Simplex 4001 Series, 4001-9304C Quick Start Manual

Page 1
Life Alarm
®
Fire Alarm Systems
ULC Listed
FEATURES
Four monitor zones
Up to 18 two-wire smoke detectors per zone
field configurable Selectable alarm verification
Self-contained audible trouble signal
One normally open city contact
One form C alarm auxiliary contact
One form C trouble contact
Transient suppression for municipal
connections on power supply Automatic battery charger
Standby batteries
Surface or semi-flush mounting
Alarm/trouble system walk test
Alarm resound
Battery supervision
Earth ground supervision
Brown out supervision of AC power
Automatic signal silence
DIP switch selectable programming
End-of-line devices and batteries included
ULC Listed to CAN-ULC-S527-99
Fire Alarm Controls
4001-9304C
Simplex
®
ZONE
ALARM
ALARME
TROUBLE TROUBLE
AC POWER ON
ALIMENTATION
SYSTEM TROUBLE
TROUBLE SYSTEM
SIGNALS SILENCED
ARRET ALARME
ZONE
1
2
3
4
FIRE ALARM CONTROL
PANNEAU DE CONTROLE AVERTISSEUR D’INCENDIE
4001-9304C
OPTIONS
Option Board - supervised annunciator output
- auxiliary resettable power
- non-silenceable trouble contact
Semi-flush trim kit
External battery & cabinet for 60 hour backup
SPECIFICATIONS
Input ..................................1.2A @ 120VAC 60 Hz
Humidity.................85% non-condensing @ 30°C
Temperature.......................................0°C to 49°C
Weight...............Approximately 10kg c/w batteries
Colour ..........................................................Beige
Knockouts.......................................................1/2”
©2003 SimplexGrinnell Canada Ltd. S01575-110-2 10/03
Page 2
CAUTION
ATTENTION
REMOVE COVER ENLEVER LE REVETEMENT
FOR SERVICE ONLY
POUR L'ENTRETIEN SEULEMENT
REPLACE COVER AFTER SERVICE LE REMETTRE UNE FOIS L'ENTRETIEN TERMINE
ALARM
AUXILIARY
ZONE ZONE
1
ALARM
ALARME
TROUBLE TROUBLE
AC POWER ON
DISCONNECT
DEBRANCHEMENT
AUXILIAIRE
DE L'ALARME
DRILL
ALIMENTATION
2
SYSTEM TROUBLE
EXERCICE
120 VAC ACROSS
TERMINALS
ATTENTION
120 VCA ENTRE
LES BORNES
3
4
OPERATOR’S PANEL
-
10k,1/2W,5%10k,1/2W,5%
3.3k,1W,5%
+
++++
2A@30VAC/VDC
654
1
H1
TB2
10
TP2
TP3
123
TB3
+
-
+
-
POT1
-
R
+24
+
H2
C
A
O
A
O
4
4+
3-
3+
2-
TB4
2
1-
1+
D
NO
C
N
N
C
GB
GB
NC
G
N
G
C
W
Z
Z
Z
Z
Z
Z
Z
Z
I
I
I
I
P
S
S
S
S
0V
R
GND
GN
2A
F4
2A
F3
SW4
1
2
3
4
5
POT2
6
F2
EARTH
TROUBLE
R
R
+
5A
M
M
T
T-
POWERSUPPLY
F
F
A
A
X
X
B
B
TP1
6A
TROUBLE
F1
+5
OV
TP4
TP5
TP6
BROWN
OUT
TB1
+-+-
T1
LGN
120V60HZ
TROUBLE SYSTEME
SIGNALS SILENCED
ARRET ALARME
TROUBLE
SILENCE
ARRET
TROUBLE
SIGNALS SILENCE
ARRET
ALARME SYSTEM
RESET
REMISE
SYSTEME
OPERATOR INTERFACE SWITCHES
Signals Silence
System Reset
Trouble Silence
Alarm Auxiliary Disconnect
Drill
LED INDICATORS
Green AC Power On
Yellow Power Trouble
Yellow System Trouble
Yellow Earth Trouble
Red Alarm for Each Zone
Yellow Trouble for Each Zone
Yellow Signal Circuit Trouble
Yellow Signals Silenced Trouble
2
Page 3
DIP SWITCH SELECTABLE PROGRAMMING
SYSTEM WALK TEST — Activating an initiating de
vice will cause the indicating appliance to signal a simple code (zone number) without actuating the municipal connection or auxiliary alarm outputs and will then automatically reset. Momentarily opening a monitor zone or signal circuit will cause the indicat ing appliance to operate for 4 seconds, thereby testing electrical supervision.
ALARM VERIFICATION — Activation of any smoke detector will initiate an alarm verification cycle. The control will retard the activation of the indicating ap pliances for 30 seconds. During this delay, if any other device activates, the alarm will be confirmed and the indicating appliances energized. If a second device does not activate during the 30-second delay, the control will reset and begin a 60-second confir mation cycle. During the confirmation cycle, should any device alarm, on any zone, the indicating appli ance circuit will energize. Should the verification cycle end without “incident” the panel will return to its normal state. Manual stations, heat detectors, and
waterflow switches will always cause the fire alarm
­control to activate immediately.
TEMPORAL PATTERN — Causes the indicating ap pliances to sound the temporal pattern.
ALARM SILENCE INHIBIT — Disables the signals
­silence and system reset switches for 1 or 3 minutes.
AUTOMATIC SIGNAL SILENCE — Silences the alarm signals after 20 minutes.
-
-
-
-
TYPICAL 4001-9304C SYSTEM LAYOUT
+
SIGA+
TB4
SIGA-
654
123
10k, 1/2W, 5%10k, 1/2W, 5%
1
H1
10
POT1
H2
F4
F3
Z4-
Z4+
Z3-
Z3+
Z2-
Z2+
2A
2A
Z1-
POT2
EARTH
TROUBLE
6A
F1
TP1
BROWN
OUT
+5 TP4
OV
TP5
+-+ -
+
++
TP2
TP3
+24
0V
SIGB-
SIGB+
GND
RPWR
GND
F2
5A
XFMR
XFMR
BAT+
BAT-
TB1
­+
TB2
Z1+
POWER SUPPLY
3.3k, 1W, 5%
TB3
1 2 3 4 5 6
TROUBLE
TP6
2A @ 30 VAC/ VDC
NO
C
NC
NO
C
SW4
NC
NO
C
LGN
120V 60HZ
1.2A
T1
TYPICAL WIRING CONNECTIONS. FOR MORE DETAILED WIRING INSTRUCTIONS, REFER TO OPERATION AND INSTALLATION INSTRUCTIONS, S01575-109.
3
Page 4
FEATURE SELECTION CHART
PID
DESCRIPTION
4001-9304C 4 Zone Control, 120VAC Input, c/w batteries & End-of-Line Resistors
4001-9850C Option Board Kit
2975-9801 Semi-Flush Trim Kit
4009-9801 & 2081-9275
External Battery Cabinet & 18 Ah Battery (order [2] 2081-9275)
(TOP)
SEMI-FLUSH MOUNT
LEFT SIDE
®
13”
NO WIRE ENTRY BATTERIES ONLY
10.5”
3”
4”
All specifications and otherinformation shown werecurrent as of printing and are subject to change withoutnotice.
(BOT TOM)
2400 Skymark Avenue, Mississauga, ON L4W 5K5
Visit us on the World Wide Web @ www.simplexgrinnell.com
Offices and Representatives Throughout the World
4”
SURFACE MOUNT
RIGHT SIDE