Simplex 4004 Installation Instructions Manual

Page 1
4004 Fire Alarm
City Connect Card and DACT Module
Installation Instructions
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs. Servicing should be performed by qualified Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
1. Ground yourself before opening or installing components (use the 553-484
Static Control Kit).
2. Keep uninstalled components wrapped in anti-static material at all times.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.
Overview
In This Publication
The 4004 Fire Alarm System is capable of supporting either one City Connect Card (565-577, 565-999, or 566-078) or one DACT module. This publication covers the procedure for installing a city connect card into a 4004 Panel. It also covers the procedure for re-installing a 2080-9044 DACT into a 4004 Panel for existing jobs.
For new DACT installations use the 4004-9810 DACT (565-626). Refer to the
Contact Closure DACT (Digital Alarm Communication Transmitter) Installation Programming Instructions (574-049) for more information on the 4004-9810
DACT.
The following topics are covered in this publication:
Topic See Page #
Overview 1
City Connect Card Installation 2
DACT Module Installation 4
1999 Simplex Time Recorder Co., Gardner, MA 01441-0001 USA
All specifications and other information shown were current as of publication, and are subject to change without notice.
Technical Manuals Online! - http://www.tech-man.com
574-077
Rev. B
Page 2
City Connect Card Installation
Introduction
Mounting
For all wiring information, use the 4004 Field Wiring Diagram (841-992). Also reference the Contractor Wiring Termination Label (519-698) inside the 4004 Door Panel. The label shows the following information:
The installation location of the city connect card.
The location of the wiring harness.
Harness interconnection with the system card.
The location of the city disconnect switches.
Programming information necessary to configure the card.
To mount the city connect card, follow Steps 1 through 3 while referring to Figure 1.
CAUTION: Disconnect 4004 Panel power at the breaker before
installing the city connect card.
1. Remove the city connect card from the packing material.
2. Install the city connect card by securing it with four #6 Torx screws
(supplied).
3. Connect the Cable Harness (733-875) from the City Connect Card (P1) to
the System Board (P5).
P6
1 2 3 4
Supervisory or trouble operation jumper plug (P6)
P1
City Circuit 1
jumper plugs
(P2 and P3)
1
TB1
CITY1+ CITY1- CITY2+ CITY2-
Figure 1. City Connect Card
Technical Manuals Online! - http://www.tech-man.com
City Circuit 2
P3
P2
11
LERP
O N
LERP
332 1 2 1
O N
LERP
P5
P4
LERP
4
jumper plugs (P4 and P5)
Disconnect Switches (SW1 and SW2) located on 565-577 and 565-999 only. The switches are not present on 566-078.
Continued on next page
2
Page 3
City Connect Card Installation, Continued
Jumper Settings
The city connect card has jumper settings that select either the Remote Station (Reverse Polarity) Interface (see Table 1), which is the default jumper setting from the factory, or the Municipal Master (Local Energy) Interface. Jumper settings to configure the city connect card for the Remote Station Interface or the Municipal Master Interface are listed below. The city connect card has silk-screening that illustrates the jumpers and selectable configurations (“RP” = Reverse Polarity, “LE” = Local Energy).
Table 1. Jumper Settings
Municipal Master
(Local Energy)
P2-1 to P2-2 P2-2 to P2-3
P3-7 to P3-8 P3-1 to P3-2
City Circuit 1
P3-9 to P3-10 P3-3 to P3-4
—— P3-5 to P3-6
P4-1 to P4-2 P4-2 to P4-3
P5-7 to P5-8 P5-1 to P5-2
City Circuit 2
P5-9 to P5-10 P5-3 to P5-4
—— P5-5 to P5-6
Remote Station
(Reverse Polarity)
Switch Settings
Power-up and Configuration
Note: City Circuit 2 can also be selected for Remote Station Supervisory or
Trouble Operation (See Table 2) by setting the following jumpers. When City Circuit 2 is selected for Trouble Operation, City Circuit 1 reports Alarm only.
Table 2. Operation of City Circuit 2
Supervisory Operation Trouble Operation
P6-1 to P6-2 ——
P6-3 to P6-4 P6-2 to P6-3
The City Connect Card (565-577 and 565-999 only) has two disconnect service switches (SW1 and SW2); the normal position for both switches is the active “ON position. City Connect Card (566-078) does not have these switches.
Power-up the 4004 System and configure the city connect card using the programming instructions located on the Termination Wiring Label (519-698) inside the door.
Technical Manuals Online! - http://www.tech-man.com
3
Page 4
DACT Module Installation
Introduction and Reference Information
Note: The following installation procedures are for the Silent Knight
Model 5128 only.
CAUTION: Disconnect power for the 4004 Panel at the breaker
before installing the DACT module.
For all wiring information, use the Field Wiring Diagram (841-992). DACT modules mount to the 4004 Back Box in a physical location where the DACT status LEDs can be viewed from a cutout slot opening on the mounting plate. The Contractor Wiring Termination Label (519-698) located on the inside of the 4004 door panel does not directly indicate where the DACT module should be mounted. Instead the label illustrates the optional City Connect Card in the area where the cutout slot is located to view the DACT status LEDs. The door label also provides the programming information to configure the DACT into the 4004 System.
There are two installation methods to mount the DACT module to the 4004 Back Box: using either VHB tape or screw mounting. Use the appropriate mounting method for your installation. If possible, install the DACT before terminating field wiring on the 4004 system cards.
CAUTION: When installing the DACT module, be careful not to
damage non-power limited and power limited wiring when removing or installing the mounting plate to/from the back box. Lay the mounting plate on a non-conductive, static free table when installing DACT module.
VHB Tape Mounting Method
Follow Steps 1 through 11 and refer to Figure 2 to mount a DACT module using VHB Tape.
1. Remove the module from its packing material.
2. Locate the DACT module onto the back box back wall so the green
POWER ON LED, yellow “SYSTEM TROUBLE” LED, and redPHONE LINE #1 and PHONE LINE #2 LEDs are over the cutout slot
opening on the mounting plate. Using a pencil, trace the DACT module edge locations onto the back box back wall.
3. Remove the two bottom #6 Torx screws and loosen the two top #6 Torx
screws that secure the 4004 Control Panel Mounting Plate to the back box.
4. Carefully remove the mounting plate from the back box by lifting it upward.
Pull the plate left past the locking tab and forward to release the plate from the back box.
5. Attach two 8-inch long strips (approximate) of double sided VHB tape
(supplied) to the back of the DACT module lengthwise.
6. Remove the protective paper and position the DACT module where the
pencil tracing marks are located. Ensure the LED windows are over the cutout slot opening on the mounting plate and that the TELCO wiring is oriented at the top of the cabinet.
Continued on next page
Technical Manuals Online! - http://www.tech-man.com
4
Page 5
DACT Module Installation, Continued
VHB Tape Mounting Method
(Continued)
Screw Mounting Method
7. Cut and strip the green Earth connect wire on the DACT module and
connect to the 4004 Back Box using an 18 AWG green wire and wire nut. Isolate the circuit ground connection from P1-1 of DACT. The ground return is provided through Wiring Harness (733-897, supplied).
8. Install the mounting plate onto the back box by positioning the right side of
the plate behind the locking tab. Secure the plate with four #6 Torx screws.
9. Connect Wiring Harness (733-897) from System Board P5 to DACT
module P2, P5, and TB1.
10. Power-up and configure the 4004 System for the DACT module using the
programming instructions located on the Contractor Wiring Termination Label (519-698) on the door.
11. Program the DACT in accordance with the installation/programming
manual that is supplied with the DACT.
Follow Steps 1 through 11 and refer to Figure 2 to mount a DACT module using #4 self-tapping screws.
1. Remove the module from its packing material.
2. Locate the DACT module onto the back box wall so the green POWER
ON LED, yellow SYSTEM Trouble LED, and red PHONE LINE #1 and PHONE LINE #2 LEDs are over the cutout slot opening on the mounting plate. Using a pencil, mark the DACT module hole locations onto the back box wall.
3. Remove the two bottom #6 Torx screws and loosen the two top #6 Torx
screws that secure the 4004 Control Panel Mounting Plate to the back box.
4. Carefully remove the mounting plate from the back box by lifting it upward.
Pull the plate left past the locking tab and forward to release the plate from the back box.
5. Drill four .099 holes with a #11 drill where the pencil locations are
positioned for the self-tapping screws.
6. Install and secure the DACT module to the back box using #4 self-tapping
screws (supplied). Ensure the LED windows are over the cutout slot opening on the mounting plate and that the TELCO wiring is oriented at the top of the cabinet.
7. Cut and strip the green Earth connect wire on the DACT module and
connect to the 4004 Back Box using an 18 AWG green wire and wire nut. Isolate the circuit ground connection from P1-1 of DACT. The ground return is provided through Wiring Harness (733-897, supplied).
8. Install the mounting plate onto the back box by positioning the right side of
the mounting plate behind the locking tab. Secure the plate with four # 6 Torx screws.
Continued on next page
Technical Manuals Online! - http://www.tech-man.com
5
Page 6
DACT Module Installation, Continued
Screw Mounting Method
(Continued)
9. Connect Wiring Harness (733-897, supplied) from System Board P5 to
DACT module P2, P5, and TB1.
10. Power-up and configure the 4004 System for the DACT module using the
programming instructions located on the Contractor Wiring Termination Label (519-698) on the door.
11. Program the DACT in accordance with the installation/programming
manual that is supplied with the DACT.
REGISTRATION LABEL
DACT MODULE
TELCO WIRING
DACT MODULE LEDS
MOUNTING LOCATION
MOUNTING PLATE
CUT OUT SLOT OPENING
Figure 2. Exploded View of 4004 Panel