable notification SLCs can support wiring distances 2 to 3 times farther than available with conventional notification, or support more appliances per SLC, or work with smaller gauge wiring, or combinations of these benefits. The result is installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.
IDNAC SLC Appliance Wiring Reference
Recommended wire type UTP, unshielded twisted pair
Up to 127 addresses and up to 139 unit loads
IDNAC SLC Capacity
Maximum wire length allowed with “T-Taps” for Class B wiring, per SLC
Maximum wire length per SLC to any appliance
Appliance Supervisory Current
Wiring connections Terminal blocks for 18 to 12 AWG
(appliances are typically one unit load, devices such as Isolators may require more than one load, refer to individual device data sheet for specific information)
10,000 ft (3048 m)
4000 ft (1219 m)
1 unit load = 0.8 mA per appliance
Page 6
Power Supply Output and Zone/Relay Module Details
Power Supply Output Details:
RUI Communications controls up to 10 remote devices
Power Supply Output Details (Continued):
Battery and Charger Monitoring includes battery
at up to 2500 ft (762 m) for single run, or 10,000 ft (3048 m) total if wiring is Class B and T-tapped; output is selectable as Class B or Class A
Compatible RUI remote equipment includes:
4606-9202 and 4606-9205 Color Touchscreen Annunciators (up to 6 total), 4100 Series 24 I/O and
Low Battery Voltage Cutout is selectable when
LED/Switch modules, 4602 Series LED/Switch and I/O Annunciator modules, including 4602-9101 Status
4 A Output Rating. This includes current for: IDNAC
Command Units (SCU), and 4602-9102 Remote Command Units (RCU)
IDNet+ SLC Output provides electrically isolated
Class B or Class A communication; standard capacity is up to 100 addressable points with expansion for up to
2 A Auxiliary Output (AUX/SNAC) can be selected
250 points using up to two 4007-9803 IDNet+ Loop Expansion Modules (as described on page 4)
Battery Charger is dual rate, temperature
compensated, and charges up to 18 Ah sealed lead­acid batteries in the battery compartment, and charges up to 33 Ah batteries in an external cabinet
Product Selection
Model* Color Description
4007-9201(BA) Red
4007-9202(BA) Platinum
* Models with (BA) are available assembled in the USA by adding the suffix “BA”.
4007ES with a 3 A, Class B, IDNAC SLC for up to 127 addressable notification appliances, and 4 A output power supply/battery charger; includes IDNet+ communications for 100 addressable points Note: Add optional module and other currents separately for battery calculations; base panel current does not subtract from the 4 A power available for optional modules and external loads
charger status and low or depleted battery conditions; status information provided to the master controller includes analog values for: battery voltage, charger voltage and current, actual system voltage and current, and IDNAC SLC current
required (required for ULC listing applications)
controlled notification appliances; IDNet devices; module currents; and auxiliary output current (battery charging, CPU, and power supply current are not subtracted from the 4 A)
either as resettable auxiliary power of 2 A @ 24 VDC, or selected to be a simple NAC (SNAC) for sounder base power, 4-wire detector power, or door holder power
Supv. Alarm
180 mA 185 mA
Module and Accessories Selection Information
Factory Programming Options
Field Installed Optional Modules (refer to diagram on page 8 for module locations)
Model Description Supv. Alarm
4007-9801
4007-9802
4007-9803
4007-9804
4007-9805
4007-9806
4007-9807 City Circuit Module with Disconnect Switch 20 mA 36 mA 4007-9808 City Circuit Module without Disconnect Switch 20 mA 36 mA 4007-9809 Relay Module; relays for Alarm, Supervisory, and Trouble; rated 2 A resistive @ 32 VDC 15 mA 37 mA
Model Description
4007-8810 Factory Programming (select)
4007-0831 Custom Labels and Programming (requires 4007-8810)
Eight Point Zone/Relay Module; each point is selectable as an IDC input or Relay output, Class A IDCs require 2 points (one out and one return); select up to 4 maximum; current shown is for 8 Class B IDCs with 4 in alarm, detector current is added separately (refer to 4007ES Hybrid data sheet S4007-0001 for additional information)
25 VDC Regulator Module; 2 A maximum output; use to power Zone/Relay modules connected to initiating devices requiring nominal 25 VDC voltage; refer to technical publication 579-832, 2-Wire Detector Compatibility Chart for application details
IDNet+ Loop Expansion Module; provides an additional isolated loop with short circuit isolation to the existing IDNet+ channel, also provides an additional 75 addressable points to the IDNet+ channel capacity, maximum of two Dual Class A IDNAC Isolator (DCAI); converts a single Class B IDNAC SLC input to two Class A or two Class B SLC outputs; provides short circuit isolation between each Class A or B output circuit; requires one IDNAC address; the total current remains controlled by the Class B input source SLC at 3 A maximum
Panel Mounted 48 LED Status Annunciator Module; provides 24 Yellow LEDs, 20 Red LEDs, and 4 Red/Green LEDs that are programmable for up to 24 IDC zones of alarm and trouble annunciation, or as required for custom annunciation requirements
SDACT Module for Point or Event Reporting; order 2080-9047 connection cables as required (see cable details under accessories)
with 1 module 190 mA 445 mA
with 2 modules 290 mA 801 mA
with 3 modules 390 mA 1156 mA
no LEDs on 10 mA 10 mA
with
LEDs on
83 mA
max
NA NA
8.3 mA 18.5 mA
1.75 mA per LED,
30 mA 40 mA
continued on next page
350 mA
max
105 mA max
6 S4007-0002-6 11/2015
Page 7
Module and Accessories Selection Information (Continued)
Field Installed Optional Modules
Model Description Supv. Alarm
4190-8001* TrueInsight Remote Service Gateway Module and Programming Selection
4190-6106 *
4190-4016 *
* Refer to data sheet S4100-0063 for additional TrueInsight Service Gateway details
TrueInsight Remote Service Gateway Module Installation Kit; includes module and harness; configured for dynamic IP address operation unless ordered with 4190-4016
TrueInsight Remote Service Gateway Module for fixed IP Addressing; optional, select if application will use fixed IP address
Required Selection
62 mA 73 mA
Batteries
Model Capacity Battery Mounting Details
2081-9272 6.2 Ah 2081-9274 10 Ah 2081-9288 12.7 Ah 2081-9275 18 Ah 2081-9287 25 Ah For remote mount in Battery Box 4009-9801
2081-9276 33 Ah For remote mount in Battery Box 4009-9802
12 V Batteries for cabinet mounting; select one battery model per system standby requirements; order quantity of two; to be wired in series for 24 VDC
Batteries for remote mounting; see battery cabinet details below
Battery Accessories
Model Color Capacity Dimensions Description
4009-9801 Beige
4009-9802 Beige
For up to 25 Ah batteries For up to 33 Ah batteries
16 ¼” W x 13 ½” H x 5 ¾” D (413 mm x 343 mm x 146 mm) 25 ¾” W x 20 ¾” H x 4 ” D (654 mm x 527 mm x 105 mm)
External battery cabinet without charger, with locking solid door and battery harness; for close-nippled mounting to fire alarm control panel cabinet
Accessories
Model Description
2080-9047 DACT cable, 14 ft (4.3 m) long, RJ45 plug one end, spade lugs on the other; order one per phone line connection required 2975-9812 Red semi-flush box trim; 1 7⁄16” (37 mm) wide, four corners and trim pieces for top, bottom, and sides 2975-9813 Platinum semi-flush box trim; 1 7⁄16” (37 mm) wide, four corners and trim pieces for top, bottom, and sides 4081-9018 10 k, 1 W end-of-line resistor harness for Class B non-addressable initiating zones (if 4007-9801 is used)
2081-9031
Series resistor for WSO, non-addressable IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 , 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2 ½” L x 1 ” W x 1” H (64 mm x 35 mm x 25 mm)
General Specifications
Input Power
4007ES Power Supply Output Ratings
Compatible Special Application Appliances
Battery Charger Ratings
(sealed lead-acid batteries)
Custom Background Display Details
Environmental
Operating Temperature 32° to 120°F (0° to 49° C)
120 VAC Input 2 A maximum @ 102 to 132 VAC, 50/60 Hz 240 VAC Input 1 A maximum @ 204 to 264 VAC, 50/60 Hz
Battery 6 A maximum @ 24 VDC (during battery operation)
4 A output for “Special Application” appliances
Power Supply Output Rating
IDNAC SLC Ratings
IDNAC SLC Wiring
Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)
Battery capacity range
Charger characteristics
and performance
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Note: The 4 A output rating was determined such that optional module currents, and external device and appliance currents can be directly added together, not to exceed 4 A total.
3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit loads; DC-DC converter circuit is >92% efficient over operating range Output terminals are rated for 18 to 12 AWG with duplicate output terminals rated for two wires each, allowing up to four (4) Class B branch circuit T-taps to be made in the cabinet; additional T-taps may be made in external wiring junction cabinets or boxes
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex product representative for compatible appliances
UL and ULC listed for battery charging of 6.2 Ah up to 33 Ah (batteries larger than 18 Ah require a remote battery cabinet) Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Supported file types: JPG, BMP, GIF, and PNG Recommended image type is JPG, recommended image size is 480 x 240, and the file size limit is 100 kb
Output switches to battery backup during mains AC failure or brownout conditions
Additional Technical Reference
Description Document Description Document
Installation Manual 579-1102 Single Page Operator Instructions 579-1109 Zone/Relay Module Installation Manual 579-1103 4007ES Hybrid Data Sheet S4007-0001 Detailed Operator’s Manual 579-1165
7 S4007-0002-6 11/2015
Page 8
4007ES Mounting and Module Location Reference
21-1/8" (537 mm)
10
11
2
1
20-7/8" (530 mm)
16" (406 mm)
3
3
4 5
6
20-3/16"
(512 mm)
7
9
8
20-7/16"
(519 mm)
Finished wall surface (including
Exposed box for semi-flush mounting
Side View Reference
semi-flush Trim Kit if used)
1-3/4" (44 mm) minimum
4-7/16" Deep (112 mm)
Module Locations:
1. Primary location for 4007-9801 Zone/Relay Module, or 4190-6106 TrueInsight Remote Service Gateway.
2. Location for a 4007-9802, 25 V Regulator Module (shown), a 4007-9804 IDNAC Dual Class A Isolator, or an additional 4007-9801 Zone/Relay Module.
3. 4007-9803 IDNet+ Loop Expansion Modules, maximum of two (two are shown).
4. IDNAC Power Supply Assembly.
5. Location for additional 4007-9801 Zone/Relay Module.
6. Location for additional 4007-9801 Zone/Relay Module.
7. 4007-9807 or 4007-9808 City Circuit Module, or 4007-9809 Relay Module.
8. Battery location for up to 18 Ah batteries. Note: No conduit entry or wiring in this area, 14-7/8” (378 mm) wide.
9. 4007-9806 SDACT location.
10. CPU and User Interface assembly.
11. Location for optional 4007-9805 LED Module.
NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be
made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.
8 S4007-0002-6 11/2015
Page 9
S
4007ES Additional Reference
4007ES with IDNAC Notification and optional 48 LED
Annunciator Module (4007-9805)
4606-9205 (Platinum) Color LCD
Touchscreen Remote Annunciator
4606-9202 (Red) Color LCD
Touchscreen Remote Annunciator
4007E
with IDNAC Notification Operator View with door open
Additional Compatible Equipment and Reference
Subject Data Sheet Subject Data Sheet
4009 IDNet NAC Extender S4009-0002 Battery and Battery Cabinet Reference S2081-0006
4003EC Voice Control Panel S4003-0002 Seismic Battery Brackets Reference S2081-0019
4606 Series Color LCD Touchscreen Remote Annunciator
Graphic I/O Modules S4100-0005 Serial DACT (SDACT) S2080-0009
4602 Series SCU/RCU S4602-0001
9 S4007-0002-6 11/2015
S4606-0003
Addressable Device Compatibility, IDNet Communication Sensors and Devices
TrueInsight Remote Service S4100-0063
S4090-0011
Page 10
)
01-
JUN-
15N
N
01-
JUN-
15N
N
01-
JUN-
15N
N
01-
JUN-
15N
N
01-
JUN-
15N
N
01-
JUN-
15N
U
01-
JUN-
15N
N
01-
JUN-
15N
N
12-
MAY-15
N
N
01-
JUN-
15N
N
01-
JUN-
15N
N
12-
MAY-
15N
N
01-
JUN-
15N
N
01-
JUN-
15N
U
12-
MAY-
15N
U
12-
MAY-
15U
U
TrueAlert ES Appliance Self-Test Last Test Results Report Example
Service Port Page 1
REPORT 10 TrueAlertES Self-Test Report 12:34:56pm MON 01-JUN-15
Point ID Custom Label Date Visual Audible
T1-1-1 VO FIRST FLOOR (up to 40 characters T1-2-5 AV FIRST FLOOR EAST WING T7-3-55 AO SECOND FLOOR EAST WING T8-2-45 AV SECOND FLOOR ROOM 29 T8-2-60 AV SECOND FLOOR ROOM 22 T1-2-4 AO FIRST FLOOR ROOM 17 TRUEALERT_ES SELF-TEST REPORT COMPLETED
Press RETURN for next Screen OR CTRL-X to abort
O OUT O OUT
/A
OT TST
ORMAL
/A
/A ORMAL O OUT
/A ORMAL NSUPP
Results Description: NORMAL = works correctly NO OUT = No Output, no light or sound was detected NOT TST = no result; either the appliance did not return a result before the test ended or the test was conducted as silent (strobes
only) and audible appliance was not activated
N/A = not applicable (no strobe on audible only, etc.) UNSUPP = appliance not compatible with Self-Test (TrueAlert addressable appliance not TrueAlert ES addressable appliance)
Note: Additional TrueAlert ES Self-Test information is detailed in Operating Instructions 579-1165 shipped with the panel.
TrueAlert ES Appliance Self-Test All Test Results Report Example
Service Port Page 1
REPORT 10 TrueAlertES Self-Test Report 12:34:56pm MON 01-JUN-15
Point ID Custom Label Date Visual Audible
T1-1-1 VO FIRST FLOOR T1-2-5 AV FIRST FLOOR EAST WING T1-2-6 AV FIRST FLOOR NORTH ENTRANCE T7-3-55 AO SECOND FLOOR EAST WING T8-2-45 AV SECOND FLOOR ROOM 29 T1-1-11 AV FIRST FLOOR SOUTH ENTRANCE T8-2-60 AV SECOND FLOOR ROOM 22 T1-2-4 AO FIRST FLOOR ROOM 17 T1-2-7 AO FIRST FLOOR ROOM 12 T8-3-43 AV SECOND FLOOR ROOM 25 TRUEALERT_ES SELF-TEST REPORT COMPLETED
Press RETURN for next Screen OR CTRL-X to abort
O OUT O OUT O OUT
/A
OT TST
ORMAL ORMAL
/A /A
NSUPP
/A ORMAL ORMAL O OUT
/A ORMAL ORMAL NSUPP NSUPP NSUPP
TrueAlert ES Appliance Self-Test Individual Appliance Report Example
CUSTOM LABEL 4-1-2 AV POINT ADDRESS: 4-1-2 Type: AV CARD: 4 CHANNEL: 1 DEVICE: 2 EXTENDED POWER SUPPLY UNIT NUMBER: 2
PRIMARY STATUS NORMAL AUDIBLE GROUP CONFIG: 0 0 0 VISUAL GROUP CONFIG: 0 0 0 STYLE: INDOOR OPERATION: GENERAL EVAC CANDELA RATING 15 CD COLOR LENS YES TONE TYPE BROADBAND CODING TYPE TEMPORAL VOLUME HIGH LAST TEST TIME: MON 01-JUN-15 01:00 AM LAST VISUAL TEST: NORMAL LAST AUDIBLE TEST: NORMAL LAST TEST VOLUME: NORMAL DEVICE TEST TROUBLE: NORMAL
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4007-0002-6 11/2015
www.simplex-fire.com
© 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
RUI NUMBER: LOCAL
Loading...