Simplex
4002 Fire Alarm
Pocket Servict
Instructions
Page 2
Technical Manuals Online! - http://www.tech-man.com
Page 3
TABLE OF CONTENTS
Description
CPU.. ....................................................................................
Test Points
Microprocessor (U23)
Terminal
Fuses
DIP Switches..
Jumpers
Enhanced CPU
Requirements ..:.
Special
4-Point Zone
Terminal
Connectors..
Jumpers
8-Point Zone
Terminal
Connectors..
Connections
Jumpers
Signal Expansion
Terminal
Connectors..
Fuses
Jumper..
...................................................................
...................................................
Blocks.. ..........................................................
...........................................................................
..............................................................
.......................................................................
...................................................................
..........................................................
Features.. .......................................................
Module.. .........................................................
Block.. ...........................................................
................................................................
......................................................................
Module.. .........................................................
Blocks.. .........................................................
................................................................
(SPRl and
......................................................................
Module.. ..................................................
Block.. ...........................................................
................................................................
..........................................................................
......................................................................
SPR2). .................................
Page No.
.2
.2
2
.2
.4
.6
.8
10
10
10
12
12
12
12
14
14
14
14
14
16
16
16
16
16
Auxiliary Relay
Terminal
Connectors..
Fuses
Jumper..
Zone Disconnect/Suppression
Terminal
Connector
Jumpers
Switches..
Board.. ........................................................
Blocks.. .........................................................
................................................................
..........................................................................
......................................................................
Block.. ...........................................................
...................................................................
......................................................................
....................................................................
For Fan Control Module and RCUs/SCUs,
see Publication FA4-51-154.
Module ...............................
17
17
17
17
17
18
18
18
18
18
Technical Manuals Online! - http://www.tech-man.com
Page 4
CPU (see Figure 1)
TEST POINT 1
TEST POINT 2
TEST POINT 3
MICROPROCESSOR
+5 Volts
+ 24 Volts
24 Volt Common
U23
Terminal Blocks
TBl
8 Initiating Device Circuits (monitor zones) (TBl-1 thru TBl-
16)
Style B (formerly Class B) (f.w.d. 841-669, pg. 6) Terminate
with 3.3k E.O.L. resistor
Style D (formerly Class A) (f.w.d. 841-669, pg. 8)
If coded manual station exists on zone 1, cut JW-11 (f.w.d.
841-669, pg. 21)
Water/sprinkler supervisory wiring (f.w.d. 841-669, pg. 21)
Remove the appropriate jumper if the zone is connected to a:
Zone Disconnect Module
Zone Suppression Module
Combination Zone Disconnect/Suppression Module
TB2
4-Wire Detector Power, TB2-I thru -3 & Annunciator
Outputs, TB2-4 thru -12 (see Figure 2)
120 Volt detectors bring 120 Volts into TB2-1 (Cut
JW-10)
24 Volt detectors use TB2-2 ( + ) and TB2-3 ( -)
TBi-1
JW 10
ER
DETECTOR
- POWER
28 v
TBZ-2 (9+
3
TB2-3 -
FIGURE 2
TB2-4 thru -11 is a pulse (-) for the zone in alarm
If Supervised Annunciator (See pg. 7)
LED annunciator wiring (f.w.d. 841-669, pg. 18)
Incandescent lamp annunciator (f.w.d. 841-669, pg.
19)
TB2-12 is a ( + ) voltage
2
Technical Manuals Online! - http://www.tech-man.com
Page 5
i
Technical Manuals Online! - http://www.tech-man.com
TB2
TBl
TEST POINT 1
TEST POINT 3
\
TEST POINT 2
MICROPR&ESSOR
FIGURE I
3
Page 6
CPU (cont’d)
Technical Manuals Online! - http://www.tech-man.com
See Figure 3
TB3
City Box Wiring (f.w.d. 841-669, pg. 20)
Reverse polarity, TB3-1 & -4 (Jl - 2,4,5,8,9 In)
Local energy, TB3-1 & -3 (Jl - 2,3,7,9,11 In)
City shunt, TB3-1 & -2 (Jl - 1,5,11 In)
Form C, TB3-1 & -3 (Jl - 1 In)
TB4
Remote reset (TB4-24)
+24 Volts in will reset the system
Remote acknowledge (TB4-23)
+ 24 Volts in will acknowledge the system
System trouble output (TB4-22)
0 Volts out when system trouble until reset
Serial bus (TB4-20 & TB4-21)
You may have 16 addresses on this bus (0 thru 15)
Address 15 is reserved for 2120 communications
Aux 1 8 2 (TB4-14 thru TB4-19)
N.O. & N.C. contacts with center strap fused (f.w.d. 841669, pg. 16)
Cutting JW12 causes relay
trouble relay (JW-20 on rev. A boards)
Trouble relay (TB4-11 thru TB4-13)
Picks until system trouble is cleared
Indicating appliance circuits 1 & 2 (signals) (TB4-3 thru TB4-
10)
Style Y (formerly Class B) (f.w.d. 841-669, pg. 13)
Style Z (formerly Class A) (f.w.d. 841-669, pg. 14)
Terminate with 10k E.O.L. resistor.
24 Volts and common (TB4-1 & TB4-2)
CAUTION: This power is not fused.
1
to act as a nonsilenceable
TB5
AC input terminals (TB5-1 thru TB5-3)
AC power wiring (f.w.d. 841-669, pg. 22)
Fuses
Fl
F2
F3
F4
F5
F6
F7
F8
F9
FlO
3 Amp for annunciator power
8 Amp for main power
8 Amp for battery power
3 Amp for aux relay 2 (K5)
3 Amp for aux relay 1 (K4)
3 Amp for signal 1 output (Kl)
3 Amp for signal 2 output (K2)
5 Amp hardwired UL fuse on the power supply
(not shown)
3 Amp for resettable + 24 VDC (K3)
5 Amp hardwired UL fuse on the power
(not shown)
4
supply
Page 7
1 rl..xL 0
0Wm49S ON
OYbOS “d3
Technical Manuals Online! - http://www.tech-man.com
Page 8
CPU (cont’d)
See Figure 4
DIP Switches
(For detailed information, see FA4-21-151).
NOTE: Setting the switch OFF selects the function.
SW1 -1 Alarm verification
-2
-3 Waterflow
-4
-5
-6 & -7
-8 2120 connection
SW2 -1
-2 Manual evacuation
-3,-4 & -5
-6 & -7 Selective coding
-8
SW3 Indicates the number of supervised modules
connected to the serial port.
SW3-4 SW3-3 SW3-2 SW3-1 MODULES
C&OSE CLOSE CLOSE CLOSE
CLOSE CLOSE CLOSE OPEN
CLOSE CLOSE OPEN CLOSE
CLOSE CLOSE OPEN OPEN
CLOSE OPEN CLOSE CLOSE
CLOSE OPEN
CLOSE OPEN OPEN CLOSE
CLOSE OPEN OPEN OPEN
OPEN CLOSE CLOSE CLOSE
OPEN
-OPEN
OPEN CLOSE OPEN OPEN
OPEN OPEN CLOSE CLOSE
OPEN OPEN CLOSE OPEN 13
OPEN
OPEN
CLOSE CLOSE OPEN 9
CLOSE OPEN
OPEN OPEN
OPEN OPEN OPEN 15
SW4
SW5
SW6
SW7
SW8
SW9
SW10 Aux 2 bypass
SW1 1 Selects annunciator supervision
Coded input
Sprinkler supervision
Time limit cutoff
Silence inhibit
System walk test
Signal coding
Expanded Simplex Programming
NUMBER OF
ANNUNCIATOR
CLOSE OPEN 5
CLOSE
CLOSE
System reset
Alarm silence
Trouble silence
Manual evacuation
City bypass
Aux 1 bypass
6
10
11
12
14
0
1
2
3
4
6
7
8
Technical Manuals Online! - http://www.tech-man.com
Page 9
SUPERVISED
ANNUNCIATOR
LED/
LAMP
SWll-1
-2
-3
-4
-5
-6
-7
-8
NOTE: Remove the resistor if annunciator is LED-type.
DO NOT remove the resistor if annunciator is LAMP-type
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
annunciator.
1
2
3
4
5
6
7
8
W
(RlO)
W2)
(RI41
(R16)
W8)
0-0)
ww
FIGURE 4
7
Technical Manuals Online! - http://www.tech-man.com
Page 10
CPU (cont’d)
See Figure 5
Jumpers
Jl is for City Connection (See pg. 4)
JW2 thru JW9 Zone Disconnect and/or Suppression
(See Pg. 2)
JWiO REMOVE if External Supply Connected to TBZ-1
(See Pg.
JWll REMOVE if zone 1 is used for Coded Input (See
Pg. 2)
JW12 REMOVE to make AUX 1 become a Trouble Relay
(See Pg. 4)
JW13 REMOVE when an expansion board is added to
the system
2)
JW14 REMOVE when an expansion power supply is
added to
the system
8
Technical Manuals Online! - http://www.tech-man.com
Page 11
JW14
FIGURE 5
9
Technical Manuals Online! - http://www.tech-man.com
Page 12
ENHANCED CPU (see Figure 6)
Requirements
You must order a (740-792) 4002 Harness Upgrade Kit and a
565-265 Power Supply Board to upgrade from a 562-909 CPU
to a 565-180 CPU. Refer to Publication FA4-21-266 for
Harness Upgrade Kit installation instructions.
A 733-746 Harness is required for signal power when one
signal expansion module is used with the 565-180 CPU.
A 733-785 Harness is required for signal power when two
expansion power supplies and a signal expansion module are
used with the 565-l 80 CPU.
Refer to 841-712 Internal Wiring Diagram for information on
connecting expansion units using these harnesses.
(For more information, see FA4-51-154.)
NOTE: Switch settings and jumper placements perform the
same functions as the 562-909 CPU.
Special Features
NOTE: New Feature locations are shown in Figure 6.
The 565-l 80 Enhanced CPU is equipped with a Signals
Silenced LED.
The 565-180 Enhanced CPU board is equipped with
removable jumpers instead of zero ohm resistors. When
jumpers are on the l&2 position, they are in the ENABLED
position. When jumpers are on the Z&3 position, they are in
the REMOVED position. Do not discard jumpers.
Technical Manuals Online! - http://www.tech-man.com
Page 13
FIGURE 6
11
Technical Manuals Online! - http://www.tech-man.com
Page 14
4-POINT ZONE MODULE (see Figure 7)
Terminal Block
4 monitor zones, TBl-1 thru TBl-8 (f.w.d. 841-
TBl
669, pgs. 6 & 8)
4 Annunciator terminals, TBl-9 thru TBl-12
(f.w.d. 841-669)
Connectors
40-pin input connector through which the monitor
Pl
card communicates with the CPU.
output
P2
P3
P4
Jumpers
JWl
JW2
JW3
JW4
40-pin
expansion card communicates with the CPU.
(When used, remove JW9)
Connects to Style D (formerly Class A) board if
Style D (formerly Class A) operation is required.
Connects to zone disconnect, zone suppression,
or zone disconnect/suppression
module.
JWl-4 selects annunciator supervision
Selects annunciator supervision for 1st zone on
card (R17)
Selects annunciator supervision for 2nd zone on
card (R19)
Selects annunciator supervision for 3rd zone on
card (R21)
Selects annunciator supervision for 4th zone on
card (R23)
connector through which the next
4
combination
Remove the jumper if supervision is required.
NOTE: If the annunciator is an LED-type
JW5-8 are removed if zones are connected to
1 st zone on card
JW5
2nd zone on card
JW6
3rd zone on card
JW7
4th zone on card
JW8
Module supervision jumper (remove if P2 is used)
JW9
annunciator, REMOVE the resistor.
disconnect, suppression, or disconnect/
suppression module.
12
Technical Manuals Online! - http://www.tech-man.com
Page 15
TBl
FIGURE 7
- JW5
_ JW6
‘JW7
‘JWB
-JWl
JW2
QJw3
13
Technical Manuals Online! - http://www.tech-man.com
Page 16
&POINT ZONE MODULE (see Figure 8)
Terminal Blocks
First four monitor zones on this module, TBl-1
TBl
thru TBl-8 (f.w.d. 841-669
First four annunciator terminals, TBl-9 thru TBl12 (f.w.d. 841-669, pg. 19)
Last four monitor zones on this module, TB2-1
TB2
thru TB2-8 (f.w.d. 841-669, pgs. 7 & 9)
Last four annunciator terminals, TB2-9 thru TB2-
Connectors
40-pin input connector through which the monitor
Pl
module communicates with the CPU.
40-pin output connector through which the next
P2
expansion module communicates with the CPU.
Connects to Style D (formerly Class A) board if
P3
required for first four zones.
P4 Connects to Style D (formerly Class A) board if
required for last four zones.
Connections
SPRl Connection
suppression,
combination module for first four zones.
for .
or zone disconnect/suppression
zone
pgs.
7 & 9)
disconnect,
4
ione
SPR2 Connection for zone disconnect, zone
suppression,
combination module for last four zones.
Jumpers
REMOVE if P2 is used (module supervision
JWl
jumper).
REMOVE when using SPRl for the second zone
JW2
on module.
REMOVE when using SPRl for the first zone on
JW3
module.
REMOVE when using SPRl for the third zone on
JW4
module.
REMOVE when using SPRl for the fourth zone on
JW5
module.
JW6 REMOVE when using SPR2 for the eighth zone
on module.
JW7 REMOVE when using SPRP for the fifth zone on
module.
REMOVE when using SPR2 for the sixth zone on
JW8
module.
REMOVE when using SPR2 for the seventh zone
JW9
on module.
or zone disconnect/suppression
14
!
,
Technical Manuals Online! - http://www.tech-man.com
Page 17
JWlO
Technical Manuals Online! - http://www.tech-man.com
REMOVE when supervised annunciator
module’s fourth zone (resistor 53).
JWll
REMOVE when supervised annunciator
module’s third zone (resistor 55).
JW12
REMOVE when supervised annunciator
module’s second zone (resistor 57).
JW13
REMOVE when supervised annunciator
module’s first zone (resistor 59).
i
JW14
REMOVE when supervised annunciator
module’s eighth zone (resistor 43).
JW15
c
REMOVE when supervised annunciator
module’s seventh zone (resistor 41).
JW16
REMOVE when supervised annunciator
module’s sixth zone (resistor 39).
JW17
REMOVE when supervised annunciator
module’s fifth zone (resistor 37).
NOTE: If the supervised annunciator is an LED-type
annunciator, also REMOVE the corresponding
resistor.
If the supervised annunciator is a filament lamp-type
annunciator, DO NOT remove the corresponding
resistor.
JWl ,
Pl
P2 ’
P3-
SPRl
TBl
SPR2
on
on
on
on
on
on
on
on
9
JW14
JWlC
JW16
JW17
P4
TE2
FIGURE 8
15
Page 18
SIGNAL EXPANSION MODULE (see Figure 9)
Terminal Block
TBl Signal wiring (f.w.d. 841-669, pgs. 13, 14 & 15)
Connectors
Pl 40-pin input connector through which the signal
module communicates with the CPU.
P2 40-pin output connector through which the next
expansion module communcates with the CPU.
4-pin connector for signal power.
P3
Fuses
Fl
5 amp for signal power
F2 3 amp for second signal circuit on card
3 amp for first signal circuit on card
F3
Jumper
1
REMOVE if P2 is used (module supervison
-Fl
5
JWl
“, -“, 2 ‘::::‘.:‘:::f;::,*““.
‘0 0
FIGURE 9
16
0 c
-F2
-F3
Technical Manuals Online! - http://www.tech-man.com
Page 19
AUXILIARY RELAY BOARD (see Figure 10)
Terminal Blocks
two form C contact connections for aux 1 and 2
TBl
one form C contact connection for aux 3
two form C contact connections for aux 4
TB2
I
7
one form C contact connection for aux 3
Connectors
40-pin input connector through which the relay
.
Pl
module communicates with the CPU.
40-pin output connector through which the next
P2
expansion module communicates with the CPU.
Fuses
Fl
F2
F3
F4
Jumper
1
3 amp connects to TBl-14 common of aux 1
3 amp connects to TBl-8 common of aux 2
3 amp connects to TBl-2 common of aux 3
3 amp connects to TB2-5 common of aux 4
REMOVE if P2 is used (module supervision
jumper).
TBl
,Fl
-F4
FIGURE 10
17
Technical Manuals Online! - http://www.tech-man.com
Page 20
ZONE DISCONNECT/SUPPRESSION MODULE
(see Figurell)
Terminal Block
TBl-1 thru TBl-8 connection for four zones
TBl
TBl -9 and TBl-10 are not used
Connector
lo-pin ribbon cable which connects to the
Pl
appropriate zone modules SPR connector.
Jumpers
1 - 6 Jumpers JW2 and JW5 are removed when
connecting to a 4002 system.
Switches
l-4 Switches which cause hardware disconnect of the
appropriate zone.
*
JUMPERS
JW2
JW5
. Pl
FIGURE 11
18
Technical Manuals Online! - http://www.tech-man.com