sime Planet Dewy 100 BFR User guide

INSTALLER INSTRUCTIONS
CONTENTS
1 DESCRIPTION OF THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 116
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 119
3 CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 130
4 USE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 133
IMPORTANT
– Make sure that there are no liquids or inflammable materials in the immediate vicinity of the boiler.
– Make sure that the electrical connections have been made correctly and that the earth wire is connected to a
good earthing system.
– Open the gas tap and check the soundness of the connections, including that of the burner.
– Make sure that the boiler is set for operation for the type of gas supplied.
– Check that the flue pipe for the outlet of the products of the combustion is unobstructed and has been pro-
perly installed.
– Make sure that any shutoff valves are open.
– Make sure that the system is charged with water and is thoroughly vented.
– Check that the circulating pump is not locked.
– Purge the system, bleeding off the air present in the gas pipe by operating the pressure relief valve on the
gas valve inlet.
FONDERIE SIME S.p.A. of Via Garbo 27 - Legnago (VR) - Italy declares that its hot water boilers, which bear the CE mark under Gas Directive 90/396/CEE and are fitted with a safety thermostat calibrated to a maximum of 110°C, are not subject to application of PED Directive 97/23/CEE as they meet the requirements of article 1 paragraph 3.6 of the Directive.
PLANET DEWY 60/100 BFR - ENGLISH
Planet Dewy 60 BFR:
Gas Council number 41-283-03
Planet Dewy 100 BFR:
Gas Council number 41-283-11
IPX4D
116
IT
ES
FR
BE
GB
RUS
RO
1.1 INTRODUCTION
Boilers (supplied as Class B devices, and can be made room sealed Class C) are pre-mixed condensation heating modules
intended only for heating, designed to work singularly or in sequence/cascade autono­mously. They are designed and constructed to meet European directives 90/396/CEE, 2004/108/CEE,
2006/95/CEE and 92/42/CEE.
Upon request, a control unit for a maxi­mum of four boilers can be supplied for sequence/cascade installation.
1 DESCRIPTION OF THE BOILER
1.2 DIMENSIONS
1.2.1 PLANET DEWY 60 BFR
275
55
12 0
60
12 0
265
17 0
75
230
M
R
C
S3
G
409=
20
870
455
500
865
12 0
15 0
13 5
CS
CA
R3
=
Fig. 1
R C.H. return G 1” (UNI-ISO 228/1) M C.H. flow G 1” (UNI-ISO 228/1) G Gas connection G 3/4” (UNI-ISO 228/1) C Filling system G 1/2” (UNI-ISO 228/1) R3 Tank return G 1” (UNI-ISO 228/1) S3 Condensation outlet ø 25 CA Inlet ø 80 CS Outlet ø 80
ATTENTION: the boiler is supplied as Class B device. To install the boiler as Class C device, remove the termi­nal inserted in the flange before connecting the intake.
203
M
R
G
R3
15 6
S3
65
115
281
120
235
865
500
CS
CA
120 160
135
600
405
18,5
870
=
=
Fig. 1/a
1.2.2 PLANET DEWY 100 BFR
R C.H. return G 1 1/2” (UNI-ISO 228/1) M C.H. flow G 1 1/2” (UNI-ISO 228/1) G Gas connection G 3/4” (UNI-ISO 228/1) R3 Tank return G 1 1/2” (UNI-ISO 228/1) S3 Condensation outlet ø 25 CA Inlet ø 80 CS Outlet ø 80
ATTENTION: the boiler is supplied as Class B device. To install the boiler as Class C device, remove the terminal inserted in the flange before connecting the intake.
117
IT
ES
FR
BE
GB
RUS
RO
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
1.3 MAIN COMPONENTS
1.3.1 PLANET DEWY 60 BFR
Fig. 2
KEY
1 Gas valve 2 Condensation drain siphon 3 Fan 4 Air pressure switch 5 Ignition electrode 6 Detection electrode 7 Ignition transformer 8 Exhaust thermostat
9 Heating probe (SM) 10 Safety thermostat 100°C 11 Differential pressure switch 12 Non return valve 13 Auto Air Vent 14 Pump 15 Control panel 16 Safety valve 4 BAR
1.3.2 PLANET DEWY 100 BFR
1
2
3
4
5
6
7
8
18
13
9
10
11
14
17
15
Fig. 2/a
KEY
1 Gas valve
2 Condensation drain siphon
3 Fan
4 Air pressure switch
5 Ignition electrode
6 Detection electrode
7 Ignition transformer
8 Exhaust thermostat
9 Heating probe (SM) 10 Safety thermostat 100°C 11 Differential pressure switch 13 Auto Air Vent 14 Pump 15 Control panel 17 Water pressure transducer 18 Flue Reducer 100/80
118
IT
ES
FR
BE
GB
RUS
RO
1.4 TECHNICAL FEATURES
PLANET DEWY 60 BFR PLANET DEWY 100 BFR
Heat output nominal (80-60°C) kW (kcal/h) 56.5 (48,600) 94.2 (81,000)
Heat output nominal (50-30°C) kW (kcal/h) 62.0 (53,400) 103.0 (88,600)
Heat output minimum G20 (80-60°C) kW (kcal/h) 17.0 (14,600) 29.3 (25,200)
Heat output minimum G20 (50-30°C) kW (kcal/h) 19.0 (16,300) 32.5 (27,950)
Heat output minimum G31 (80-60°C) kW (kcal/h) 22.6 (19,500) 29.3 (25,200)
Heat output minimum G31 (50-30°C) kW (kcal/h) 25.4 (21,800) 32.5 (27,950)
Nominal heat output kW (kcal/h) 58.0 (49,900) 96.6 (83,100)
Minimum heat output G20 kW (kcal/h) 17.4 (15,000) 30.0 (25,800)
Minimum heat output G31 kW (kcal/h) 23.2 (19,900) 30.0 (25,800)
Efficiency minimum/nominal output (80-60°C) % 97.6 - 97.5 97.7 - 97.5
Efficiency minimum/nominal output (50-30°C) % 109.3 - 107.0 108.8 - 106.4
30% yield (50-30°C) % 109.8 109.0
Termal efficiency (CEE 92/42 directive) ★★★★ ★★★★
Class NOx 5 5
Smokes temperature maximum (80-60°C) °C 70 70
Smokes temperature minimum (80-60°C) °C 62 62
Smokes temperature maximum (50-30°C) °C 50 50
Smokes temperature minimum (50-30°C) °C 32 32
Smokes flow kg/h 97 166
CO2 maximum/minimum G20 % 9.0/9.0 9.0/9.0
CO2 maximum/minimum G31 % 10.0/10.0 10.0/10.0
Maximum pressure exhaust manifold output Pa 110 170
Adsorbed power consumption W 198 330
Electrical protection grade
IPX4D IPX4D
Losses after shutdown at 50°C W/h 134 195
CE certification 1312BP4141 1312BP4141
Category II2H3P II2H3P
Category in FRANCE II2Er3P II2Er3P
Category in BELGIUM I2E(S)B - I3P I2E(S)B - I3P
Type B23-53 / B23P-53P / C13-33-43-53-83 B23-53 / B23P-53P / C13-33-43-53-83
C.H.
Maximum water head bar 4 5
Maximum temperature °C 85 85
Water content boiler l 4.8 8.2
C.H. setting range (D.H.W. setting range) °C 20/80 (30/60) 20/80 (30/60)
GAS PRESSURE END NOZZLES
Gas supply pressure G20/G25 mbar 20/25 20/25
Gas supply pressure G31 mbar 37 37
Nozzles quantity 1 1
Nozzles diameter G20/G25 ø 9,3 11.0
Nozzles diameter G31 ø 6,7 8.4
Gas consumption nominal/minimum G20 m3/h 6.14/1.84 10.22/3.17
Gas consumption nominal/minimum G31 kg/h 4.51/1.80 7.50/2.33
WEIGHT kg 61 92
119
IT
ES
FR
BE
GB
RUS
RO
The boiler must be installed in a fixed loca­tion and only by specialized and qualified firms in compliance with all instructions contained in this manual. Furthermore, the installation must be in accordance with current standards and regulations.
2.1 BOILER ROOM
The boilers can be installed in boiler rooms
whose size and requirements meet current regulations. Furthermore, vents, with surface areas at least 3.000 sq. cm or 5.000 sq. cm for gas with density over 0.8, must be installed in the outer walls for room ventilation.
2.2 INSTALLATION
For single installations, it is also possible to order an optional compensator kit (code
8101520 for the version “60 BFR” and cod. 8101523 for the version “100 BFR”). The kit can be fitted on accumulation boilers with a capacity equivalent to or above 80 liters. For installation for single or sequen­ce/cascade operations, refer to the exam­ple in fig. 3. With control unit code 8096301, supplied by Sime upon request, a maximum of four boilers can be controlled. The control unit kit is supplied with assembly and use instructions.
2 INSTALLATION
45
14 6
R3
500
865
582
88
330
R
M
M2
M2
265
305
455
265
Fig. 3
WARNING:
- In both single and sequence/cascade installation, the heating system must be equipped with a hydraulic separator and safety components.
- When replacing one or more boilers in existing plants, it is advisable to install a heat exchanger to separate the boiler circuit from the secondary circuits. See the pressure curve for the boiler supply shown in figure 14.
M
S3
R
G
Single installation with kit optional code 8101520 for "60 BFR"
Installation in sequence/cascade
R C.H. return M C.H. flow G Gas connection S3 Condensation outlet
Single installation with kit optional code 8101523 for “100 BFR”
M C.H. flow R C.H. return M2 Tank flow R3 Tank return
70
R3
600
235
500
865
301
M2
355
265
M2
663
MR
115
120
IT
ES
FR
BE
GB
RUS
RO
2.3 CONNECTING UP
SYSTEM
To protect the heat system from being damaged by corrosion, incrustation or deposits, after installation it is extremely important to clean the system using suita­ble products such as, for example, Sentinel X300 or X400. Complete instructions are provided with the products but, for further information, you may directly contact SENTINEL PERFORMANCE SOLUTIONS LTD. For long-term protection agains corrosion and deposits, the use of inhibitors such as Sentinel X100 is recommended after clea­ning the system. It is important to check the concentration of the inhibitor after each system modifica­tion and during maintenance following the manufacturer’s instructions (specific tests are available at your dealer). The safety valve drain must be connected to a collection funnel to collect any dischar­ge during interventions.
WARNING: Failure to clean the heat system or add an adequate inhibitor inva­lidates the device’s warranty.
Gas connections must be made in accor­dance with current standards and regula­tions. When dimensioning gas pipes from the meter to the module, both capacity volume (consumption) in m3/h and gas density must be taken into account. The sections of the piping making up the system must be such as to guarantee a supply of gas sufficient to cover the maxi-
mum demand, limiting pressure loss between the gas meter and any apparatus being used to not greater than: – 1.0 mbar for family II gases (natural gas); – 2.0 mbar for family III gases (butane or
propane). A sticker inside the module includes identifi­cation and gas type data specific to the module.
2.3.1 Condensation drain
installation.
A siphoned drain must be connected to the civil drain by a pipe with minimum 5 mm per meter gradient for condensation collec­tion.
Only normal plastic civil drain pipes are suitable to convey condensation to the building's sewer drain.
2.3.2 Gas pipe filter
The gas valve is fitted with a standard filter. This filter is not capable of filtering all impuri­ties and to prevent poor gas valve operation or failure of any gas valve safety feature, it is advisable to fit a suitable filter on the gas supply pipe.
2.5 FILLING THE SYSTEM
Cold system filling pressure must be 1 bar.
The system must be filled slowly so that air bubbles are released through the specific escapes.
2.6 EXHAUST
The boiler is supplied with a 80mm gasket, which must be fitted over the exhaust ter­minal prior to the flue being installed. (11 fig. 4-4/a-4/b).
2.6.1 Type B (fig. 4)
If the inlet is not connected, the boiler should be regarded a Class B device. When installing the boiler in locations where it needs to be protected from water, replace the intake terminal inser ted in the flange with terminal code 8089510. For informa­tion on how to configure the boiler in this mode see figure 4.
The maximum overall length of ø 80 exhaust flues is determined by the load losses of the single accessories installed and should not exceed 16 mmH2O (“60 BFR”) and 28 mmH2O (“100 BFR”).
2.6.2 Type C (figg. 4/a-4/b)
The boiler becomes a Class C device when the intake terminal is removed from the flange and the intake is connected to sepa­rate exhaust ducts (fig. 4) or with coaxial exhaust (fig. 4/b).
ø 80 ACCESSORY LOAD LOSS TABLE
WARNING: Before installing accessories, lubricate the internal part of gaskets with silicon-based pro­ducts. Avoid using oils and greases.
KEY
1
90° MF polypr. curve (6 pcs.) code 8077450
2a
Polypr. extension L.1000 (6 pcs.) code 8077351
2b
Polypr. extension L. 500 (6 pcs.) code. 8077350
3
Hinged tile code 8091300
4
Roof Terminal kit L 1285 code 8091205
5
Polypropylene extension L. 250 with test outlet code 6296513
6
45° MF polypr. curve (6 pcs.) code. 8077451
7
Exhaust terminal code 8089501
8
Internal-external ring nut kit code 8091500
11 Rubber gasket ø 80 (supplied as standard)
Load loss
(mm H2O)
“60 BFR” “100 BFR”
90° MF polypropylene curve
1,30 3,00
45° MF polypropylene curve
0,70 2,00
Polypr. extension L. 1000
0,60 1,20
Polypr. extension L. 500
0,30 0,60
Roof exit terminal
L. 1381 1,20 4,30
Exhaust terminal
1,30 3,60
Polypropylene extension L. 250
0,15 0,30
Type B
Fig. 4
600
2.6.3 Maximum usable length for separate ø 80 flues
The maximum overall length of ø 80 suc­tion and exhaust flues is determined by the load losses of the single accessories installed and should not exceed 16 mmH2O (”60 BFR”) and 28 mmH2 O (”100 BFR”).
When the length of the flues ranges between 11 and 16 mm H20 (“60 BFR”) -
17 and 27 mm H20 (“100 BFR”), it is necessary to adjust trimmer “MAX” on the
fan board and set the “Max. air p” values
provided in paragraph 4.3 in order to ensu­re a correct operation.
2.6.4 Maximum usable length for coaxial ø 80/125 flues
In installations with ø 80/125 coaxial
exhaust, the maximum horizontal length including the 90° curve, should not exceed 5 m (“60 BFR”) and 2 m (“100 BFR”). For roof exits it should not exceed 8 m along vertical for the “60 BFR” and 3 m along vertical for the version “100 BFR”.
In the version “60 BFR” when the length of the flue ranges from 2 to 5 m horizontally and from 4 to 8 m vertically, it is necessary to adjust trimmer “MAX” on the fan board
121
IT
ES
FR
BE
GB
RUS
RO
WARNING:
- Installations with roof exit terminal (4a) and coaxial exhaust (13) require the use of a condensation recovery (12) that has to be connected to the water drain siphon (waste water).
- The installation of the roof exit terminal (4a) requires the removal of the two ø 60 and ø 100 reducers.
- Before fitting the accessories, it is always advisable to lubricate the internal section of the gaskets with silicon products and generally avoid the use of oils and greases.
TABLE OF LOAD LOSSES OF ACCESSORIES
Fig. 4/a
KEY
1 ø 80 curve, 90° MF (6 pcs) code 8077450 2 a ø 80 extension, L. 1000 (6 pcs.) code 8077351 2 b ø 80 extension, L. 500 (6 pcs.) code 8077350 3 Hinged tile, code 8091300 4 Roof exit terminal, L. 1381, code 8091204 4 a Coaxial roof exit terminal, L. 1285 code 8091205 5 ø 80 extension, L. 250, with socket, code 6296513 6 ø 80 curve, 45° MF (6 pcs.), code 8077451 7 ø 80 exhaust terminal, code 8089501
8 Kit with internal/external ring nuts, code 8091500 10 Suction/exhaust fitting, code 8091401 11 ø 80 rubber gasket (supplied with unit) 12 ø 80 condensation recovery, L. 135, code 8092800 13 ø 80/125 coaxial exhaust, L. 885, code 8091210
Load loss (mm H2O)
“60 BFR” “100 BFR”
Suction Exhaust Suction Exhaust
90° MF polypropylene curve 1.00 1.30 2.00 3.00 45° MF polypropylene curve 0.60 0.70 1.50 2.00 Polypropylene extension, L.1000 0.60 0.60 1.20 1.20 Polypropylene extension L.500 0.30 0.30 0.60 0.60 Coaxial roof exit terminal, L.1285 + Fitting (pos. 10) - 4.30 - 14.00 Roof exit terminal L.1381 - 1.20 - 4.30 Exhaust terminal - 1.30 - 3.60 Suction terminal 0.20 - 1.60 -
Polypropylene extension, L. 250 with socket - 0.15 - 0.30 Coaxial exhaust, L.885 + Fitting (pos. 10) - 5.20 - 15.00
Condensation recovery, L.135 2.50 - 5.00 -
Type C (separate ø 80 flues and
coaxial exhaust terminal)
Type C (separate ø 80 flues)
Type C (ø 80/125 coaxial exhaust)
KEY 2 a ø 80/125 extension, L. 1000, code 8096171 2 b ø 80/125 extension, L. 500, code 8096170 3 Hinged tile, code 8091300 4 a Coaxial roof exit terminal, L. 1285, code 8091205 10 Suction/exhaust fitting with test outlet, code 8091401 11 ø 80 rubber gasket (supplied with unit) 12 ø 80 condensation recovery, L. 135, code 8092800 13 ø 80/125 coaxial exhaust, L. 885, code 8091210 14 a 90° curve, ø80/125, code 8095870 14 b 45° cur ve, ø80/125, code 8095970
Fig. 4/b
Model H (m) L (m)
60 BFR 85
100 BFR 32
NOTES:
- Installation requires the use of a condensation recovery (12) that must be connected to a water drain siphon (waste water).
- The installation of the coaxial roof exit terminal (4a) requires the removal of the two ø60 and ø100 reducers.
- Before fitting the accessories, it is always advisable to lubricate the internal section of the gaskets with silicon products and generally avoid the use of oils and greases.
- Horizontal terminals must be LEVEL
WARNING: – In the versions “60 BFR” he
insertion of a 90° additional curve reduces the available length by 2 meters end the insertion of a 45° additional curve reduces the available length by 1 meter.
– In the versions “100 BFR” inse-
rimenti of additional curves are not admitted.
122
IT
ES
FR
BE
GB
RUS
RO
and set the “Max. air p” values provided in
paragraph 4.2 in order to ensure a correct operation. In the version “100 BFR” for all pipe lengths it is necessary to adjust trimmer “MAX” on the fan board and set the “Max.
air p” values provided in paragraph 4.3 in
order to ensure a correct operation.
2.6.5 Positioning the outlet terminals
The outlet terminals for forced-draught
appliances may be located in the external perimeter walls of the building.
To provide some indications of possible solu­tions, Table 2 gives the minimum distances to be observed, with reference to the type of building shown in fig. 5.
123
IT
ES
FR
BE
GB
RUS
RO
2.7 ELECTRICAL CONNECTION
The boiler is supplied with an electric cable. Should this require replacement, it must be purchased exclusively from SIME. The electric power supply to the boiler must be 230V - 50Hz single-phase through a fused main switch, with at least 3 mm spa­cing between contacts. Respect the L and N polarities and the earth connection.
NOTE: SIME declines all responsibility for injury or damage to persons, animals or property, resulting from the failure to pro­vide for proper earthing of the appliance.
2.7.1 Room stat connection (fig. 8 pos. A)
To gain access to the electronic board con­nector (3), remove the control panel cover and connect the room stat to the terminals TA after having removed the jumper. The thermostat or timer-thermostat,
recommended for better room temperatu­re control, must be class II as specified by standard EN 60730.1 (clean contact).
WARNING: Applying mains voltage to the terminals of conector (3) will irreparably damage the control board. Make sure that any connections to be made are not carrying mains voltage.
2.7.2 “Logica Remote Control” connection (fig. 8 pos. B)
The electrical plant must comply with local standards and all cables must comply with low safety voltage requirements of EN
60730. For lengths up to 25 m, use cables
of section 0.25 mm2, for longer lengths up to 50 m use cables of section 0.5 mm
2
. First of all, assemble and wire the socket (2), then insert the equipment which will start-up as soon as it receives current. To gain access to connector (3) remove the control panel cover and connect the climate
regulator to terminals CR.
WARNING: External voltage must not be connected to terminals 1-2-3-4 of the "Logica Remote Control". A telephone remote switch with a zero potential con­tact or a window contact can be connected to terminals 3-4.
Equipment for the checking of civil plants via a telephone line includes the model TEL 30.4 LANDIS & STAEFA.
2.7.3 External temperature
sensor connection (fig. 8 pos. C)
The cables must comply with low safety vol­tage requirements of EN 60730. For lengths up to 25 m, use cables of sec­tion 0.25 mm2, for longer lengths up to 50 m use cables of section 0.5 mm
2
. To gain access to boiler connector (3) remo­ve the control panel cover and connect the external temperature sensor to terminals SE.
–If the terminal discharges into a pathway or passageway check that combustion products will not cause nuisance
and that the terminal will not obstruct the passageway.
–Where the lowest part of the terminal is fitted less than 2 m (78 in) above ground, above a balcony or above a flat
roof to which people have access, the terminal MUST be protected by a purpose designed guard. Terminal guards are available from Quinnell, Barrett, and Quinnell, Old Kent Road, London. State model C2, (G.C. Part No 382946).
–Where the terminal is fitted within 850 mm (34 in) of a plastic or painted gutter, or 450 mm (18 in) of painted
eaves, an aluminium shield at least 1,500 mm (59 in) long must be fitted to the underside of the painted surface. –The air inlet/outlet flue duct MUST NOT be closer than 25 mm (1 in) to combustible material. –In certain weather conditions the terminal may emit a plume of steam. This is normal but positions where this would
cause a nuisance should be avoided.
Terminal position Minimum spacing A Directly below an openable window, air vent
or any other ventilation opening 300 mm 12 in
B Below guttering, drain pipes or soil pipes 75 mm 3 in C/D Below eaves, balconies or carport roof 200 mm 8 in E From vertical drain pipes or soil pipes 75 mm 3 in F From internal or external corners 300 mm 12 in G Above adjacent ground, roof or balcony level 300 mm 12 in H From a boundary or surface facing the boiler 600 mm 24 in I From a terminal facing the terminal 1,200 mm 48 in J From an opening in the carport
(eg door, window into dwelling) 1,200 mm 48 in
K Vertically from a terminal on the same wall 1,500 mm 60 in L Horizontally from a terminal on the same wall 300 mm 12 in M Horizontally from a vertical terminal to a wall 300 mm 12 in N Horizontally from an openable window or other opening 300 mm 12 in P Above an openable window or other opening 300 mm 12 in
TABLE 2
Fig. 5
124
IT
ES
FR
BE
GB
RUS
RO
2.7.4 Wiring diagram “PLANET DEWY 60 BFR”
J1
J3
J4
J5
J6J7
J8
J9
J10
J2
Fig. 9
KEY EV1 Gas valve coil EV2 Gas valve coil EA Ignition electrode ER Detection electrode TS Safety thermostat 100°C V Fan TPA Water pressure transducer PI System pump SE External probe (optional) TA Room thermostat SM Heating probe TR 230 - 24V transformer PD Differential pressure switch CR Remote Control Logic (optional) SV Fan board
TF Exhaust thermostat PA Air pressure switch SB Boiler probe PB Boiler pump TRA Ignition transformer
NOTE: Connect the room thermostat (TA) to terminals 5-6 after removing the bridge. Fan control board (SV) “MAX” and “MIN” trimmers are sealed and must never be tampered with.
CONNECTOR SPARE PART CODES:
J2 cod. 6278613 J3 cod. 6299970 J4 cod. 6293589 J5 cod. 6293586 J7 cod. 6293587
1
2
A
C
LOGICA REMOTE CONTROL
SONDA ESTERNA
CRONOTERMOSTATO
LOGICA REMOTE CONTROL
B
3
Fig. 8
KEY 1 Control panel 2 “Logica Remote Control” socket 3 Conector (J2) TA Room stat (not supplied) CR Logica Remote Control (optional) SE External temperature sensor (optional)
ROOM STAT
EXTERNAL SENSOR
125
IT
ES
FR
BE
GB
RUS
RO
J8
J7
J6
J5
J4
J9
J3
J2
J10
J1
2.7.5 Wiring diagram “PLANET DEWY 100 BFR”
Fig. 9/a
KEY EV1 Gas valve coil EV2 Gas valve coil EA Ignition electrode ER Detection electrode TS Safety thermostat 100°C V Fan TPA Water pressure transducer PI System pump SE External probe (optional) TA Room thermostat SM Heating probe TR 230 - 24V transformer PD Differential pressure switch CR Remote Control Logic (optional) SV Fan board TF Exhaust thermostat
PA Air pressure switch SB Boiler probe PB Boiler pump TRA Ignition transformer
NOTE: Connect the room thermostat (TA) to terminals 5-6 after removing the bridge. Fan control board (SV) “MAX” and “MIN” trimmers are sealed and must never be tampered with.
CONNECTOR SPARE PART CODES:
J2 cod. 6278613 J3 cod. 6316242 J4 cod. 6293589 J5 cod. 6316241 J7 cod. 6316241
126
IT
ES
FR
BE
GB
RUS
RO
N
L
VR
M
R
SEPARATORE IDRAULICO
PI
BOLLITORE
PB
VR
L
N
PC
PB
R
CR
J7
J6
J2
SCHEDA COD. 6230696
PI
R1
CR1
TA
R2
CR2
POSIZIONAMENTO
DIP-SWITCH
PLANET DEWY 60 BFR
PLANET DEWY 100 BFR
J7
J6
J2
SCHEDA COD. 6230696
CR2
PC
PB
R
CR
R1
PI
R2
CR1
COD. 6260505
POSIZIONAMENTO
DIP-SWITCH
2.7.6 The electric connection between the boiler and heater is downstream from the hydraulic separator
Fig. 10
KEY PC Pump PB Boiler pump PI System pump R-R1-R2 Relay CR-CR1-CR2 Relay contact TA Room thermostat VR Non return valve M C.H. flow R C.H. return
Note
- The relay (R) disconnects the heating pump when the requirements of both services are met.
- The relay (R1) disconnects the plant pump during the hot water preparation phase.
- Remember to correctly position the DIP-SWITCH on the board.
BOARD CODE 6230696
POSITION
DIP-SWITCH
BOARD CODE 6230696
POSITION
DIP-SWITCH
HYDRAULIC COMPENSATOR
TANK
127
IT
ES
FR
BE
GB
RUS
RO
2.8 LOGICA REMOTE CONTROL USED WITH SINGLE BOILERS.
All the boiler's functions can be managed by a optional digital multifunctional device code 8092204 for the remote of the boi­ler itself and for regulating room climatic conditions with an operational reserve of 12 hours. The heating circuit is controlled by the room temperature sensor built-in the equipment or by the atmospheric conditions, with or without environmental inflow, if the boiler is connected to an external sensor.
Characteristics:
– Ergonomic control unit divided according
to function (control levels)).
– Clear division of basic functions:
operating regime, correction of set
value and presence button are directly accessible;
Different real current values are
accessible through the "info" button;
other functions can be programmed
after the cover has been opened;
special service level with protected
access;
– Each setting or modification is displayed
and confirmed.
– Tome setting (special line for changing
BST/CET).
– Heating programme with max. 3 heating
periods per day, individually selectable.
Copy function for easy transfer of hea­ting programme to the next or pre-
vious day.
– Holiday programme: the programme is
interrupted for the holiday period and automatically restarted on returning home.
– Option to return the heating program to
default values.
– Programming lock (child safety).
Functions:
– Delivery temperature control guided by
the atmospheric conditions, taking into account the dynamics of the building.
– Delivery temperature control guided by
atmospheric conditions with influence of
ambient temperature. – Ambient temperature control only. – Adjustable influence of ambient tempera-
ture shift . – Switch-on and switch-of f optimisation. – Rapid lowering. – ECO functions (daily heating limiter, auto-
matic summer/winter switch-over). – Controllable maximum delivery tempera-
ture limit (specifically for floor plants). – Limitation of increase in pre-set delivery
temperature. – Anti-freeze protection for buildings. – Hourly programming of the tank unit
temperature on two levels: comfort and
reduced. – Domestic hot water control with nominal
value requirement and enable. – Connection to room sensor or switching
of operating regime through the telepho-
ne system with external contact or
through a window contact.
– Anti-bacterial.
2.8.1 Installation
The unit must be installed in the main living room. For installation, follow the assembly instructions inserted in the package. At this point, with the selector knob on ( ), the installer can adjust the basic parameters set­tings according to the individual needs (point
2.8.2).
The radiators in the room that the Logica is fitted must not have thermostatic valves.
2.8.2 Installation settings
The settings for the basic operating para­meters for individual needs are shown in the instruction leaflet supplied with the "Logica Remote Control" and in the section reserved for the user in this manual. For further adjustments which can be car­ried out by the installer, the "Logica Remote Control" offers a level of service and para­meterising which can only be accessed through a special combination of buttons. To activate this level of service or parame­terising press buttons and least 5 seconds. This will activate the parameterising level. Then use the same arrow buttons to select the individual input lines and adjust the values with or .
Antifreeze protection "Pre-set ambient temperature value"
Summer/Winter switch-over temperature
Type of control: 0 = with ambient influence 1 = without ambient influence
Influence of ambient temperature
Heating takes place up to this pre-set value if the plant is activated in standby (e.g. holidays). In this way, the building antifreeze function is active, preventing an excessive lowering of the ambient.
This parameter regulates the temperature of the automatic summer/win­ter switch-over.
This parameter de-activates the ambient influence and as a result all the optimisations and adaptations. If a valid external temperature is not transmitted , the controller switches to the pure ambient control guide variable.
If the ambient controller is used only as a remote control (placed in the refe­rence room and without an external sensor connected), the value must be set at 0 (zero). If the change in ambient temperature from the pre-set value remains high during the entire day, the influence must be increased. If the ambient tem­perature is around the pre-set value (control oscillation), the influence must be reduced.
Note: If the ambient temperature influence constant is set at 0, the adap­tation of the heating curve is deactivated. In this case, parameter 57 will have no effect at all.
54
HEATING CIRCUIT SETTINGS
52
53
51
128
IT
ES
FR
BE
GB
RUS
RO
DOMESTIC HOT WATER SETTINGS
Reduced domestic hot water pre-set value
Domestic hot water load
The reduced pre-set value of the temperature of the domestic hot water allow the required water temperature to be obtained outside the programmed usage times (daily programme 8).
0 = 24 hours/ day - Hot water is always available at the temperature set
with user parameter n°3.
1 = standard - Hot water according to the daily heating programme.
In the comfort areas of heating the temperature of the boiler unit is regu­lated to the value set with user parameter n° 3. In the reduced areas of heating the temperature of the boiler unit is regulated to the value set with parameter n° 61 of the service level.
2 = service disconnected 3 = second daily programme (8) - Every day of the week the temperature of
the hot water is set according to programme 8. In this case there is a single programming for all the days of the week and three time zones are available. In the time spans set the temperature of the boiler unit is regu­lated according to that set in parameter n°3. In the remaining hours the boiler unit is controlled to the temperature set with parameter n° 61 the of service level.
62
61
Maximum limit of delivery temperature
Variation of the maximum speed of the delivery temperature
Activation of adaptation
Optimisation of switch-on time
Heating gradient
Presetting switch-off time (00 = off)
The delivery temperature is limited to the maximum set value.
The increase per minute of the prescribed delivery temperature value sent in °C is limited to the imposed value.
With the activation of the adaptation, the pre-set value transmitted to the boiler regulator is adapted to the effective heat need. The adaptation functions with both the atmospheric guide with ambient influence and with pure ambient control. If the "Logica Remote Control" is set as a remote control only, the adaptation must be is deactivated.
If the switch-on time optimisation is active, the "Logica Remote Control" modi­fies the heating gradient until it finds the optimum heating point
0 = off 1 = on
The "Logica Remote Control" selects the switch-on time such that the set value has more or less been reached at the start of the usage time. The more severe the night-time cooling, the earlier the heating time starts.
Example: Current ambient temperature 18.5°C
Nominal ambient temperature 20°C Heating gradient 30 min/K Presetting of switch-on time:
1.5 K x 30 min/K = 45 minutes
00 means that the switch-o time has not been pre-set (function disabled).
If the switch-off time optimisation is active (value > 0), the "Logica Remote Control" modifies the pre-set time until it finds the optimum switch-off time..
55
56
57
58
59
60
Final user level 2 programming block
This block (1) can be activated to display all the parameters without modifying them. Pressing buttons or displays “OFF”.
WARNING:
The activation block can be deactivated temporarily by pressing buttons and simultaneously; a confirmation sign appears on the display. At this point press simultaneously the buttons and for at least 5 seconds. To permanently remove the activation block, set parameter 63 on 0.
63
SERVICE VALUES
129
IT
ES
FR
BE
GB
RUS
RO
2.8.3 Gradient of the characteristic heating curve
The gradient of the characteristic heating curve is imposed on the current value “15” of Logica. Increasing the gradient as shown in the drawing of fig. 11, the delivery temperature increases in correspondence to the outside temperature.
2.9 EXTERNAL TEMPERATURE
SENSOR
The "Logica Remote Control" can be connec­ted to an external temperature sensor availa­ble a an optional extra (code 8094100). This configuration ensures and maintains the required temperature constant in the room. The ambient temperature is, in fact, indicted and evaluated as the calculated mean of the value measured inside and outside the dwel­ling. For installation, follow the assembly instructions inserted in the package.
Fig. 11
Example: Choosing a gradient of 15 with an outside temperature of –10°C we shall have a delivery temperature of 60°C.
Input function terminal 3-4
The freely programmable input (terminals 3-4) allows three different functions to be activated. The parameter has the following significance: 1 =
If an external sensor is connected, the display will show the temperature of the external sensor ( _ _ = no sensor connected, function disabled).
2 = With an external contact, it is possible to switch-over to "reduced pre-
set value of the ambient temperature".
3 = With an external contact, it is possible to switch-over to "reduced pre-
set value of the antifreeze ambient temperature" (short circuit 0 0 0 or interruption _ _ _ ). The display shows the current status of the external contact.
64
Operating mode of external contact
External and ambient sensor influence
Anti-bacterial function
(with storage capacity boiler unit)
If the entrance (terminals 3 and 4 of the base) is connected to a zero potential external contact (parameter 64 = 2 or 3), the operating mode of the contact can be determined (remote telephone switch or window contact). The operating mode specifies the status of the contact in which the required function is active.
Display: Operating mode closed (shor t circuit) 0 0 0
Operating mode open (interruption) _ _ _
Determines the mix ratio between the internal and external ambient sensor when parameter 64 = 1.
0 % = internal sensor only active (0% external - 100% internal) 50 % = mean value of external + internal sensor 100 % = external sensor only active
The set mix is used for ambient control and display. If the external sensor is short circuited or interrupted, the operation conti­nues with the internal sensor.
This function allows the hot water to be brought to a high temperature once a week in order to eliminate eventual pathogenic agents. It is active every Monday for a maximum duration of 2.5 hours at a delivery temperature of 65°C.
0 = not active 1 = active
65
66
69
130
IT
ES
FR
BE
GB
RUS
RO
3.1 ELECTRONIC BOARD
Built according to Low Voltage direc­tive 2006/95/CEE and powered at 230 Volt, via a transformer it sends 24 Volt power to the following compo­nents: gas valve, safety thermostat, heating probe, external temperature probe (optional), water pressure transducer, air pressure switch, room thermostat or “Remote Control Logic”. An automatic and continual modulation system permits the boiler to adjust power to the various system or user needs. Electronic components are guaranteed to ope­rate in a temperature range from 0 to +60°C.
3.1.1 Malfunctions
Boiler malfunctions or failures can be indicated by a flashing temperature LED as shown in fig 12.
3.1.2 Devices
The electronic board is equipped with the following devices: – “HEATING POWER” TRIMMER
(10 fig. 13) Adjusts maximum heating power. To increase the value, rotate the trim­mer clockwise, to reduce it, rotate
the trimmer counter-clockwise.
“IGNITION POWER” TRIMMER
(6 fig. 13) Trimmer to vary the gas valve ignition pressure level (STEP). According to the type of gas the boiler is designed for, the trimmer must be adjusted to achieve a burner pressure of approxi­mately 6.5 mm H
2O for methane gas
and 9.5 mm H
2O for propane gas
(G31). To increase pressure, rotate the trimmer clockwise, to reduce it, rotate the trimmer counter-clockwi­se. The slow ignition pressure level can be set during the first five seconds after the burner is lit.
After setting the ignition pressure level (STEP) according to the type of gas, make sure that the heating gas pressure is still the previously set value.
“ANN. RIT.” CONNECTOR
(5 fig. 13) The electronic board is program­med, during heating, with a techni­cal burner delay of about 90 seconds that is performed both at cold start and subsequent ignitions. This is to prevent rapid ignitions and shutdowns that could, in particular, occur in systems with high load los­ses. Each time the boiler restarts, after the slow ignition, for about 1 minute it will run at minimum modu-
lation pressure before moving to the set heating pressure. The addition of a bridge will cancel both the programmed technical delay and the minimum pressure operating period at ignition. In this case, the time between shut­down and the next ignition will depend on a 5°C differential detec­ted by the heating probe (SM).
DIP SWITCH (13 fig. 13)
For correct module operations, the dip switches must be positioned as indicated below:
“Modureg Sel.” connector (14 fig. 13) The bridge must always be connec- ted.
“Albatros”
connector
(15 fig. 13) The bridge must always be off. It is only engaged in sequence/cascade installations with several boilers.
WARNING: All the above operations must be performed by authorised personnel, otherwise the warranty shall be invalidated.
3 CHARACTERISTICS
Flashing red led,
communication fault
with “Logica Remote Control”
Green led off if
power is cut-off
Blinking red air pressure switch fault led
Flashing red led, water pressure is too low (*)
Flashing red led, heating sensor fault
(SM)
Flashing red led,
plant safety
valve tripped (*)
Red led on, ignition blocked:
rotate selector CR/OFF/EST/INV/RESET
to release position
()
to restore operation
Flashing red led, safety stat tripped.
Rotate selector CR/OFF/EST/INV/RESET
to release position
()
to restore operation
(*)
When all 0.5 to 2.5 bar leds are off, check the water pressure transducer
connection.
WARNING: the operation of plants with open vessels is guaranteed only for static pressures above 0.7 bar. On model “100 BFR” continuous operation can be guaranteed, even for pres­sure reductions > 4 bars, by activating jumpers X4 e X25 (fig. 13) only and electrically disconnecting the connector from the water pressure transducer. The operating pressure can be measured using the pressure gauge installed in the plant.
Fig. 12
Flashing red led, flame detection circuit fault
Blinking red fan fault led. 30 minutes af ter the fan turns off, the board attempts to
restart it. To identify where the fault occurred in sequence/cascade installations, turn
the CR/OFF/INV/RELEASE selector on each module to the
()
position and check
where the red fault led blinks.
131
IT
ES
FR
BE
GB
RUS
RO
3.2 TEMPERATURE PROBE AND WATER PRESSURE TRANSDUCER
Antifreeze system made up of the NTC heating sensor that activates when the water temperature reaches 6°C. Tables 1 - 1/a include the resistance
values () that are obtained on the
probe (SM) when the temperature changes and those on the transducer when pressure changes.
The boiler will not work if the heating probe (SM) is open circuit or discon­nected.
3.3 ELECTRONIC IGNITION
Ignition and flame detection is con­trolled by two electrodes located on the burner. These guarantee maxi­mum safety with intervention times, for accidental switching off or gas fai­lure, of within one second.
3.3.1 Operating cycle
Rotate the selector to summer or win­ter and check the green led ( ) to make sure power is on. The burner should ignite within max. 10 seconds. An ignition failure will cause the "Ignition Blocked" indicator (fig 12) to illuminate, This may be due to the fol­lowing:
Ignition electrode does not spark
Gas is being supplied to the boiler and, after 10 sec., the block led turns on. This may be due a faulty or discon­nected spark generator, faulty or disconnected ignition electrode.
No flame detection
At ignition, the electrode continues to spark even though the burner is on. After 10 sec. it stops sparking, the burner turns off and the block led turns on. This may be due to a faulty, discon­nected or damaged ionisation elec­trode, wrong polarity(live and neu­tral reversed).
The boiler should resume automatical­ly after a power failure.
3.4 AIR PRESSURE SWITCH
The air pressure switch is not adjusta­ble. Its value is shown on the air pres­sure switch.
15
13
1
3
5
8
9
10
11
12
14
6
6
10
X25
X4
16
17
Fig. 13
TABLE 1/a (Transducer)
Pressure Resistance (Ω)
(bar) mín máx
0 297 320
0,5 260 269
1 222 228
1,5 195 200
2167173
2,5 137 143
3108113
3,5 90 94
TABLE 1 (Sensors)
Temperature (°C) Resistance (Ω)
20 12.090 30 8.313 40 5.828 50 4.161 60 3.021 70 2.229 80 1.669
KEY
1 Ignition electrode earth faston 3 Fuse (1,6 AT) 5 “ANN. RIT.” connector 6 “POT. ACC.” trimmer 8 D.H.W.potentiometer
9 Detector electrode faston 10 “POT. RISC.” trimmer 11 C.H. potentiometer 12 Selector CR/OFF/EST/INV/RESET 13 DIP SWITCH 14 Connector “Modureg Sel.” 15 Connector “Albatros” 16 Connector X25 17 Connector X4
NOTE: To gain access to trimmers (6) and (10), unscrew the central heating potentiometer knob.
132
IT
ES
FR
BE
GB
RUS
RO
3.5 SYSTEM AVAILABLE HEAD
The residual prevalence of the boiler supply and return lines varies accor­ding to capacity, as shown in the dia­gram of fig. 14.
3.6 MAINS ELECTRICITY CONNECTION
Use a separate electrical line where the room thermostats with relevant area pumps must be connected. Switch or relay contacts must be con­nected to the electronic board con­nector (J2) after removing the link (fig.
15).
CR1
CR
TA
TA
Connettore J2
PLANET DEWY 60-100 BFR
L
N
TA
TA
1
PZ
R
PZ
1
R
1
Fig. 15
KEY TA-TA1 Zone room stat PZ-PZ1 Zone pump R-R1 Zone relay CR-CR1 Relay contact
0
600
500
4000
350030002500200015001000
PO RTATA (l/h)
PREVALENZA RESIDUA (mbar)
500
400
10 0
200
300
Planet Dewy 60-100 BFR
4500
700
800
60 BFR
100 BFR
Fig. 14
FLOW RATE (l/h)
RESIDUAL HEAD (mbar)
J2 connector
Fig. 15/a
3.7 “PLANET DEWY 60 BFR” WITH KIT (CODE 8101520) AND "BT" BOILER (optional)
KEY
1 Gas valve 2 Condensation drain siphon 3 Boiler pump (not supplied) 4 Fan 5 Heating probe (SM) 6 Safety thermostat 95°C 7 Exhaust thermostat 8 Primary exchanger
9 Diaphragm 10 Differential pressure switch 11 Water pressure transducer 12 Air relief valve
13 Circulation pump
14 Drain plug 15 Gas cock (not supplied) 16 Non return valve 17 4-BAR safety valve 18 Non return valve (not supplied)
19 Hydraulic compensator (supplied in the kit) 20 Drain tap (not supplied) 21 Expansion vessel 8 liter (supplied in the kit) 22 Air relief valve (not supplied) 23 Oblique filter (not supplied) 29 Series BT tank (optional)
CONNECTIONS M C.H. flow R C.H. return G Gas S3 Condensation drain C System filling M2 Tank flow R3 Tank return
CURVE LOAD LOSSES/CAPACITY BETWEEN THE ATTACKS R3 and M2
FOLW RATE (l/h)
LOAD LOSSES (mbar)
R
S3
23
7
5
2
21
6
4
14
1
17
15
G
22
19
12
8
9
13
M2
M
10
11
16
CR3
20
18
3
29
800
700
600
500
400
300
PERDITE DI CARICO TRA
GLI ATTACCHI R3 e M2 (mbar)
200
100
1000
60 BFR
PO RTATA (l/h)
100 BFR
400035003000250020001500
4500
5000
Planet Dewy 60-100 BFR
5500
133
IT
ES
FR
BE
GB
RUS
RO
4.1 GAS VALVE
The boiler “60 BFR” is equipped stan­dard with the SIT 848 SIGMA gas valve. The boiler “100 BFR” is equipped standard with the DUNGS GB-GD 057 gas valve (fig. 16).
4 USE AND MAINTENANCE
Fig. 16
SIT 848 SIGMA DUNGS GB-GD 057
3.8 “PLANET DEWY 100 BFR” WITH KIT (CODE 8101523) AND "BT" BOILER (optional)
Fig. 15/b
KEY
1 Gas valve 2 Condensation drain siphon 3 Boiler pump (not supplied) 4 Fan 5 Heating probe (SM) 6 Safety thermostat 95°C 7 Exhaust thermostat
8 Primary exchanger 10 Differential pressure switch 11 Water pressure transducer 12 Air relief valve 13 Circulation pump 14 Drain plug 15 Gas cock (not supplied) 16 Non return valve 17 4-BAR safety valve 18 Non return valve (not supplied) 19 Hydraulic compensator (supplied in the kit)
20 Drain tap (not supplied) 21 Expansion vessel 8 liter (supplied in the kit) 22 Air relief valve (not supplied) 23 Oblique filter (not supplied) 29 Series BT tank (optional)
CURVE LOAD LOSSES/CAPACITY BETWEEN THE ATTACKS R3 and M2
FOLW RATE (l/h)
LOAD LOSSES (mbar)
CONNECTIONS M C.H. flow R C.H. return G Gas S3 Condensation drain C System filling M2 Tank flow R3 Tank return
KEY 1 Upstream pressure test point 2 Intermediate pressure test point 3 Air signal intake 4 Downstream pressure test point 5 Shutter
6 OFF-SET
7
5
6
8
12
4
11
R3
S3
1
2
10
15
17
13
14 16
G
18
3
21
29
22
M2
19
23
R
M
20
800
700
600
500
400
300
PERDITE DI CARICO TRA
GLI ATTACCHI R3 e M2 (mbar)
200
100
1000
60 BFR
100 BFR
PO RTATA (l/h)
4500
400035003000250020001500
5000
Planet Dewy 60-100 BFR
5500
4
3
2
1
5
6
5
1
6
134
IT
ES
FR
BE
GB
RUS
RO
p air” ADJUSTMENT
To measure “p air” simply con-
nect the differential pressure gauge, equipped with a decimal scale in mm H2O or Pascal, to the positive and negative sockets on the air pressure switch
(Drawing
1)
.
Operating sequence:
1) Rotate the module heating
power adjustment trimmer clockwise to the limit
(B –
Drawing 2)
; fan on maximum.
2) Find the “max ∆p air” values in
the table, using the fan board “MAX” trimmer
(Drawing 3)
:
Max. p
air
(mm H2O)
3)
Rotate the module heating power adjustment trimmer counter-clockwise to the limit
(B
– Drawing 2)
; fan on minimum.
4) Find the “min ∆p air” values in
the table, using the fan board “MIN” trimmer
(Drawing 3)
:
Min. p
air
(mm H2O)
p air-gas” ADJUSTMENT
To measure “p air-gas” simply
connect the positive socket on the differential pressure gauge to the downstream pressure fixture and the negative socket to the air pressure switch
(Drawing 4)
.
Gas pressure is always adjusted with the fan on minimum.
Operating sequence:
1)
Rotate the module heating power adjustment trimmer counter-clockwise to the limit
(B – Drawing 5)
; fan on
minimum.
2) Completely unscrew the valve gas shutter
(1 – Drawing 6)
.
Single modules are calibrated in heating position.
Pressostato aria
60 kW
100 kW
1
2
60 kW
100 kW
2
1
After calibrations, check the CO2 values with a combustion analyser. If they deviate more than 0.2 from the table values, the following corrections must be made:
– To correct CO2 to the “MIN” power, use the OFF-SET screw
(2 – Drawing 6)
.
– To correct CO2 to the “MAX” power, use the shutter
(1 – Drawing 6)
.
Drawing 6
Single module 60 kW 100 kW
G20 60.0 ±2 65.0 ±2 G31 63.0 ±2 70.0 ±2
Single module 60 kW 100 kW
G20 5.8 ±0,2 6.5 ±0,2 G31 10.9 ±0,2 7.0 ±0,2
B
Drawing 5
3) Use the gas valve OFF-SET adjustment screw
(2 – Drawing 6)
and
find the “p air-gas” value in the table.
Shutter open (mm H2O)
4) Use the shutter
(1 – Drawing 6)
and find the “p air-gas” value in
the table:
Adjusted shutter (mm H
2O)
Single module 60 kW 100 kW
G20 4.2 ±0,1 5.2 ±0,1 G31 9.2 ±0,1 6.5 ±0,1
Single module 60 kW 100 kW
G20 3.8 ±0,1 4.3 ±0,1 G31 8.7 ±0,1 4.6 ±0,1
CO
2
Methane (G20) Propane (G31)
“MIN” Power 9.0 ±0,2 10.0 ±0,2 “MAX” Power 9.0 ±0,2 10.0 ±0,2
Pressostato aria
B
Drawing 2
Drawing 1
Air pressure switch
Drawing 3
Air pressure switch
Drawing 4
p air”
min/max
adjustment
GAS CONVERSION
– Close the gas cock. – Replace the injector (pos. 30)
and the relevant gasket (pos.
45).
Cut the specified resistance on the fan control board.
– Test for soundness all the gas
connections using soapy water or appropriate products. DO NOT USE NAKED FLAMES.
– Stick onto the casing panel the
plate showing the relevant fee­ding gas.
– Proceed with air and gas cali-
bration as described below.
30
45
GB - 04/08
4.2 BOILER CALIBRATION
Fig. 18
135
IT
ES
FR
BE
GB
RUS
RO
4.3 SHELL REMOVAL
For easy boiler maintenance the shell can be completely removed by fol­lowing these instructions (fig. 19):
- Pull the front panel forward to unhook it from the pegs on the sides.
- Unscrew the two screws that secu­re the instrument panel to the sides
- Unscrew the four screws that secu­re the side to the instrument panel support.
- Push the sides upwards sliding them off the frame hooks.
4.4 CLEANING AND
MAINTENANCE
During maintenance operations the authorised technician must check that the condensate trap is full of water (this is of particular importan­ce if the boiler has been out of use for some time). Filling is done via the spe­cial opening (fig. 20).
4.4.1 Chimney sweep function
To check single module combustion, rotate the selector to position ( ) until the yellow led ( ) starts to blink (fig. 21). At this time the module will start to heat at maximum power and turn off at 80°C, restarting at 70°C.
Before starting the chimney sweep function, make sure the radiator val­ves are open.
After checking combustion, turn OFF the module by rotating the selector to (OFF); return the selector to the requi­red function.
ATTENTION: After about 15 minutes the chimney sweep function automa­tically deactivates.
Fig. 19
KEY 1 Screw 2 Frame 3 Left side 4 Right side 5 Front panel
Fig. 21
FLASHING YELLOW LED
Fig. 20
SPIA GIALLA INTERMITTENTE
136
IT
ES
FR
BE
GB
RUS
RO
BOILER IGNITION (fig. 1)
Open the gas tap, lower the control cover and turn on the boiler by rota­ting the selector knob to winter ( ). The green led ( ) turn on to indica­te that power is on. The boiler, once the temperature set on the potentio­meter is reached, will start automa­tic operations to provide the system with the required power.
BOILER SHUTDOWN (fig. 1)
To turn OFF the boiler, turn the selec­tor knob to (OFF). For prolonged periods of disuse, disconnect the power supply, close the gas tap and, in the event of low tempe­ratures, empty the boiler and hydraulic system to prevent pipes from bursting due to frozen water.
TEMPERATURE ADJUSTMENT (WITHOUT LOGICA)
(fig. 2)
- Heating temperature is adjusted using the heating knob ( ). The set temperature is indicated on the red led scale from 35 - 80°C and the yel­low heating led ( ) turns on simulta­neously. If the water return tempera­ture is lower than about 55° C, com­bustion product condensates further increasing heat exchange efficiency.
GAS CONVERSION
Should it be necessary to convert the appliance to a different gas from the
WARNINGS
– In case of fault and/or incorrect equipment operation, turn the boiler off. Contact an authorised technician.
– The installation of the boiler and any servicing or maintenance job must be carried out by qualified personnel. Under
no circumstances, the devices sealed by the manufacturer can be tampered with.
– Any ventilation or air intake grills to the room where the boiler is installed must be kept open and unobstructed.
LIGHTING AND OPERATION
Fig. 1
Fig. 2
USER INSTRUCTIONS
OPEN
GREEN LED
RED LED YELLOW LED
APRE
SPIA VERDE
SPIA GIALLASPIA ROSSA
137
IT
ES
FR
BE
GB
RUS
RO
one for which the boiler has been equipped, approach the technical staff.
CLEANING AND MAINTENANCE
Preventive maintenance and checking of the efficient operation of the equipment and safety devices
must be carried out exclusively by the authorized technical staff. Should any component require repla­cement, only manufacturers original parts must be used.
MALFUNCTIONS
Ignition lock (fig. 3)
If the burner does not light the red led ( ) turns on. To attempt ignition again, rotate the selector knob to ( ) and release it immediately after returning it to winter operations ( ).
If the problem persists, contact a authorised engineer .
Insufficient water pressure (fig. 4)
If the “0.5 bar” red light blinks, the boiler does not work. To restore operations, fill the system until the green “1 bar” led turns on. If all leds are off, request an authorised engineer.
Safety/exhaust thermostat
triggered (fig. 5) If the safety/exhaust thermostat triggers the red “35°C” led blinks. To attempt ignition again, rotate the selector knob to ( ) and release it immediately after returning it to winter operations ( ).
If the problem persists, contact an authorised engineer.
Other faults (fig. 6)
When one of the red “40-80°C” leds blinks, turn off the boiler and attempt ignition again. This opera­tion can be repeated 2-3 times at most, in the event of failure, request an authorised engineer.
Fig. 6
Fig. 3
Fig. 4
SPIA ROSSA INTERMITTENTE IN CONDIZIONE DI SICUREZZA
Fig. 5
RED LED
FLASHING RED LED
FLASHING RED LED
IN SAFETY CONDITION
FLASHING RED LED
SPIA ROSSA
SPIA ROSSA INTERMITTENTE
SPIA ROSSA INTERMITTENTE
138
IT
ES
FR
BE
GB
RUS
RO
When the boiler is connected to the “Logi­ca Remote Control” regulator, the selector CR/OFF/SUM/WIN/UNBLOCK must be placed in the position ( ); the knobs of the hot-water service heating potentiometers do not have any effect and all of the func­tions will be managed by the regulator (fig.
7). If the “Logica Remote Control” breaks
down, the boiler will function by placing the
selector on the ( o ), position, obviou­sly without consequent control of the room temperature. Inside the cover should be the Operating instructions (Fig. 8). Each programming or modification is displayed and confirmed on the display (fig. 9).
LOGICA REMOTE CONTROL
KEY 1 Display 2 Info button 3 Operating mode button: automatic operation 4 Operating mode button: manual operation 5 Operating mode button: availability 6 Cover with instruction compartment 7 Temperature knob 8 Presence button
Fig. 8
KEY
1 Display, time 2 Heating programme 3 Unit (%/C°) 4 Presence button display 5 External temperature 6 Outside temperature (if sensor fitted) 7 Holiday function 8 Operating mode
9 Line number/day 10 Burner on 11 Heating function 12 Domestic hot water/temperature/D.H.W. load
Fig. 9
Fig. 7
“PLANET DEWY 60-100 BFR” BOILER INSTALLATION IN SEQUENCE/CASCADE
WHEN THE BOILER IS CONNECTED TO REGULATOR RVA 47.320 IN SEQUENCE/CASCADE INSTALLA­TIONS, ALL BOILERS IN THE HEATING UNIT MUST HAVE THEIR “CR/OFF/INV/RELEASE” SELECTORS POSITIONED AS INDICATED IN FIG. 7. THE HEATING POTENTIOMETER AND WATER KNOB NO LONGER HAS ANY CONTROL AND ALL FUNC­TIONS WILL BE CONTROLLED BY THE TVA 47.320 REGULATOR.
1
2
3
4
5
6
7
8
139
IT
ES
FR
BE
GB
RUS
RO
The fixed temperature can be adjusted with the control knob.
Before adjusting it again, however, allow the temperature to stabilise first.
Note: With the temperature knob you can only adjust the fixed temperature, the reduced tem-
perature remains the same.
Adjusting the temperature
If you turn the knob towards the + sign, the fixed temperature is increased by about 1 °C for every notch.
If you turn the knob towards the - sign, the fixed temperature is decreased by about 1 °C for every notch.
Ensure that the radiators in the room with the Logica do not have thermostatic valves, and are not turned off.
For every operation of the Info key the fol­lowing list of items, one after the other, are displayed. The thermo-feeler continues to function independently of the display.
Day, hour, room temperature
External temperature*
Hot-water service temperature*
* Only with outside sensor fitted.
Info key
(reference key grey colour)
The operating mode desired is selected by pressing the relative key with the correspon­ding symbol. The choice is displayed with the symbol
Automatic functioning: the heating functions automatically according to the hea­ting programme entered. The programme may be excluded for brief periods with the on-line key.
Manual functioning: the heating functions manually according to the choice made with the on-line key.
Availability: the heating is deactivated.
Selection of the operating mode
(reference keys grey colour)
ACTIVATING
During functioning the lid of the regulator must be closed.
140
IT
ES
FR
BE
GB
RUS
RO
If the rooms remain unused for a long period of time, the temperatu­re can be reduced with the on-line key, in this way saving energy. When the rooms are occupied again, press the on-line key to re-heat them. The current choice is displayed on the display:
On-line key
Fixed temperature heating
Reduced temperature heating
NOTE:
In automatic mode, the apparatus switches from the fixed temperature to the reduced tem­perature according to the time programme. The manual switching of the temperature is done manually with the on-line key.
Temperature regulation
Fixed temperature: temperature when the rooms are occupied (basic setting)
Reduced temperature: temperature during periods of absence or night
Hot-water service temperature: – desired temperature of hot-water service – comfort temperature of the hot-water service
(with storage capacity boiler unit)
Reduced temperature of hot-water service (with storage capacity boiler unit): temperature desired for hot-water service at reduced level. To have access to the “reduced hot-water service temperature” parameter, press the and keys at the same time for at least 5 seconds and then go along the entered lines with the key until parameter 61 is reached. Regulate the value with and
.
Before proceeding with the adjustment in the temperature on the regulator, the thermosta­tic valves, which may be present, have to be regulated to the desired temperature.
1
2
3
61
PROGRAMMING
To enter the programming mode the flap on the control must be open.
As soon as the cover is open, the display and the key functions are switched on. The number in the square represents the programme lines that may selected with the arrow keys.
You can set or display the following values:
• Temperatures up to
• Heating programme up to
• Day of the week and hour up to
• Current values up to
• Vacation period
• Return to the default values
1
3
4
11
12
14
15
17 18 19
If the control is in the manual mode , If the control is in the automatic mode the control will revert automatically at the next change of the heating programme.
Programme line
Value
Value adjustment keys
Programme line selector
141
IT
ES
FR
BE
GB
RUS
RO
– Programme for hot-water service
(with storage capacity boiler unit)
Select the days that correspond with the heating phase. 1= Monday, ... 7 = Sunday/8 = hot-water service programme
Start of phase 1: Start of first comfort period.
End phase 1: End of first comfor t period.
Start phase 2: Start of second comfor t period.
End phase 2: End of second comfort period.
Start phase 3: Start of third comfort period.
End phase 3: End of third comfort period.
Copying of the daily programme
By pressing this key it is possible to repeat the current heating programme for the next day.
By pressing this key it is possible to repeat the current heating programme for the previous day.
As a confirmation the following day is displayed.
4 5 6 7
8
9
10
11
With the Logic Remote Control it is possible to manage the temperature of boiler unit on two levels (a comfort level and one at reduced temperature) in accordance with the programme chosen with parameter 62 (load hot-water service). To have access to the parameter press the and keys for at least 5 seconds and then go along the entered lines with the key until parameter 62 is reached. At this point four different programmes may be selected with o keys, with the following characteristics:
0 = 24 hours/ day - Hot water always available at the temperature set in parameter 3. 1 = standard - Hot water according to the daily heating programme. In the comfort periods
of the heating the temperature of the boiler unit is regulated at the value set via para­meter 61.
2 = sservice suspended. 3 = second daily programme (8) - Everyday of the week the temperature of the hot-water ser-
vice is set according to programme B. In this case the programming is one for all the days of the week and three periods of time are available. In the periods of time set, the tem­perature of the boiler unit is controlled via the temperature setting of parameter 61.
Start phase 1: Start time of first comfort period.
End phase 1: End time of first comfor t period
Start phase 2: Start time of second comfor t period.
End phase 2: End time of second comfort period.
Start phase 3: Start time of third comfort period.
End phase 3: End time of third comfort period.
5 6 7
8
9
10
– Heating/hot-water
service programme
With the heating programme it is possible to set the switching times of the temperature for a period of a week. The weekly programme consists of 7 daily programmes. One daily program­me allows 3 phases of heating. Each phase is defined by a star ting time and a finishing time. The n. 8 daily programme is for the hot-water service (if storage unit connected). If a phase is not required, the same starting and finishing time may be entered.
142
IT
ES
FR
BE
GB
RUS
RO
Default values
To take the setting to the default values, press the and keys at the same time for at least 3 seconds. As confirmation a sign will appear on the display.
19
ATTENTION
The values of the following line numbers previously entered will be lost.
• Temperature and time programme to
• Vacation period
1 10
18
Vacation function
To enter the number of days of absence.
In the display the vacation symbol will be shown ( ), on the lef t the day of activa­tion (1 = Monday/7 = Sunday) and on the right the number of vacation days.
18
During the vacation the regulator will be on the availability mode.
When the set days have elapsed, the regulator will go on to the automatic function.
NOTE:
The vacation period may be cancelled by pressing a key of the operating mode.
Current values
Display and setting of the gradient of the heating characteristics curve. When the room temperature set is not reached choose the gradient indicated in point 2.8.3
Display of the current boiler temperature.
Display of the current power of the burner and of the current operating mode ( = = heating/ = hot-water ser vice)
15
16
17
Setting the time
To set the current day of the week (1 = Monday/7 = Sunday)
To set the current hour
To set the current minute Once the hour is completed, the setting of the hour changes.
12 13 14
With and keys the current hour is regulated. Pressing these keys together, the regulation is speeded up in an increasing sense.
68
69
70
192
193
195
Heating sensor fault (SM)
Call an authorised Service Centre.
Insufficient water pressure
Reset operation using the boiler charge valve.
Plant overpressure
Call an authorised Service Centre.
Safety thermostat trips
Call an authorised Service Centre.
Ventilator malfunction
Call an authorised Service Centre.
No communication between the "Logica Remote Control" and the boiler.
Call an authorised Service Centre.
1
0
– Error display
Ignition lock-out
Rotate selector CR/OFF/EST/INV/RESET on the boiler control panel to the release position ()
to reset operation. If the lock-out re-occurs, call an authorised Service Centre.
Safety thermostat trip
Rotate selector CR/OFF/EST/INV/RESET on the boiler control panel to the release position ()
to reset operation. If the lock-out re-occurs, call an authorised Service Centre.
Loading...