This quick guide serves as a fast introduction for
the installation by trained, experienced specialist
personnel (e. g. mechatronics technician or electrician) and / or specialist personnel with knowledge
involving the installation of electrical devices.
The complete operating manual can be found on
our product website:
short.simon-protec.com/sheven
Please precisely observe the connection assignment, the minimum and maximum performance
data (see chapter 6. „Technical data“ on page 11)
and the supplementary sheet „Safety instructions
and warranty conditions“.
2. Functional description
SHEV 3 / 6 (Smoke and Heat Exhaust Ventilation)
represent the compact control panel system, mainly used in staircases for smoke extraction and daily
ventilation.
It allows the direct connection of following devices
such as:
and the control of actuators.
The SHEV 3 / 6 essentially consist of three components:
1.2 Use for the intended purpose
The electric control panels SHEV 3 / 6 are compact
devices in steel-sheet or plastic housing (optional
variants are shown in the product catalogue) containing power supply, emergency power supply and
the total operating and control electronics for the
operation of 24 V DC - actuators for windows and
smoke exhaust flaps.
SHEV 3 / 6 control the connected actuators in case
of fire, as well as for daily ventilation. During a power failure, the emergency power supply ensures the
function of the SHEV - equipment for at least 72
hours. The connection lines for SHEV- emergency
switch, smoke detector, Fire Alarm System (FAS)
and actuators are monitored.
2.1 Power supply (Tested according to
If the SHEV 3 / 6 is connected to the mains, it provides the maximum output via the power supply
(mains-operation).
2.2 Emergency power supply
The emergency power supply of the SHEV 3 / 6 is
ensured by two 12 V lead batteries.
2.3 Control electronics (Tested according
The complete control of the SHEV 3 / 6 is taken
over by a microcontroller.
• smoke detector,
• SHEV - emergency switch,
• fire alarm-signal
1. power supply
2. emergency power supply
3. control electronics
EN 12101-10)
to prEN 12101-9)
2.4 Operating status indicators (OK,
FAULT and ALARM)
The SHEV 3 / 6 have three operational status indicators on the control board to display the actual operation mode.
• The green LED indicates mains operation.
• The yellow LED serves as status or fault
indicator.
• The red LED indicates alarm.
Page 3
Functions
3. Functions
3.1 Ventilation function
In order to use the SHEV 3 / 6 for ventilation, ventilation OPEN / CLOSE switches can be connected.
Pressing both switches (OPEN / CLOSE) simultaneously causes the function STOP. The ventilation
function can only be controlled during mains
operation.
Figure 1: DIP switch SW1
Many different action behaviors can be allocated to
the switches. Therefore see table 1 underneath.
Table 1: Matrix ventilation switch
Kon-
SW1
SW1
SW1
SW1
fig.
– 1
– 2
– 3
1OFFOFFOFFOFF Continuous OPEN / CLOSEDDelivery state
Dead man function – the actuator
will run as long as the vent button
is pressed in OPEN or CLOSE.
In case of ventilation, the actuators
open for the programmed time.
The system closes automatically
after the expiration of the time.
Combination of configuration 5
and 6.
Page 4
Mounting
3.2 Gap ventilation
Gap ventilation can be activated by setting DIPswitch SW1 – 3 to ON. This function is time con-
trolled and factory-set to 3 seconds.
ATTENTION
The dead man function in the OPEN direction is inactive during limited ventilation.
3.3 Automatic ventilation CLOSED
(time-dependent)
The automatic close function of the actuators after
ventilation can be activated by setting DIP-switch
SW1 – 1 and SW1 – 3 to ON. This function is time
controlled and factory-set to 10 minutes.
4. Mounting
Mounting shall be carried out only by professional personnel (qualified electrician)!
The openings of the battery cells (round lids on top
of the batteries) must not point downwards, because
this would lead to a leak out of the battery!
Do NOT connect the battery during installation!
3.4 Wind / rain detector (WTS)
if a wind / rain detector is installed, the SHEV 3 / 6
receives in case of rainfall or strong winds (>5 Bft)
a signal from the wind / rain detector and triggers
the connected actuators automatically in closing
direction.
4.1 Mounting plastic housing
Figure 2: Mounting points plastic housing
3.5 Reset function of the SHEVemergency switch
Any ALARM-signal can be reseted by the SHEV emergency switch. By pressing the RESET push-button for the first time, the ALARM-signal will be
reseted.
By pressing the RESET push-button a second
time, the actuators will be triggered in closing
direction.
Danger
ATTENTION
ATTENTION
SHEV 3
Mounting points housing
Mounting points batteries
Battery port
3.6 External output of messages
For redirection of fault or other messages the
SHEV 3 / 6 is equipped with two volt-free relays or
contacts.
In the factory setting contact 1 indicates „ALARM“
and contact 2 indicates „OK".
INFORMATION
Further information on the functions described here
in chapter 3 can be found in the operating instructions for download at
short.simon-protec.com/sheven.
Page 5
Mounting
Figure 3: Mounting points plastic housing
SHEV 6
4.2 Mounting steel-sheet housing
Figure 4: Mounting points steel-sheet housing
SHEV 3-AP
Mounting points housing
Battery port
Figure 5: Mounting points steel-sheet housing
SHEV 6-AP
Figure 6: Connecting cable
Cable tie
Page 6
Mounting
4.3 Electrical connection
DANGER
Disconnect the power supply cord for all poles from the mains. The connection of the SHEV 3 / 6 (-AP) must be
done volt-free!
Figure 7: Wiring diagram total (simplified illustration)
FAS
27kΩ
RM 3000
Vent
Switch
Actuator 2Actuator 1
WTS
27kΩ
27kΩ
1
2
–
–
+
AZ
E
OS
DD-100
DD-100
OS
51 2
3 4
RA
RZ
B1
GND
M
HE 081/
HE 086
SGO
SGO
HE 080/
HE 082/
HE 087
363534333231302928
SW1
Contact 2Contact 1FASSmoke DetectorVent Switch
NO NCCNO NCCRARA
1
2
–
–
+
AZ
E
RA
RZ
B1
GND
M
Y
OK
––
B3
–
B2
AZE
SOGIGOSOOSS
ELZOK YM RZ
–
B1
RA
27
2625
24
23
2221
20
18 19
17
1516
14
13
11 12
67 8910
5
4
3
2
1
Motor fuses:
SHEV 3 – T3,15A
Motor 1Motor 2
Wind/Rain
Emergency Button
SHEV 6 – T6,3A
Reset
Alarm
LED OK
10
9
LED Alarm
4
6
7
8
5
LED Fault
LED indications are only visualized
during mains operation.
OFF
ON
1
2
3
+
Battery
+
–
L1
NPE
–
+
Battery Connection
Battery
–
L1
NPE
Mains Connection
all-pole disconnecting mains switch
provided by client (L1, N)
Page 7
INFORMATION
The use of shielded cables is recommended for the
detection lines.
Figure 8: Wiring diagram smoke detector
Mounting
Figure 9: Wiring diagram thermostat
Thermostat
(2 Channel)
ϑ
RM 2860 / TH 4860
(max. 6)
27kΩ
L2
L1
o
L1
i
L2
L1
o
L1
i
Smoke Detector
RM 3000
(max. 8)
27kΩ
Smoke Detector
4.4 FAS Auto-RESET function
Generally, all SHEV-alarms must be reseted manually by pressing the RESET button (onboard /
EOS). For the detection line 3 (FAS / fire alarm system), the Auto-RESET function can be activated
which will reset the SHEV and power the relays into
CLOSE direction after the FAS has been reseted.
Setting: DIP switch SW1 – 10 set to ON.
THM 200
(not part of delivery)
grey
white
AZ
E
AZ–
blue
black
green
AZ
E
Ventilation Button
521
43
WTS
4.5 Wire lengths
INFORMATION
Dimension indications (rule of thumb):
Wire cross-section [mm
x number of motors
x power input per motor [A]
/ 73.
The national regulations continue to apply.
2
] = wire length [m]
SHEV 3/6
AZE
242322
Ventilation Button
LZE
1098
–
Wind / Rain
4.6 Motor cable monitoring by DD-100
The EOL diode terminators DD-100 are for the
cable monitoring of the motor outputs. They need
to be installed in the junction box of the last
actuator.
Page 8
Commissioning
5. Commissioning
ATTENTION
Only after the SHEV 3 / 6 (-AP) has been commissioned successfully and the permanent on-site
mains power supply is ensured, the battery may be
installed and connected.
INFORMATION
An error message if the battery is disconnected may
appear at least after 8 minutes (green LED flashes,
yellow LED lights up).
ATTENTION
Only batteries approved by the panel manufacturer
are allowed for connection. The control panel loses
the relevant certifications if any other battery is
used, warranty expires.
5.1 Commissioning SHEV 3 / 6 plastic
housing
Connect battery plug to port “Battery backup”
(see fig. 2 / 3 on page 5 / 6).
Place the battery pack on the bottom panel of
the housing.
Connect battery plug to port "Battery backup"
(see fig. 4 / 5 on page 6).
Figure 12: Battery Connection SHEV 3-AP
steel-sheet housing
Figure 10: Mounting points battery
SHEV 3 plastic housing
Mounting points battery
Figure 13: Battery Connection SHEV 6-AP
steel-sheet housing
Anschluss „Akku“ X5
Page 9
Commissioning
ATTENTION
After connecting the battery pack, the RESET button must be pressed for 5 seconds to initialize the
SHEV!
Connect the PE cable to the PE-connection on
the lid.
Figure 14: PE-connection
PE-connection
5.3 Troubleshooting
ATTENTION
Due to the low loop current, the insulation resistance
of the monitored wires (B1, B2 and B3) must be
checked!
The insulation resistance must be > 20 MΩ / km
(manufacturer information), otherwise wire
interruptions will no longer be detected reliably .
INFORMATION
The operating states of SHEV 3 / 6 (-AP) can optionally be visualized with SIMON-LINK (only during
mains operation).
For more information visit
short.simon-protec.com/slen
Place the cover and fasten it with the two
screws on the side.
Figure 15: Close the housing
Fixing screws
Page 10
Technical data
6. Technical data
Power supply Information
Nominal voltage230 V AC
Acceptable voltage range195 V AC to 264 V AC
Power consumption
Min. series fuse (on site) C 16 A
Connected load103 VA (SHEV 3)
Inrush currentapprox. 10 A (SHEV 3)
Frequency range47 Hz to 63 Hz
Mains fuse (internal)Fuse characteristic: Type T 1.25 A
Clamp format0.5 mm² – 2.5 mm²
Output information motor channels
Duty cycle (D)30 %
Output voltage mains operation (nominal)24 V DC
Voltage range (mains operation)23.0 V DC to 24.5 V DC
Output voltage (battery operation (nominal)24 V DC
Voltage range (battery operation)21 V DC to 28.6 V DC
Output current (I
(I
= I
out
mot1
Power output (non-stop operation)50 W (SHEV 3)
Power output (short-term operation)73.5 W (SHEV 3)
Output fuse for actuatorsFuse characteristic:
Ripple of the output voltage
(0 A < I
Power outage bridge-over time10 ms
Clamp format0.5 mm² – 2.5 mm²
1. Power consumption at maximum load of the supply system
< 3 A resp. 0 A < I
out
1
) (short-term operation)
out
+ I
)
mot2
out
< 6 A)
0.56 A (SHEV 3)
1.20 A (SHEV 6)
206 VA (SHEV 6)
approx. 20 A (SHEV 6)
3 A (SHEV 3)
6 A (SHEV 6)
100 W (SHEV 6)
145 W (SHEV 6)
Type T 3.15 A (SHEV 3)
Type T 6.3 A (SHEV 6)
500 mVpp
Page 11
Technical data
Connection data of the emergency switches (HE 080 / HE 082 / HE 087 & HE 081 / HE 086)
Maximum number of main emergency switches
(e.g. HE 080 / HE 082 / HE 087)
Maximum number of the off site emergency switches
(e.g. HE 081 / HE 086)
Output voltage range (B1)Clamp 717.5 V DC to 18 V DC
Connection information fire alarm system (FAS)
Output voltage range (B3)Clamp 2817.5 V DC to 18 V DC
Reset time after SHEV-reset
(by disconnecting from mains B3)
Connection information smoke detector (RM 3000 / RM 2860)
Maximum number
Output voltage range (B2)Clamp 2517.5 V DC to 18 V DC
Connection information wind - / rain detector (WTS)
Maximum number1
The connection of the wind and rain detector (WTS) is deactivated in emergency power operation
Output voltage range (E)Clamp 923.0 V DC to 24.5 V DC
Current carrying capacity (E)Clamp 9max. 150 mA
Connection information ventilation switch
Output voltage range (E)Clamp 2223.0 V DC to 24.5 V DC
Connection information free input
Input voltage range (I)Clamp 16DO NOT USE!
Connection information volt free contacts (NO – C – NC)
Voltage and current rating of the switching
contacts 1 and 2
Clamp 283 sec
Clamp 32 on 31 / 33
Clamp 35 on 34 / 36
1
7
8 x RM 3000
6 x RM 2860
max. 30 V DC,
2 A DC (60 W / 62.5 VA)
Mechanical features — plastic housing
Size SHEV 3 (w x h x d)254 x 180 x 111 mm
Size SHEV 6 (w x h x d)361 x 254 x 111 mm
Weight (incl. battery)4.40 kg (SHEV 3)
Protection type
HousingPolystyrol Halogen-free
Mechanical features — steel-sheet housing
Size SHEV 3 AP (w x h x d)301 x 323 x 85 mm
Size SHEV 6 AP ( w x h x d)301 x 444 x 85 mm
Weight (incl. battery)4.80 kg (SHEV 3 AP)
Protection typeIP20 according to EN 60 529
Housingsteel-sheet (powder-coated)
ColourRAL 9010
Protection class
6.40 kg (SHEV 6)
1
according to EN 60 529
IP66
8.30 kg (SHEV 6 AP)
2
I
Page 12
Technical data
Connection and operation
Connectionsee chapter Figure 7: „Wiring diagram total (simplified illustra-
Terminal clampsTension spring clamps 0.5 mm² – 2.5 mm²
Deadlock according to prEN 12101-9Option, factory setting: Yes
Maximum wire length between control unit and
actuator
Pause time during direction change200 ms
MaintenanceSee supplement „Safety instructions and warranty conditions“
Installation and environmental requirements
Operating temperature
Storage temperature
Suitable for outdoor installationNo
Registrations and certificates
EN compliantAs per EMC-directive 2004 / 108 / EC
Additional registrations, certificatesISO 21927-9
Classification as per prEN 12101- 9Class D
Classification as per EN 12101-10Class A
Environmental Class as per EN 12101-101
Control time of analog- / digital-input
Input digital (RZ, RA, LZ, Z, A)500 ms
Input analog (B1, B2, B3) during mains operation500 ms
Input analog (B1, B2, B3) during emergency power
operation
Technical information lead battery
Maintenance-free lead battery
Size (w x d x h)178 x 34 x 64 mm
Weight2 x 0,95 kg
VdS registrationG101139
Output voltage per battery10.5 V DC to 14.1 V DC
Output voltage total (series connection)21.0 V DC to 28.2 V DC
Rated capacity (total)2.3 Ah
Service lifeapprox. 4 years
1. With respective use of IP66 cable lead-through
2. The protective conductor is used as a functional conductor for a higher EMC immunity and should therefore be connected.
3. This temperature range applies to all components of the SHEV 3 / 6 system (including the battery).
tion)“ on page 7
see chapter 4.5 „Wire lengths“ on page 8
-5 to 40 °C
and the low-voltage directive 2006 / 95 / EC
prEN 12101-9
EN 12101-10
EPD acc. ISO 14025 and EN 15804
2500 ms
3
Page 13
Appendix
7. Appendix
7.1 Manufacturer‘s declaration
We hereby declare the conformity of
the product with the applicable guide-
lines. The declaration of conformity
can be viewed in the company and will be delivered
upon request. This declaration certifies conformity
with the directives mentioned, but gives no guarantee of characteristics. This declaration becomes invalid following a change that has been made without our consent.
7.2 EC manufacturer‘s declaration
(distributor)
The installer is responsible for the proper mounting
or commissioning and the preparation of the declaration of conformity in accordance with the EU directives.
General Conditions of Business and
7.3
Terms of Delivery
The currently valid conditions for products and services of the electrical and electronics industry
(green delivery terms) apply for deliveries and services, including the supplementary clause “Extended retention of title”. These are published by ZVEI
Frankfurt. If you are not familiar with these, we
would be happy to send them to you.
The agreements are also available for download at
short.simon-protec.com/agben
7.4 Company addresses
7.4.1. System manufacturer
SIMON PROtec Systems GmbH
Medienstraße 8
D ದ 94036 Passau
Tel.: +49 (0) 851 988 70 - 0
Fax: +49 (0) 851 988 70 - 70
E-Mail: info@simon-protec.com
Internet: www.simon-protec.com
7.4.2. Germany
SIMON PROtec Deutschland GmbH
Medienstraße 8
D ದ 94036 Passau
Tel.: +49 (0) 851 379 368 - 0
Fax: +49 (0) 851 379 368 - 70
SIMON PROtec Deutschland GmbH
Ammerseestraße 75
D ದ 82061 Neuried
Tel.: +49 (0) 89 78 17 0 - 0
Fax: +49 (0) 89 79 17 972