4004 Fire Alarm
City Connect Card and DACT Module
Installation Instructions
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS
DAMAGED. Upon unpacking your Simplex product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any
internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore,
handle as follows:
1. Ground yourself before opening or installing components (use the 553-484
Static Control Kit).
2. Keep uninstalled components wrapped in anti-static material at all times.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with
the instruction manual, may cause interference to radio communications. It has
been tested and found to comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference when operated in a commercial
environment. Operation of this equipment in a residential area may cause
interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.
Overview
In This Publication
The 4004 Fire Alarm System is capable of supporting either one City Connect
Card (565-577, 565-999, or 566-078) or one DACT module. This publication
covers the procedure for installing a city connect card into a 4004 Panel. It also
covers the procedure for re-installing a 2080-9044 DACT into a 4004 Panel for
existing jobs.
For new DACT installations use the 4004-9810 DACT (565-626). Refer to the
Contact Closure DACT (Digital Alarm Communication Transmitter) Installation
Programming Instructions (574-049) for more information on the 4004-9810
DACT.
The following topics are covered in this publication:
Topic See Page #
Overview 1
City Connect Card Installation 2
DACT Module Installation 4
1999 Simplex Time Recorder Co., Gardner, MA 01441-0001 USA
All specifications and other information shown were current as of publication, and are subject to change without notice.
Technical Manuals Online! - http://www.tech-man.com
574-077
Rev. B
City Connect Card Installation
Introduction
Mounting
For all wiring information, use the 4004 Field Wiring Diagram (841-992). Also
reference the Contractor Wiring Termination Label (519-698) inside the 4004
Door Panel. The label shows the following information:
• The installation location of the city connect card.
• The location of the wiring harness.
• Harness interconnection with the system card.
• The location of the city disconnect switches.
• Programming information necessary to configure the card.
To mount the city connect card, follow Steps 1 through 3 while referring to
Figure 1.
CAUTION: Disconnect 4004 Panel power at the breaker before
installing the city connect card.
1. Remove the city connect card from the packing material.
2. Install the city connect card by securing it with four #6 Torx screws
(supplied).
3. Connect the Cable Harness (733-875) from the City Connect Card (P1) to
the System Board (P5).
P6
1
2
3
4
Supervisory or
trouble operation
jumper plug (P6)
P1
City Circuit 1
jumper plugs
(P2 and P3)
1
TB1
CITY1+ CITY1- CITY2+ CITY2-
Figure 1. City Connect Card
Technical Manuals Online! - http://www.tech-man.com
City Circuit 2
P3
P2
11
LERP
O
N
LERP
332 1 2 1
O
N
LERP
P5
P4
LERP
4
jumper plugs
(P4 and P5)
Disconnect Switches
(SW1 and SW2)
located on 565-577 and
565-999 only. The
switches are not present
on 566-078.
Continued on next page
2