Simplex 4006 Series User Manual

Page 1
LifeAlarm Fire Alarm Control Panels
UL, ULC, CSFM Listed; FM Approved; 4006 Series Fire Alarm Control Panels MEA (NYC) Acceptance* Providing up to Ten IDCs and Four NACs
Features
Control panel operator convenience features:
Wide viewing angle 2 x 20 (40 character) alphanumeric
LCD and dedicated LEDs provide convenient panel status information
Operation is programmable using a multi-function
RS-232 service port provides upload/download PC
access for panel configuration and event history logs
Software updates are via PC download Convenient library of standard custom label terms Standard on-board DACT provides: Contact ID, 3/1, 4/2,
BFSK, and SIA formats
WALKTEST silent or audible system test Voltage and current for both the battery charger and the
battery can be displayed at the front panel LCD
Five Standard Initiating Device Circuits (IDCs):
Five Class B IDCs with optional expansion to ten, all
with individual zone disable
Monitor 2-wire or 4-wire initiating devices including
TrueAlarm smoke detectors
Optional Class A Adapter Module
4006-9102 (Beige) Standard Control Panel
FIRE
SYSTEM
ALARM
SUPERVISORY
ALARM
SUPV
ACK
ACK
Fire Alarm Annunciator
FIRE
SYSTEM
ALARM
SUPERVISORY
ALARM
SUPV
ACK
ACK
SYSTEM
ALARM
TROUBLE
SILENCEDACPOWER
TROUBLE
ALARM
SYSTEM
ACK
SILENCE
RESET
SYSTEM
ALARM
TROUBLE
SILENCEDACPOWER
TROUBLE
ALARM
SYSTEM
ACK
SILENCE
RESET
CAUTION
DISCONNECT
BATTERY AND A. C. POWER
SERVICING
BEFORE
Two Standard Notification Appliance Circuits (NACs):
Class A or Class B outputs with solid state overcurrent
protection per NAC, each rated for 2 A
®
Selectable for Simplex
SmartSync two-wire
horn/strobe control or synchronized strobe control
Standard Power Supply:
Provides 3 A maximum @ nominal 24 DC Automatic input power selection operates with 120 VAC
or 240 VAC, 50 or 60 Hz
On-board temperature compensated battery charger for
up to 12.7 Ah batteries in cabinet (UL and ULC) and up to 25 Ah batteries in separate cabinet (UL only)
Additional standard features:
Programmable Active Status Reminder Two auxiliary relays IDCs, NACs, and Relay outputs are power limited (AC
input, battery circuits, and City Circuit Module outputs are non-power limited)
Available with beige or red cabinet UL listed to Standard 864
Available option modules:
Door mounted 24 LED annunciator (standard on ULC
models)
3 A Expansion Power Supply with two on-board 2 A
NACs that operate the same as standard NACs
S4006-0001-8 8/2012
4006-9122 (Beige) Control Panel with 24 LED Annunciator
Available option modules (Continued):
Expansion IDC module with five Class B IDCs Class A IDC Adapter Module, City Interface Module,
and Auxiliary Relay Module
Remote LCD and LED/Switch Annunciators
Description
For areas requiring from five to ten initiating zones, the Simplex 4006 Series fire alarm control panels provide flexible initiating circuit monitoring, extensive programmable control capability, and LCD annunciated circuit-specific 20 character custom labels.
See page 2 for additional ULC and MEA information. This product has been approved by
*
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:318 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Additional listings may be applicable, contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Page 2
Standard Feature Details
Five Class B IDCs are each capable of supporting up to 30
Simplex current-limited smoke detectors or electronic heat detectors (see list on page 4) as well as manual stations and other compatible contact closure initiating devices. IDCs are capable of Class A operation with an optional adapter module and can be programmed as Style C (short or open initiates a trouble) for use with current limited devices only.
Two, 2 A On-Board NACs provide conventional reverse
polarity operation, selectable as Class A or Class B, with electronic control and overcurrent protection. Operation is selectable for synchronized strobe or SmartSync horn/strobe two-wire operation. Horn control can be selected at the panel for: Temporal pattern coding, Steady On, Slow March Time of 20 beats per minute (BPM), or Fast March Time of 120 BPM. Note: When selected for SmartSync horn/strobe control, March Time produces 60 BPM.
The 24 VDC Auxiliary output provides up to 500 mA
for system use. (Auxiliary output current is counted for total power supply capacity.)
Standard Auxiliary Relay Outputs. Two relay outputs
are available, selectable as normally open or normally closed, rated 2 A @ 30 VDC per below:
Aux Relay 1 is normally assigned to General Alarm operation but is programmable (see page 7)
Aux Relay 2 (Trouble) is energized when Normal and is de-energized with a Trouble condition.
On-Board Dual Line DACT. Operation can be selected
for Contact ID, SIA, 3/1, 4/2, and BFSK formats. Reporting includes Alarm, Supervisory, Trouble, and AC Failure. Operation includes automatic 24 hour test and programmable power fail report delay.
Product Selection
Standard Feature Details (Continued)
Power Supply and Battery Charger. DC power output
is 3 A @ 24 VDC for panel use. The temperature compensated battery charger (sealed lead-acid batteries only) is rated for up to 25 Ah batteries per UL 864 and up to 12.7 Ah per ULC-S527. (Up to 12.7 Ah batteries fit in the cabinet, larger batteries require an external cabinet.) Panel electronics can measure and display voltage and current for the power supply, batteries and the battery charger (standard and expansion power supply). Depleted battery trouble is monitored and annunciated and depleted battery cutout can be selected. Active battery status monitor supervises charger operation.
Optional Feature Details
Expansion Power Supply. Provides 3 A total @
24 VDC, two additional 2 A NACs, and an additional auxiliary power output of 500 mA. Output operation is the same as on the standard power supply.
Expansion IDC Module. Provides 5 additional Class B
IDCs with operation the same as the standard IDCs.
Expansion Relay Module. Provides 10 programmable
relays, jumper selectable as N.O. or N.C. Contacts are rated 2 A @ 30 VDC. Typical application is to track status of each IDC. See page 7 for relay program options.
Class A Adapter Module. Converts 5 IDCs from
Class B to Class A operation. Two modules can be mounted for use with the Expansion IDC Module.
City Circuit Modules. These modules are available with
or without on-board disconnect switches, depending on local requirements (either type can be disconnected through the front panel under password control). Connections are for Remote Station (reverse polarity) or Municipal Master (local energy). Reporting includes Alarm, Supervisory, and Trouble.
Control Panel
Model Color Description Listings Standard Feature Summary
4006-9102 Beige 4006-9101 Red
4006-9122 Beige 4006-9121 Red
Option Modules
Model Description
4006-9801 Expansion Power Supply; 3 A, with 2 NACs, 120/240 VAC, 50/60 Hz 4006-9802 Expansion IDC Module; 5 Class B IDCs 4006-9803 Expansion Relay Module; 10 relays selectable as either N.O. or N. C.
4006-9804 Class A Adapter Module; converts 5 IDCs from Class B to Class A Select up to two maximum
4006-9805 City Circuit Module with disconnect switch 4006-9806 City Circuit Module without disconnect switch
Accessories
Model Description
2975-9811 Beige semi-flush trim kit; 1-7/16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides 2975-9812 Red semi-flush trim kit; 1-7/16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides
4009-9801
Batteries, 12 Volt (select one battery model per system standby requirements; order quantity of two)
Model Size Model Size Location Model Size Location
2081-9272 6.2 Ah 2081-9288 12.7 Ah 2081-9274 10 Ah 2081-9827 25 Ah
2 S4006-0001-8 8/2012
Beige External Battery Cabinet for up to 25 Ah batteries; mounts close-nippled to control panel cabinet; dimensions = 16-1/4” W x 13-1/2” H x 5-3/4” D (413 mm x 343 mm x 146 mm) [depth increased for 25 Ah effective 7/2005]
Standard fire alarm control panel MEA
Fire alarm control panel with 24 LED Annunciator on front door
For cabinet mount
UL, FM,
ULC
2081-9275 18 Ah
& CSFM
5 Class B IDCs, 2 Class B/Class A NACs, 3 A power supply with battery charger; on-board DACT; 120/240 VAC, 50/60 Hz (autoselect)
Select up to one of each as required
Select one if required
Requires 4009-9801 External Battery Cabinet (UL listed only)
Page 3
Keyboard Reference
FIVE STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset
2 X 20 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions, provides up to 20 characters for custom label information
FIRST ALARM DISPLAY: Operation can be selected for maintained display of fir st alarm until acknowledged
THREE PROGRAMMABLE LEDs
provide custom labeling (labels insert into a pocket), the top two LEDs are selectable as red or yellow, the bottom LED is selectable as green or yellow
CONTROL PANEL VIEW
with door closed
ALARM ACK acknowledges a Fire Alarm condition, logs the acknowledge, silences the operator panel and all annunciator tone-alerts, and steps through the active Alarm list
SUPV ACK acknowledges system supervisory conditions, logs the acknowledge, silences the operator panel and all annunciator tone-alerts, and steps through the active Supervisory list
FIVE NAVIGATION KEYS: MENU selects the on-screen programming menu; left and right arrows moves the position on the screen, and PREVIOUS and NEXT navigate screen selections
FIRE
ALARM
ALARM
ACK
SYSTEM
SUPERVISORY
SUPV
ACK
PREVIOUS
MENU
NEXT
SYSTEM
TROUBLE
TROUBLE
TROUBLE ACK acknowledges
system troubles, logs the acknowledge, silences the operator panel and all annunciator tone-alerts, and steps through the active Trouble list
ACK
ALARM
SILENCEDACPOWER
ALARM
SILENCE
DISABLE ENABLE
FUNCTION
CLEAR
ENTER
EXIT
SYSTEM
RESET
ALARM SILENCE causes audible notification appliances
to be silenced, used after evacuation is complete and while alarm source is being investigated
FOUR EXTENDED FUNCTION KEYS: ENTER confirms selections, EXIT/CLEAR backs out of the present screen menu and clears information that has not been entered, FUNCTION enables the active function menu, DISABLE/ENABLE toggles the function or circuit status as appropriate per the selected screen
1ABC2DEF
3
GHI4JKL5MNO
6
PQRS7TUV8WXYZ
9
0
SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal
ALPHANUMERIC KEYPAD provides
programming entry of numbers and letters
Door LED Annunciator Details
Fire Alarm Annunciator
IDC 1
IDC 2
IDC 3 IDC 4
14 CUSTOM LABEL AREAS are available, typically for IDC and NAC annunciation (shown labeled for reference, blank labels are provided); dual LED locations have a Red LED (top) and a Yellow LED (bottom); labels insert into pockets behind the overlay; LED operation is pr ogrammable to track other monitored status conditions
3 S4006-0001-8 8/2012
YELLOW LED
IDC 5
IDC 6
IDC 7 IDC 8
RED LED
IDC 9
IDC 10 NAC 1
NAC 2 NAC 3 NAC 4
FOUR YELLOW LEDs provide default NAC Trouble annunciation (shown label ed as NAC 1-4)
Page 4
Specifications (Refer to Installation Instructions 579-704 for additional information)
Power Ratings
Input Voltage 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select
AC Input Ratings
Power Supply Output Rating 3 A maximum @ 24 VDC in alarm (see NAC details on page 6)
Battery Charger
Standby Current 130 mA; with 5 IDCs fully loaded, tone-alert silenced, trouble LED on
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum)
Notification Appliance Circuits (NACs) NOTE: See details on page 6
Initiating Device Circuits (IDCs)
Annunciator Communications
Auxiliary Power Output 500 mA maximum @ 24 VDC
Standard Auxiliary Relay Outputs
Wiring Connections for Above Circuits and AC Input
Option Module Ratings
Class A IDC Adapter Module Five circuits per module, rated same as circuits
Ten Relay Auxiliary Module 4006-9803
Environmental Ratings
Operating Temperature Range 32° to 120°F (0° to 49° C) Operating Humidity Range Up to 93% RH, non-condensing @ 100.4° F (38° C) maximum
Reference Information, Compatible Simplex Peripherals
Compatible Simplex Detectors
Model Type Description Data Sheet
4098-9601 4098-9605 Reduced sensitivity detector (3.5% nominal) 4098-9602 Combination smoke and heat detector S4098-0017
4098 Series Duct detector housings 2-wire and 4-wire models S4098-0029
4098 Series Ionization Smoke Detectors 2-wire and 4-wire models S4098-0018
4098-9612 4098-9614 200° F (93°C)
4098-9613 135° F (57°C) 4098-9615 200° F (93°C)
Compatible System Expansion Panels
Model Type Description Data Sheet
4003 Series Voice Control Panel
4009 Series Remote NAC Extender
Note: Contact your local Simplex Product Supplier for additional compatible peripherals.
4 S4006-0001-8 8/2012
Input Current, Standard 2 A maximum @ 120 VAC input; 1.5 A maximum @ 240 VAC input
Input Current with
Expansion Power Supply
Supervisory Current 3 mA maximum
Alarm Current 60 mA maximum
End-of-Line Resistor 3.3 k, 1/2 W; Model 4081-9002 (P/N 733-893) for Class B IDCs
Quantity Supported Up to four annunciator modules per panel (see page 5 for details)
Line Matching Resistor
Capacity
Wiring Type Twisted pair, or twisted, shielded pair; 18 AWG (0.82 mm2)
Bus-Style Wiring Up to 4000 ft (1219 m); 0.58 µF (580 nF) maximum capacitance; 35 max.
“T-Tap” Wiring Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device
Suppression
Relay 1 Programmable operation Relay 2 Trouble operation
Contact Ratings 2 A @ 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C.
Photoelectric smoke detectors for 2-wire and 4-wire bases
Electronic heat detectors for 2-wire and 4-wire bases
4 A maximum @ 120 VAC input; 3 A maximum @ 240 VAC input
Temperature compensated charger is rated for up to 25 Ah per UL 864; up to
12.7 Ah per ULC-S527
2 A maximum @ 24 VDC, per circuit; available as Class A or Class B; Class B end-of-line resistor = 10 k, 1/2 W; Model 4081-9008 (P/N 733-894)
Each IDC supports up to 30 detectors (smoke or electronic heat) and manual stations as required; wiring distance is limited to 50 maximum
Bus-style, connect one at panel and one at end of line T-Tap, connect one at panel and one at farthest device
Use 2081-9044 Overvoltage Protectors where wiring leaves and enters a building (refer to data sheet S2081-0016)
Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2)
Standard detector (2.8% nominal)
100 , 1/2 W; 4081-9011; (part number 733-974)
Contacts rated 2 A @ 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C.
135° F (57°C)
Provides a remote voice control panel with on-board NACs, internal microphone, and remote microphone input
Provides remote NACs; includes power supply and battery charger;
Fixed temperature heat detector
Fixed temperature heat detector with rate-of-rise detection
4 extenders max/NAC; 4006 uses NAC output to provide control
S4098-0015
S4098-0014
S4003-0002
S4009-0002
Page 5
Supervisory and Alarm Currents
Model Module Supervisory Alarm
4006-9101 4006-9102
4006-9121 4006-9122
Standard fire alarm control panel 130 mA
Control panel with 24 LED Annunciator 148 mA
+ 60 mA per IDC in Alarm
+ 60 mA per IDC in Alarm
160 mA
210 mA
4006-9801 Expansion Power Supply 50 mA 60 mA
4006-9802 Expansion IDC Module 50 mA
4006-9803 Expansion Relay Module
4006-9804 Five Circuit IDC Class A Adapter
4006-9805
4006-9806
4606-9101
4610-9111
City Circuit Module with disconnect switch
City Circuit Module without disconnect switch
Remote LCD Annunciator (see data sheet S4606-0001)
Remote LED/Switch Annunciator (see data sheet S4610-0001)
+ 10 mA per energized relay
10 mA per IDC in trouble
0 mA
0 mA normal;
30 mA 60 mA
30 mA 60 mA
65 mA 140 mA
40 mA
+ 60 mA per IDC in Alarm
+ 10 mA per energized relay
10 mA per IDC in trouble
(all LEDs and tone-alert on)
50 mA
0 mA
0 mA normal;
70 mA
** Current Calculation Information:
1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads.
2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads
and all auxiliary loads.
Remote Annunciator Options
The 4006 supports up to four annunciator options including:
Door Mounted 24 LED Annunciator 4610-9111 Remote LED/Switch Annunciators 4606-9101 Remote LCD Annunciators
Annunciators communicate at a rate of 9600 baud with 24 VDC power supplied by separate wiring.
4610-9111 LED Annunciator Features:
16 LEDs with programmable functions and dedicated
LEDs for Alarm Silenced, Lost Communications, Trouble, and Power-on
Keyswitch access controlled switches for
Acknowledge, Alarm Silence, Reset, and Lamp Test
Local tone-alert
4606-9101 LCD Annunciator Features:
LCD readout with two lines of 40 characters each and
LED backlighting
Wide viewing angle, super-twist design Keyswitch access controlled
Control switches and status LEDs for:
Alarm, supervisory, or trouble acknowledge Alarm silence and System Reset
Three programmable LED indicators:
Two LEDs are selectable as red or yellow One LED is selectable as green or yellow With provisions for custom labeling
Fire Alarm Annunciator
ALARM
ACK
SILENCE
LAMP
RESET
TEST
4610-9111 LED/Switch Annunciator
5 S4006-0001-8 8/2012
ALARM
SILENCED
LOST COM
TROUBLE
POWER
CONTROL
ENABLE
FIRE
ALARM
ALARM
ACK
SYSTEM
SUPERVISORY
SUPV ACK
4606-9101 LCD Annunciator
SYSTEM
TROUBLE
TBL ACK
POWER
ALARM
SILENCED
ON
SYSTEM
ALARM
RESET
SILENCE
Page 6
IDC Operation Modes
The following IDC operation modes are selectable from either the front panel or the PC programmer
Function Type Description Device State IDC Status
FIRE Fire monitor zone
WATER Waterflow monitor zone
HEAT Heat detector zone
DUCT Duct detector zone
PULL Manual (pull) station zone
SMOKE Smoke detector zone
SO Sprinkler Supervisory
WSO
SUPV Supervisory monitor
UTIL Supervised utility monitor
TROUBLE Trouble monitor
VSMOKE
STYLEC Style C fire monitor
LATSUPV
Combination waterflow and water supervisory
Verified fire alarm; the abnormal (current limited) state causes the alarm verification cycle to start;
a short is an immediate alarm
Latching supervisory monitor (supervisory
latches until system is reset)
zone
Normal =
Current Limited =
Short = Open =
Normal =
Current Limited =
Short = Open =
Normal =
Current Limited =
Short = Open =
Normal =
Current Limited =
Short = Open =
Normal =
Current Limited =
Short = Open =
Normal =
Current Limited =
Short = Open =
Normal =
Current Limited =
Short = Open =
Normal =
Current Limited =
Current Limited =
Current Limited =
Short = Open =
Normal =
Short = Open =
Normal =
Short = Open =
NORMAL FIRE FIRE TROUBLE
NORMAL FIRE FIRE TROUBLE
NORMAL SUPERVISORY SUPERVISORY TROUBLE
NORMAL SUPERVISORY ALARM TROUBLE
NORMAL SUPERVISORY SUPERVISORY TROUBLE
OFF ON ON TROUBLE
NORMAL TROUBLE TROUBLE TROUBLE
NORMAL VERIFY FIRE TROUBLE
NORMAL FIRE TROUBLE TROUBLE
NORMAL SUPERVISORY SUPERVISORY TROUBLE
Detailed NAC Ratings
NAC Ratings, Maximum per NAC Appliances Special Application: 2 A;
strobe synchronization is UL listed across all 4 system NACs for these 4906 Series appliances
Regulated 24 VDC: 1.5 A NOTE: Maximum strobe
supply or expansion power supply is 1.35 power supply (2.7 A total); remainder of power supply rating is available for other loading
load on main power
6 S4006-0001-8 8/2012
A per
Simplex 4901 Series (horns) and 4906 Series Multi-Candela non-addressable strobes, horn/strobes, and speaker/strobes (contact your Simplex product representative for compatible appliances)
Power for other UL listed appliances; use associated external synchronization modules where required
Page 7
NAC Operation Modes
Function Type Description
SSIG Alarm signal, on until silenced RSIG Alarm signal, on until reset TROUBLE Trouble signal SUPV Supervisory signal QALERT SmartSync 2-wire horn/strobe control; horn on until silenced, strobe on until reset
WHEELOCK
UTILITY Utility signal, generic non-alarm
Provides Wheelock strobe synch protocol when using only Wheelock strobes on panel, not to be mixed with Simplex strobes
Relay Operation Modes
The following relay operations are selectable from either the front panel or the PC programmer.
Common Fire Alarm Operations
Function Type Relay Acti va t e s Up on Relay Deactivates Upon
SRELAY General Alarm Silence RRELAY General Alarm Reset SUPV Supervisory condition Clear TRBL Trouble condition Clear
Special Functions
Function Type Description
UTILITY Utility IDC in the same alarm group activates PRIMARY General alarm; relay is tied to Primary Elevator Recall contacts ALTERN General alarm; relay is tied to Alternate Elevator Recall contacts DRESET Relay provides 24 VDC power to 4-wire detectors; relay turns off for 5 seconds on System Reset
DHOLDER
Relay provides 24 VDC to larger door holder relay with separate power source; relay activates on general alarm to remove power to door holder relay and close doors
Additional Programming Feature Details
Function Details
Custom labels
Message Library
History logs
Autoprogram
Alarm Groups
WALKTEST
Manual Control Allows selection of individual relays or NACs for system testing
Passcode Protection
(4-digit number)
Up to 20 characters per point; a built-in message library provides for commonly used words for easy front panel programming
For front panel label creation convenience, the following words can be selected as part of a custom label ( _designates a built-in space; typing the first letter of a word/number will select the closest word in alphabetical/numerical sequence)
North South East West Front
Three separate logs: Alarm (100 entries), Supervisory (100 entries), and Trouble (300 entries); logs can be queried separately, or as a combined log; logs can be downloaded for printing or archiving using the RS-232 service port
Automatically scans system for installed option modules and configures panel programming accordingly; modes are available to detect new modules only, recreate default programming and then add all modules found
Up to 99 alarm groups are available, any point may be in up to 3 alarm groups; this allows NAC and relay operation to be associated with IDC inputs according to local response requirements
Allows one person to perform system testing; alarm or trouble tests are followed by automatic reset; the alarm zone is sounded out by associated audible notification or the response is silently logged into the Alarm log
Level 1 = Acknowledge, Silence, System Reset, View logs, View point information, and Lamp Test Level 2 = All Level 1 + Set Time/Date, Point Control, Enable/Disable points Level 3 = All Level 2 + Clear logs, Clear verification tallies, Custom label editing, and WALKTEST Level 4 = All Level 3 + Programming, Upload/Download; this is the Service access level
Center rear 5th Flr_1 Flr_2
Flr_3 Flr_4 Flr_5 RM_
Basement Floor Garage Hallway HVAC_Room Kitchen
Lobby Office Patient upper lower
main first 2nd 3rd 4th
Boiler_RM Classroom Closet_ Corridor Elect_RM
Elevator Entrance Restroom Room Stairway
Storeroom Wing Zone
7 S4006-0001-8 8/2012
Page 8
Installation and Module Placement Reference
Box width 15-5/8" (397 mm)
Knockouts are located on top
and sides
(Top and side views are shown with door installed)
Box depth = 4-3/4" (121 mm)
Main board
Relay
Expansion
Module*
Main board
13-1/2"
(343 mm)
11-1/4" (286 mm)
FIRE
SYSTEM
SYSTEM
SUPERVISORY
PREVIOUS
MENU
NEXT
ALARM
TROUBLE
SILENCEDACPOWER
SUPV
TROUBLE
ALARM
ACK
SYSTEM
ACK
SILENCE
RESET
ABC2DEF
DISABLE
ENABLE
1
3
GHI4JKL5MNO
FUNCTION
EXIT
CLEAR
ENTER
PQRS7TUV8WXYZ
0
6
9
Display
Assembly
ALARM
ALARM
ACK
AC Input Terminals City Module*
Battery Area
No conduit or wiring in this area
13-1/4" (337 mm)
* Indicates optional modules
IDC Expansion
Module*
Class A Adapter
Modules*
Door thickness
5/8" (16 mm)
Expansion
Power Supply* (extends under IDC Expansion
Module space)
NOTE: For semi-flush mounting, cabinet
must extend 1-1/2" (38 mm) minimum from wall surface
16"
(406 mm)
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4006-0001-8 8/2012
www.simplexgrinnell.com
© 2012 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Loading...