Simplex 2098-9207A Installation Instructions Manual

Multi-Application Peripherals
UL, ULC* Listed FM Approved
FEATURES:
UL Listed to Standard 268
Microprocessor Based Design Provides:
Fast Response Settings
Temperature CompensationAutomatic Gain Control
Coverage Up to 350 ft x 60 ft
Easily Adjusted Optics with Internal Sighting
Mechanisms Simplify Alignment
LED Status Indicators for Normal (Green),
Alarm (Red), and Trouble (Yellow)
Auxiliary Contacts for Alarm and Trouble
Access Covers Monitored by Tamper Switch
2098-9207A Includes:
Transmitter and Receiver PairReceiver Remote LED Status Indicator PanelSensitivity Measurement Filters
Transmitter and Receiver are a Matching
Design with Beige Housings and Black Face Plates
SPECIFICATIONS:
(Refer to Installation Instructions for further details)
Operating Voltage .................................. 18 to 32 VDC
Maximum Ripple............................................4 V pk-pk
Receiver Normal Current....................................40 mA
Receiver Alarm Current......................................60 mA
Transmitter Current............................................20 mA
Coverage Distance......30 ft to 350 ft (9.1 m to 107 m)
Coverage Width ............................ up to 60 ft (18.3 m)
Optics Adjustment....... ± 90º Horizontal, ± 10º Vertical
30 Second Delay Sensitivity.....20%, 30%, 40%, 50%,
60%, or 70% (% of Obscuration)
5 Second Delay Sensitivity....................... 30% or 60%
Trouble Signal Delay..................................20 seconds
Auxiliary Contact Ratings (resistive loads):
Alarm....................................1 A at 60 VDC, form “A”
Trouble.................................1 A at 60 VDC, form “B”
Auxiliary Alarm......................1 A at 60 VDC, form “C”
Tamper Switch .................In Series w/Trouble Contact
Temperature Range.....32º F to 130º F (0º C to 54º C)
Mounting Requirements..........4” Square or Octagonal
Electrical Boxes (furnished separately)
and Accessories
Photoelectric Smoke Detectors
2098-9207A
Projected Beam Type
T R
2098-9207A BEAM DETECTOR
TRANSMITTER AND RECEIVER
DESCRIPTION:
Projected photoelectric beam smoke detection is used to protect large areas such as gymnasiums, lecture halls, theaters, warehouses, atriums, etc., where spot type smoke detection is impractical. The Simplex 2098-9207A is a sophisticated microprocessor based long range beam smoke detector consisting of a separate transmitter and matching receiver providing accurate and repeatable monitoring of smoke passing through the light beam.
The transmitter produces a crystal controlled, infrared beam which is monitored by the receiver to determine smoke obscuration. When the receiver measures beam intensity below a preset, selectable threshold, an alarm output is generated. Standard alarm delay is 30 seconds. For special applications where fast developing fires might be likely (such as airplane hangars), a five second delay setting is available. (Contact Simplex for application guidance).
Complete beam blockage and dust accumulation that reduces signal level to 50% will initiate a trouble output. Intermittent beam blockage, such as cleaning, is ignored. Tamper switches monitor the access covers and cause a circuit trouble if activated.
Installation is simplified due to convenient beam alignment adjustments and easy receiver calibration. Although external light sources must be considered when locating the beam detector pair, the transmitter beam has a format signature that allows the receiver to minimize interference from such sources.
*ULC listed model is 2098-9207CA.
© 1996 Simplex Time Recorder Co. S2098-0060 E 06-96 page 1 of 2
LOCATION:
The following general information provides assistance for locating projected beam smoke detectors. Refer to the Installation Instructions (shipped with detectors), the National Fire Alarm Code (NFPA 72), and all applicable local codes for additional information.
1. Smooth, Flat Ceilings. Mount the
units with beam paths between 4” (102 mm) and 12” (305 mm) from the ceiling.
2. Sloped Or Peaked Ceiling. The
beam path should be within three feet (904 mm) of the peak of the ceiling.
3. Air Stratification. Air stratification
may hinder smoke from reaching beam detectors, especially those mounted close to the ceiling. If this is a possibility, extra beam detectors should be installed to provide proper coverage. (Smoke rises because it is warmer than the surrounding air. Stratification occurs when the smoke reaches a height where it is the same temperature as the surrounding air, thus blocking the smoke from rising to the ceiling.)
4. Adjacent Units. When two or more adjacent
units are installed in the same area, alternate the transmitter and receiver locations.
5. Sunlight and Artificial Light Sources. Mount
the receiver such that external light sources do not interfere with reception of the transmitter’s beam. Ensure that extremely bright light sources such as sunlight and the exposed bulbs of high pressure sodium, mercury vapor, and metal halide lights are not pointed directly at the receiver. Incandescent and fluorescent lighting that is not directly in the beam path is typically ignored by the receiver.
6. Beam Path Integrity. Install the transmitter and
receiver with a clear line-of-sight path free of moving objects. Do not use mirrors or other reflective paths. The beam should not pass close to heating, ventilation, or air conditioning outlets where air flow might circulate smoke away from the beam. Avoid areas subject to normal smoke concentrations such as kitchens and garages.
7. Observe Operating Temperature Limits. Do
not install units where normal ambient temperature is below 32º F (0º C) or above 130º F (54º C).
2098-9207A HOUSING DIMENSIONS:
(95 mm)
6 3/4"
(171 mm)
5 1/2" (140 mm)
REMOTE INDICATOR PANEL
REMOTE INDICATOR PANEL:
A remote indicator panel is included that provides LED indications for Alarm, Trouble, and Power-On. Test points are available to remotely monitor the detector calibration voltage. Connections require five color-coded wires to the receiver.
Panel color is off-white. Mounting requires a single gang switch box with minimum depth of 2 inches. Maximum distance is 50 ft (15 m) from the receiver.
3 3/4"
1 1/4" (32 mm)
GREEN, POWER ON
YELLOW, TROUBLE RED, ALARM
TEST POINTS
DIMENSIONS: 3 1/4"W x 4 7/8"H x 1 1/16"D (83 mm x 124 mm x 27 mm)
4 1/4"
(108 mm)
S2098-0060 E 06-96 page 2 of 2
Gardner, Massachusetts 01441-0001 U. S. A.
Offices and Representatives Throughout the World
Please visit our homepage “http://www.simplexnet.com”.
All specifications and other information shown were current as of printing and are subject to change without notice.
Loading...