Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted
in any form or by any means, electronic or mechanical, for any purpose, without the express written consent of Tyco Safety
Products.
Tyco, Simplex, the Simplex logo, IDNet, SmartSync and WALKTEST are registered trademarks of Tyco International Services AG or its affiliates in the US and/or other countries.
TrueAlarm analog smoke detection is protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683;
5,543,777. IDNet addressable communications are protected by U.S. Patent No. 4,796,025. IDNet duplicate device detection
is protected under U.S. Patent No. 6,034,601. WALKTEST system test is protected under US Patent No. 4,725,818. SmartSync horn/strobe operation is protected under U.S. Patent No. 6,281,789. Two wire synchronization circuit operation is protected by U.S. patent No. 5,559,492.
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the door of this equipment is a label that contains, among other information, the following product identifier: US:5QWAL01B4008. If requested,
the number must be provided to the telephone company.
In the event of equipment malfunction, all repairs should be performed by an authorized agent. It is the responsibility of users
requiring service to report the need for service to our company or to one of our authorized agents. Service can be arranged
through our office at:
Tyco Safety Products
91 Technology Drive
Westminster, MA 01473
978-731-2500
The Ringer Equivalence Number (REN), which is 01 for the DACT installed in this panel, is used to determine the number of
devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the devices not ringing in
response to an incoming call. In most, but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the
number of devices that may be connected to a line, as determined by the total number of RENs, contact the local telephone
company. For products approved after July 23, 2001, the REN is part of the product identifier, which uses the format
US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g. 01 is a REN of 0.1).
If the DACT causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. But if advance notice isn’t practical, the telephone company will notify you as soon as
possible. If your service is discontinued, you will be advised of your right to file a complaint with the FCC.
The telephone company may make changes to its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make the necessary modifications to maintain uninterrupted service.
If trouble is experienced with the DACT, please contact Tyco Safety Products at the location identified above. If the equipment
is causing harm to the telephone network, the telephone company may request that you disconnect the equipment until the
problem is resolved.
Alarm Dialing Equipment
This equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this
even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so,
the DACT must be electrically in series with and ahead of all other equipment attached to the same telephone line. Proper
installation is depicted in the figure below. If you have any questions concerning these instructions you should consult your
telephone company or a qualified installer about connecting the alarm dialing equipment for you.
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation manual. These instructions must be
followed to avoid damage to this product and associated equipment. Product operation and reliability depends upon proper
installation.
DO NOT INSTALL ANY PRODUCT THAT APPEARS DAMAGED. Upon unpacking your product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. Servicing
should be performed by qualified Technical Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
•Ground yourself before opening or installing components.
•Prior to installation, keep components wrapped in anti-static material at all times.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not installed
and used in accordance with the instruction manual, can cause interference to radio communications. It has been tested and
found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of
this equipment in a residential area may cause interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must
be tested in accordance with NFPA72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to
system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In
addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
User Interface .......................................................................................................................................... 1-3
Logging In and Out .................................................................................................................................. 1-5
Back Box Mounting.................................................................................................................................. 2-1
City Connect Module Wiring ...................................................................................................................2-12
Auxiliary 24 V Wiring ..............................................................................................................................2-13
Connecting to AC Power ........................................................................................................................2-14
Normal Operation .....................................................................................................................................7-1
Lamp Test ................................................................................................................................................7-1
System Reset ...........................................................................................................................................7-2
Control Functions .....................................................................................................................................7-4
Setting the Time and Date........................................................................................................................7-5
This publication describes how to install, configure, operate, program,
and test an 4006-9101 and 4006-9121 (includes door-mounted annunciator) Fire Alarm Control Panel (FACP). In cases where the installation,
wiring, or programming procedure is identical for both panels, the term
4006 is used. If the procedure applies only to a specific panel, the complete product name (i.e., 4006-9121 is used).
The 4006 is a conventional fire alarm control panel. The base system
includes five Class B Initiating Device Circuits (IDCs), which may be
wired as Class A circuits with the addition of an optional Class A module. The base system also includes two Notification Appliance Circuits
(NACs), which may be wired class A or class B. A built-in DACT provides a means for remote station or central station monitoring.
The 4006 provides audible and visible indications during alarm, supervisory, or trouble conditions. Should any of these conditions occur, the
system activates the applicable notification appliances, LEDs, and the
panel tone-alert. The indications continue until an operator acknowledges the condition.
Main System Board
The 4006 base system includes the Main System Board (MSB) mounted
in a steel enclosure with locking door.
•Battery charger up to 25 Ah batteries per UL864; temperature compensated. Recharge 12.7Ah batteries per
ULC-S527.
Note: The 4006 back box can accommodate up to
12.7 Ah batteries.
Environmental Specifications
The panel operates normally with ambient temperatures
from 32° F to 120° F (0° C to 49° C), inclusive.
The panel operates normally under non-condensing humidity conditions up to 93% relative humidity at 90° F (32° C).
Option Modules
The following lists all of the option modules for the 4006.
Refer to the individual instructions that accompany each
module for more information. Refer to the label inside the
door of the 4006 for the placement of optional modules.
4006-9801 Expansion Power Supply (EPS)
When additional notification appliance circuits are required,
an expansion power supply may be added. The expansion
power supply provides two additional 2A NACs, and filtered/regulated 24 VDC, 3A power. The expansion power
supply is mounted to the right of the MSB at the bottom of
the chassis. It connects to the MSB with a ribbon harness.
The 3A alarm power of the EPS may be split between the 2
NACs and the 1/2A Aux. 24V power tap. One EPS per system is allowed.
4006-9802 Expansion IDC Module (XIM)
This module mounts to the right of the MSB. It includes five
Class B Initiating Device Circuits, and a mounting point for
the optional IDC Class A adapter module.
4006-9805 and 4006-9806 City Circuit Cards
The city circuit card connects to the MSB with a ribbon harness to provide connections to either Remote Station
(reverse polarity), or Municipal Master (local energy)
receiving units (selectable). The card has two circuits - circuit 1 reports alarm or alarm/trouble events (Remote Station
only) and circuit 2 can be configured to report trouble events
or supervisory events. In the event of a CPU failure, a city
card configured for a trouble output sends a trouble to the
city circuit. The card is mounted to the right of the MSB at
the top of the chassis. The 4006-9805 and 4006-9806 city
cards are identical except that the 4006-9805 provides hardware disconnect switches for each circuit. One City Circuit
Card per system is allowed.
4006-9803 Expansion Relay Module
The Expansion Relay Module (ERM) includes 10 relays.
The relays may be programmed for per-zone operation, one
relay per IDC, or as desired. For example, it is possible to
program any relay for general alarm, trouble or supervisory
conditions. Normally Open or Normally Closed contact
operation is selected by shunt jumper placement. Contacts
are rated for 2A, 30VDC, 0.35 power factor.
Annunciator Modules
The 4006 supports the following annunciator modules. A
total of four annunciators may be added to the system, one of
which can be located in the panel (the Local Zone LED
module).
• Local Zone LED Module. The local Zone LED
Modules provides 24 LEDs for visible zone alarm and
trouble indication. (The Local Zone LED module,
which mounts on the front of the panel, is standard for
ULC-S527 compliant systems.) There are 10 Red and
14 Yellow LEDs. This provides a red alarm and yellow
trouble LED for each of 10 initiating device circuits.
This module also provides 4 Yellow LEDs, one for each
of 4 NACs. The LEDs are programmable, and can be
used for other functions as appropriate per application.
•4610-9111 Remote LED/Switch Annunciator.
This annunciator provides the following:
-10 programmable red LEDs (default programming
tracks alarm state of IDC1-IDC10)
-6 programmable yellow LEDs (no default operation)
-Green “power on” LED
-Yellow “Alarm Silenced” LED
-Yellow “Trouble”
-Yellow “Comm Loss” LED
-Tone-Alert
-Switches for ACK, Alarm Silence, System Reset,
and Lamp Test
-Key switch to enable switch functions
4009-9201/4009-9202CA NAC
Extender
The 4009-9201/4009-9202CA (Canadian) Notification
Appliance Circuit (NAC) Extenders are self-contained
adjunct panels for use with 4006 Fire Alarm Control Panels
(FACPs).
The base version of the NAC Extender is a single-board system consisting of four NACs, a power supply and charger,
and two conventional NAC inputs that connect to the host
panel for hardwired control of the NAC extender.
Option cards are available to provide the following additional capabilities:
•4009-9808 Class A Adapter Option Card -- allows fault
tolerance in the case of open circuit wiring faults on the
NACs.
The 4006 is compatible with the following conventional initiating devices.
Photoelectric Smoke Detector
Photoelectric smoke detectors detect smoke by means of
optical sensing technology.
•4098-9601/4098-9601C: Standard Sensitivity (2.8%/
foot) Photoelectric Smoke Detector
•4098-9605: Special Sensitivity (3.5%/foot) Photoelectric Smoke Detector
Heat Detector
Four models of conventional electronic heat detector are
available:
• 4098-9612/4098-9612C: 135°F Fixed Temperature
Heat Detector
• 4098-9613/4098-9613C: 135°F Fixed Temperature
Heat Detector w/ rate of rise detection
• 4098-9614/4098-9614C: 200°F Fixed Temperature
Heat Detector
•4098-9615/4098-9615C : 200°F Fixed Temperature
Heat Detector w/ rate of rise detection
•Fixed temperature trip point: 135°F
Rate of Rise trigger: 15°F-25°F per minute only at temperatures of 90°F or greater
Detector Bases
The detectors described above may be installed in the following detector bases:
• 4098-9788/4098-9788C: Two-wire detector base with
remote LED connection.
• 4098-9683/4098-9683C: Two wire detector base with
auxiliary relay (limit 1 per IDC).
• 4098-9684/4098-9684C: Two wire detector base with
alarm LED output. For use with 4098-961x series heat
detectors only.
• 4098-9682/4098-9682C: Four wire detector base with
auxiliary alarm relay .
Each of the smoke detectors includes an output for a remote
alarm LED. Base 4098-9684 is required for remote LED
control with 4098-9612 through 4098-9615 electronic heat
detectors.
Maximum of 30 total bases per IDC, except for 4098-9683
(limit one per IDC).
User Interface
The user interface consists of control keys, LEDs, a 2-line
by 20-character backlit LCD, and a sounder mounted in the
control panel. The purpose of the Operator and Menu keys is
listed below.
The rate of rise trigger is 15°F-25°F per minute.
Combination Photo/Heat Detector
The combination photo/heat detector ( 4098-9602/40989602C) is a combination photoelectric detector and thermal
detector in one head. This detector correlates smoke and
thermal activity to provide earliest alarm initiation.
alarms in the system, and scrolls
through the alarms in the active Alarm
List.
Acknowledges any unacknowledged
supervisories in the system, and scrolls
through the supervisory conditions in the
active Supervisory List.
Acknowledges any unacknowledged
troubles in the system, and scrolls
through the trouble conditions in the
active Trouble List.
Silences any silenceable output types
(generally all audible notification appliances).
Allows the operator to reset all alarm
notification appliances and controls,
remove alarms from the Alarm List,
silence all silenceable outputs, reset
detectors, and return the system to a
normal state (provided that no alarm,
supervisory or trouble conditions are
present). The display indicates that a
reset is in progress and whether or not a
reset completes successfully.
Pressing the <SYSTEM RESET> key
will only attempt to return the system to
a normal, non-alarm state. All outputs
that were activated by the alarm will
remain active until all alarm inputs have
been restored and the reset was able to
successfully complete.
An open circuit fault on a Class A NAC
does not require a System Reset to
restore to normal.
Open circuit faults on the optional City
Connect module are cleared with a system reset after the circuit has been
repaired.
The Menu key always brings you to the
top of the main menu structure unless
you are in the Programming menu.
KeyFunction
The Function Menu is displayed when
the <Function> key is pressed at the
high-level status screen. Use the <Previ-
FUNCTION
DISABLE/
ENABLE
EXIT/
CLEAR
ENTER
RIGHT/LEFT
ARROWS
PREVIOUS/
NEXT
ous> and <Next> keys to scroll through
the list of functions. The function key
provides access to commonly used control and display functions.
The <Disable/Enable> key allows the
operator to quickly disable or enable any
point that is currently displayed. This key
is passcode protected. A confirmation
screen is displayed requesting <Enter>
be pressed before the actual enable or
disable is performed.
The <Exit/Clear> key is used to back out
of menus or displays and return to the
top-level menu structure. Where possible, the <Exit/Clear> key backs out one
level at a time. There are cases, however, that the Exit/Clear key will return
the operator directly to the top-level
menu.
The <Enter> key is used to confirm
selections. When pressed, this key provides additional information about the
point shown on the display. In a programming screen, pressing <Enter>
indicates that the information on the display is correct and can be accepted. The
<Enter> key is used in various other
places within the menu structure, always
for this same type of operation.
The right and left arrows are used in
screens with multiple choices. The keys
advance the focus (square brackets [ ])
from field to field.
The Previous & Next keys are used to
scroll through the system lists, historical
log, point database, etc. The <Next> key
selects the next display screen in
sequence, and the <Previous> key
selects the previous screen. These keys
are also used to view additional information about abnormal points or in viewing
historical logs.
Certain operator functions are passcode-protected at different levels. This section describes the operator functions,
their default access level, and the login/logout procedure.
Table 1-2 Access Levels and Features
Access
Level
Acknowledge, Silence, System Reset,
1
2
Passcode =
2000
3
Passcode =
3000
4
Passcode =
4000
View Historical Logs,
View Point Information, Lamp Test
All Level 1 operations, plus:
Set Time/Date, Point Control,
Enable/Disable points
All Level 1, 2, & 3 operations, plus:
Programming,
Upload/Download
Login/Logout Procedure
To perform any of the functions protected at Level 2 or
above, you must login to the panel using a passcode. After
completing a task at a certain access level, you should then
logout to return the access level to Level 1 to prevent unauthorized operation. When logged in at Level 2 or above and
no panel keys are pressed for more than 10 minutes, the
panel automatically returns the system to Level 1.
All passcodes consist of a 4-digit number. Logging in at
Level 4 causes a Service Mode trouble that may only be
cleared by restarting the panel.
To login, perform the following steps:
1.Obtain the passcode information for the desired level.
2.Press <MENU>
3.Press <NEXT> until [Login/Logout] is displayed, then
press <ENTER>. A prompt similar to the following
appears.
Access: Level 1
<ENTER>=[Login]
Operation
Access: Level 1
Passcode:[0]
5.Use the Keypad to enter the appropriate passcode.
6.When the passcode is correct, press the <ENTER> key
to login.
A “Login Accepted” message, which indicates your current
access level, is displayed briefly upon a successful login
attempt. If you did not enter the appropriate Login passcode,
a “Login Invalid” screen appears.
To logout, perform steps 1-4 above, but select Logout
instead of Login.
Overview - Programming a Job
A job refers to the file containing all of the panel’s programming information. This manual describes the process
required to create a job from the front panel of the system.
Creating a job involves:
•Setting the attributes of each IDC, NAC, and AUX
relay, including:
-Function Type. Determines the way in which the
IDC, NAC, or relay operates (i.e., fire point, trouble
point, on til silence, etc.)
-Custom Label. This is a 20-character label that
describes each zone, NAC, or relay.
-Alarm Group. Allows inputs and outputs to be
associated into groups to implement selective signaling applications. See “Alarm Groups” below.
•Defining the attributes (phone numbers, account numbers, reporting format, etc.) of the panel’s Digital Alarm
Communicator Transmitter (DACT). If the DACT will
not be used, programming consists of disabling the
DACT.
•Programming the operation of the LEDs contained on
the panel and connected annunciators. Programming an
annunciator consists of identifying the point being monitored by the LED and the mode (i.e., fire alarm, trouble, etc.) that will trigger the LED to illuminate.
•Setting values for the panel’s system options, which are
pre-defined modes of operation with a range of settings
from which to choose. System Options define global
operations such as the time and date format, door drop
timers, and whether the city circuit is enabled, etc.
4.Press <NEXT> until [Login] is displayed, then press
<ENTER>. A prompt similar to the following appears.
Alarm groups allow you to implement basic selective signalling applications. As you program input (zone of smoke
detectors) and output points (NAC or relay), you are given
the opportunity to associate the point with an alarm group
number. The number can range from 1-100 and each point
can be in up to three alarm groups. When programming is
complete, an initiating device can only trigger the output
devices (relays, NACs) that share its alarm group(s).
•All Aux Relay loads must be powered from the AUX
power circuit or from a regulated, 24 VDC, power-limited power supply that is UL-listed for fire protective
signaling service.
Guidelines for Locating Backbox
Always refer to engineering drawings/site installation plans
before beginning installation. The system is designed to
operate in a typical commercial environment. Choose a site
for each backbox that is:
•Well-ventilated, clean, and dust-free.
•Located near a dedicated AC individual branch circuit
with Earth ground (to maintain a consistent supply voltage).
•Away from sources of heat, including direct sunlight.
•Away from sources of vibration or physical shock.
•Away from sources of Radio Frequency Interference
(RFI), such as a radio transceiver base station or hand
held unit.
•Isolated from sources of strong electromagnetic fields,
such as air conditioners, large fans, and large electric
motors.
Be sure to mount the backbox to the wall so that the top of
the enclosure is no more than six feet above the floor.
Semi-Flush Mounting
Semi-flush mounting involves recessing the backbox into a
wall and attaching it directly to the wall's studs. At a minimum, 1.5 inches of the backbox must protrude from the wall
to allow for clearance of the panel door.
Figure 2-3 Semi-Flush Mounting
General Wiring Guidelines
Surface Mounting
Refer to the figure below for hole dimensions.
Figure 2-2 Surface Mounting Hole Dimensions
All wiring to the 4006 and its peripherals must be performed
in accordance with NFPA 70, NFPA 72, all local codes, and
per the technical requirements listed in each section below.
Before connecting any wires to the system, including option
modules, wires must be tested as follows:
1.Use a voltmeter (VOM) to verify no stray voltages are
applied to the field wiring. Test for AC and DC voltages
across each pair of wires and from each wire to earth.
2.Use a VOM to verify that all wiring tests free of
grounds. Each conductor should test “open” against
earth (chassis).
•Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
•All wiring is supervised and power-limited. IDCs
should be segregated from AC supply wiring. If wired
power-limited, segregate IDC wiring from non-power
limited wiring.
•Leave a 3.3K, 1/2 W resistor (supplied) across all
unused IDC terminals.
•Terminate Class B circuits with listed 3.3K, 1W end-ofline resistor, part number 733-893. For Canadian applications, mount end-of-line resistor to TEPG-US Model
431537 EOL plate in accordance with ULC-S527.
•Class A Circuits. Wire as follows:
-Wire from B+/B- from of TB3 to each initiating
device. Wire in a daisy-chain style, in and out from
each device to the next device.
-Do not “T-Tap” wiring.
-Wire from last device back to the A+/A- terminals
on the Class A adapter for that circuit. EOLR is
built onto Class A board.
•For Class A, set CLA Adapter 1 (IDCs 1-5) or CLA
Adapter 2 (IDCs 1-10) System Option to ON. If using
expansion IDC module, set EXP IDC system option to
ON. See Chapter 6.
•Class B Circuits. Wire the circuit to the B+ / B- terminals. The circuit must be wired with IN/OUT wiring
from detector to detector and terminate with 733-893
EOLR.
•Maximum allowed wiring resistance is 50 ohms per circuit. Suggested wire is 18 AWG, allowing up to 3500’
distance from panel to EOLR (Class B) or Class A
Board (Class A). For Simplex Model 4098-9683 relay
base, limit is one device per circuit. For all other detectors and bases, up to 30 devices per circuit are allowed.
•Maximum detector standby current is 3 mA per IDC.
Maximum detector alarm current is 60 mA per IDC.
16-32 VDC, 1/2 V peak-to-peak maximum ripple. Maximum circuit capcitance is 100 uf per IDC.
•Compatible detectors:
-4098-9601, photoelectric smoke (2.8%) detector
-4098-9602, combination photo/heat detector
-4098-9605, photoelectric smoke (special
sensitivity) detector
-4098-9612, 135° F, Fixed temp heat detector
-4098-9613, 135° F, Fixed temp/rate of rise heat
-4098-9614, 200° F Fixed temp heat detector
-4098-9615, 200° F Fixed temp/rate of rise heat
The compatibility identifier is the model number associated with the board or module.
•Compatiblebases:
-4098-9788, two-wire base (max. 30 per loop).
-4098-9683, two-wire base with auxiliary relay
(limit of one per IDC).
-4098-9684, two-wire base with LED for use with
heat detectors 4098-9612
-through 9615 (max. 30 per loop).
-4098-9682, 4-wire base with aux. alarm relay (max.
30 per loop). See “Wiring 4098-9682 Four-Wire
Base” below.
General Wiring Notes -- Apply to NACs on Main
System Board (MSB) and Expansion Power Supply
Refer to Figure 2-6 and Figure 2-7.
•All wiring must be 18 AWG (min.) to 12 AWG (max.).
•Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
•All wiring is supervised and power limited.
•Terminate Class B (Style Y) NACs as shown using 733-
894. For Canadian applications, mount end-of-line
resistor to TEPG-US Model 431537 EOL plate in accordance with ULC-S527.
•Wire Class A (Style Z) NACs from B+/B- to each appliance as shown. No EOL device is required. Connect
wires from +/- terminals of last appliance to the A+/Aterminals as shown.
•System is shipped with 10K, 1/2 W resistors connected
across NAC B+/B- of each circuit. Remove this resistor
from any circuits in use. Leave resistor installed if circuits are unused.
•Voltage rating: Refer to “NAC Ratings” on Page 2-7 for
specific voltage specifications. Maximum ripple: 1/2V
peak-to-peak.
•Current rating: 2A maximum for either circuit. 3A total
between both circuits and Aux. 24 V load.
•Terminal designations (+/-) are for the alarm state.
•When using two-wire audible/visible appliances, maximum wiring capacitance must be considered. For
TrueAlert Non-Addressable notification appliances,
.22uF maximum is allowed.
•If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex 20819028 or 2081-9044. A protector must be installed at
each building exit/entrance. Each 2081-9028 adds .2
ohms wiring resistance. 2081-9044 adds 6 ohms wiring
resistance. Use of 2081-9044 will greatly reduce wiring
distance.
•Wiring chart gives max. distance for 1/4 -2A loads. For
Class B circuits wiring distance is from panel terminals
to last appliance. For Class A circuits, wiring distance is
from panel terminals to last appliance and back to panel
terminals. Use of 2081-9044 reduces wiring distance.
Table 2-1 Wiring Distances
Maximum Wiring Distance in Feet
Alarm
Current
(Amps)
.2584013352126338212
.50420667106316916
.7528044570911274
1.02103345328453
1.251682674256762.4
1.501402223545642
1.751201913044831.71
2.01051672664231.5
18
AWG
16
AWG
14
AWG
12
AWG
Line
Resistance
(Ohms)
Location of Expansion Power Supply NACs (If
Used)
The Expansion Power Supply (EPS) is located to the bottom
right of the main system board (MSB), as shown below. Wiring guidelines for these NACs are identical to the guidelines
for the MSB NACs.
The panel is rated Special Application for 2A maximum per
NAC with Simplex 4901 and 4906 TrueAlert & TrueAlert
Multi-Candela Notification Appliances.
For all other UL Listed Notification Appliances, NACs are
rated regulated 24 VDC at 1.5 A maximum each. Maximum
allowed strobe load on either the main or expansion power
Table 2-2 NAC Ratings
15Cd30Cd75Cd110Cd
4906-
91010.060330.094210.186100.2527
91020.075260.125160.23380.3166
91030.060330.094210.186100.2527
91040.075260.125160.23380.3166
91270.075260.116170.22190.2857
91280.086230.132150.25080.3206
91290.075260.116170.22190.2857
91300.086230.132150.25080.3206
Rated
Current
Max. # per
NAC
Rated
Current
Max. #
per NAC
supply is 1.35 A. The balance of the 3 A capacity can be
auxiliary loads or audible notification appliances.
Synchronization of strobes across all NACs in a system is
UL Listed for the Simplex models noted in the table below.
See the table below for maximum number allowed of each
appliance per NAC.
Rated
Current
Max. # per
NAC
Rated
Current
Max. # per
NAC
91510.060330.094210.186100.2527
91540.075260.125160.23380.3166
91530.060330.094210.186100.2527
All other regulated 24 VDC synchronized notification
appliances require the use of their associated, listed external
synchronization module. Notification Circuit rating is 1.5 A
maximum, 1.35 A maximum strobe load per power supply.
Use the UL-rated operating current to determine maximum
number of appliances allowed per NAC.
•All wiring must be 18 AWG (minimum) to 12 AWG
(maximum). Conductors must test free of all grounds
and stray voltages before connection to appliances,
devices, and panel.
•Contact rating: 30VDC @ 2A, 0.35 power factor
•If using expansion relay module, set EXP RELAY system option to ON.
•Each relay is selected for normally closed or normally
open operation. Shunt jumper setting (see figure) selects
desired contact.
•Relay 1 is programmable. Its default operation is Common Alarm - On Until Reset. Jumper is P1.
•Relay 2 is a normally energized, common trouble relay.
The jumper settings noted in the figure account for the
relay being normally energized. Jumper is P2.
•When the panel is completely powered off, the trouble
relay will be in the “Off Normal” state.
The DACT connection is made from the Main System Board
to the public telephone system via terminals TB5-1/TB5-2
and TB5-5/TB5-6. Wiring information is shown in
Figure 2-9.
•The DACT requires two telephone line connections to
meet NFPA72 requirements. Wire from TB5-3/TB5-4
and TB5-7/TB5-8 to an RJ-11 or other Telcom wiring
block for connection to other telephone equipment. The
DACT will seize control of the telephone line (if necessary) to transmit emergency messages. When wired as
shown, the DACT will properly control access to lines
in an emergency.
•Wire from Telcom equipment to TB5 using 18 AWG to
24 AWG.
•All DACT wiring is supervised.
•Digital Alarm Communicator Receiver (DACR) compatibility is shown in Table 2-3.
•If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex 20819028 or 2081-9044. A protector must be installed at
each building exit/entrance. Each 2081-9028 adds .2
ohms wiring resistance. 2081-9044 adds 6 ohms wiring
resistance. Use of 2081-9044 will greatly reduce wiring
distance.
RAM = Remote Annunciator Module
MSB = Main System Board
Remote Annunciator Wiring
•All wiring must be 18 AWG (min.) to 12 AWG (max.),
twisted pair or shielded twisted pair.
•Conductors must test free of all grounds and stray voltages before connection to appliances, devices, or panel.
•All wiring is supervised and power-limited.
•Refer to instructions packed with remote annunciator
modules for connection details to each module.
•Remote annunciators require power and communications wiring.
•For “bus-style” wiring (see figure), maximum wiring
limit is 4, 000 feet.
-Maximum wiring capacitance is 0.58µF total,
wire-to-wire plus wire-to-shield.
-Attach 733-974 (100 ohm, 1/2W) resistor as shown
for line matching. See Note A in figure below. Wire
remote devices “daisy-chain” style, using in/out
terminals on each device.
•For “T-Tap” style wiring, total cable limit is 10,000 feet,
2,500 feet to the furthest device.
-Maximum wiring capacitance is .58uF total, wire-
to-wire plus wire-to-shield.
-Attach 733-974 (100 ohm, 1/2W) resistor (see Note
A in figure) for line matching.
•Shielded wire is not required for most installations. If
communications wiring is not in conduit with strobes or
voice speaker circuits, shielded wiring is not required.
Use shielded wiring if remote annunciator wiring shares
a conduit with these signals. Terminate shield to 0V
(Aux 24V Neg.) or to chassis.
•If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex 20819028 or 2081-9044. A protector must be installed at
each building exit/entrance. Each 2081-9028 adds .2
ohms wiring resistance. 2081-9044 adds 6 ohms wiring
resistance. Use of 2081-9044 will greatly reduce wiring
distance.
•Wiring must pass through a ferrite bead. Wrap the wiring twice through the ferrite bead, as shown in
Figure 2-12.
•City connect module mounts to the main system as
shown. Refer to City Module Installation Instructions
for details.
•City module consists of two circuits that are jumperconfigured. Circuits may be configured for reversepolarity or local energy operation. See jumper setting
table for details. Modules must also be added to the system configuration. See “System Options” later in this
manual.
•All wiring to be per NPFP-72, NEC, and local codes.
Minimum 20 AWG for reverse polarity; minimum 18
AWG for local energy circuits.
•Conductors must test free of all grounds.
•Wiring is supervised for opens and grounds, but not
power-limited.
•For specific information about reverse polarity and local
energy circuits, see Figure 2-13.
•If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex 20819028 or 2081-9044. A protector must be installed at
each building exit/entrance. Each 2081-9028 adds .2
ohms wiring resistance. 2081-9044 adds 6 ohms wiring
resistance. Use of 2081-9044 will greatly reduce wiring
distance.
•Circuits are shipped with 3.3K, 1/2W resistor installed.
Remove resistor before wiring circuit. Leave installed
on unused circuits.
•All wiring must be 18 AWG (minimum) to 12 AWG
(maximum).
•Conductors must test free of all grounds and stray voltages before connection to appliances, devices, and
panel.
•All wiring is supervised and power-limited.
•Voltage rating (24 VDC special application): 1 V p-p
ripple (maximum)
-0.5 A maximum available aux 24 V from EPS
-Additional 0.5 A maximum available from Main
System Board (MSB) AUX 24 V
-3 A total available from MSB NACs and MSB
AUX 24 V.
-3 A total available from EPS NACs and EPS AUX
24 V.
•Compatible with Simplex 4098 Series Peripherals; 2098
Series Relay Modules; all Simplex 4090 Series IDNet
Peripherals; and 4610-9111 / 4606-9101 Annunciators.
•If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex Model
2081-9028 or 2081-9044. A protector must be installed
at each building exit/entrance. Each 2081-9044 adds 6
ohms wiring resistance, and is rated for 200mA. Each
2081-9028 adds .2 ohms wiring resistance, and is rated
for more than 1/2A Aux. 24V capacity.
•Compatible devices must operate from a range of 19.5
to 28 VDC or greater, and have a total current draw of 1/
2 A or less.
•Before handling AC feed, use a voltmeter to verify the
feed is not live. Make sure the circuit is de-energized
and tagged to prevent injury.
•AC feed must be routed in the wiring area below the
main system board, in the area designated “not power
limited.”
•AC power must be wired from a dedicated circuit
breaker or fuse, rated 20 A, per NFPA-72, NEC, and
local codes.
•AC supply wiring must be 14 AWG minimum to 12
AWG maximum.
•Connect a 12 AWG copper ground wire from safety
ground in the electrical distribution panel to the panel
safety ground stud.
•Input voltage range:
-120 VAC, 60 Hz
-240 VAC, 50Hz
-No configuration settings required to select
•The Expansion Power Supply (EPS) is an option, and
requires AC power when used. Connect the Black/
White AC harness from the EPS to the TB4 AC input
terminals on the main system board. Wire Black to the
left terminal of TB4. Wire White to the right terminal of
TB4.
•AC wiring is supervised. Safety ground wire is not
supervised.
•Supply Power Requirements
-120 VAC 60 Hz, 2A maximum
-240 VAC 50 Hz, 1.5A maximum
1.Remove insulating cover marked with the high voltage
warning.
2.Connect AC feed wires to terminal block located at bottom left of board. Terminals are labeled LINE (120V)
and NEUTRAL. Wire the AC feed through the ferrite
bead (provided). Refer to Figure 2-18.
3.Before applying AC power to the system, connect the
batteries per the instructions on the following page, and
replace the protective cover removed in step 1.
4.Connect Safety Ground from electrical service to
mounting stud (see Figure 2-18) marked with Earth
symbol. Use a terminal lug that is suitable for the
ground wire and nut used.
•The main battery harness connects the main system
board to the battery set in the same cabinet.
•The system requires 24V battery backup. Use two 12V
batteries, connected in series. The main battery harness
connects to the .250” fast-on battery terminals, as follows:
1.Connect black wire to the negative battery terminal
of Battery 1
2.Connect white wire from the positive battery termi-
nal of Battery 1 to the negative battery terminal of
Battery 2.
3.Connect the red wire to the positive battery termi-
nal of Battery 2.
•Connect the main battery harness to the four-position
header, located approximately in the center of the bot-
tom edge on the main system board. Insert the connector left-justified, with the red wire to the left.
•The EPS connects to the battery header next to the battery harness described in the previous bullet. Install the
EPS red/black harness right-justified to the battery
header, with the black wire to the right.
•Battery circuit is supervised, but not power-limited.
•For depleted battery cutout operation, remove jumper
per installation instructions. Separate jumper removal
required for main system board and EPS. System programming option “Depleted Battery Cutout” must also
be selected. ULC-S527 depleted battery operation
requires jumper removal.
•For 18 Ah or larger batteries, the 4009-9801 external
battery cabinet must be used. Mount the battery box
within 20 feet of the control panel, in accordance with
the mounting instruction label in the box. All interconnecting wiring must be enclosed in conduit.
For depleted battery cutout, remove the jumper shown in
Figure 2-17 from the main system board. If you are using an
Expansion Power Supply (EPS), you must also remove
Jumper R76 from the EPS. (When programming the panel,
make sure to enable the Depleted Battery Cutout system
option.)
Figure 2-17 Location of Depleted Battery Jumper
Safety Ground/Ferrite Bead
System Powerup and Checkout
Use the following procedure to apply AC and battery power
to the 4006.
On power up, the panel performs the following:
•Displays revision of boot-loader software
•CPU self test
•Link Scan - checks for a programming unit connection
•Memory Test - Verifying system and job-specific software
•Startup - 4006 Exec startup
If the panel successfully completes its start up self-test, it
will indicate a warm or cold start trouble, which clears when
acknowledged. If there are no other troubles in the system,
the following is displayed:
SYSTEM NORMAL
12:00 am 21-FEB-03
If other troubles exist in the system, the following is displayed:
FIRE | SUPV | TRBL
00 | 00 | 02
Proper operation and protection against transient energy per
UL864 and ULC-S527 requires connection of safety ground
wire to cabinet chassis as shown in Figure 2-18.
In addition, a ferrite bead must be attached to the incoming
AC power line as shown in the figure. Wrap the LINE and
Neutral legs of the power line twice through the ferrite bead.
Figure 2-18 Safety Ground and Ferrite Bead
Pressing the <TROUBLE ACK> key allows the operator to
acknowledge the troubles (silencing the panel sounder) and
scroll through the troubles on the active Trouble List.
If the 4006 self-test fails, the panel displays an error code
and waits 30 seconds before attempting a restart.
Acceptance Testing
When you are finished with the original installation, programming and all modifications, conduct a complete operational test on the entire installation to verify compliance with
applicable NFPA standards and Local Codes. Testing should
be conducted in the presence of a representative of the
Authority Having Jurisdiction (AHJ), and the customer's
representative. Follow procedures outlined in Chapter 10
“Inspection, Testing, and Maintenance” of NFPA standard
72-2002 and as dictated by local codes.
Testing Circuit Supervision
Use the following procedures to confirm that IDCs and
NACs are supervising for opens, shorts and grounds. The
right column in this table shows the LEDs that illuminate
when an open, short, or ground occurs on a specific circuit.
•Class B Circuit. Remove the
end-of-line resistor from
either the IDC or NAC.
•Class A Circuit. Disconnect
the return wiring from the
main system board (NAC
only), or from the IDC Class A
module.
To create a short:
Apply a zero ohm jumper across
the IDC or NAC circuit.
To create an Earth ground:
Place a 10K or smaller value resistor from supervised wiring to Earth
ground.
Illuminates the System Trouble
LED.
Illuminates the System Trouble
LED.
Illuminates the System Trouble
LED.
If you have programmed a front
panel or annunciator LED to detect
Earth ground conditions, the programmed LED also illuminates.
Refer to “Common Panel LED
Applications” in Chapter 5 of this
manual for information on programming an Earth Fault LED.
Chapter 2. Installation and System Checkout
Test mode is activated by placing the magnet at the location
indicated by the "I" mark, which is embossed on the detector
housing. The visible LED flashes to indicate the detector's
condition.
•NORMAL - When in test mode, the detector latches
into alarm if the unit is within calibration range. The
visible LED stays on, with no blink codes transmitted.
•MORE SENSITIVE - When in test mode, if the detector
is too sensitive, (more sensitive than the maximum calibration), the visible LED quickly flashes, at a twice per
second rate. Following the sixth flash, the detector
latches into alarm and the visible LED stays ON.
•LESS SENSITIVE - When in test mode, if the detector
is less sensitive than the minimum calibration, the visible LED slowly flashes, at a rate of one flash every two
seconds. Following the fourth flash, the detector latches
into alarm and the visible LED stays ON.
Table 2-5 Test Modes
StateNormal Test
Mode
Replacing Lithium Battery
The panel uses a lithium battery to maintain non-volatile
memory on the panel. In the event of a total power-down
(AC power and lead-acid battery), the lithium battery allows
the panel to maintain all historical logs, time/date information, list of disabled points, and the alarm verification tallies.
Important Note: The lithium battery must be replaced only
by a qualified service technician.
Periodic Testing and Maintenance
The minimum requirements for periodic testing of the fire
alarm system are outlined in chapter 10 of NFPA-72, 2002
edition. Local codes may require additional testing and
maintenance. All system components must be tested in
accordance with governing codes. Specific details on select
system components are provided below.
Smoke Detector Tests
The detectors include magnetically operated functional tests.
The magnet tests indicate if the detector is within sensitivity
settings. The detector will also indicate whether or not it
needs cleaning due to buildup of dirt or dust. This indication
is via LED blink codes. The table shown below shows the
blink codes associated with the detectors during magnetic
test. Refer to the detector installation documents for additional details.
LED
NormalXX
More Sensitive
Less Sensitive
Not Functioning
flashes
every 4
seconds
XXX
XXX
X
LED fastflashes
six times
LED
slowflashes
four times
Latches
in alarm
LED
stays ON
Battery Tests
The batteries used with the 4006 FACP are sealed lead-acid
type. The battery charger is temperature compensated per
battery manufacturer recommendations. There is no charger
voltage adjustment. Batteries should be tested by discharging them with a suitable tester and verifying that battery
voltage is at least 21V when fully discharged. Battery discharge tests should be performed annually, and batteries
should be replaced no longer than 4 years from date of
installation. Batteries should be installed within six months
of the date of manufacture. At normal room temperature,
battery voltage should be 27-27.6V when the battery set is
fully charged. At higher temperatures, the voltage will be
lower. At lower temperatures, the voltage will be higher. The
battery charger has a negative temperature coefficient. At
higher temperatures, the chemical process in the battery is
accelerated. This means that the ideal charger voltage is
lower. Likewise, at lower temperatures, a higher output volt-
age is required for full charge. Control of battery charge
voltage relative to ambient temperature prolongs battery life.
The chart below shows the proper range of battery voltage
across the specified operating range of the equipment. The
chart is for 12-cell battery sets, with nominal 24V rating.
NOTICE TO INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program Feature or OptionPermitted in UL 864? (Y/N)Possible SettingsSettings Permitted in UL 864
This chapter describes setting the characteristics of each initiating
device, notification appliance, and the programmable AUX relay to the
specific values required for the job. Refer to Chapter 4 for information
on programming the DACT; refer to Chapter 5 for information on programming annunciator LEDs.
You can set the following attributes for each of the panel’s IDCs, NACs,
and AUX Relays:
•Function Type. Determines the operation of the point. For a NAC
or relay, for example, you can set whether the device turns off on
silence or reset, etc.
•Label. Up to 20 characters can be used to create a custom label for
the point. A word library, containing common words associated
with fire alarm points, and an alphanumeric keypad allow labels to
be quickly and accurately created.
•Alarm Group. Applies to NACs, Relays, and Initiating Device
Circuit points. Allows you to define selective signalling groups.
Each NAC or Relay point can be associated with up to three alarm
groups, allowing you to specify which initiating devices are
allowed to activate the device.
Keep the following in mind if you are adding or deleting an
expansion IDC module.
•Adding Expansion IDCs (only if 4006-9802 Expan-
sion IDC Module is installed). To add an expansion IDC
module to the job, set the “Exp IDC” system option,
described in Chapter 6 of this manual, to ON.
•Deleting Expansion IDCs (only if 4006-9802 Expan-
sion IDC Module was previously installed and has been
removed). To delete an expansion IDC module from the
job, change the setting of the “Exp IDC” system option
from ON to OFF. The “Exp IDC” option is described in
Chapter 6 of this manual.
If an Expansion Power Supply Module is installed in the
system, you must first set the Expansion Power Supply system option to ON before programming NACs. Refer to
Chapter 6 - System Options for information on doing this.
All operations described in this chapter require you to first
login at Access Level 4. See Chapter 1 for information on
doing this.
Note: The <Exit/Clear> key is used to back out of menus or
displays and return to the top-level menu structure. Where
possible, the <Exit/Clear> key backs out one level at a time.
There are cases, however, that the Exit/Clear key will return
the operator directly to the top-level menu.
2.Press <ENTER>. The Programming menu appears.
[Points] is the default selection, which allows you to
make changes to a specific point’s programming.
<ENTER>=Accept
Prg:[Points]
3.Press <ENTER>. A prompt appears, allowing you to
select the type of point to manually edit. By default,
[IDC] is the first choice.
<ENTER>=Accept
Prg:[IDC]
4.Use the <NEXT> and <PREV> keys to scroll to the
appropriate choice and then press <ENTER>.
•IDC
•NAC
•RELAY (Use for on-board and expansion relays).
Select the operation you want to perform and see the appropriate section in this chapter. (The other options that appear
when you perform Step 4 -- LED, Input, User SW LED -apply to annunciators. Programming annunciator points is
described in Chapter 5 of this manual.)
Editing IDCs
Default General Alarm Programming
The panel ships with the following default programming
installed on the panel.
•All IDCs are configured as general fire alarm monitor
zones.
•NAC1 and NAC2 are configured for on-til-silence operation (temporal coding).
Accessing Menus
Use the following steps to gain access to the programming
menu.
1.Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
Editing an IDC allows you to change the following attributes
for each circuit.
•Function - change the functional characteristics of each
IDC zone (i.e., change the zone from a Fire monitoring
zone to a Supervisory zone).
•Alarm Group. Assign the IDC to up to three system
alarm groups.
•Edit/Clear Label. Allows you to assign or clear the 20character custom label for the zone.
Setting IDC Function Type
The Function Type determines the way in which the IDC
operates (whether the zone is a fire, trouble, waterflow/
sprinkler zone, etc.).
1.Follow the steps in “Accessing Menus”. Make sure to
choose IDC as the type of device to program.
<ENTER>=Accept
Prg: [IDC]
2.Press <ENTER>. A prompt similar to the following
appears.
3.Use the <NEXT> and <PREV> keys to scroll through
the choices until [Edit] is displayed.
<ENTER>=Accept
IDC: [Edit]
4.Press Enter. Information on the first IDC in the list
appears.
IDC1
FireM1
The top line shows the custom label assigned to the first
IDC point (IDC1 in the example). Use the <NEXT> and
<PREV> keys to scroll through the list of IDC circuits.
5.Press <ENTER> when the appropriate IDC is displayed. A prompt appears, asking you to specify the
function type.
IDC1
Fn: [Function]
6.Press <ENTER> and use the <NEXT> and <PREV>
keys to scroll through the choices shown in Table 3-1.
The default function type assigned to all IDCs is FIRE.
7.Pressing <ENTER> will accept any changes made and
exit, and the <EXIT/CLEAR> key quits editing without
saving.
Note: Refer to table located at top of Page 3-1 for
UL 864 compliant options.
Note: The alarm verification cycle works on a per-zone
basis as follows. If a device with the function type
VSMOKE enters a current-limited state, the alarm verification cycle begins. The panel starts a delay timer of 30 seconds. When the timer expires, the zone containing the
activated detector is reset. Following the reset, another 10
second timer starts. When the 10 second timer expires, the
system checks the zone for an alarm. If a current-limited
condition exists on the zone, the panel initiates a fire alarm.
If no current-limited condition exists, the panel starts a 2
minute timer. While the timer is counting down, any currentlimited condition on any zone will trigger a fire alarm.
A short from a pull-station always triggers an alarm condition, regardless of the alarm verification cycle.
At any stage of the alarm verification cycle, the presence of
two devices in alarm triggers an alarm condition.
The VSMOKE function type shall not be enabled for Canadian applications.
Entering Labels
1.Follow the steps in “Accessing Menus”. Make sure to
choose IDC as the type of device to program.
<ENTER>=Accept
Prg: [IDC]
2.Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
IDC: [Add]
and allows editing. Clear Label deletes the existing label
first and then allows editing.)
IDC1
Fn: [Edit Label]
6.Press <ENTER>. A cursor appears beneath the leftmost
letter of the currently assigned custom label. Use the left
and right arrow keys to move the cursor between letters.
You can edit a label in one of three ways:
•Using the Keypad. Press the alphanumeric key cor-
responding to the letter you want. For example, for
the letter “C”, press the “2” key on the keypad three
times. Use the left and right arrow keys to move to
the next letter in the label.
•Use the <NEXT> and <PREV> keys. Each time
you press the <NEXT> key, the display advances to
the next character. Likewise, each press of the
<PREV> key moves backward one character. Use
the left and right arrow keys to move to the next letter in the label.
•Use the Word Library, which is a stored list of com-
mon words sorted alphabetically. Press the
<FUNCTION> key on the front panel. A prompt
similar to the following appears.
IDC1
<FUNC>=Word Library
To jump to a word, press the alphanumeric key cor-
responding to the first letter in the word. For example, to use the word Floor, press the “3” key
repeatedly until Floor appears.
3.Use the <NEXT> and <PREV> keys to scroll through
the choices until [Edit] is displayed.
<ENTER>=Accept
IDC: [Edit]
4.Press Enter. Information on the first IDC in the list
appears.
IDC1
FireM1
The top line shows the custom label assigned to the first
IDC point (IDC1 in the example). Use the <NEXT> and
<PREV> keys to scroll through the list of IDC circuits.
5.Press <ENTER> when the appropriate IDC is displayed. Use the <NEXT> and <PREV> keys to scroll
through the choices until <Edit Label> or <Clear
Label> appears. (Edit Label preserves the existing label
The following is a list of all words in the library.
Table 3-2 Word Library
Default of blanks5thFloor
NorthFlr_1Garage
SouthFlr_2Hallway
EastFlr_3HVAC_Room
WestFlr_4Kitchen
FrontFlr_5Lobby
CenterRM __Office
rearBasementPatient
3-4
Page 41
Chapter 3. Programming IDCs, NACs, and AUX Relays
Table 3-2 Word Library (Continued)
upperBoiler_RMRestroom
lowerClassroomRoom
mainCloset__Stairway
firstCorridorStoreroom
2ndElect_RMWing
3rdElevatorZone
4thEntrance
7.Pressing <ENTER> saves the current label. Pressing
<EXIT/CLEAR> will quit label editing without saving.
Editing Alarm Groups
Alarm groups allow you to program selective signaling.
Assign the IDC an alarm group number from 1 to 99. Assign
the same alarm group number to the notification appliances
that you want to turn on when one of the IDCs in the alarm
group activates. Each IDC can be in up to three groups.
1.Follow the steps in “Accessing Menus”. Make sure to
choose IDC as the type of device to program.
<ENTER>=Accept
Prg: [IDC]
2.Press <ENTER>. Use the <NEXT> and <PREV> keys
to choose EDIT, and then press <ENTER>. Use
<NEXT> and <PREV> keys to choose the circuit
(IDC1, IDC2, etc.) to program.
IDC1
FIREM1
move between the alarm groups. Press <ENTER> when
all the values are set correctly.
Programming NACs
Use the following procedure to edit the programming of the
two Notification Appliance Circuits (NACs) on the base
panel, or the two optional NACs on the expansion power
supply. NACs cannot be added or deleted - only edited.
Note: If the panel is using an Expansion Power Supply, set
the EXP POWER system option to ON before programming
NACs.
NAC editing provides the following options:
•Edit Function, which defines the following for a NAC:
-When the NAC activates and deactivates.
-The “output method” used by the NAC when it
activates (coded, steady, etc.).
•Alarm Group
•Edit Point Label
•Clear Point Label
Setting NAC Function Type
The Function Type determines the way in which the NAC
operates (whether it is an audible, visual, etc.) and its output
method (steady, etc.)
1.Follow the steps in “Accessing Menus”. Make sure to
choose NAC as the type of device to program
<ENTER>=Accept
Prg: [NAC]
2.Press <ENTER>, and then use <NEXT> and <PREV>
keys to choose the circuit (NAC1, NAC2, NAC3, or
NAC4) to program.
3.Press <ENTER> and then press the <NEXT> and
<PREV> keys until [Alarm Groups] is displayed. For
example:
IDC1
Fn: [Alarm Groups]
4.Press <ENTER>. A prompt similar to the following
appears.
ALARM GROUPS
[99]0000
5.Use the <NEXT> and <PREV> keys to scroll the number in the brackets. Use the right and left arrow keys to
3.Press <ENTER> when the appropriate NAC is displayed. A prompt appears, asking you to specify the
function type.
NAC1
Fn: [Function]
4.Press <ENTER>. As shown in the example below, the
NAC function type is comprised of two parts -- the
function (On Till Silence, On Till Reset, etc.) and the
coding pattern (temporal, 120 BPM, etc.)
3-5
Page 42
Chapter 3. Programming IDCs, NACs, and AUX Relays
NAC1
[SSIG]TEMPRL
5.Use the <NEXT> and <PREV> keys to select the
appropriate Function. Use the right arrow key (>)to
move the cursor to the coding pattern, and then use the
<NEXT> and <PREV> keys to set the pattern. Refer to
Table 3-3 and Table 3-4 for information on NAC function types and coding patterns.
6.Pressing <ENTER> will accept any changes made and
exit, and the <EXIT/CLEAR> key quits editing without
saving
Note: Refer to table located at top of Page 3-1 for
UL 864 compliant options.
Table 3-3 NAC Function Types
Function
Type
General Alarm Horn/Strobe (horn on-til-silence;
strobe on-til-reset). Use for NAC circuits containing
both horns and strobes.
Compatible visual-only devices include:
• 4906-9101, wall-mount, visual-only, red
• 4906-9102, ceiling-mount, visual-only, red
• 4906-9103, wall-mount, visual-only, white
• 4906-9104, ceiling-mount, visual-only, white
Description
Function
Type
RSIG
SUPV
TRBL
UTILITY
Table 3-3 NAC Function Types
Description
General Alarm (on steady-til-reset). Use for NAC
circuits containing visual-only devices. Set NAC
Coding Pattern (see Table 3-4) to SYNC.
Compatible devices include:
• 4906-9101, wall-mount, visual-only, red
• 4906-9102, ceiling-mount, visual-only, red
• 4906-9103, wall-mount, visual-only, white
• 4906-9104, ceiling-mount, visual-only, white
NAC activates when there is a supervisory condition active in the system. NAC is on until supervisory condition is cleared.
NAC activates when there is a trouble condition
active in the system. NAC is on until trouble condition is acknowledged.
NAC activates when an IDC with the following
attributes activates:
• IDC must be in same alarm group as utility NAC.
• IDC must be assigned a Utility function type.
Typically used for process monitoring function. For
example, a relay on a machine is tied to the IDC.
When the relay activates, the utility IDC activates
and triggers the utility NAC.
QALERT
SSIG
Compatible A/V devices include:
• 4906-9127, wall-mount, red
• 4906-9128, ceiling-mount, red
• 4906-9129, wall-mount, white
• 4906-9130, wall-mount, red
Compatible audible-only devices include:
• 4901-9820, wall-mount, red, horn only. Horn
must be selected for two-wire horn strobe control. See Horn Instruction manual.
General Alarm (on til-silence). Use for NAC circuits
containing only audible devices.
Compatible audible-only devices include:
• 4901-9820, wall-mount, red, horn only.
Table 3-4 NAC Coding Patterns
OperationDescription
Standard Temporal coded pattern. A three
Temporal
Synch
SteadySteady On
20 BPMSlow March Time - 20 beats per minute
120 BPMFast March Time - 120 beats per minute
pulse coding pattern consisting of three ½
second pulses, each separated by ½ second
silence. Each group of three pulses is separated by 1.5 seconds of silence.
Generates synchronization pulse for visualonly NAC circuits that use the following
visual-only devices.
This option allows you to assign a 20-character custom label
to each NAC point.
1.Follow the steps in “Accessing Menus.” Make sure to
choose NAC as the type of device to program.
<ENTER>=Accept
Prg: [NAC]
2.Press <ENTER>, and then use <NEXT> and <PREV>
keys to choose the circuit (NAC1, NAC2, NAC3, or
NAC4) to program.
NAC1
Signa11/4
3.Use the <NEXT> and <PREV> keys to scroll through
the choices until <Edit Label> or <Clear Label>
appears. (Edit Label preserves the existing label and
allows editing. Clear Label deletes the existing label
first and then allows editing.)
Refer back to Table 3-2 for a list of words in the
library.
5.Pressing <ENTER> saves the current label. Pressing
<EXIT/CLEAR> will quit label editing without saving.
Editing Alarm Groups
Alarm groups allow you to program selective signaling.
Assign the NAC an alarm group number from 1 to 99.
Assign the same alarm group number to the initiating
device(s) that you want to control the NAC. Each NAC can
be in up to three groups.
1.Follow the steps in “Accessing Menus”. Make sure to
choose NAC as the type of device to program
<ENTER>=Accept
Prg: [NAC]
2.Press <ENTER>, and then use <NEXT> and <PREV>
keys to choose the circuit (NAC1, NAC2, NAC3, or
NAC4) to program.
NAC1
Fn: [Edit Label]
4.Press <ENTER>. A cursor appears beneath the leftmost
letter of the currently assigned custom label. Use the left
and right arrow keys to move the cursor between letters.
You can edit a label in one of three ways:
•Using the Keypad. Press the alphanumeric key cor-
responding to the letter you want. For example, for
the letter “C”, press the “2” key on the keypad three
times. Use the left and right arrow keys to move to
the next letter in the label.
•Use the <NEXT> and <PREV> keys. Each time
you press the <NEXT> key, the display advances to
the next character. Likewise, each press of the
<PREV> key moves backward one character. Use
the left and right arrow keys to move to the next letter in the label.
•Use the Word Library, which is a stored list of com-
mon words sorted alphabetically. Press the
<FUNCTION> key on the front panel. A prompt
similar to the following appears.
NAC1
Signal1/4
3.Press <ENTER> and then press the <NEXT> and
<PREV> keys until [Alarm Group] is displayed. For
example:
NAC1
Fn: [Alarm Groups]
4.Press <ENTER>. A prompt similar to the following
appears.
ALARM GROUPS
[99]0000
5.Use the <NEXT> and <PREV> keys to scroll the number in the brackets. Use the right and left arrow keys to
move between the alarm groups. Press <ENTER> when
all the values are set correctly.
NAC1
<FUNC>=Word Library
To jump to a word, press the alphanumeric key cor-
responding to the first letter in the word. For example, to use the word Floor, press the “3” key
repeatedly until Floor appears.
Aux Relay programming allows you to define the following
for the first auxiliary relay located on the MSB, and the
expansion relays (if installed). (Aux Relay 2 is always a
trouble relay.)
•Function, defines the following for a relay.
-When the Relay activates and deactivates.
-The "output method" that defines how the Relay
activates (coded, steady, etc.)
•Edit or Clear Point Label. Allows you to set a 20 character label for the relay point.
•Alarm Group. Allows you to associate the relay with up
to 3 groups of initiating devices, providing the ability to
perform selective activation of the relay.
1.Follow the steps in “Accessing Menus.” Make sure to
choose Relay as the type of device to program.
<ENTER>=Accept
Prg: [Relay]
2.Press <ENTER>, and then use <NEXT> and <PREV>
to choose the relay to program.
Note: Refer to table located at top of Page 3-1 for
UL 864 compliant options.
Table 3-5 Relay Function Types
Function
Type
SRELAY
RRELAY
SUPV
TRBL
Utility
PRIMARY
See Note
Below
ALTERN
See Note
Below
Relay activates on general alarm; remains on-tilsilence.
Relay activates on general alarm; remains on-tilreset.
Relay activates when a Supervisory condition
occurs; remains on-til-cleared.
Relay activates when a Trouble condition occurs;
remains on-til-acknowledge.
Relay activates when a utility IDC in the same
alarm group activates.
Relay activates on general alarm. Relay is tied to
Primary Elevator Recall contacts.
Relay activates on general alarm. Relay is tied to
Alternate Elevator Recall contacts.
Description
AUX1
Alarm1/2
3.Press <ENTER>. A prompt for the Function Type displays. For example:
AUX1
FN: [Function]
4.Press <ENTER>. As shown in the example below, the
function type is comprised of two parts -- the function
(On Till Silence Relay, On Till Reset, etc.) and the coding pattern (Steady, 120 BPM, etc.)
AUX1
[RRELAY]STEADY
5.Use the <NEXT> and <PREV> keys to select the
appropriate Function. Use the right arrow key to move
the cursor to the coding pattern, and then use the
<NEXT> and <PREV> keys to set the pattern.
6.Pressing <ENTER> will accept any changes made and
exit. <EXIT/CLEAR> key will quit the alarm group edit
without saving
DRESET
DHOLDER
Table 3-6 Relay Operation Settings
Relay provides 24V power to four wire detectors.
Relay turns off for 5 secs on system reset)
Relay typically provides 24V power to larger door
holder relay with separate power source. Relay
activates on general alarm and signals door
holder relay to cut power to door holder magnets.
OperationDescription
Standard Temporal coded pattern. A three pulse coding pattern consisting of three ½
Temporal
SteadySteady On
SYNCHN/A - Do not use
20 Bpm
second pulses, each separated
by ½ second silence. Each
group of three pulses is separated by 1.5 seconds of
silence.
•The relay must have a function type of Primary or Alternate and must be wired to the appropriate elevator control contact.
•The IDC zones used to trigger elevator recall must be
associated with the following alarm groups.
-Alarm Group 98. Associate all zones used to recall
the elevator to the primary floor in this alarm
group.
-Alarm Group 97. Associate all zones used to recall
the elevator to the alternate floor in this alarm
group.
Editing Point Label
This option allows you to assign a 20-character custom label
to each relay point.
1.Follow the steps in “Accessing Menus”. Make sure to
choose Relay as the type of device to program.
<ENTER>=Accept
Prg: [RELAY]
2.Press <ENTER>, and then use <NEXT> and <PREV>
keys to choose the relay (AUX1, AUX2, etc.) to program.
AUX1
Alarm1/2
Use the left and right arrow keys to move to the
next letter in the label.
•Use the Word Library, which is a stored list of common words sorted alphabetically. Press the
<FUNCTION> key on the front panel. A prompt
similar to the following appears.
AUX1
<FUNC>=Word Library
To jump to a word, press the alphanumeric key cor-
responding to the first letter in the word. For example, to use the word Floor, press the “3” key
repeatedly until Floor appears.
Refer back to Table 3-2 for a list of words in the
library.
5.Pressing <ENTER> saves the current label. Pressing
<EXIT/CLEAR> will quit label editing without saving.
Pressing the <ENTER> key will save the current label,
and <EXIT/CLEAR> will quit label editing without
saving.
Clear Point Label
The "Clear Point Label" menu performs the same function as
"Edit Point Label" described above except that it clears the
point's currently assigned label first.
Saving Changes
3.Press <ENTER>, and then use the <NEXT> and
<PREV> keys until <Edit Label> is displayed. For
example:
AUX1
Fn: [Edit Label]
4.Press <ENTER>. A cursor appears beneath the leftmost
letter of the currently assigned custom label. Use the left
and right arrow keys to move the cursor between letters.
You can edit a label in one of three ways:
•Using the Keypad. Press the alphanumeric key cor-
responding to the letter you want. For example, for
the letter “C”, press the “2” key on the keypad three
times. Use the left and right arrow keys to move to
the next letter in the label.
•Use the <NEXT> and <PREV> keys. Each time
you press the <NEXT> key, the display advances to
the next character. Likewise, each press of the
<PREV> key moves backward one character.
When IDC, NAC, and relay programming is complete, press
the EXIT/CLEAR key until the following prompt is shown.
[Cont]DscrdSave
Use the right arrow key to move the cursor to one of the following options and press <ENTER>.
•Cont - continues the edit session.
•Dscrd - exits the edit session without saving your
changes (keeps the job that was loaded before you
started editing).
The panel’s DACT (Digital Alarm Communicator Transmitter) allows
the panel to use one or two telephone lines to call a supervising station
(remote station or central station) and report a local alarm, trouble, or
supervisory condition.
This chapter describes programming the DACT options to specify the
characteristics of the DACT’s phone connection, communication format, and the format of the event or CID codes used by the supervising
station.
Login at Level 4 before starting DACT programming. See Chapter 1 for
information on doing this.
Note: The <Exit/Clear> key is used to back out of menus or displays
and return to the top-level menu structure. Where possible, the <Exit/
Clear> key backs out one level at a time. There are cases, however, that
the Exit/Clear key will return the operator directly to the top-level
menu.
Accessing DACT Menu
1.Press the <MENU> key. Press <NEXT> or <PREV> until the [Programming] option is displayed. Press <ENTER>. The following
displays:
5.Use the <NEXT> and <PREV> keys to select one of the
following choices.
•Options. This choice allows you to program a wide
range of DACT parameters (supervising station
phone numbers and account codes, dialing mode,
communications format, etc.). Refer to “Programming DACT Options” below for specific information.
Note: If no DACT is installed, use this option to
disable the DACT. See “Programming DACT
Options,” below for more information.
•Event Codes. The 3/1, 4/2, BFSK, and SIA com-
munication formats support per-event reporting of
fire alarms, trouble conditions, etc. With these formats, the supervising station receives a general
code for an event type that does not specify the
activated point.
Use this choice to verify and edit the codes for each
event type. Refer to “Programming Event Codes,”
below for more information.
Note: Only the 3/1 and 4/2 formats allow editing.
•CID Points. The Contact ID communication for-
mat supports per-point reporting of system events.
The supervising station receives a code identifying
the point and the event type (alarm, trouble, etc.).
With this format, the DACT can also send a restoral code to the supervising station after the device
experiencing the alarm, trouble, or supervisory
condition is restored to a normal state. Use this
choice to verify and edit the activation and restoral
codes for each point. Refer to “Programming Contact ID (CID) Event Codes,” below for more information.
Programming DACT Options
1.Follow the steps in “Accessing DACT Menu”. Make
sure to choose Options as the type of device to program.
<ENTER>=Accept
DACT: [Options]
Enabling/Disabling DACT
1.Press <ENTER> at the DACT: [Options] prompt. The
following prompt appears, allowing you to enable or
disable the DACT.
<ENTER>=Accept
Opt: [Enable DACT]
2.Press <ENTER>. The following appears.
Enable DACT
[OFF]
3.Use the <NEXT> or <PREV> keys to change the setting to ON.
By default, the DACT is enabled, but unconfigured. The
DACT will report a configuration trouble until the
phone numbers and account numbers are programmed,
or until it is disabled if it will not be used.
4.Press <ENTER>. A prompt appears, asking you to confirm the choice.
5.Press <ENTER> to confirm the selection. The prompt
shown in Step 1 reappears. Use the <NEXT> key to
move to the prompt for primary phone number.
Setting Primary Phone Number
The next prompt allows you to set the Primary Phone Number of the supervising station. This is the number that the
DACT dials first.
<ENTER>=Accept
Opt: [Pri Phone #]
1.Press <ENTER>. The following prompt appears.
Pri Phone #
[X] XXXXXXXXXXXXXXXX
2.Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and
PREV keys to enter each number. Press <ENTER>
when the number is correctly entered. A prompt appears
asking you to confirm the number that you entered.
Note: The following special characters are available for
use when setting the primary and secondary phone numbers.
•B -- Use if it is necessary to input an DTMF (touch-
tone) asterisk (*) into the phone number.
•C -- Use if it is necessary to input a DTMF pound
sign (#) into the phone number.
•D -- Inserting this character into the phone number
causes a 3 second delay at the point at which the D
appears.
•E -- This character causes the DACT to wait two
seconds for a secondary (outside line) dial tone. It
may be necessary to use this character if you must
dial a specific number (9, for example) to get an
outside line on the phone system. For example, 9E
would cause the DACT to request an outside line
and then wait 2 seconds for the secondary dial tone
before proceeding with the rest of the phone number. If you use the “E” special character, make
sure to set the Dial Mode to Tone; do not use
Tone else Pulse.
3.Press <ENTER>. The prompt shown in Step 1 reappears.
4.Press the <NEXT> key. The prompt for the primary
account number appears.
Setting Primary Account Number
The primary account number is a unique identifier assigned
and used by the Central Station.
Pri Account #
[0] 000
1.Use the arrow keys to move the cursor from one number
to another. Use the NEXT and PREV keys or the keypad to enter each number.
2.Press <ENTER> when the number is correctly entered.
A prompt appears asking you to confirm the number
that you entered.
3.Press <ENTER>. The prompt shown above Step 1 reappears.
4.Press the <NEXT> key. The prompt for the Secondary
Phone Number appears.
Setting Secondary Phone Number
The Secondary Phone Number specifies the alternate phone
number that the DACT can use if attempts to dial the primary phone number fail.
3.Press <ENTER> again. The prompt shown above Step 1
reappears.
4.Press the <NEXT> key. The prompt for the Secondary
Account Number appears.
Setting Secondary Account Number
The secondary account number is a unique identifier
assigned and used by the Supervising Station.
Sec Account #
[0] 000
1.Use the arrow keys to move the cursor from one number
to another. Use the NEXT and PREV keys or the keypad to enter each number.
2.Press <ENTER> when the number is correctly entered.
A prompt appears asking you to confirm the number
that you entered.
3.Press <ENTER>. The prompt shown above Step 1 reappears.
4.Press the <NEXT> key. The prompt for setting the dialing mode appears.
Setting Dialing Mode
The dialing mode specifies the type of phone line being used
by the DACT.
<ENTER> = Accept
Dialing Mode
1.Press <ENTER>.
Dialing Mode
[Tone else Pulse]
Note: You can also use the special characters B, C, D, and E
when specifying the Secondary Phone Number. See the
description of these characters in the section “Setting Primary Phone Number” above.
<ENTER>=Accept
Opt: [Sec Phone #]
1.Press <ENTER>. The following prompt appears.
Sec Phone #
[X] XXXXXXXXXXXXXXXX
2.Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and
PREV keys to enter each number. Press <ENTER>
when the number is correctly entered. A prompt appears
asking you to confirm the number that you entered.
2.Use the NEXT and PREV keys to move from one
choice to another. Choices are tone (touchtone), pulse,
and tone else pulse (attempt to dial with a touchtone format and if that fails, use a pulse format).
3.Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4.Press <ENTER>. The prompt shown above Step 1 reappears.
5.Press the <NEXT> key. The prompt for the Pulse Rate
appears.
Setting Pulse Rate
The Pulse Rate option specifies the pulse rate used with
either the 3/1 or 4/2 pulse format. This option does not apply
to other formats.
4-3
Page 50
Chapter 4. Programming the DACT
<ENTER> = Accept
Pulse Rate
1.Press <ENTER>.
Pulse Rate
[20 PPS]
2.Use the NEXT and PREV keys to move from one
choice to another. Choices are 20 pulses per second
(PPS), which is the default, and 10 PPS.
3.Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4.Press <ENTER>. The prompt shown above Step 1 reappears.
5.Press the <NEXT> key. The prompt for the Pulse Frequency appears.
Setting Pulse Frequency
The pulse frequency specifies the frequency (in KHz) of the
pulses used by the DACT.
<ENTER> = Accept
Opt: [Pulse Freq]
Report Format
[Contact ID]
The DACT can report in any of the following communication formats.
•3/1 pulse = Three-digit account code followed by
one-digit reporting code, double round at 20 pulses
per second (PPS). Allows programmable reporting
codes. Refer to “Programming Event Codes” later
in this chapter.
•4/2 pulse = Four-digit account code followed by
two-digit reporting code, double round at 20 PPS.
Allows programmable reporting codes. Refer to
“Programming Event Codes” later in this chapter.
•BFSK = Three-digit account code followed by
two-digit reporting code, single transmission of
constant tones. Features built-in error checking and
fixed reporting codes.
•SIA = Level 1 compatibility. Four-digit account
code features tonal acknowledge, basic reports, and
fixed reporting codes.
•Contact ID (Default). Uses a four digit account
code, followed by a two- digit group number and
three digit contact number.
1.Press <ENTER>.
Pulse Freq
[1.9KHz Data]
2.Use the NEXT and PREV keys to move from one
choice to another. Choices are
1.9 KHz
1.8 KHz
3.Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4.Press <ENTER>. The prompt shown above Step 1 reappears.
5.Press the <NEXT> key. The prompt for the Reporting
Format appears.
Reporting Format
Before you select the Communications Format Code, determine, from an authorized person at the Supervising Station,
the required reporting format.
<ENTER> = Accept
Opt: [Report Format]
1.Press <ENTER>. The following prompt appears.
2.Use the NEXT and PREV keys to move from one
choice to another.
3.Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4.Press <ENTER>. The prompt shown above Step 1 reappears.
5.Press the <NEXT> key. The prompt for the AC Fail
Delay appears.
AC Fail Delay
The AC Fail Delay allows you to specify the interval
between power loss at the panel and when the DACT notifies the central station of the power loss. AC fail delay is
selectable from 0-24 hours.
AC Fail Delay
[06] Hrs
1.Use the NEXT and PREV keys to move from one
choice to another.
2.Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
3.Press <ENTER>. The prompt shown above Step 1 reappears.
4.Press the <NEXT> key. The prompt for the Test Report
Time appears.
Test Report Time
This option specifies the time at which the Test Report Event
is sent to the supervising station. Time is set in 24 hour, military format.
<ENTER> = Accept
Opt: [Test Rpt Time]
1.Press <ENTER>.
Test Rpt Time
[02] : 00
2.Use the NEXT and PREV keys to increment or decrement the hour setting (two digits on left). Use the right
arrow key to move the cursor to the minutes (two digits
on right). Use the NEXT and PREV keys to increment
or decrement the minutes setting.
3.Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4.Press <ENTER>. The prompt shown above Step 1 reappears.
5.Press the <EXIT/CLEAR> key. The prompt for setting
DACT options reappears. Press the <NEXT> key to
access either the CID Points or Event Codes menus.
Table 4-1 Default CID Event Codes
Function TypeFireSupervisoryTrouble
PULL115-330
SMOKE111-330
SO-200330
WSO110200330
SUPV-200330
UTIL--330
TROUBLE--330
VSMOKE111-330
LATSUPV-200330
STYLEC110-330
OTHER TRBL*--330
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
1.Follow the steps in “Accessing DACT Menu,” earlier in
this chapter. Use the <NEXT> or <PREV> keys to
choose CID Points.
<ENTER>=Accept
DACT: [CID Points]
Programming Contact ID (CID)
Points
Follow the procedure below only if the DACT is using the
Contact ID (CID) reporting format. CID reporting format
requires you to specify the group and Contact ID for each
point, but there is no need to specify the type of event with
the CID format. This information is automatically derived
from the point’s function type.
Note: Default CID point values are provided in the panel.
Before changing these values, please contact an authorized
representative at the supervising station.
Table 4-1 Default CID Event Codes
Function TypeFireSupervisoryTrouble
FIRE110-330
WATER113-330
HEAT114-330
DUCT116-330
2.Press <ENTER>. A prompt similar to the following
appears.
[GarageIDC1]
GRP: 01ID: 001
This prompt consists of the following fields.
•Point Custom Label. The top line of the prompt dis-
plays the custom label assigned to the point.
•Grp. A 2-digit number used to group associated
devices together.
•ID (Contact ID). A 3-digit number used to identify
a specific point/device.
3.For each point, use the right arrow key to move between
the digits of the GRP and ID fields. Use the <NEXT>
and <PREV> keys to increment or decrement the value
of a digit.
4.To choose another point, press the right arrow key until
the cursor is on the top line (custom label) of the
prompt. Use the <NEXT> and <PREV> keys to scroll
to another point and then repeat Step 3.
5.When all points have been configured, press the
<ENTER> key. A prompt similar to the following
appears, asking you to confirm the changes you made.
<ENTER>=Confirm
GRP: [01]ID:001
6.Press <ENTER>. The prompt shown in Step 1 appears.
Programming Event Codes
Follow the procedure below only if the DACT is using the
3/1 or 4/2 reporting format.
1.Follow the steps in “Accessing DACT Menu,” earlier in
this chapter. Use the <NEXT> or <PREV> keys to
choose Event Codes.
<ENTER>=Accept
DACT: [Event Codes]
2.Press <ENTER>. A prompt similar to the following
appears.
[FIRE ALARM]
Code: A1
Table 4-2 Event Categories and Codes
Event3/1BFSK4/2SIA
Trouble RestoralEE474FJ4
Phone Line 1
Trouble
Phone Line 1
Restoral
Phone Line 2
Trouble
Phone Line 2
Restoral
AC FailureFFA6AAT0
AC RestoralEEA7AAR0
Auto Test ReportEEE3ARP0
Manual Test
Report
Off-normal at
test
FFB31LT1
EEB35LR1
FFC32LT2
EEC36LR2
EEE3ARX0
FF833YX0
3.For each code, use the right arrow key to move between
the letter/digit of the Code field. Use the <NEXT> and
<PREV> keys to increment or decrement the value of a
letter or digit. See Table 4-2 for a list of Event types and
their corresponding codes.
4.To choose another code to edit or verify, press the right
arrow key until the cursor is on the top line of the
prompt. Use the <NEXT> and <PREV> keys to scroll
to another code and then repeat Step 3.
5.When all points have been configured, press the
<ENTER> key. A prompt similar to the following
appears, asking you to confirm the changes you made.
<ENTER>=Confirm
Code: A1
6.Press <ENTER>. The prompt shown in Step 1 appears.
Table 4-2 Event Categories and Codes
Event3/1BFSK4/2SIA
Fire Alarm111A1FA1
Supervisory333A3SS3
Note: Event codes for SIA and BFSK are non-editable.
Saving Changes
When DACT programming is complete, press the EXIT/
CLEAR key until the following prompt is shown.
[Cont]DscrdSave
Use the right arrow key to move the cursor to one of the following options and press <ENTER>.
•Cont - continues the edit session.
•Dscrd - exits the edit session without saving your
changes (keeps the job that was loaded before you
started editing).
This chapter describes programming LEDs located on the following
annunciators:
•Local Zone LED Annunciator. This is a door-mounted annun-
ciator containing 10 Red and 14 Yellow LEDs, which provides a
red alarm and yellow trouble LED for each of 10 initiating device
circuits. This module also provides 4 Yellow LEDs, one for each of
4 NACs. The LEDs are programmable, and can be used for other
functions as appropriate per application.
•4610-9111 Remote LED/Switch Annunciator
-10 programmable red LEDs (default programming tracks
alarm state of IDC1-IDC10)
-6 programmable yellow LEDs (no default operation)
-Green “power on” LED (not programmable)
-Yellow “Alarm Silenced” LED (not programmable)
-Yellow “Trouble” (not programmable)
-Yellow “Comm Loss” LED (not programmable)
-Tone-Alert (not programmable).
-Switches for ACK, Alarm Silence, System Reset, and Lamp
Test. Note that these switches are not programmable.
-Key switch to enable switch functions.
Up to four annunciators can be added to the panel. Annunciator
addresses must be within the range of 4 through 7, and the address setting on the annunciator (set via an 8-position dipswitch) must match the
setting that you specify when you program the unit.
For Canadian applications, one red LED and one yellow LED must be
programmed for each IDC and each NAC. Yellow LEDs must be programmed for indicating Earth Detect, City/DACT Disconnect, and Signal Silence Inhibit Enabled. If the total number of IDCs plus NACs
exceeds 10, an additional remote annunciator shall be mounted adjacent
to the panel. See “Common LED Applications” later in this manual for
information on programming the LEDs for Earth Detect, City/DACT
disconnect, and Signal Silence Inhibit Enabled.
Note: The <Exit/Clear> key is used to back out of menus or displays
and return to the top-level menu structure. Where possible, the <Exit/
Clear> key backs out one level at a time. There are cases, however, that
the Exit/Clear key will return the operator directly to the top-level
menu.
Use the Automatic Programming option to automatically
add annunciator modules to the job. (This option will also
detect and add an Expansion Power Supply and City Card, if
installed.)
1.Press the <MENU> key. Press <NEXT> or <PREV>
until the [Automatic Programming] option is displayed.
Press <ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.Press <ENTER>. The following prompt appears.
<ENTER>=Accept
AP: [Reconfig All]
3.Use the <NEXT> key to select [Detect New]. The following prompt appears.
<ENTER> to Continue
*May CHANGE Setting*
4.Press <ENTER> to detect and add annunciators to the
job.
4.Press <ENTER>. Use the <NEXT> and <PREV> keys
to scroll through the choices until “Add” is displayed.
<ENTER>=Accept
Annuns: [Add]
5.Press <ENTER>. A prompt appears, asking you to identify the specific type of annunciator.
<ENTER>=Accept
Add: [LCD]
6.Use the <NEXT> and <PREV> keys to select one of the
following:
•Zone Ann
•Remote LED/SW
•LCD. Option not applicable to this panel.
7.Press <ENTER>. A prompt appears, asking you to set
the card address for the annunciator. The address you
specify must match the address set via dip switch on the
annunciator. The address must be in the range of 4
through 7.
8.Use the <NEXT> and <PREV> keys to select the
appropriate address and press ENTER.
9.A prompt appears asking you to confirm the addition of
the annunciator. Pressing <ENTER> will accept any
changes made and exit. Use the <EXIT/CLEAR> key to
quit without saving.
Manually Adding an Annunciator Module
Use the following procedure to manually add the annunciator module to the job.
1.Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.Press Enter. The Programming menu appears:
<ENTER>=Accept
Prg:[Points]
3.Use the <NEXT> and <PREV> keys to scroll through
the choices until “Annuns” is displayed.
<ENTER>=Accept
Prg:[Annuns]
Accessing Annunciator Menus
1.Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.Press <ENTER>. The Programming menu appears.
[Points] is the default selection, which allows you to
make changes to a specific point’s programming.
<ENTER>=Accept
Prg:[Points]
3.Press <ENTER>. A prompt appears, allowing you to
select the type of point to manually edit. By default,
[IDC] is the first choice.
Point 17
Point 20
Point 22
Point 4
Point 5
Point 6
Point 7
Point 8
Point 9
Point 10
Point 11
Point 12
Point 13
Point 14
Point 15
Point 16
Prg:[IDC]
4.Use The <NEXT> and <PREV> keys to scroll to the
appropriate choice and then press <ENTER>.
•LED. Use this selection for programming the fol-
lowing:
-LEDs on 4610-9111 Remote LED/Switch
Annunciator.
-LEDs on Local Zone LED Annunciator (doormounted annunciator).
•INPUT. Option not applicable to this panel.
•USER SWITCH/LED (Panel LEDs). Option not
applicable to this panel.
Programming LEDs Located on
Zone Annunciator and Remote LED/
Switch Modules
Use the procedures outlined in this section to program any of
the following:
•LEDs on Local Zone Annunciator
•LEDs on Remote LED/Switch Module
Note: The three LEDs on the front of the display are programmed in a different manner. Refer to ”Programming
Panel LEDs” at the end of this chapter for information.
Mapping LEDs to Software Points
Figure 5-1 identifies the way in which the software points
map to the LEDs on the annunciators. For example, to control the LED in the upper left corner of the Local Zone LED
Annunciator, you need to program Point 17.
Chapter 5. Programming Annunciator LEDs
Figure 5-1 Mapping LEDs to Software Points
Programming Overview
Programming an LED consists of performing the following
tasks
•Identify which point is being monitored by the LED
(called the reference point).
•Identify which point state (fire alarm, trouble, etc.) triggers the LED to turn on. This is called the mode.
See “Programming the LED’s Mode and Reference Point”
later in this chapter.
For example, you can associate an LED with a smoke detector point and have the LED turn on only when the point
enters a trouble state.
Default Programming
The LEDs on the Local Zone LED and Remote LED/Switch
annunciators have the pre-defined operations listed in Table
5-1 and Table 5-2.
In both tables, a default function of FIRE means the LED
illuminates if a current-limited condition occurs on the corresponding reference point. A default function of TROUBLE means the LED illuminates if a short occurs on the
corresponding reference point.
5-3
Page 56
Chapter 5. Programming Annunciator LEDs
Table 5-1 Default LED Assignments,
Local Zone LED Module
LED/ColorDefault Function
1TROUBLEIDC10
2TROUBLENAC2
3FIREIDC9
4TROUBLEIDC2
5FIREIDC3
6TROUBLEIDC3
7FIREIDC4
8TROUBLEIDC4
9FIREIDC5
10TROUBLEIDC5
11FIREIDC6
12TROUBLEIDC6
13FIREIDC7
14TROUBLEIDC7
15FIREIDC8
16TROUBLEIDC8
17FIREIDC1
18TROUBLEIDC9
19FIREIDC10
20TROUBLEIDC1
21TROUBLENAC 1
22FIREIDC2
23TRBLNAC 3
24TRBLNAC4
Table 5-2 Default LED Assignments, Remote LED/
Switch Module
PointType
1Tone-Alert
2Yellow LED
4Red LEDFIREIDC4
5Red LEDFIREIDC5
6Red LEDFIREIDC6
7Red LEDFIREIDC7
8Red LEDFIREIDC8
Default
Function
PIEZO (tracks state
of main piezo).
General Trouble (illuminates on any trouble).
Default Reference
Point
Default
Reference
Point
none
none
Table 5-2 Default LED Assignments, Remote LED/
Switch Module
PointType
9Red LEDFIREIDC9
10Red LEDFIREIDC10
11Yellow LEDTROUBLE.IDC1
12Yellow LEDTROUBLEIDC2
13Yellow LEDTROUBLEIDC3
14Yellow LEDTROUBLEIDC4
15Yellow LED - TROUBLEIDC5
16Yellow LED - TROUBLEIDC6
17Red LED - FIREIDC1
18Yellow LED - nonenone
20Red LED - FIREIDC2
22Red LED - FIREIDC3
Default
Function
Default
Reference
Point
Note: Do not program Point 2 (Common Trouble LED
or Point 18 (Comm Loss) on the LED/Switch Annunciator.
Programming the LED’s Mode and Reference Point
An LED’s mode allows you to specify which point is being
monitored by the LED (called the reference point) and what
point state triggers the LED to turn on. For example, you can
associate an LED with a smoke detector point and have the
LED turn on only when the point enters a trouble state.
1.Follow the steps in “Accessing Annunciator Menus”
earlier in this chapter. Choose LED as the type of
device to program.
<ENTER>=Accept
Prg:[LED]
2.Press <ENTER>. A scrollable list of points appears.
Use the <NEXT> and <PREV> keys to scroll to the
LED point you want to edit. The display appears similar
to the following.
LED Card 5, Pt 1
LED1/24
3.Press <ENTER>. The next prompt appears similar to
the following:
4.Press <ENTER>. A prompt similar to the following
appears.
Mode Prg - Output
[TRBL]15-10
5.Use the <NEXT> and <PREV> keys to scroll through
the available modes. As you scroll through the modes,
the default reference address for the mode appears to the
right of the mode. Refer to Table 5-3 for a list of the
available modes.
6.When the appropriate mode is selected, use the right
arrow key to move the cursor brackets over to the reference point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a
text-based description. Refer to Table 5-4 for a list of
common reference points. For example:
Type: BZONEFire
IDC10
7.Use the <NEXT> and <PREV> keys to scroll through
the list of available reference points.
8.Press <ENTER> when the appropriate reference point is
displayed. The prompt shown in Step 4 reappears.
9.Press <ENTER>. A prompt appears, asking you to confirm the changes.
10. Press <ENTER> to confirm the changes.
Table 5-3 LED Modes
Table 5-3 LED Modes
ModeDescription
LS
LT
Output activates when any point is in a supervisory condition.
Output activates when any point is in a trouble condition.
Table 5-4 Common LED Reference Points
Reference
Point
IDCs 1-10
Aux Relays 1
and 2
City/DACT Disconnect (18-14)
City Trouble
Control Bypass
Elevator Bypass
Door Bypass
List - General
Alarm Points
Separate reference point for each IDC. State
monitored determined by selected LED
mode.
Separate reference point for each relay. State
monitored determined by selected LED
mode.
Separate reference point for disconnect and
trouble. Typical use is to monitor the ON state
of either point.
Separate reference point for each type of
bypass.Typical use is to monitor the ON state
of any of the points.
List contains all zones with FIRE, VERIF, or
STYLEC function type. Monitoring the Fire or
Trouble state of this list allows you to illuminate an LED when any zone in the list enters
an alarm or trouble state. Select either FIRE
or TRBL as the mode.
Description
ModeDescription
FIRE
SUPV
TRBL
DISA
ON
OFF
LF
Output activates when referenced point is in
an Alarm condition.
Output activates when referenced point is in a
Supervisory condition.
Output activates when referenced point is in a
Trouble condition.
Output activates when the referenced point is
Disabled.
Output activates when the state of the reference point is ON.
Output activates when the state of the reference point is OFF.
Output activates when any point is in an
alarm condition.
List contains all zones with WATER or WSO
function type. Monitoring the Fire or Trouble
state of this list allows you to illuminate an
LED when any zone in the list enters an
alarm or trouble state. Use output mode to
select which state (Fire, Trouble) is monitored.
List contains all zones with SO or WSO function type. Monitoring the Fire, Trouble, or
Supervisory state of this list allows you to illuminate an LED when any zone in the list
enters an alarm, trouble, or supervisory state.
Select either FIRE, TRBL, or SUPV as the
mode.
Separate list for each alarm group. Monitoring
the Fire, Supervisory, Trouble, or ON state of
an alarm group list allows you to illuminate an
LED if any point in the group enters the fire,
trouble, supervisory, or ON state. Use output
mode to select state monitored.
Page 58
Chapter 5. Programming Annunciator LEDs
Table 5-4 Common LED Reference Points (Cont’d)
Reference
Point
NACs 1 - 4
Separate list for each NAC. Monitoring the
ON or trouble state of a NAC allows you to
illuminate an LED if the NAC enters trouble
state or turns on. Use output mode to select
state (ON or trouble) monitored.
Description
Programming Panel LEDs
This section describes how to program the operation of the
three LEDs built-in to the front panel display. Programming
involves setting the reference point, mode (the point and
point state that triggers the LED to illuminate), and the color
of the LED.
Setting LED Color
1.Follow Steps 1 through 4 in “Accessing Annunciator
Menus” earlier in this chapter. Choose User SW/LED
as the type of device to program.
<ENTER>=Accept
Prg: [User SW/LED]
2.Press <ENTER>. A scrollable list of points appears.
Use the <NEXT> and <PREV> keys to scroll to the
point you want to edit. The display appears similar to
the following.
User LED 1
Y LED1/5
3.Press <ENTER>. Use the <NEXT> and <PREV> keys
to scroll through the options until [FUNCTION] is
shown.
User LED 1
Fn: [Function]
4.Press <ENTER>. A prompt similar to the following
appears, allowing you to set the LED color.
User LED 1
[Y LED]
5.Use the <NEXT> and <PREV> keys to toggle between
the following LED colors
•Y - Programs LED as a yellow LED.
•RG - Programs LED as a Red / Green LED. If you
assign this type to LED1 (top LED), its color will
be red. If you assign this type to LED2 (middle) or
LED3 (bottom), its color will be green.
6.Press <ENTER> to choose a color. A prompt appears
asking you to press <ENTER> to confirm the choice.
For Canadian applications, LED colors must comply with
Table 5-5.
Table 5-5 ULC LED Color Requirements
FunctionColor
Alarm InputsRed
Alarm SignalRed with unique identifier
Signal Circuit FaultYellow
InhibitYellow
Supervisory InputsYellow with unique identifier
Power - ONGreen
Trouble SignalYellow
Alarm Signal SilenceYellow
Setting LED Mode and Reference Point
An LED’s mode allows you to specify which point is being
monitored by the LED (called the reference point) and what
point state triggers the LED to turn on.
1.Follow Steps 1 through 4 in “Accessing Annunciator
Menus” earlier in this chapter. Choose User SW/LED
as the type of device to program.
<ENTER>=Accept
Prg: [User SW/LED]
2.Press <ENTER>. A scrollable list of points appears.
Use the <NEXT> and <PREV> keys to scroll to the
point you want to edit. The display appears similar to
the following.
User LED 1
Y LED1/5
3.Press <ENTER>. Use the <NEXT> and <PREV> keys
to scroll through the options until [Edit Mode] is shown.
User LED 1
Fn: [Mode]
4.Press <ENTER>. The next prompt appears similar to
the following:
Mode Prg - LED
[NONE]--
5.Use the <NEXT> and <PREV> keys to scroll through
the available modes. As you scroll through the modes,
the default reference address for the mode appears to the
right of the mode. Refer to Table 5-4 for a list of the
available modes.
6.When the appropriate mode is selected, use the right
arrow key to move the cursor brackets over to the reference point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a
text-based description. For example:
Type: BZONEFire
IDC10
7.Use the <NEXT> and <PREV> keys to scroll through
the list of available reference points.
8.Press <ENTER> when the appropriate reference point is
displayed. The prompt shown in Step 4 reappears.
9.Press <ENTER>. A prompt appears, asking you to confirm the changes.
10. Press <ENTER> to confirm the changes.
Common LED Applications
Common applications for programmable LEDs are:
•Earth Fault Detect LED. This LED tracks whether the
panel’s Earth fault system point is active or not. If the
point enters a trouble state (i.e., there is an Earth fault),
the yellow LED illuminates. Program the LED as follows:
-Make sure the color is yellow
-Select the "TRBL" mode
-Select 17-06 as the reference point
•Waterflow LED, which illuminates if a device with the
function type WATER or WSO activates. Program the
LED as follows:
-Make sure the LED color is red
-Select the "FIRE" mode
-Select 22-101 as the reference point
•City/DACT Disconnect (required for Canadian panels).
This LED tracks whether the City/DACT Disconnect
system point is active or not. If the point turns ON (i.e.,
either the city circuit or DACT has been disconnected),
the yellow LED illuminates. Program the LED as follows:
-Make sure the color is yellow
-Select the "ON" mode
-Select 18-14 as the reference point
•Signal Silence Inhibit Enabled (required for Canadian
panels). This LED tracks whether the Signal Silence
Inhibit Enabled system point is active or not. If the point
turns ON (i.e., Signal Silence Inhibit system option is
set to ON), the yellow LED illuminates. Program the
LED as follows:
-Make sure the color is yellow
-Select the "ON" mode
-Select 18-35 as the reference point
Saving Changes
When Annunciator programming is complete, press the
EXIT/CLEAR key until the following prompt is shown.
[Cont]DscrdSave
Use the right arrow key to move the cursor to one of the following options and press <ENTER>.
•Cont - continues the edit session.
•Dscrd - exits the edit session without saving your
changes (keeps the job that was loaded before you
started editing).
•Pre-defined modes of operation with a range of settings from which
to choose. These type of System Options define global operations
such as the time and date format, door drop timers, etc.
•Options that allow you to enable or disable a specific hardware
module, such as the Expansion Power Supply, City Circuit, etc.
Accessing System Options Menu
1.Login at Access Level 4. See Chapter 1 for information on logging
in and out of the system.
2.Press the <MENU> key. Press <NEXT> or <PREV> until the [Programming] option is displayed. Press <ENTER>. The following
displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
3.Press <ENTER>. The Programming menu appears. Press the
<NEXT> or <PREV> keys until <OPTIONS> appears.
<ENTER>=Accept
[Options]
In This Chapter
Accessing System Options Menu . . . . . . . . . .6-1
4.Press <ENTER>. The first prompt appears as follows:
<ENTER>=Accept
Opt: [Time/Date]
Note: The <Exit/Clear> key is used to back out of menus or displays
and return to the top-level menu structure. Where possible, the <Exit/
Clear> key backs out one level at a time. There are cases, however, that
the Exit/Clear key will return the operator directly to the top-level
menu.
Programming Options
Refer to the appropriate entry in the table below for details on each
option. In each case, programming the option involves using the
<NEXT> and <PREV> keys to scroll through the choices and then
using the <ENTER> key to set the option to the value you choose.
Choose 12 (am/pm) or 24-hour (miliTime/Date
Format
Reminder
Inhibit
(reference
point 18-35)
Alarm Cutout Timer
tary) format. Use <NEXT> and
<PREV> to scroll between options
and <ENTER> to set.
The Active Status Reminder option
allows you to set an interval and
duration during which the panel
reminds operators that a FIRE,
SUPV, or TBL condition still exists.
This is accomplished by sounding
the front panel tone-alert.
•Choose: ON or OFF (default =
OFF).
•Set reminder interval
(1-12 hours)
•Signal duration. This option sets
the duration of the acknowledge signal. (0-60 seconds;
0=on until ack).
The default for this option is 0,
meaning an acknowledge is
required to silence the reminder.
While timer is counting down, the
Alarm Silence/Reset Inhibit Timer
prevents a system operator from
using either the Alarm Silence or
System Reset functions. When the
inhibit timer expires, the panel may
be reset/silenced.
Choose a timer range from 0-60
minutes (default=0 - no inhibit)
The Alarm Signal Cutout timer
allows you to set a duration for how
long notification appliances sound
after an alarm. In other words, when
an alarm condition exists, the signals sound until silenced. With this
option set at two minutes, building
signals sound on alarm for two minutes and then stop sounding. However, the alarm condition remains
active.
OptionSettings
Allows the panel to hold doors open
for a set duration during an alarm
condition. After that duration has
expired, the panel shuts off the door
holder relays (all DHOLDER point
Alarm Doors
AC Doors
Door Holder
types). Choose a timer range from
0-60 minutes (default=0 - immediate
door drop). This option applies to all
DHOLDER relay function types,
regardless of their Alarm Group setting.
The Door Holder Drop on AC Failure
allows the panel to hold doors open
for a set duration during an AC
power loss condition. After that timer
has expired, the panel turns off the
door holder relays (all DHOLDER
point types). The range for the timer
is 0-60 minutes with a default setting
of 5 minutes. To have the door holders drop the doors immediately
upon AC power loss, set the timer to
0. This option applies to all
DHOLDER relay function types
regardless of their Alarm Group setting.
Enables or disables whether door
holder magnets receive power from
the panel during an alarm condition.
Set this option to ON if you want the
panel to provide power to all relays
with a DHOLDER function type
when an alarm occurs. Set this
option to OFF if you want the panel
to cut power to these relays when
an alarm occurs.
Choose a timer range from 0-60
minutes (default=0 - no cutout)
This option selects the operation of
the panel if an alarm occurs during
an AC power loss while a depleted
battery trouble exists. If this option
is selected, the system does the following:
•WILL NOT initiate an alarm if
the first alarm occurs after the
Depleted
Battery Cutout
Display 1st
Alarm
depleted battery state has been
detected. If the hardware jumper
for depleted battery cutout has
been clipped, the system will
shut down 60 seconds after the
depleted battery condition is
detected
•WILL continue sounding the
alarm if the depleted battery
state is reached after the system
is already in the alarm state.
When this option is selected, the
panel will automatically display the
first (oldest) alarm instead of the
Alarm Tally abnormal screen. This
allows the first responder to determine the location of the first alarm in
the system without having to open
the door and press the acknowledge
key.
If an unacknowledged alarm exists,
the system displays that alarm.
When that alarm is acknowledged,
the system shall revert to displaying
the oldest alarm.
If no fire alarms exist in the system,
the first supervisory event is shown
on the display. If no supervisories
exist, the first trouble is shown on
the display. If there are no fire
alarms, supervisories, or troubles,
the SYSTEM NORMAL screen is
displayed.
OptionSettings
This option activates the panel’s city
circuit Module. If a city circuit is used
in the system this option must be
selected or a trouble will be
Enable City
Circuit
Enable
Expansion
Power
Cross Zone
EXP IDC
reported. If this option is selected
and the city module is not connected, the trouble will also report.
There is no other programming
required for the city module. The city
type is configured with jumpers on
the city circuit board.
This option activates the panel’s
Expansion Power Supply Module
and its associated NACs. If the
expansion power supply is installed,
this option must be selected or a
trouble will be reported. If this option
is selected and the EPS is not connected, the trouble will also report.
Activation of this module allows the
two expansion NACs to be edited in
the Point programming menu.
Allows you to enable cross zoning
per alarm group. For example, if you
enable cross zoning for Alarm
Group 1, it takes two activated
alarms in Alarm Group 1 before outputs associated with that Alarm
Group will activate. To set this
option, use the <NEXT> and
<PREV> keys to increment or decrement the alarm group. Use the
Right arrow key to move to the On/
Off field. Use the <NEXT> and
<PREV> keys to toggle between On
and Off.
Alarm Groups programmed as
Cross Zone shall not contain any
zones programmed as VSMOKE
IDC Function Type.
Set to ON if an expansion IDC module is installed on the panel. Set to
OFF if the module is not used.
The panel’s operator interface shows the following under normal conditions:
•Green AC power LED is on steady
•All other panel indicator LEDs are off
•Front panel LCD shows the following:
SYSTEM NORMAL
1:45:07 pm 3/10/04
Lamp Test
Lamp Test is accomplished during normal monitoring (Access Level 1)
by pressing the Function key and then pressing ENTER. All LEDs energize and all LCD segments are written to.
Abnormal Conditions
Abnormal conditions are indicated on the panel by flashing the alarm,
supervisory, or trouble LED and sounding the tone-alert. The tone-alert
pulses for an alarm condition, and is on steady for a trouble or supervisory. If the “Display First Alarm” option is selected, the display provides information about the first, highest-priority alarm in the system
without operator intervention. If “Display First Alarm” is not selected, a
screen showing the overall system status is shown:
When the appropriate Acknowledge key is pressed, the tone-alert turns
off and the indicator LED illuminates steady, indicating that the operator
has acknowledged all events in that category. The first abnormal point
in that category is then shown on the display:
The panel is a Global Acknowledge system meaning that
one press of an Acknowledge key acknowledges every
abnormal point in the system within that category. Pressing
the Ack key allows the operator to scroll through all the
abnormal points in that category. The additional information
listed below can be obtained by pressing the <ENTER> key.
•The electrical state of the point (open, short circuit, normal, abnormal)
•Enable/Disable state of the point
•Manual override state (if output)
•Assigned Alarm Groups
Silencing Alarms
The "Alarm Silence" key allows the operator to silence
active Notification Appliance Circuits that are programmed
for "on-til-silence" operation.
Caution: Pressing the Alarm Silence key causes fire alarm
evacuation signals to turn OFF. Follow local procedures to
silence alarm evacuation signals.
To silence an alarm, press the <ALARM SILENCE> key.
•All "on-til-silence" notification appliance circuits will
turn OFF
•The Alarm Silenced indicator LED turns on
Viewing/Clearing Historical Logs
The panel has three separate, non-volatile historical logs:
Alarm, Supervisory, and Trouble. These logs can be viewed
separately, or they can be viewed in chronological order as a
single combined log. Each log records information about the
event and the time the event occurred. The following table
describes the different logs and their stored events.
Table 7-1 Log Contents
Historical
Log
ALOG
(Alarm Log
100 Entries)
SLOG
(Supervisory
Log
100 Entries)
TLOG
(Trouble Log
300 Entries)
CLOG
(Combined
Log)
Alarms
Alarm Acknowledge
Log Cleared
Alarm Silence
System Reset
Trouble Events
Login/Logout for Level 2 or higher
Log Cleared
WALKTEST Events
All Events in Chronological Order
Stored Events
If a subsequent alarm occurs, the notification appliance circuits resound.
System Reset
The <SYSTEM RESET> key restores the system to its normal state after an alarm condition has been cleared. When
the <SYSTEM RESET> key is pressed, it causes all latched
circuits to reset automatically. The system displays the
"RESET IN PROGRESS" message when the key is pressed.
After a short delay and if all alarms are cleared, the system is
restored to its normal, non-alarm state (e.g. all alarm notification, relays, etc. are turned off). The alarm points are
removed from the alarm list and the alarm LED turns off.
If a device remains in alarm during the reset period, the system reset is aborted, and the system remains in the alarm
state. The display continues to show the device(s) that
remain in alarm.
Viewing Logs
1.Press <MENU>.
2.Press <NEXT> and <PREV> until the following
prompt appears.
<ENTER>=Accept
Menu: [History Logs]
3.Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
Rep: [ALOG]
4.Use the <NEXT> or <PREV> key to select one of the
logs described in Table 7-1.
5.Press <ENTER> to access the contents of the log. Use
<NEXT> and <PREV> to scroll through each log entry.
The logs may be viewed at Access Level 1, however they
may not be cleared unless you are at Access Level 2 or
higher. To clear the log you are currently viewing, press
<ENTER> while viewing any log entry. The following
screen will be displayed:
<ENTER>= Clear Log
<EXIT> to cancel
Press <ENTER> to clear the current log. An entry is added
to the log to indicate that it was cleared.
Viewing and Controlling Points
The panel allows you to view each point in the system to
obtain additional information, or to control or disable/enable
it. Points may be viewed at Access Level 1, but control and
disable/enable operations are protected at Level 2 or higher.
Viewing Point Information
1.Press <MENU>.
2.Press <NEXT> and <PREV> until the following
prompt appears.
<ENTER>=Accept
Menu: [Control/View]
3.Press <ENTER>. A prompt similar to the following
appears.
6.Use the <NEXT> or <PREV> key to scroll through the
list of points for the selected category.
7.Press <ENTER> when the point whose status you want
to view is displayed. The Hardware Type and Function
Type for the point are shown. For example:
IDC1
FireNORMALM1
8.Additional information and control options are available
as described in the following table.
Table 7-2 Additional Point Information
a.Press <ENTER> to view the point’s
hardware type and assigned function
type. For example:
IDC1
BZONEFIRE
IDC
b.Press the <NEXT> key to view the fol-
lowing information for the IDC.
• Enable/Disable status
• Alarm Verification Tally
• Electrical state (normal, short, open,
abnormal)
• Assigned Alarm Groups
<ENTER>=Accept
Ctrl/View: [IDC]
4.Use the <NEXT> or <PREV> key to select one of the
following.
-IDC
-Relay
-NAC
-Input (Not Applicable)
-Output (LED)
-System Point - these are logical system points used
for on/off control of system functions. Control of
these points is not allowed.
5.Press <ENTER> when the appropriate point category
(i.e., IDC, NAC) is selected. A display similar to the
following appears.
IDC1
FireNORMAL
a.Press <ENTER> to view the point’s
b.Press the <NEXT> key to view the fol-
Relay or
NAC
InputN/A
hardware type and assigned function
type. For example:
NAC1
NAC
lowing information for the IDC.
•Electrical State (open/short/normal)
•Enable/Disable status
•Output state (on/off/coding)
•Automatic/Manual control status. See
“Manually Controlling a NAC/Relay”
below for additional information.
Table 7-2 Additional Point Information (Continued)
Output
(LED)
a.Press <ENTER> to view a description of
the first system point in the list. Press
NEXT to scroll through the list of points.
System
Point
a.Press <ENTER> to view a description of
the first system point in the list. Press
NEXT to scroll through the list of points.
Manually Activating a NAC/Relay
Follow these steps to manually turn a NAC or Relay on or
off, or set it to automatic operation.
1.Press <MENU>.
2.Press <NEXT> until Control/View is shown.
3.Press <ENTER>. Use the <NEXT> or <PREV> key to
select NAC or Relay.
4.Press <ENTER>. Use the <NEXT> or <PREV> key to
scroll through the list of points for NAC or Relay.
5.Press <ENTER> when the point you want to turn on or
off is displayed.
6.Press <NEXT> until a prompt similar to the following is
shown.
ENTER = Control AUX
TROUBLE STEADY
7.Press <ENTER>. The following prompt appears.
ENTER = Accept
FN: ON
8.Use <NEXT> to select one of the following:
•ON. Use this option to turn the relay or NAC on. To
return the NAC/Relay to automatic operation, first
set it to OFF, and then reselect the point and set it to
AUTO.
•OFF. Turns the relay or NAC off.
•AUTO. Use this option to return the NAC or Relay
to automatic operation.
3.Press <ENTER>. Use the <NEXT> or <PREV> key to
select IDC, NAC, or Relay.
4.Press <ENTER>. Use the <NEXT> or <PREV> key to
scroll through the list of points.
5.Press <DISABLE/ENABLE> when the point you want
to turn enable/disable is displayed. A prompt similar to
the following appears.
IDC1
FN: [Enable]
6.Use NEXT to toggle between Enable and Disable. Press
<ENTER>. A prompt appears asking you to confirm the
operation. Press <ENTER>. Keep the following in mind
when enabling/disabling points.
•When a monitor point is disabled, any status
changes occurring on the point are ignored by the
panel. If a control point is disabled, any automatic
functions are inhibited. A disable trouble will exist
for each disabled point in the system.
•When a monitor point is enabled, a 30-second
countdown will start to prevent an operator from
accidentally enabling a point that will alarm the
system. The point may be enabled immediately by
pressing <ENTER>, or the enable can be aborted
by pressing <EXIT>.
Control Functions
The panel includes the pre-programmed functions listed in
the table below. To access these functions, press the
<FUNCTION> key, and then use the <NEXT> key to scroll
through the options. Press <ENTER> to activate a function.
The table below shows the operations available in the Function menu.
Table 7-3 Control Functions
DrillActivates the drill operation (all notifica-
tion appliances).
Manual Evacuation
Activates manual evacuation (general
alarm).
Enabling or Disabling Points
Use the following steps to enable or disable points.
Disconnects the city circuit or DACT
(causes a trouble).
Page 69
Chapter 7. Operating
Table 7-3 Control Functions (Continued)
Control Point
Bypass
Bypasses the following control points
(causes a trouble):
•On-til-Silence NACs
•On-til-Reset NACs/relays
Elevator
Bypass
Doorholder
Bypass
Lamp TestIlluminates all LEDs and LCD segments
Earth Fault
Latch
Display TimeShows the current time and date.
Send DACT
Test
Bypasses Elevator Recall operation
(causes a trouble).
Bypasses the door holder operation
(causes a trouble).
on the operator interface.
Latches intermittent Earth troubles in the
panel, preventing them from automatically clearing.
Sends the DACT test event to the central station.
a.Connect a 733-794 download cable between the
Service Port on the panel and a serial communication port on the PC.
b.Create a connection profile for the serial port. Set
the serial communication parameters to 9600 baud,
8 bits, no parity, 1 stop bit, and no flow control.
c.Configure the application to capture the informa-
tion coming in on the serial port. (Choose Capture
Text in the Hyperterminal Transfer menu.)
To generate a report, do the following.
1.Press <MENU>.
2.Press <NEXT> and <PREV> until the following
prompt appears.
<ENTER>=Accept
Menu: [Reports]
3.Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
Rep: [ALOG]
Setting the Time and Date
Selecting the “Set Time/Date” option from the main menu
allows you to change the system time and date. This operation is protected at Access Level 2.
<ENTER>=Accept
[11]:23 pm 11/12/03
The Right/Left arrow keys allow you to move the focus from
field-to-field for editing. The <NEXT/PREV> keys allow
you to change the currently selected fields. The am/pm field
and the day-of-week field are not editable.
Reports
Reports, which are either text-based archives of system
activity or a text-based description of the panel configuration, can be archived and printed in the following manner.
•The panel supports an unsupervised, 80-column serial
printer that can be used to record events, or to print history log reports.
4.Use the <NEXT> or <PREV> key to select one of the
options described in Table 7-4.
Table 7-4 Reports
ReportDescription
ALOGDisplays contents of alarm log.
SLOGDisplays contents of supervisory log.
TLOGDisplays contents of trouble log.
CLOGCombined alarm, supervisory, and trou-
ble logs.
CONFIGText description - including custom label,
function type.
5.Press <ENTER>. The panel displays a message noting
that the report has been sent to the printer.
Diagnostics
Use the following procedure to run the panel’s diagnostic
options.
•Use Windows Hyperterminal (or similar application), as
follows:
2.Press <NEXT> and <PREV> until the following
prompt appears.
7-5
Page 70
Chapter 7. Operating
<ENTER>=Accept
Menu: [Diagnostics]
3.Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
Diag: [BAT CHGR METR]
4.Use the <NEXT> or <PREV> key to select one of the
options described in Table 7-5.
Table 7-5 Diagnostic Options
OptionDescription
BAT CHGR
METER
Battery MeterView battery voltage and battery load.
HW ResetThe Hardware Reset is context sensitive. If
CLR Tally/TBLThis option clears the alarm verification tallies
View battery charger incoming voltage, and
output current.
the reset is performed with an alarm in the
system, the alarms are allowed to reset. If
there are no alarms present, a HW reset
(power is dropped to all zones for 15 seconds) is performed. The hardware reset will
attempt to clear any latched troubles.
for all IDCs in the system. Typically this is
only done when an Alarm Verification Tally
Limit trouble occurs. The Alarm Verification
Tally Limit trouble occurs if an IDC programmed for alarm verification starts the verification cycle, but does not verify 10 times.
5.Press <ENTER>. The function you chose in Step 4 executes.
WalkTest
WalkTest allows one person to test the functionality of the
panel’s devices. Once the panel is placed into WalkTest
mode, you can test the following:
•Initiating Device Alarm Sensing. To test each detector’s
alarm capability, use a pole magnet or canned smoke to
activate the initiating device. If the device is functioning
correctly, one of two things happen:
-If the WalkTest signaling option is set to SIG, the
panel pulses the device’s zone number on the
panel’s NACs. After 15 seconds the panel drops
power to the zone, resetting the activated device.
Subsequently activating another initiating device
on the same zone sounds a double pulse on the
NAC.
-If the WalkTest signaling option is set to SIL, the
panel logs the alarm activation to the ALOG (alarm
log). Use the History Logs menu option to view the
ALOG. Use the Reports menu option to print a
copy of the ALOG.
•Initiating Device Trouble Sensing. To test the panel’s
ability to sense a trouble condition for each initiating
device, disconnect one of the IDC wires at the detector.
If the panel senses the trouble condition correctly, one
of two things happen:
-If the WalkTest signaling option is set to SIG, the
panel activates the panel’s NACs for four seconds.
-If the WalkTest signaling option is set to SIL, the
panel logs the trouble in the TLOG (trouble log).
Use the History Logs menu option to view the
TLOG. Use the Reports menu option to print a copy
of the TLOG.
•Earth Ground Sensing. To test the panel’s ability to
detect an Earth Ground, short one of the panel’s circuits
to Earth. If the panel senses the trouble condition correctly, one of two things happen:
-If the WalkTest signaling option is set to SIG, the
panel activates the panel’s NACs for four seconds.
-If the WalkTest signaling option is set to SIL, the
panel logs the trouble in the TLOG (trouble log).
Use the History Logs menu option to view the
TLOG. Use the Reports menu option to print a copy
of the TLOG.
•NAC Trouble Sensing. To test the panel’s ability to
sense a trouble condition for each NAC, disconnect one
of the NAC wires at the panel. If the panel senses the
trouble condition correctly, one of two things happen:
-If the WalkTest signaling option is set to SIG, the
panel activates the panel’s NACs for four seconds.
-If the WalkTest signaling option is set to SIL, the
panel logs the trouble in the TLOG (trouble log).
Use the History Logs menu option to view the
TLOG. Use the Reports menu option to print a copy
of the TLOG.
Setting WalkTest Options
WalkTest options are set via the WalkTest entry at the main
menu. You must be logged in at either Access Level 3 or 4 to
set the WalkTest options.
1.Press the <MENU> key. Press <NEXT> or <PREV>
until the [Walktest] option is displayed. Press
<ENTER>. The following displays:
2.For each option, use the <NEXT> and <PREV> keys to
scroll through the option’s choices. Use the right and
left arrow keys to move from one option to another.
Available options include
•ON/OFF. Used to enable and disable WalkTest.
When set to ON, a WalkTest Enabled trouble is displayed on the panel.
•LG/NL. Controls whether alarms and troubles gen-
erated by WalkTest are sent to the alarm or trouble
log. Lg enables logging; NL disables logging.
•SIG/SIL. Controls whether the NACs are used to
signal activation of an alarm or trouble condition.
SIG enables NACs for Walktest; SIL disables
NACs for WalkTest.
•PR/NoPR. Enables (PR) or disables (NoPR)
whether WalkTest alarms and troubles are sent to
the locally attached printer.
3.When the options are set, press the <ENTER> key. The
system prompts you to confirm the settings. Press
<ENTER> again to confirm.
Advanced Operations
Upload/Download
Uploading and downloading files allows you to transfer the
panel’s job file between a service PC and the panel. The term
Uploading refers to transferring a job file from the panel to a
PC; whereas, the term Downloading refers to moving a job
file from the PC to the panel.
•Warm. Clears the Access Level 4 trouble, restarts
the panel, but preserves the panel’s non-volatile
memory, including time/date information, historical
logs, and all currently disabled points
•Cold. Clears the Access Level 4 trouble and re-initializes the panel’s non-volatile memory, clearing
all time/date information, historical logs, and disabled points.
3.Choose an option and press <ENTER>. System startup
prompts appear on the screen, followed by the system
status message.
Viewing Software Revision Number and Job Info
1.Press <MENU>.
2.Press <NEXT> or <PREV> until Software Rev is
shown. Press <ENTER>. A message similar to the following appears, displaying the revision level of the
panel’s software.
Rev 1.00.11
<NEXT> = View Job Info
3.Press <NEXT> to see the job revision number (i.e., the
number of times the job has been edited and saved), and
the date on which the panel was edited.
JOB REV:1
12:00:00 am 04/09/04
Note: The UPLD/DWNLD menu option enables the panel
for an upload or download operation. This option does not,
however, perform the transfer operation.
1.Press <MENU>.
2.Use the <NEXT> or <PREV> keys to scroll to the
UPLD/DWNLD menu choice.
3.Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
XFER: [Start XFER]
Restarting the CPU
This option is used to clear an Access Level 4 Trouble (i.e., a
“Service Mode Trouble”).
1.Press <MENU>.
2.Press <NEXT> and <PREV> and choose one of the following options.
Each component of the panel has a specified alarm and standby current rating. To calculate the current draw for the system,
add the specified standby current for each module and device to obtain an alarm and a standby current rating for your system.
Also refer to “Module Current Specifications” at the end of this appendix.
Note: Auxiliary power from the system’s AUX 24 V taps must also be included in the calculation, unless that power is
switched off during battery standby. For example, door holders operated from 24 V need not be included if they are disconnected via a relay during a battery standby condition. Notification Appliance load must be included in the alarm current total.
ModuleStandby CurrentAlarm Current
Main System Board
(5 IDCs, 30 detectors each
Expansion IDC Module
(30 detectors per IDC)
Expansion Power Supply50 mA60 mA
Auxiliary Relay Module
Class A Adapter
Remote LCD Annunciator100 mA150 mA
Remote LED Annunciator100 mA100 mA
City Connect Module or Relay Module30 mA60 mA
130 mA
50 mA
0 mA + 10 mA
per energized relay
0 mA + 10 mA
per zone in trouble
Total Standby Current:____________Total Alarm Current:____________
1.Identify Standby Time (C), in hours. C = ______ (typically 4, 24, 48, or 60 hr)
2.From previous calculations, locate total Alarm Current (B) in amperes. B = ______
3.Identify Alarm Time (D) in minutes. D = ______ (typically 5, 10, or 15 min)
160 mA + 60 mA
per zone in alarm
50 mA + 60 mA
per zone in alarm
0 mA + 10 mA
per energized relay
0 mA + 10 mA
per zone in trouble
4.Using the values in Steps 1-4, perform an Initial Battery Calculation per the following:
5.(A x C) + (0.0167 x B x D) = _______ Ah (Ah = ampere hours)
6.Select a battery size LARGER than the number from the Initial Battery Calculation from the following list of batteries
using the 20 Hour Rating value:
7.If either the Standby Current or the Alarm Current is greater than the C/20 current for the initial battery size selected, a
Discharge Factor (DF) must be applied. For example, 1A load on a 10 Ah battery requires a Discharge Factor of 1.08 (10
Ah / 1 A gives discharge time of 10 hours; DF = 1.08). Use the following table to determine Discharge Factor (use the 20
hr value for 24 hr standby):