sime Planet Dewy 100 BFR User guide

INSTALLER INSTRUCTIONS
CONTENTS
1 DESCRIPTION OF THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 116
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 119
3 CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 130
4 USE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pag. 133
IMPORTANT
– Make sure that there are no liquids or inflammable materials in the immediate vicinity of the boiler.
– Make sure that the electrical connections have been made correctly and that the earth wire is connected to a
good earthing system.
– Open the gas tap and check the soundness of the connections, including that of the burner.
– Make sure that the boiler is set for operation for the type of gas supplied.
– Check that the flue pipe for the outlet of the products of the combustion is unobstructed and has been pro-
perly installed.
– Make sure that any shutoff valves are open.
– Make sure that the system is charged with water and is thoroughly vented.
– Check that the circulating pump is not locked.
– Purge the system, bleeding off the air present in the gas pipe by operating the pressure relief valve on the
gas valve inlet.
FONDERIE SIME S.p.A. of Via Garbo 27 - Legnago (VR) - Italy declares that its hot water boilers, which bear the CE mark under Gas Directive 90/396/CEE and are fitted with a safety thermostat calibrated to a maximum of 110°C, are not subject to application of PED Directive 97/23/CEE as they meet the requirements of article 1 paragraph 3.6 of the Directive.
PLANET DEWY 60/100 BFR - ENGLISH
Planet Dewy 60 BFR:
Gas Council number 41-283-03
Planet Dewy 100 BFR:
Gas Council number 41-283-11
IPX4D
116
IT
ES
FR
BE
GB
RUS
RO
1.1 INTRODUCTION
Boilers (supplied as Class B devices, and can be made room sealed Class C) are pre-mixed condensation heating modules
intended only for heating, designed to work singularly or in sequence/cascade autono­mously. They are designed and constructed to meet European directives 90/396/CEE, 2004/108/CEE,
2006/95/CEE and 92/42/CEE.
Upon request, a control unit for a maxi­mum of four boilers can be supplied for sequence/cascade installation.
1 DESCRIPTION OF THE BOILER
1.2 DIMENSIONS
1.2.1 PLANET DEWY 60 BFR
275
55
12 0
60
12 0
265
17 0
75
230
M
R
C
S3
G
409=
20
870
455
500
865
12 0
15 0
13 5
CS
CA
R3
=
Fig. 1
R C.H. return G 1” (UNI-ISO 228/1) M C.H. flow G 1” (UNI-ISO 228/1) G Gas connection G 3/4” (UNI-ISO 228/1) C Filling system G 1/2” (UNI-ISO 228/1) R3 Tank return G 1” (UNI-ISO 228/1) S3 Condensation outlet ø 25 CA Inlet ø 80 CS Outlet ø 80
ATTENTION: the boiler is supplied as Class B device. To install the boiler as Class C device, remove the termi­nal inserted in the flange before connecting the intake.
203
M
R
G
R3
15 6
S3
65
115
281
120
235
865
500
CS
CA
120 160
135
600
405
18,5
870
=
=
Fig. 1/a
1.2.2 PLANET DEWY 100 BFR
R C.H. return G 1 1/2” (UNI-ISO 228/1) M C.H. flow G 1 1/2” (UNI-ISO 228/1) G Gas connection G 3/4” (UNI-ISO 228/1) R3 Tank return G 1 1/2” (UNI-ISO 228/1) S3 Condensation outlet ø 25 CA Inlet ø 80 CS Outlet ø 80
ATTENTION: the boiler is supplied as Class B device. To install the boiler as Class C device, remove the terminal inserted in the flange before connecting the intake.
117
IT
ES
FR
BE
GB
RUS
RO
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
1.3 MAIN COMPONENTS
1.3.1 PLANET DEWY 60 BFR
Fig. 2
KEY
1 Gas valve 2 Condensation drain siphon 3 Fan 4 Air pressure switch 5 Ignition electrode 6 Detection electrode 7 Ignition transformer 8 Exhaust thermostat
9 Heating probe (SM) 10 Safety thermostat 100°C 11 Differential pressure switch 12 Non return valve 13 Auto Air Vent 14 Pump 15 Control panel 16 Safety valve 4 BAR
1.3.2 PLANET DEWY 100 BFR
1
2
3
4
5
6
7
8
18
13
9
10
11
14
17
15
Fig. 2/a
KEY
1 Gas valve
2 Condensation drain siphon
3 Fan
4 Air pressure switch
5 Ignition electrode
6 Detection electrode
7 Ignition transformer
8 Exhaust thermostat
9 Heating probe (SM) 10 Safety thermostat 100°C 11 Differential pressure switch 13 Auto Air Vent 14 Pump 15 Control panel 17 Water pressure transducer 18 Flue Reducer 100/80
118
IT
ES
FR
BE
GB
RUS
RO
1.4 TECHNICAL FEATURES
PLANET DEWY 60 BFR PLANET DEWY 100 BFR
Heat output nominal (80-60°C) kW (kcal/h) 56.5 (48,600) 94.2 (81,000)
Heat output nominal (50-30°C) kW (kcal/h) 62.0 (53,400) 103.0 (88,600)
Heat output minimum G20 (80-60°C) kW (kcal/h) 17.0 (14,600) 29.3 (25,200)
Heat output minimum G20 (50-30°C) kW (kcal/h) 19.0 (16,300) 32.5 (27,950)
Heat output minimum G31 (80-60°C) kW (kcal/h) 22.6 (19,500) 29.3 (25,200)
Heat output minimum G31 (50-30°C) kW (kcal/h) 25.4 (21,800) 32.5 (27,950)
Nominal heat output kW (kcal/h) 58.0 (49,900) 96.6 (83,100)
Minimum heat output G20 kW (kcal/h) 17.4 (15,000) 30.0 (25,800)
Minimum heat output G31 kW (kcal/h) 23.2 (19,900) 30.0 (25,800)
Efficiency minimum/nominal output (80-60°C) % 97.6 - 97.5 97.7 - 97.5
Efficiency minimum/nominal output (50-30°C) % 109.3 - 107.0 108.8 - 106.4
30% yield (50-30°C) % 109.8 109.0
Termal efficiency (CEE 92/42 directive) ★★★★ ★★★★
Class NOx 5 5
Smokes temperature maximum (80-60°C) °C 70 70
Smokes temperature minimum (80-60°C) °C 62 62
Smokes temperature maximum (50-30°C) °C 50 50
Smokes temperature minimum (50-30°C) °C 32 32
Smokes flow kg/h 97 166
CO2 maximum/minimum G20 % 9.0/9.0 9.0/9.0
CO2 maximum/minimum G31 % 10.0/10.0 10.0/10.0
Maximum pressure exhaust manifold output Pa 110 170
Adsorbed power consumption W 198 330
Electrical protection grade
IPX4D IPX4D
Losses after shutdown at 50°C W/h 134 195
CE certification 1312BP4141 1312BP4141
Category II2H3P II2H3P
Category in FRANCE II2Er3P II2Er3P
Category in BELGIUM I2E(S)B - I3P I2E(S)B - I3P
Type B23-53 / B23P-53P / C13-33-43-53-83 B23-53 / B23P-53P / C13-33-43-53-83
C.H.
Maximum water head bar 4 5
Maximum temperature °C 85 85
Water content boiler l 4.8 8.2
C.H. setting range (D.H.W. setting range) °C 20/80 (30/60) 20/80 (30/60)
GAS PRESSURE END NOZZLES
Gas supply pressure G20/G25 mbar 20/25 20/25
Gas supply pressure G31 mbar 37 37
Nozzles quantity 1 1
Nozzles diameter G20/G25 ø 9,3 11.0
Nozzles diameter G31 ø 6,7 8.4
Gas consumption nominal/minimum G20 m3/h 6.14/1.84 10.22/3.17
Gas consumption nominal/minimum G31 kg/h 4.51/1.80 7.50/2.33
WEIGHT kg 61 92
119
IT
ES
FR
BE
GB
RUS
RO
The boiler must be installed in a fixed loca­tion and only by specialized and qualified firms in compliance with all instructions contained in this manual. Furthermore, the installation must be in accordance with current standards and regulations.
2.1 BOILER ROOM
The boilers can be installed in boiler rooms
whose size and requirements meet current regulations. Furthermore, vents, with surface areas at least 3.000 sq. cm or 5.000 sq. cm for gas with density over 0.8, must be installed in the outer walls for room ventilation.
2.2 INSTALLATION
For single installations, it is also possible to order an optional compensator kit (code
8101520 for the version “60 BFR” and cod. 8101523 for the version “100 BFR”). The kit can be fitted on accumulation boilers with a capacity equivalent to or above 80 liters. For installation for single or sequen­ce/cascade operations, refer to the exam­ple in fig. 3. With control unit code 8096301, supplied by Sime upon request, a maximum of four boilers can be controlled. The control unit kit is supplied with assembly and use instructions.
2 INSTALLATION
45
14 6
R3
500
865
582
88
330
R
M
M2
M2
265
305
455
265
Fig. 3
WARNING:
- In both single and sequence/cascade installation, the heating system must be equipped with a hydraulic separator and safety components.
- When replacing one or more boilers in existing plants, it is advisable to install a heat exchanger to separate the boiler circuit from the secondary circuits. See the pressure curve for the boiler supply shown in figure 14.
M
S3
R
G
Single installation with kit optional code 8101520 for "60 BFR"
Installation in sequence/cascade
R C.H. return M C.H. flow G Gas connection S3 Condensation outlet
Single installation with kit optional code 8101523 for “100 BFR”
M C.H. flow R C.H. return M2 Tank flow R3 Tank return
70
R3
600
235
500
865
301
M2
355
265
M2
663
MR
115
120
IT
ES
FR
BE
GB
RUS
RO
2.3 CONNECTING UP
SYSTEM
To protect the heat system from being damaged by corrosion, incrustation or deposits, after installation it is extremely important to clean the system using suita­ble products such as, for example, Sentinel X300 or X400. Complete instructions are provided with the products but, for further information, you may directly contact SENTINEL PERFORMANCE SOLUTIONS LTD. For long-term protection agains corrosion and deposits, the use of inhibitors such as Sentinel X100 is recommended after clea­ning the system. It is important to check the concentration of the inhibitor after each system modifica­tion and during maintenance following the manufacturer’s instructions (specific tests are available at your dealer). The safety valve drain must be connected to a collection funnel to collect any dischar­ge during interventions.
WARNING: Failure to clean the heat system or add an adequate inhibitor inva­lidates the device’s warranty.
Gas connections must be made in accor­dance with current standards and regula­tions. When dimensioning gas pipes from the meter to the module, both capacity volume (consumption) in m3/h and gas density must be taken into account. The sections of the piping making up the system must be such as to guarantee a supply of gas sufficient to cover the maxi-
mum demand, limiting pressure loss between the gas meter and any apparatus being used to not greater than: – 1.0 mbar for family II gases (natural gas); – 2.0 mbar for family III gases (butane or
propane). A sticker inside the module includes identifi­cation and gas type data specific to the module.
2.3.1 Condensation drain
installation.
A siphoned drain must be connected to the civil drain by a pipe with minimum 5 mm per meter gradient for condensation collec­tion.
Only normal plastic civil drain pipes are suitable to convey condensation to the building's sewer drain.
2.3.2 Gas pipe filter
The gas valve is fitted with a standard filter. This filter is not capable of filtering all impuri­ties and to prevent poor gas valve operation or failure of any gas valve safety feature, it is advisable to fit a suitable filter on the gas supply pipe.
2.5 FILLING THE SYSTEM
Cold system filling pressure must be 1 bar.
The system must be filled slowly so that air bubbles are released through the specific escapes.
2.6 EXHAUST
The boiler is supplied with a 80mm gasket, which must be fitted over the exhaust ter­minal prior to the flue being installed. (11 fig. 4-4/a-4/b).
2.6.1 Type B (fig. 4)
If the inlet is not connected, the boiler should be regarded a Class B device. When installing the boiler in locations where it needs to be protected from water, replace the intake terminal inser ted in the flange with terminal code 8089510. For informa­tion on how to configure the boiler in this mode see figure 4.
The maximum overall length of ø 80 exhaust flues is determined by the load losses of the single accessories installed and should not exceed 16 mmH2O (“60 BFR”) and 28 mmH2O (“100 BFR”).
2.6.2 Type C (figg. 4/a-4/b)
The boiler becomes a Class C device when the intake terminal is removed from the flange and the intake is connected to sepa­rate exhaust ducts (fig. 4) or with coaxial exhaust (fig. 4/b).
ø 80 ACCESSORY LOAD LOSS TABLE
WARNING: Before installing accessories, lubricate the internal part of gaskets with silicon-based pro­ducts. Avoid using oils and greases.
KEY
1
90° MF polypr. curve (6 pcs.) code 8077450
2a
Polypr. extension L.1000 (6 pcs.) code 8077351
2b
Polypr. extension L. 500 (6 pcs.) code. 8077350
3
Hinged tile code 8091300
4
Roof Terminal kit L 1285 code 8091205
5
Polypropylene extension L. 250 with test outlet code 6296513
6
45° MF polypr. curve (6 pcs.) code. 8077451
7
Exhaust terminal code 8089501
8
Internal-external ring nut kit code 8091500
11 Rubber gasket ø 80 (supplied as standard)
Load loss
(mm H2O)
“60 BFR” “100 BFR”
90° MF polypropylene curve
1,30 3,00
45° MF polypropylene curve
0,70 2,00
Polypr. extension L. 1000
0,60 1,20
Polypr. extension L. 500
0,30 0,60
Roof exit terminal
L. 1381 1,20 4,30
Exhaust terminal
1,30 3,60
Polypropylene extension L. 250
0,15 0,30
Type B
Fig. 4
600
2.6.3 Maximum usable length for separate ø 80 flues
The maximum overall length of ø 80 suc­tion and exhaust flues is determined by the load losses of the single accessories installed and should not exceed 16 mmH2O (”60 BFR”) and 28 mmH2 O (”100 BFR”).
When the length of the flues ranges between 11 and 16 mm H20 (“60 BFR”) -
17 and 27 mm H20 (“100 BFR”), it is necessary to adjust trimmer “MAX” on the
fan board and set the “Max. air p” values
provided in paragraph 4.3 in order to ensu­re a correct operation.
2.6.4 Maximum usable length for coaxial ø 80/125 flues
In installations with ø 80/125 coaxial
exhaust, the maximum horizontal length including the 90° curve, should not exceed 5 m (“60 BFR”) and 2 m (“100 BFR”). For roof exits it should not exceed 8 m along vertical for the “60 BFR” and 3 m along vertical for the version “100 BFR”.
In the version “60 BFR” when the length of the flue ranges from 2 to 5 m horizontally and from 4 to 8 m vertically, it is necessary to adjust trimmer “MAX” on the fan board
121
IT
ES
FR
BE
GB
RUS
RO
WARNING:
- Installations with roof exit terminal (4a) and coaxial exhaust (13) require the use of a condensation recovery (12) that has to be connected to the water drain siphon (waste water).
- The installation of the roof exit terminal (4a) requires the removal of the two ø 60 and ø 100 reducers.
- Before fitting the accessories, it is always advisable to lubricate the internal section of the gaskets with silicon products and generally avoid the use of oils and greases.
TABLE OF LOAD LOSSES OF ACCESSORIES
Fig. 4/a
KEY
1 ø 80 curve, 90° MF (6 pcs) code 8077450 2 a ø 80 extension, L. 1000 (6 pcs.) code 8077351 2 b ø 80 extension, L. 500 (6 pcs.) code 8077350 3 Hinged tile, code 8091300 4 Roof exit terminal, L. 1381, code 8091204 4 a Coaxial roof exit terminal, L. 1285 code 8091205 5 ø 80 extension, L. 250, with socket, code 6296513 6 ø 80 curve, 45° MF (6 pcs.), code 8077451 7 ø 80 exhaust terminal, code 8089501
8 Kit with internal/external ring nuts, code 8091500 10 Suction/exhaust fitting, code 8091401 11 ø 80 rubber gasket (supplied with unit) 12 ø 80 condensation recovery, L. 135, code 8092800 13 ø 80/125 coaxial exhaust, L. 885, code 8091210
Load loss (mm H2O)
“60 BFR” “100 BFR”
Suction Exhaust Suction Exhaust
90° MF polypropylene curve 1.00 1.30 2.00 3.00 45° MF polypropylene curve 0.60 0.70 1.50 2.00 Polypropylene extension, L.1000 0.60 0.60 1.20 1.20 Polypropylene extension L.500 0.30 0.30 0.60 0.60 Coaxial roof exit terminal, L.1285 + Fitting (pos. 10) - 4.30 - 14.00 Roof exit terminal L.1381 - 1.20 - 4.30 Exhaust terminal - 1.30 - 3.60 Suction terminal 0.20 - 1.60 -
Polypropylene extension, L. 250 with socket - 0.15 - 0.30 Coaxial exhaust, L.885 + Fitting (pos. 10) - 5.20 - 15.00
Condensation recovery, L.135 2.50 - 5.00 -
Type C (separate ø 80 flues and
coaxial exhaust terminal)
Type C (separate ø 80 flues)
Type C (ø 80/125 coaxial exhaust)
KEY 2 a ø 80/125 extension, L. 1000, code 8096171 2 b ø 80/125 extension, L. 500, code 8096170 3 Hinged tile, code 8091300 4 a Coaxial roof exit terminal, L. 1285, code 8091205 10 Suction/exhaust fitting with test outlet, code 8091401 11 ø 80 rubber gasket (supplied with unit) 12 ø 80 condensation recovery, L. 135, code 8092800 13 ø 80/125 coaxial exhaust, L. 885, code 8091210 14 a 90° curve, ø80/125, code 8095870 14 b 45° cur ve, ø80/125, code 8095970
Fig. 4/b
Model H (m) L (m)
60 BFR 85
100 BFR 32
NOTES:
- Installation requires the use of a condensation recovery (12) that must be connected to a water drain siphon (waste water).
- The installation of the coaxial roof exit terminal (4a) requires the removal of the two ø60 and ø100 reducers.
- Before fitting the accessories, it is always advisable to lubricate the internal section of the gaskets with silicon products and generally avoid the use of oils and greases.
- Horizontal terminals must be LEVEL
WARNING: – In the versions “60 BFR” he
insertion of a 90° additional curve reduces the available length by 2 meters end the insertion of a 45° additional curve reduces the available length by 1 meter.
– In the versions “100 BFR” inse-
rimenti of additional curves are not admitted.
122
IT
ES
FR
BE
GB
RUS
RO
and set the “Max. air p” values provided in
paragraph 4.2 in order to ensure a correct operation. In the version “100 BFR” for all pipe lengths it is necessary to adjust trimmer “MAX” on the fan board and set the “Max.
air p” values provided in paragraph 4.3 in
order to ensure a correct operation.
2.6.5 Positioning the outlet terminals
The outlet terminals for forced-draught
appliances may be located in the external perimeter walls of the building.
To provide some indications of possible solu­tions, Table 2 gives the minimum distances to be observed, with reference to the type of building shown in fig. 5.
123
IT
ES
FR
BE
GB
RUS
RO
2.7 ELECTRICAL CONNECTION
The boiler is supplied with an electric cable. Should this require replacement, it must be purchased exclusively from SIME. The electric power supply to the boiler must be 230V - 50Hz single-phase through a fused main switch, with at least 3 mm spa­cing between contacts. Respect the L and N polarities and the earth connection.
NOTE: SIME declines all responsibility for injury or damage to persons, animals or property, resulting from the failure to pro­vide for proper earthing of the appliance.
2.7.1 Room stat connection (fig. 8 pos. A)
To gain access to the electronic board con­nector (3), remove the control panel cover and connect the room stat to the terminals TA after having removed the jumper. The thermostat or timer-thermostat,
recommended for better room temperatu­re control, must be class II as specified by standard EN 60730.1 (clean contact).
WARNING: Applying mains voltage to the terminals of conector (3) will irreparably damage the control board. Make sure that any connections to be made are not carrying mains voltage.
2.7.2 “Logica Remote Control” connection (fig. 8 pos. B)
The electrical plant must comply with local standards and all cables must comply with low safety voltage requirements of EN
60730. For lengths up to 25 m, use cables
of section 0.25 mm2, for longer lengths up to 50 m use cables of section 0.5 mm
2
. First of all, assemble and wire the socket (2), then insert the equipment which will start-up as soon as it receives current. To gain access to connector (3) remove the control panel cover and connect the climate
regulator to terminals CR.
WARNING: External voltage must not be connected to terminals 1-2-3-4 of the "Logica Remote Control". A telephone remote switch with a zero potential con­tact or a window contact can be connected to terminals 3-4.
Equipment for the checking of civil plants via a telephone line includes the model TEL 30.4 LANDIS & STAEFA.
2.7.3 External temperature
sensor connection (fig. 8 pos. C)
The cables must comply with low safety vol­tage requirements of EN 60730. For lengths up to 25 m, use cables of sec­tion 0.25 mm2, for longer lengths up to 50 m use cables of section 0.5 mm
2
. To gain access to boiler connector (3) remo­ve the control panel cover and connect the external temperature sensor to terminals SE.
–If the terminal discharges into a pathway or passageway check that combustion products will not cause nuisance
and that the terminal will not obstruct the passageway.
–Where the lowest part of the terminal is fitted less than 2 m (78 in) above ground, above a balcony or above a flat
roof to which people have access, the terminal MUST be protected by a purpose designed guard. Terminal guards are available from Quinnell, Barrett, and Quinnell, Old Kent Road, London. State model C2, (G.C. Part No 382946).
–Where the terminal is fitted within 850 mm (34 in) of a plastic or painted gutter, or 450 mm (18 in) of painted
eaves, an aluminium shield at least 1,500 mm (59 in) long must be fitted to the underside of the painted surface. –The air inlet/outlet flue duct MUST NOT be closer than 25 mm (1 in) to combustible material. –In certain weather conditions the terminal may emit a plume of steam. This is normal but positions where this would
cause a nuisance should be avoided.
Terminal position Minimum spacing A Directly below an openable window, air vent
or any other ventilation opening 300 mm 12 in
B Below guttering, drain pipes or soil pipes 75 mm 3 in C/D Below eaves, balconies or carport roof 200 mm 8 in E From vertical drain pipes or soil pipes 75 mm 3 in F From internal or external corners 300 mm 12 in G Above adjacent ground, roof or balcony level 300 mm 12 in H From a boundary or surface facing the boiler 600 mm 24 in I From a terminal facing the terminal 1,200 mm 48 in J From an opening in the carport
(eg door, window into dwelling) 1,200 mm 48 in
K Vertically from a terminal on the same wall 1,500 mm 60 in L Horizontally from a terminal on the same wall 300 mm 12 in M Horizontally from a vertical terminal to a wall 300 mm 12 in N Horizontally from an openable window or other opening 300 mm 12 in P Above an openable window or other opening 300 mm 12 in
TABLE 2
Fig. 5
Loading...
+ 19 hidden pages