Life Alarm
®
Fire Alarm Systems
ULC Listed
FEATURES
Four monitor zones
•
Up to 18 two-wire smoke detectors per zone
•
Signal circuits — 2 class B or 1 class A —
•
field configurable
Selectable alarm verification
•
Self-contained audible trouble signal
•
One normally open city contact
•
One form C alarm auxiliary contact
•
One form C trouble contact
•
Transient suppression for municipal
•
connections on power supply
Automatic battery charger
•
Standby batteries
•
• Surface or semi-flush mounting
•
Alarm/trouble system walk test
•
Alarm resound
•
Battery supervision
•
Earth ground supervision
•
Brown out supervision of AC power
•
Automatic signal silence
•
DIP switch selectable programming
•
End-of-line devices and batteries included
•
ULC Listed to CAN-ULC-S527-99
Fire Alarm Controls
4001-9304C
Simplex
®
ZONE
ALARM
ALARME
TROUBLE
TROUBLE
AC POWER ON
ALIMENTATION
SYSTEM TROUBLE
TROUBLE SYSTEM
SIGNALS SILENCED
ARRET ALARME
ZONE
1
2
3
4
FIRE ALARM CONTROL
PANNEAU DE CONTROLE AVERTISSEUR D’INCENDIE
4001-9304C
OPTIONS
•
Option Board - supervised annunciator output
- auxiliary resettable power
- non-silenceable trouble contact
•
Semi-flush trim kit
•
External battery & cabinet for 60 hour backup
SPECIFICATIONS
Input ..................................1.2A @ 120VAC 60 Hz
Humidity.................85% non-condensing @ 30°C
Temperature.......................................0°C to 49°C
Weight...............Approximately 10kg c/w batteries
Colour ..........................................................Beige
Knockouts.......................................................1/2”
©2003 SimplexGrinnell Canada Ltd. S01575-110-2 10/03

CAUTION
ATTENTION
REMOVE COVER ENLEVER LE REVETEMENT
FOR SERVICE ONLY
POUR L'ENTRETIEN SEULEMENT
REPLACE COVER AFTER SERVICE LE REMETTRE UNE FOIS L'ENTRETIEN TERMINE
ALARM
AUXILIARY
ZONE
ZONE
1
ALARM
ALARME
TROUBLE
TROUBLE
AC POWER ON
DISCONNECT
DEBRANCHEMENT
AUXILIAIRE
DE L'ALARME
DRILL
ALIMENTATION
2
SYSTEM TROUBLE
EXERCICE
120 VAC ACROSS
TERMINALS
ATTENTION
120 VCA ENTRE
LES BORNES
3
4
OPERATOR’S PANEL
-
10k,1/2W,5%10k,1/2W,5%
3.3k,1W,5%
+
++++
2A@30VAC/VDC
654
1
H1
TB2
10
TP2
TP3
123
TB3
+
-
+
-
POT1
-
R
+24
+
H2
C
A
O
A
O
4
4+
3-
3+
2-
TB4
2
1-
1+
D
NO
C
N
N
C
GB
GB
NC
G
N
G
C
W
Z
Z
Z
Z
Z
Z
Z
Z
I
I
I
I
P
S
S
S
S
0V
R
GND
GN
2A
F4
2A
F3
SW4
1
2
3
4
5
POT2
6
F2
EARTH
TROUBLE
R
R
+
5A
M
M
T
T-
POWERSUPPLY
F
F
A
A
X
X
B
B
TP1
6A
TROUBLE
F1
+5
OV
TP4
TP5
TP6
BROWN
OUT
TB1
+-+-
T1
LGN
120V60HZ
TROUBLE SYSTEME
SIGNALS SILENCED
ARRET ALARME
TROUBLE
SILENCE
ARRET
TROUBLE
SIGNALS
SILENCE
ARRET
ALARME
SYSTEM
RESET
REMISE
SYSTEME
OPERATOR INTERFACE SWITCHES
•
Signals Silence
•
System Reset
•
Trouble Silence
•
Alarm Auxiliary Disconnect
•
Drill
LED INDICATORS
•
Green AC Power On
•
Yellow Power Trouble
•
Yellow System Trouble
•
Yellow Earth Trouble
•
Red Alarm for Each Zone
•
Yellow Trouble for Each Zone
•
Yellow Signal Circuit Trouble
•
Yellow Signals Silenced Trouble
2

DIP SWITCH SELECTABLE PROGRAMMING
SYSTEM WALK TEST — Activating an initiating de
vice will cause the indicating appliance to signal a
simple code (zone number) without actuating the
municipal connection or auxiliary alarm outputs and
will then automatically reset. Momentarily opening a
monitor zone or signal circuit will cause the indicat
ing appliance to operate for 4 seconds, thereby
testing electrical supervision.
ALARM VERIFICATION — Activation of any smoke
detector will initiate an alarm verification cycle. The
control will retard the activation of the indicating ap
pliances for 30 seconds. During this delay, if any
other device activates, the alarm will be confirmed
and the indicating appliances energized. If a second
device does not activate during the 30-second delay,
the control will reset and begin a 60-second confir
mation cycle. During the confirmation cycle, should
any device alarm, on any zone, the indicating appli
ance circuit will energize. Should the verification
cycle end without “incident” the panel will return to its
normal state. Manual stations, heat detectors, and
waterflow switches will always cause the fire alarm
control to activate immediately.
TEMPORAL PATTERN — Causes the indicating ap
pliances to sound the temporal pattern.
ALARM SILENCE INHIBIT — Disables the signals
silence and system reset switches for 1 or 3 minutes.
AUTOMATIC SIGNAL SILENCE — Silences the
alarm signals after 20 minutes.
-
-
-
-
TYPICAL 4001-9304C SYSTEM LAYOUT
+
SIGA+
TB4
SIGA-
654
123
10k, 1/2W, 5%10k, 1/2W, 5%
1
H1
10
POT1
H2
F4
F3
Z4-
Z4+
Z3-
Z3+
Z2-
Z2+
2A
2A
Z1-
POT2
EARTH
TROUBLE
6A
F1
TP1
BROWN
OUT
+5
TP4
OV
TP5
+-+ -
+
++
TP2
TP3
+24
0V
SIGB-
SIGB+
GND
RPWR
GND
F2
5A
XFMR
XFMR
BAT+
BAT-
TB1
+
TB2
Z1+
POWER SUPPLY
3.3k, 1W, 5%
TB3
1
2
3
4
5
6
TROUBLE
TP6
2A @ 30 VAC/ VDC
NO
C
NC
NO
C
SW4
NC
NO
C
LGN
120V 60HZ
1.2A
T1
TYPICAL WIRING CONNECTIONS. FOR MORE DETAILED WIRING INSTRUCTIONS, REFER TO
OPERATION AND INSTALLATION INSTRUCTIONS, S01575-109.
3

FEATURE SELECTION CHART
PID
DESCRIPTION
4001-9304C 4 Zone Control, 120VAC Input, c/w batteries & End-of-Line Resistors
4001-9850C Option Board Kit
2975-9801 Semi-Flush Trim Kit
4009-9801 &
2081-9275
External Battery Cabinet &
18 Ah Battery (order [2] 2081-9275)
(TOP)
SEMI-FLUSH MOUNT
LEFT SIDE
®
13”
NO WIRE
ENTRY
BATTERIES
ONLY
10.5”
3”
4”
All specifications and otherinformation shown werecurrent as of printing and are subject to change withoutnotice.
(BOT TOM)
2400 Skymark Avenue, Mississauga, ON L4W 5K5
Visit us on the World Wide Web @ www.simplexgrinnell.com
Offices and Representatives Throughout the World
4”
SURFACE MOUNT
RIGHT SIDE