Sime Format 25/60 OF, Format 30/60 BF, Format 25/60 BF Installer's Instructions

CONTENTS
1 DESCRIPTION OF THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 73
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 76
3 CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 84
4 USE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 87
INSTALLER INSTRUCTIONS
IMPORTANT
– Make sure that there are no liquids or inflammable materials in the immediate vicinity of the boiler.
– Make sure that the electrical connections have been made correctly and that the ear th wire is connected to a
good earthing system.
– Open the gas tap and check the soundness of the connections, including that of the burner.
– Make sure that the boiler is set for operation for the type of gas supplied.
– Check that the flue pipe for the outlet of the products of the combustion is unobstructed and has been pro-
perly installed.
– Make sure that any shutoff valves are open.
– Make sure that the system is charged with water and is thoroughly vented.
Check that the circulating pump is not locked (CAUTION: Remember to release the pump coupled with the control
panel, if necessary, to protect the electronic control card).
– Purge the system, bleeding off the air present in the gas pipe by operating the pressure relief valve on the gas
valve inlet.
FORMAT 25-30/60
ENGLISH
FONDERIE SIME S.p.A. of Via Garbo 27 - Legnago (VR) - Italy declares that its hot water boilers, which bear the CE mark under
Gas Directive 90/396/CEE and are fitted with a safety thermostat calibrated to a maximum of 110°C, are not subject to appli­cation of PED Directive 97/23/CEE as they meet the requirements of article 1 paragraph 3.6 of the Directive.
1.1 INTRODUCTION
The “FORMAT” wall hung boilers with D.H.W. storage tank allow for a multiple number of requests to be met thanks to the abundance of available water which the capacious tank unit makes possible. They comply with the European directives 90/396/EEC, 89/336/EEC, 73/23/EEC,
92/42/EEC and the European norms EN 483 - EN 625. They may be fuelled by natural gas (metha­ne) and butane gas (G30) or propane (G31). In this manual you will find the instructions relative to the following boiler models:
“FORMAT 25/60 OF”
with electronic ignition and modulation,
open chamber, natural draught.
“FORMAT 25/60 BF - 30/60 BF”
with electronic ignition and modulation, room sealed, forced draught.
Follow the instructions given in this manual for the correct installation and perfect func­tioning of the appliance.
73
1 DESCRIPTION OF THE BOILER
1.2 DIMENSIONS
1.2.1 “25/60 OF” model
600
13 5
D
865
225
110
495
782
460
=
=
25
12 5
80 70 70 70 107
EUCMRG
63
Fig. 1
600
10 5
865
235
110
495
782
460
=
=
25
12 5 80 7 0 70 7 0 10 7
E
U
CMRG
ø100/60
910
63
Fig. 1/a
1.2.2 “25/60 BF - 30/60 BF” models
CONNECTIONS R C.H. return 3/4” M C.H. flow 3/4” G Gas connection 3/4” E D.H.W. inlet 1/2” U D.H.W. outlet 1/2” C Re-circulation 1/2”
CONNECTIONS R C.H. return 3/4” M C.H. flow 3/4” G Gas connection 3/4”
E D.H.W. inlet 1/2” U D.H.W. outlet 1/2” C Re-circulation 1/2”
25/60 OF
D ø mm 130
74
1.3 TECHNICAL FEATURES
(1) Flow calculated with a fixed temperature on the D.H.W. potentiometer of 60 °C for a maximum period of 10 minutes (2) The gas consumptions refers to the calorific value at standard conditions at 15°C - 1013 mbar (3) Dif ferential measure between the pressure upstream of the gas valve and the depr ession in the sealed room
25/60 OF 25/60 BF 30/60 BF
Heat output
Nominal kW 8,4 ÷ 23,2 9,3 ÷ 25,0 11,6 ÷ 29,5
kcal/h 7.200 ÷ 20.000 8.000 ÷ 21.500 10.000 ÷ 25.400
Minimum kW 8,4 9,3 11,6
kcal/h 7.200 8.000 10.000
D.H.W. heat output
Nominal kW 23,2 25,0 29,5
Heat input
Nominal kW 10,8 ÷ 25,8 10,8 ÷ 26,7 13,5 ÷ 31,6
Minimum kW 10,8 10,8 13,5
Water content l 445
Adsorbed power consumption W 105 165 180
Electrical protection grade
IP X4D IP X4D IP X4D
Maximum water head bar 3 3 3
Maximum temperature °C 85 85 85
Expansion vessel
Water content/Preloading pressure l/bar 8/1 8/1 8/1
C.H. setting range °C 40÷80 40÷80 40÷80
D.H.W. setting range ° C 10 ÷6 0 10 ÷6 0 10 ÷6 0
D.H.W. production
Tank capacity l 60 60 60
Continuous D.H.W. flow rate at ∆t 30°C l/h 684 684 774
Specific D.H.W. flow rate EN 625
(1)
l/min 14,5 14,5 16,1
D.H.W. maximum water head bar 7 7 7
Recovery time from 25°C to 55°C min 4’ 30” 4’ 30” 4’
D.H.W. expansion vessel l 2,5 2,5 2,5
Smoke temperature °C 110 123 123
Smoke flow gr/s 21,0 17,0 20,0
Category II2H3+ II2H3+ II2H3+
Type B11BS
C12 - C32 - C42 - C52 C12 - C32 - C42 - C52
Weight kg 74 82 82
Main gas nozzles
Quantity 13 13 15
Methane ø mm 1,30 1,30 1,30
G30 - G31 ø mm 0,75 0,76 0,76
Gas flow
(2)
Methane m3st/h 2,73 2,83 3,34
Butane (G30) kg/h 1,99 2,06 2,44
Propane (G31) kg/h 1,96 2,03 2,40
Gas burner pressure
Methane mbar 1,8÷9,7 1,9÷10,8
(3)
1,7÷11,3
(3)
Butane (G30) mbar 4,7÷27,4 4,7÷28,4
(3)
4,7÷28,1
(3)
Propane (G31) mbar 6,3÷35,3 4,7÷35,3
(3)
4,7÷35,9
(3)
Gas supply pressure
Methane mbar 20 20 20
Butane (G30) mbar 30 30 30
Propane (G31) mbar 37 37 37
75
7
1
6
24
2
3
4
18
15
8
28
9
19
20
16
13
14
27
12
22
26
21
17
23
5
25
11
8
28
10
14
G
R
M
C
U
E
1.4 FUNCTIONAL DIAGRAM
KEY
1 Fan (“25/60 BF - 30/60 BF” versions) 2 Water-gas exchanger 3 Combustion chamber 4 Gas valve 5 D.H.W. tank 6 Heating sensor 7 Safety stat 100°C 8 Air vent valve
9 C.H. pump 10 D.H.W. pump 11 Expansion vessel 12 D.H.W. safety valve 13 Safety valve 14 Boiler drain 15 Water pressure switch 16 Automatic by-pass 17 D.H.W. expansion vessel 18 Gas cock (optional) 19 C.H. return cock (optional) 20 C.H. flow cock (optional) 21 D.H.W. cock (optional) 22 D.H.W. drain cock 23 D.H.W. sensor (SB) 24 Limit st at 80°C 25 Magnesium anode 26 Fixing jig (optional) 27 Filling cock 28 Non return valve
1.5 MAIN COMPONENTS
17
16
15
14
13
12
11
1
2
3
4
5
6
7
8
9
10
Fig. 3
KEY
1 Control panel 2 Gas valve 3 C.H. pump 4 Non return valve 5 Burner 6 Water pressure switch
7 Water-gas exchanger 8 Limit stat 80°C 9 Fan (“BF” version)
Smoke stat (“OF” version)
10 Smoke pressure switch (“BF” version)
Smoke chamber (“OF” version)
11 Expansion vessel 12 D.H.W. storage tank 13 Safety stat 100 °C 14 Heating sensor (SM) 15 Air vent valve 16 D.H.W. pump
17
16
15
14
12
13
11
1
2
3
4
5
6
7
8
9
10
FORMAT 25/60 OFFORMAT 25/60 BF - 30/60 BF
Fig. 2
The boiler must be installed in a fixed loca­tion and only by specialized and qualified firms in compliance with all instructions contained in this manual. Furthermore, the installation must be in accordance with current standards and regulations.
2.1 VENTILATION OF BOILER ROOM
The “25/60 OF”
version boilers must be installed in adequately ventilated domestic rooms. It is essential that in rooms where the boiler are installed at least as much air can arrive as required by normal combu­stion of the gas consumed by the various appliances. Consequently, it is necessary to make openings in the walls for the air inlet into the rooms. These openings must meet the following requirements:
– have a total free section of at least 6
cm2for every kW of heat input, with a minimum of 100 cm2;
– They must be located as close as possi-
ble to floor level, not prone to obstruc­tion and protected by a grid which does not reduce the effective section required for the passage of air.
The “25/60 BF - 30/60 BF” version boi­lers may instead be installed, without any constraints regarding location or supply of air for combustion, in any domestic rooms.
2.2 BOILER SUPPORT BRACKET
For the mounting of the suppor t bracket of the boiler, which is supplied, observe the fol­lowing instructions (fig. 4): – Fix the bracket to the wall with appro-
priate dowels.
– Check with a spirit level that it is perfec-
tly in horizontal plane.
2.2.1 Fixing jig (optional)
The fixing jig code 8081209 is supplied with an instruction sheet for the fixing.
2.2.2 Fitting the pipe elbows (optional)
To fit the connecting elbows supplied in kit code 8075419, follow the instructions reported in fig. 5.
2.2.3 Fitting isolating valves (optional)
To fit the isolating valves, supplied in kit code 8091807, follow the instructions mentioned in fig. 6.
2.2.4 Replacement wall kit for other makes (optional)
The kit code 8093900 is supplied comple­te with mounting instructions.
2.3 CONNECTING UP SYSTEM
Before proceeding to connect up the boiler, you are recommended to make the air cir­culating in the piping in order to eliminate any foreign bodies that might be detrimen­tal to the operating ef ficiency of the applian­ce. When making the hydraulic connections, make sure that the dimensions indicated in fig. 1 are respected.
The discharge pipe of the safety valve must be connected to a collector funnel for channelling away any discharge if the safety valve goes into action.
The gas connection must be made using seamless steel pipe (Mannesmann type), galvanized and with threaded joints provi­ded with gaskets, excluding three-piece con­nections, except for initial and end connec­tions. Where the piping has to pass through walls, a suitable insulating sleeve must be provided. When sizing gas piping, from the meter to the boiler, take into account both the volume flow rates (consumption) in m3/h and the relative density of the gas in question. The sections of the piping making up the system must be such as to guarantee a supply of gas sufficient to cover the maxi­mum demand, limiting pressure loss between the gas meter and any apparatus being used to not greater than: –
1.0 mbar for family II gases (natural gas);
– 2.0 mbar for family III gases (butane or
propane).
An adhesive data plate is sticked inside the front panel; it contains all the technical data identifying the boiler and the type of gas for which the boiler is arranged.
76
2 INSTALLATION
Fig. 4
KEY
1 Fixing jig 2 Copper pipe 3/4”x18 3 Gasket ø 24/17 4 Gas cock 3/4”MF 5 Elbow 3/4”x 18 6 Gasket ø 18,5/11,5 7 Elbow 1/2”x14 9 Elbow 1/2”x14
Fig. 5
KEY
1 Fixing jig 2 Straight coupling 1/2”x14 3 Gasket ø 18,5/11,5 4 Elbow 1/2”x14 5 D.H.W. cock stub pipe 6 D.H.W. cock 1/2”MF 7 C.H.-D.H.W cock
3/4”MF 8 Gasket ø 24/17 9 Gas cock 3/4”MF
10 Straight coupling 3/4”x18 11 Copper pipe 3/4”x18 12 Straight coupling
3/4”x18 with olive
13 Flow cock:
yellow (“25/60” vers.)
and brown (“30/60” ver s.)
Fig. 6
2.3.1 Filter on the gas pipe
The gas valve is supplied ex factory with an inlet filter, which, however, is not adequate to entrap all the impurities in the gas or in gas main pipes. To prevent malfunctioning of the valve, or in cer tain cases even to cut out the safety device with which the valve is equip­ped, install an adequate filter on the gas pipe.
2.4 CHARACTERISTICS OF FEEDWATER
To prevent lime scale and damage to the tap water exchanger, the water supplied should have a hardness of no more than 20°F. In all cases the water used should be tested and adequate treatment devices should be installed. To prevent lime scale or deposits on the primar y exchanger, the water used to supply the heating circuit should must be treated in accordance with UNI-CTI 8065 standards. It is absolutely essential that the water is to be treated in the following cases: – very extensive system (with high con-
tents of feedwater);
– frequent addition of makeup water into
the system;
– should it be necessary to empty the
system either par tially or totally.
2.5 SYSTEM FILLING
The filling of the boiler and of the system is carried out by pressing the filling cock loca­ted on the bottom of the boiler (fig. 7). The filling pressure of the system cold must be 1 bar. Once the filling has been comple-
ted, close the filling cock.
2.6 FLOW REGULATOR (fig. 7/a)
At the inlet of the hot water a flow regulator can be installed, from 10 l/min (yellow) for the “25/60” version and from 12 l/ min (brown) for the “30/60” version; the regu­lator is supplied in the kit of the connecting taps code 8091805.
2.7 FLUE
The flue for the atmospherical expulsion of the combustion products from natural draught appliances must meet the following requirements: –
Be gas-tight to the combustion products, waterproof and thermally insulated.
Be built of materials suitable for keep resisting to normal mechanical stresses, heat, and the action of combustion pro­ducts and their possible condensates.
– Follow a ver tical path and not present
any throttling throughout its entire length.
– Be adequately insulated to prevent phe-
nomena of condensation or smokes coo­ling, in particular if located outside the building or in unheated ambiences.
– Be set at an adequate distance from
combustible or easily inflammable mate­rial by means of an air gap or suitable insulating material.
– Have beneath the mouth of the first
smoke duct a chamber for collecting solid material and any condensate; the height of the chamber must be at least 500 mm. Access to the chamber must be guaran­teed by means of an opening provided with an air-tight metal door.
– Have a circular, square, or rectangular
internal cross section; in the case of square or rectangular sections, the cor­ners must be rounded off with a radius of not less than 20 mm. However, hydraulically equivalent cross sections are allowed.
– Be equipped with a chimney-pot at the
top, which must be outside the so-called back-flow zone, so as to prevent the for­mation of back-flow, which prevents free discharge of the products of combustion into the atmosphere.
– Be devoid of mechanical means of suc-
tion located at the top of the pipe.
– No overpressure should be present in a
chimney that passes within or close up to inhabited rooms.
2.7.1 Connecting up flue
Fig. 8 refers to the connection of the boiler
“25/60 OF” to the flue or chimney throu­gh smoke ducts. When making the con­nection, in addition to respecting the dimensions given, you are recommended to use gas-tight materials capable of resi­sting over time mechanical stresses and the smokes heat. At any point along the smoke duct, the tem­perature of the combustion products must be higher than the dew point. More than a total of three changes of direction must not be made, including the inlet connection to the chimney/flue. For any changes of direc­tion use only curved pipe lengths.
Fig. 8/a shows some applications of drau­ght terminals that ensure proper expulsion of the combustion products, in case of discharge through the wall.
77
Fig. 8
Fig. 7
Fig. 7/a
CLOSE
Fig. 8/a
2.8 COAXIAL DUCT
“25/60 BF -30/60 BF”
The coaxial inlet and outlet duct ø 60/100 is supplied in a kit code 8084805 complete with mounting instructions.
2.8.1 Diaphragm installation
The diaphragm is supplied together with the “30/60 BF” boiler version. See figure 9 for the positioning.
ATTENTION: Install the diaphragm only when the length of the ø 60/100 coaxial duct is less than 1 m.
2.8.2 Coaxial duct
accessories
The accessories necessary for the realisa­tion of this type of discharge and some of the connecting systems that can be used are shown in fig. 10.
With the elbow supplied in the kit the maximum length of the duct should not be greater than 3 metres.
2.8.3 Positioning the
outlet terminals
The outlet terminals for forced-draught appliances may be located in the external perimeter walls of the building. To provide some indications of possible solu­tions, Table 1 gives the minimum distances to be observed, with reference to the type of building shown in fig. 11.
2.8.4 Roof outlet
coaxial duct
The roof outlet terminal L.1284 cannot be shortened and the positioning of the tile distances must be no less than 600 mm from the discharge terminal outlet (fig. 12). The fittings required for this type of dischar­ge and some of the connecting systems that can be used are shown in fig. 13.
Up to a maximum of three extensions can be added to reach a rectilinear length of
3.7 m. If it proves necessary to provide for
78
KEY
1a-b Coaxial duct kit code 8084802
2 Extension L.815 code 8084800 3 Vertical extension L.584 code 8086900 4 Supplementary 90° elbow code 8085600
TABLE1
Siting of terminal Appliances from 7 t o 35 kW
(distances in mm) A - below openable window 600 B - below ventilation opening 600 C - below eaves 300 D - below balcony (1) 300 E - from adjacent window 400 F - from adjacent ventilation opening 600 G - from horizontal or ver tical soil or drain pipes (2) 300 H - from corner of building 300 I - from recess in building 300 L - from ground level or other treadable surface 2500 M - between two terminals set vertically 1500 N - between two t erminals set horizontally 1000 O - from a surface facing without openings or terminals 2000 P - as above but with openings and terminals 3000
Fig. 11
Fig. 10
1
) Terminals below a practicable balcony must be located in such a way that the total
path of the smoke from its outlet point from the terminal to its outlet point from the external perimeter of the balcony, including the height of possible railings, is not less than 2000 mm.
2) When siting terminals, where materials that may be subject to the action of the combu­stion products are present in the vicinity, e.g., eaves, gutters and downspouts painted or made of plastic material, projecting timberwork, etc., dist ances of not less than 1500 mm must be adopted, unless adequate shielding is provided to guard these materials.
Fig. 9
IMPORTANT: Each additional 90° curve installed reduces the available length by 0.90 metres. Each additional 45° curve installed reduces the available length by 0.45 metres.
two changes of direction in the duct, the maximum length must not be greater than 2 m.
2.9 SEPARATE DUCTS “25/60 BF -30/60 BF”
In the installation it is best to observe the directions requested by the Norms and a few practical considerations: – With direct external suction, when the
duct is than 1 m in length, insulation is recommended in order to avoid, in parti­cularly cold periods, the formation of dew on the outside of the tubing.
– With discharge duct positioned on the
outside of the building, or in cold environ­ments, insulation is necessary to avoid starting failures of the burner. In such cases, a system for the collection of con­densation must organised.
If a segment of the flue passes through a flammable wall, this segment must be insulated with a glass wool pipe insula­tor 30 mm thick, with a density of 50 kg/m
3
.
The maximum total length obtained by summing up the lengths of the suction and discharge tubing is determined by the load losses of the single fittings attached (exclu­ding the splitter) and must not be greater than 8.00 mm H20 (vers. “25/60”) and
9.00 mm H2O (vers. “30/60”). For the load losses of the fittings refer to Table 2.
2.9.1 Fittings separate ducts
A kit code 8093000 (fig. 14) is supplied for
the realisation of this type of discharge. The sector diaphragm that comes with the kit must be used as indicated in fig. 15 according to the maximum load loss
allowed in both ducts. The complete range of the fittings neces­sary for each type of installation is given in fig. 16.
79
KEY 1 Tile with articulated joint 2 Lead panel 3 Collar 4 Locking screw
Fig. 12
Fig. 13
KEY 1 Vertical extension L. 194
with take-off point code 8086903 2 Extension L. 815 code 8084804 3 Tile with articulation joint code 8091300 4 Roof outlet terminal L. 1284 code 8091200 5 Supplementaty 90° elbow code 8085601
Example of allowable installation calculation (“25/60” version) in that the sum of the head losses of the single fittings is less than 8.00 mm H
2
O:
Intake Outlet
7 meter horizontal pipe ø 80 x 0.20 1.40 – 7 meter vertical pipe ø 80 x 0.30 2.10 n° 2 90° elbows ø 80 x 0.30 0.60 – n° 2 90° elbows ø 80 x 0.40 0.80 N° 1 terminal ø 80 0.10 0.30
Total head loss 2.10 + 3.20 = 5.3
mm H2O
With this total head loss, remove the ø 38 baffle from the intake pipe.
TABLE 2
Accessories ø 80 Head loss (
mm H2O)
“25/60” version “30/60” version
Inlet Outlet Roof outlet Inlet Outlet Roof outlet
90° elbow MF 0.30 0.40 0.30 0.50 45° elbow MF 0.20 0.30 0.20 0.40 Extension L. 1000 (horizontal) 0.20 0.30 0.20 0.40 Extension L. 1000 (ver tical) 0.30 0.20 0.30 0.30 Outlet terminal 0.30 0.40 Intake terminal 0.10 0.10 Doubler fitting 0.20 0.30 Roof outlet terminal L. 1390 – 0.50 0.60 Tee condensation outlet 1.00 – 1.10
105
120
150
ø80
4
3
1
2
80
Fig. 14
KEY 1 Sponge-rubber gasket ø125/95 2 Fixing screw 3 Air-smokes flow splitting unit
with take-off point
4 Sectors of diaphragm ø 38
Fig. 15
Fig. 16
KEY 1 Air-smokes flow plitting unit
with take-off point code 8093000 2a 90° elbow MF code 8077404 2b Isolated 90° elbow MF code 8077408 3a Extension L. 1000 code 8077303 3b Isolated extension L. 1000 code 8077306 4 Outlet terminal code 8089501 5 Int.-est. ring kit code 8091500 6 Intake terminal code 8089500 7 45° elbow MF code 8077406 8 Condensation outlet L. 135 code 8092800 9 Locking junction (n. 5) code 8092700
Sectors of diaphragm Total head loss
to remove mm H
2OPa
0 0 ÷ 2 0 ÷ 19,6 2 2 ÷ 3 19,6 ÷ 29,4 4 3 ÷ 4 29,4 ÷ 39,2 6 4 ÷ 5 39,2 ÷ 49,0
Remove diaphragm 5 ÷ 8 49,0 ÷ 78,4
Sectors of diaphragm Total head loss
to remove mm H
2OPa
4 0 ÷ 4 0 ÷ 39,2 5 4 ÷ 5 39,2 ÷ 49,0 6 5 ÷ 6 49,0 ÷ 58,8
Remove diaphragm 6 ÷ 9 58,8 ÷ 88,2
“25/60” version
“30/60” version
SECTOR OF DIAPHRAGM
2.9.2 Roof outlet separate ducts
The roof outlet terminal L. 1390 cannot be shortened and in the positioning of the tile the distance from the discharge outlet of the terminal must not be less than 700 mm (fig. 17). The fittings necessary for this type of discharge and some of the other type of systems that it is possible to use are shown in fig. 18. By utilising the manifold (7 fig. 18) it is possible to have a concentric discharge. In these cases, during assembly, it is neces­sary to get the washer in silicon used on the reduction of the terminal (5 fig. 17) to be substituted with the manifold and place it in the housing of the manifold.
For this type of discharge the sum of the maximum development allowed of the ducts must not be greater than 8.00 mm H2O (vers. “25/60”) - 9.00 mm H2O (vers. “30/60”).
To calculate the load losses of the single fit­tings attached refer to Table 2.
2.10 ELECTRICAL CONNECTION
The boiler is supplied with an electric supply cable, which in case of replacement must be requested from SIME. The supply must be carried out with a monophase voltage of 230V - 50 Hz via a general switch protec­ted by fuses, with a distance between con­tacts of at least 3 mm. Observe the L-N polarities and the earth connection.
NOTE: Device must be connected to an efficient earthding system. SIME declines
any responsibility for damages to persons or objects due to failing to earth the boiler.
2.10.1 Control board (fig. 19)
To access the electrical panel, turn off the power supply and then remove the front panel and the two screws that anchor the control panel to the sides (see point 4.6). The panel will move towards the bottom at an angle that will allow access to the com­ponents. To remove the protection (6) unscrew the fixing screws and with a screw­driver press on the upper splines to detach them from the control panel.
2.10.2 Room stat connection (fig. 19)
In order to have access to the “TA” con- nector, remove the cover (7) of the con­trol panel and electrically connect the room stat to the terminals 10-11 after having removed the existing bridge.
The thermostat or chronothermostat to be used, whose installation allows a bet­ter regulation of the temperature and comfort of the environment, must be class II in compliance with norm EN
60730.1 (clean electrical contact).
81
KEY 1 Tile with articulated joint 2 Lead panel 3 Collar 4 Locking screw 5 Reducing fitting with washer
Fig. 17
Fig. 18
KEY
1 Air-smokes flow splitting unit
with take-off point code 8093000
2 a 90° elbow MF
code 8077404 2 b Isolated 90° elbows MF code 8077408 3 a Extension L. 1000 code 8077303 3 b Isolated extension L. 1000 code 8077306 4 Int.-est. ring kit code 8091500 5 Intake terminal code 8089500 6 Locking junction (n. 5) code 8092700 7 Doubler fitting code 8091400 8 Tile with ar ticulated joint code 8091300 9 Roof outlet terminal L. 1390 code 8091201
10 45° elbow MF code 8077406
11 Condensation outlet L. 135 code 8092800
12 Tee condensation outlet code 8093300
82
2.10.3 Wiring diagram “25/60 OF”
Fig. 20
KEY F1 Fuse (F 1, 6A) TR Transformer 230-24V PI C.H. pump PB D.H.W. pump EV1 Gas valve coil EV2 Gas valve coil TF Smoke stat TL Limit stat 80°C M Modulator PA Water pressure switch C Rotary switch SM Heating sensor (blue) SB D.H.W sensor TA Room stat EAR Ignition/detection electr ode TRA Ignition transformer TS Safety stat 100°C
Note: The room stat or the chronothermostat must be connected to terminals 10-11 of the “TA” connector after having removed the bridge.
12
6
7
5
8
3
4
Fig. 19
KEY 1 Thermometer 2 Time programmer 3 Rotary switch 4 Electronic board 5 Earth faston 6 Instrument protection 7 Room stat cover 8 Room stat connector (TA)
CONNECTOR SPARE PART CODES:
J2 cod. 6278622 J3 cod. 6278639 J5 cod. 6278624 J6 cod. 6278640
J10 cod. 6278641
83
2.10.4 Wiring diagram “25/60 BF -30/60 BF”
Fig. 20/a
KEY F1
Fuse (F 1,6A) TR Transformer 230/24V PI C.H. pump PB D.H.W. pump EV1 Gas valve coil EV2 Gas valve coil V Fan PF Smoke pressure switch TL Limit stat 80 °C M Modulator
PA Water pressure switch C Rotary switch SM Heating sensor (blue) SB D.H.W. sensor TA Room stat EAR Ignition/detection electr ode TRA Ignition transformer TS Safety stat 100°C
Note: The room stat or the chro­nothermostat must be connected
to terminals 10-11 of the “TA” con­nector after having removed the bridge
CONNECTOR SPARE PART CODES:
J2 cod. 6278622 J3 cod. 6278621 J5 cod. 6278625 J6 cod. 6278620
J10 cod. 6278623
3.1 ELECTRONIC BOARD
Made in accordance with the Low Voltage EEC directive 73/23, supplied with 230 Volt; via a transformer it sends 24 Volt to the following components: modulator, C.H. and D.H.W. sensors, gas valve, limit stat, room stat, water pressure switch and time programmer. An automatic and continuous modulating system allows the boiler to adjust the power to the various systems or user demands. The electronic components are guaranteed to work in a temperature range between 0 and +60 °C.
3.1.1 Functioning faults
The leds that show an irregular and/or incorrect functioning of the boiler are shown in fig. 21.
3.1.2 Devices
The electronic board has the following devi­ces (fig. 22):
Trimmer “POT. RISC.” (1)
It regulates the maximum value of hea­ting power. To increase the value turn the trimmer in a clockwise direction and to decrease it turn the trimmer in an anti-clockwise direction.
Trimmer “POT. ACC.” (6)
Trimmer to vary the pressure level (STEP) in the ignition of the gas valve. In accordance with the type of gas for
which the boiler is predisposed, the trim­mer must be regulated so as to provide the burner with a pressure of around 3 mbar for methane gas or 7 mbar for butane (G30) and propane gas (G31). To increase the pressure turn the trim­mer in a clockwise direction, to decrease it turn the trimmer in an anti-clockwise direction. The level of pressure of slow starting is able to be set during the first 3 seconds from the star ting of the burner. After having established the level of
pressure at starting (STEP) according to the type of gas, check that the heating gas pressure is still on the value previou­sly set.
Connector “METANO-GPL” (4)
With the connector disconnected, the boiler is ready to function with METHANE; with the connector connected with GPL.
Connector “ANN. RIT.” (5)
The electronic board is programmed, in heating phase, with a technical pause by
84
3 CHARACTERISTICS
Fig. 22
KEY
1 “Heating Power” trimmer 2 Fuse (F 1,6A) 3 Hot-water service potentiometer 4 Connector “METHANE/GPL”
5 Connector “Delay cancellation” 6 “Start up Power” trimmer 7 Block red led 8 Heating potentiometer 9 Bi-colour led green/orange
10 Connector “TA”
NOTE: To have access to the regulating trimmers (1) and (6) take off the hea­ting potentiometer knob.
Fig. 21
Bicolour green led off in case of no electricity
Bicolour orange led flashing in case of insufficient water pressure
Bicolour orange led flashing - C.H. sensor (SM) fault.
Bicolour green led flashing - in case of interception by the smoke safety device in
the version “25/60 OF”: reinstate the thermostat button to restore functioning.
Green led flashing - fan/pressure switch failure in the vers. “BF”.
Red led - ignition blocked / safety stat interception:
turn the rotary switch in the position
( ) to restore functioning
0
306090
120
bar
°C
034
1
B
A
C
6
1
2
3
5
9
7
6
1
8
4
10
85
the burner of around 90 seconds, both at the beginning when the plant is cold and in subsequent restartings. This is so to avoid startings and swit­ching off with very short intervals, that may in particular be found in plants with high losses. At every restarting, following the period of slow starting, the boiler will position itself for around 1 minute to the mini­mum modulating pressure to then return to the set value of heating pressure. With the insertion of the bridge both the technical pause programmed and the period of functioning at minimum pressu­re in the starting phase will be elimina­ted. In such a case, the time that runs between the switching off and the next starting will be in function of a variance of 5°C, as detected by the heating sen­sor (SM).
ATTENTION: All of the operations descri­bed above must be carried out by authori­sed personnel.
3.2 TEMPERATURE DETECTION SENSORS
In Table 3 the resistance (Ω) values are given. They are obtained by the sensors when the temperature varies.
With the C.H. sensor (SM) interrupted the boiler will not function with both ser­vices. With the D.H.W. sensor (SB) interrupted the boiler functions only with heating.
3.3 ELECTRONIC IGNITION
The ignition and flame sensing are control­led by a single electrode on the burner that guarantees the maximum safety, with a time of intervention of one second for acci­dental switching of f or lack of gas.
3.3.1 Functioning cycle
Turn the rotary switch to summer or winter and note, from the lighting up of the green led, whether electricity is present. We can summarise the manifestations of a failure to start, with consequent activation of the failure signal as follows:
Lack of gas
The ignition electrode continues to spark
for a maximum of 10 seconds, the pilot burner does not start, the apparatus is blocked.
This may occur at the first ignition attempt or after long periods of inactivity with the presence of air in the tubing. May be due to the gas tap being closed or a break in the valve coil, which do not allow opening.
The ignition electrode does not spark.
In the boiler only the gas opening to the burner is noted, after 10 seconds the block signal lights up.
May be due to the fact that the cable of the electrode is interrupted or is not well fixed to the terminal of the ignition tran­sformer. The electrode is ear thed or very worn and needs to be substituted. The electronic board is faulty.
Due to a sudden fall in electricity the burner is immediately arrested, once the electricity is restored, the boiler will automatically restart.
3.4 SMOKE SAFETY DEVICE “25/60 OF”
It is a safety measure against the outflow of smoke into the environment due to ineffi­ciency or a partial clogging up of the flue (9 fig. 3). It acts by blocking the gas valve when the release of smoke into the environment is continuous and in such a quantity as to be dangerous. To restart the boiler, and reacti­vate the button of the thermostat. If the blockage occurs repeatedly a thorough con­trol of the flue will be necessary, making all the modifications and taking all the precau­tions necessary in order for it to be efficient.
3.5 SMOKE PRESSURE SWITCH “25/60 BF -30/60 BF”
The smoke pressure switch with fixed set­tings 4.5-6 mm H2O (vers. “25/60”) and 10-13 mm H2O (vers. “30/60”) is able to guarantee the functioning of the boiler even with suction and discharge tubing at the maximum limit length permitted (10 fig. 3). Impurities and the formation of condensa­tion, most probable during the colder periods of the season, could cause starting failure of the boiler.
3.6 WATER PRESSURE SWITCH
A water pressure switch intercepts, blocking the functioning of the burner when the pressure in the boiler is less than 0.5 bar (6 fig. 3). To restore the functioning of the burner, press on the charging key (fig. 7) and take the pressure to a value between 1-1.2 bar.
3.7 SYSTEM AVAILABLE HEAD
The residual prevalence for the heating plant is represented, according to flow, by the graph in fig. 23.
3.8 TIME PROGRAMMER OPTIONAL (fig. 24)
The control panel allows a time program­mer to be utilised for the management of the heating, supplied on request in the kit code 8092203. For the assembly of the time programmer remove the control panel and the cover for the positioning and, with the panel open, fix the clock to the panel with the screws spe-
TABLE 3
Temperature (° C) Resistance ()
20 12.090 30 8.313 40 5.828 50 4.161 60 3.021 70 2.229 80 1.669
0
600
200
1600
140012001000800600400
PORTATA (l/h)
PREVALENZA RESIDUA (mbar)
500
400
10 0
200
300
25/60
30/60
Format e Planet 25 - 30/60
Fig. 23
FLOW RATE (l/h)
RESIDUAL HEAD (mbar)
cifically supplied. Remove the faston that connects terminal 3 of the rotary switch and insert it in termi­nal 3 of the clock. Complete the connection of the electric clock as indicated in the diagram.
3.9 ELECTRICAL CONNECTION ZONE SYSTEMS
Use a separate electric line to link up the room stats and relative zone valves or
pumps. The connection of the micros or the relay contacts is carried out on termi­nals 10-11 of the “TA” connector of elec­tronic panel after having removed the existing bridge (fig. 25).
86
C
OP
KEY OP Time programmer C Rotary switch
Fig. 24
REMOVE
L
N
TA
TA
1
VZ
R
VZ1
R1
CIRCUITO CON VALVOLE DI ZONA
NOTA: I relé vengono impiegati solo nel caso le valvole di zona siano prive di micro.
CIRCUITO CON POMPE DI ZONA
CR1
CR
Connettore "TA"
10 11
RL
Cavo
pompa
impianto
NOTA: Sostituire la pompa impianto della caldaia con il tronchetto optional cod. 8094001. Collegare il cavo della pompa impianto ad un relè di potenza (RL).
L
N
TA1
CRL
R1
P
TA
R
P1
CR
CR1
LEYENDA TA-TA1 Zone room stat VZ-VZ1 Zone valve R-R1 Zone relay CR-CR1 Relay contact or micro zone valve P-P1 Zone pump RL Power relay CRL Power relay contact
Pump cable
“TA” connector
CIRCUIT WITH ZONE VALVES CIRCUIT WITH ZONE PUMPS
NOTE: Relays are used only if the area valves have no microswitches.
NOTE: Replace the heating pump with the option­al stub pipe, code 8094001. Connect the pump cable to a power relay (RL).
Fig. 25
4.1 D.H.W. PRODUCTION
The preparation of hot water is guaranteed by the tank unit in glass enamelled steel with magnesium anode for the protection of the tank unit and inspection flange for its control and cleaning.
The magnesium anode must be checked annually and substituted when it is worn. If the boiler does not produce hot water, make sure that the air has been released by pressing on the manual outlets after having switched off the main switch.
4.2 GAS VALVE
The boiler is produced with gas valve model SIT 845 SIGMA (fig. 26) and gas valve model HONEYWELL VK 4105M (fig. 27). The gas valve is set at two pressure values: maximum and minimum, that correspond, according to the type of gas, to the values indicated in Table 4. The setting of the gas pressure at minimum and maximum values is carried out by SIME: variations are discouraged. Only in the pas­sing from one type of gas supply (methane) to another (propane) is a change in the working pressure allowed.
Such an operation must be carried out by authorised personnel, or the guarantee will lose validity. Once the change in working pressure has been carried out, seal the regulators.
When the gas pressures are to be reset, this must be done following a set order
first setting the MAXIMUM and then the MINI­MUM.
4.2.1 Maximum and minimum
pressure adjustment SIT 845 SIGMA (fig. 29):
In order to carry out the setting of the maxi­mum pressure proceed in the following way: – Connect the manometer to the down-
stream pressure plug of the gas valve. In the “BF” versions, instead, connect the manometer as shown in fig. 28.
Remove the plastic cap of the modulator (1).
– Place the heating potentiometer knob on
the maximum value.
– Start the boiler by pressing on the four
way switch and the hot water cock.
– Using a ø 10 wrench turn the nut (3) to
find the maximum pressure as shown in Table 4: to reduce the pressure turn the nut anti-clockwise, to increase the pres­sure turn the nut clockwise.
– Turn off and turn on the burner a few
times whilst keeping the hot water tap constantly open to verify that the pressu­re corresponds to the values given in Table 4.
After having regulated the maximum pres­sure, proceed with the setting of the mini­mum pressure:
87
4 USE AND MAINTENANCE
3
4
2
1
5
6
Fig. 26
KEY 1 Modulator 2 EV1-EV2 coils 3 Upstream pressure inlet 4 Downstream pressure inlet 5 VENT
TABLE 4
Burner max. Modulator Burner min. Modulator
Type of gas pressure current pressure current
mbar mA mbar mA
Methane (G20) 10 - 11 130 2 0 Butane (G30) 27 - 28 165 5 0 Propane (G31) 35 - 36 165 6 - 5 0
1
2
4 35
Fig. 27
1
2
3
4
Fig. 28
KEY 1 Modulator 2 EV1-EV2 coils 3 Upstream pressure inlet 4 Downstream pressure inlet 5 VENT
KEY 1 Downstream pressure inlet 2 VENT 3 Sealed chamber 4 Differential manometer
– Disconnect the electric supply of the
modulator.
– With the D.H.W. potentiometer knob on
the maximum value, the hot water cock open and the burner alight, holding the nut (3) blocked, turn the screw (2) to find the minimum pressure value as shown in Table 4: to decrease the pressure turn the nut anti-clockwise and to increase the pressure turn the nut clockwise.
– Turn on and turn of f the burner a few
times whilst keeping the hot water cock constantly open and verify that the pres­sure corresponds to the values fixed.
– Reconnect the electrical supply of the
modulator.
– Replace the plastic cap (1)
4.2.2 Maximum and minimum pressure adjustment HONEYWELL VK 4105M (fig. 30)
To set the maximum pressure, proceed as follows : –
Connect the pressure column to the pres­sure inlet downstream of the gas valve.
– For the “BF” models connect the pressu-
re column as shown in fig. 28.
– Remove the plastic cap on the modula-
tor (1).
– Set the knob of the D.H.W. potentiome-
ter to the maximum value. – Ignite the boiler and open the D.H.W. cock. – Using a ø 9 spanner, turn the nut (3) to
achieve the maximum pressure value
given in
Table 4
: to reduce the pressure, turn the nut counterclockwise; to increa­se the pressure, turn it clockwise.
Operate the main switch a number of times, keeping the D.H.W. cock open all the time, and check that the pressure corre­sponds to the values given in Table 4.
After adjusting maximum pressure, pro­ceed to calibrate minimum pressure: –
Disconnect the electric power supply from the modulator.
With the hot water potentiometer knob set to the maximum, the hot water tap turned on and the burner lit, hold nut (3) locked in place and simulta­neously turn nut (2) using a fixed ø 7
wrench to identify the minimum pres­sure value shown in Table 4: turn the nut anti-clockwise to reduce pressure or clockwise to increase it.
– Turn the boiler on and off repeatedly
while keeping the hot water tap turned on, checking that pressure corresponds to the values shown in Table 4.
– Connect up the power supply to the
modulator again.
– Replace the plastic cap (1).
4.3 ADJUSTMENT OF HEATING OUTPUT
To regulate the heating output, modifying the factory settings whose power value is around 16 kW, it is necessary to work with a screwdriver on the trimmer of the heating power (1 fig. 22). To increase the operating pressure turn the trimmer in a clockwise direction, to decrea­se the pressure turn the trimmer in an anti­clockwise direction. To facilitate the search
for the adjusting of the heating power the diagrams pressure/ heat output for natu­ral gas (methane) and butane or propane gas are available (fig. 31).
4.4 CONVERSION TO ANOTHER GAS
For the functioning with butane (G30) or propane (G31) gas, a kit with that needed for the conversion is supplied. To convert from one gas to another carry out the following operations (fig. 32):
88
3
2
1
Fig. 29
KEY 1 Plastic cap 2 Minimum pressur e
adjusting screws
3 Maximum pressur e
adjusting nut
Fig. 30
KEY 1 Plastic lid 2 Minimum pressur e
regulating nut
3 Maximum pressur e
regulating nut
11
10
9
8
7
6
5
4
3
2
1
8,1 (7.000) 11,6 (10.000) 17,4 (15.000) 23,2 (20.000)
POTENZA TERMICA kW (kcal/h)
PRESSIONE UGELLO mbar
29,0 (25.000)
12
25 30
Fig. 31/a
Pressure/heat output diagram for natural gas (methane)
HEAT OUTPUT kW (kcal/h)
NOZZLE PRESSURE mbar
89
– Close the gas tap – Undo the burner group –
Replace the main nozzles (5) supplied in kit, and placing the copper washer (4); to carry out this operation use a ø 7 wrench.
– Insert the bridge of the ìMETHANE-GPLî
connector of the electronic panel onto the ìGPLî position (4 fig. 22).
For the setting of the values of the maxi­mum gas pressure and the minimum fol­low the indications as specified in point
4.2. Once the operating pressure changes have been carried out seal the regulators.
– The supply pressure must never be
greater than 50 mbar.
– Once the operations have been finished
cover, with the label supplied, the gas
pre-setting data on the data tag.
NOTE: After assembly the sealing capa­city of all the gas connections must be tested, using soapy water and special pro­ducts, and avoiding the use of naked fla­mes. The conversion must be carried out only by authorised personnel.
4.5 DISASSEMBLY OF EXPANSION VESSEL
To disassemble the expansion vessel pro­ceed in the following way: – Make sure that the boiler has been emp-
tied of water
– Unscrew the union that connects the
expansion vessel and the screws that release it from its bracket.
Before refilling the system, make sure that the expansion vessel is pre-loaded to a pres­sure of 0.8÷1 bar.
4.6 REMOVAL THE OUTER CASING
For easy maintenance of the boiler it is pos­sible to completely dismantle the casing fol­lowing these simple instructions (fig. 33): – Pull the front panel (5) fixed with pin clut-
ches forward.
– Unscrew the two screws that fix the con-
trol panel to the shell.
– Remove the side panel (6) by unscrewing
the two screws that fix it to the upper bracket (7) and to the support control panel. Push upwards to free it from the notches in the right side.
20
15
10
5
8,1 (7.000) 11,6 (10.000) 17,4 (15.000) 23,2 (20.000)
POTENZA TERMICA kW (kcal/h)
PRESSIONE UGELLO mbar
25
30
0
29,0 (25.000)
25 30
35
20
15
10
5
8,1 (7.000) 11,6 (10.000) 17,4 (15.000) 23,2 (20.000)
POTENZA TERMICA kW (kcal/h)
PRESSIONE UGELLO mbar
25
30
0
29,0 (25.000)
25 30
Pressure/heat output diagram for propane gas (G31)
Fig. 31/b
Fig. 31/c
4
1
2
5
6
7
3
Fig. 32
KEY 1
Burner manifold 2 Extension 1/2” 3 Lock nut 1/2” 4 Washer ø 6,1 5 Nozzle M6 6 Protection 7 Burners
WARNING: To ensure a perfect seal, always use the washer (4) supplied in the kit when replacing nozzles, even in burner units for which it is not specified.
Pressure/heat output diagram for butane gas (G30)
HEAT OUTPUT kW (kcal/h)
NOZZLE PRESSURE mbar
HEAT OUTPUT kW (kcal/h)
NOZZLE PRESSURE mbar
– Unscrew the four lower screws that fix
the sides to the suppor t control panel and the two screws that fix it to the upper bracket (7). Push the sides (3) and (4) upwards freeing them from the not­ches in the frame (2).
4.7 CLEANING AND MAINTENANCE
Carry out the cleaning of the generator in the following way: – Remove the electricity supply to the boi-
ler and close the gas supply tap.
– Disassembly the casing as described in
point 4.6.
– Disassembly the burner - gas manifold
group (fig. 32).
– Clean direct a stream of air towards the
inner par t of the burner to blow out any dust that has accumulated.
– Then clean the heat exchanger removing
dust and combustion deposits.
– In cleaning the heat exchanger and that
of the burner, chemical products or steel brushes must never be used.
– Make sure that the top perforated part
of the burners is free of encrustations.
– During the assembly and disassembly of
the burner it is recommended that attention be paid to the ignition and detection electrodes.
– Reassemble the parts removed from the
boiler, observing the succession of the
phases. – Check the functioning of the main burner. – After the assembly all the gas connec-
tions must be checked for the seal, using
soapy water or specific products, avoi-
ding the use of naked flames.
Preventive maintenance and checking of efficient operation of equipment and
safety devices must be carried out exclu­sively by authorized technical personnel.
4.7.1 Chimney sweep function
To carry out the verification of combustion in the boiler turn the selector and stop on the position ( ) until the green/ orange led starts to flash intermittently (fig. 34). From that moment the boiler will start func­tioning in heating mode at the maximum power (20,000 - 25,000 kcal/ h), with swit­ching off at 80°C and restarting at 70°C. Before activating the chimney sweep func­tion make sure that the radiator valves or eventual zone valves are open. The test may be carried out also during hot­water service functioning. To do so it is enough, after having activated the chimney sweep function, to take some hot water from one or more cocks. Even in this condition the boiler functions at the maximum temperature always with the pri­mary controlled between 80°C and 70° C. During the entire duration of the testing the hot water taps must remain open. After verifying the combustion the boiler should be switched off by placing the selec­tor on the OFF position; then return the selector to the desired function.
ATTENTION: After about 15 minutes, or once the hot water request has been fulfilled, the chimney sweep function automatically deactivates.
4.8 FAULT FINDING
The burner does not light up and the cir­culator functions.
– Check that the water pressure is on a
value of 1 - 1.2 bar.
– The water pressure switch is faulty and
needs to be replaced.
The main burner does not start either in the hot water or heating drawing.
– Check and eventually replace the water
pressure switch.
– If the smoke stat has intercepted, then
reinstate it.
– Check that the coils of the gas valve are
receiving electricity, check the functio­ning and eventually replace it.
Check the functioning of the limit stat of the smoke pressure switch (vers. “BF”).
– The fan works but at a reduced number
of turns and not activating the smoke manostat, it is necessary to replace it (vers. “BF”).
– Replace the electronic board.
The boiler starts up but after 10 seconds it blocks.
– Check that in the electrical connection
the positions of phase and neutral have been respected.
– The ignition/detection electrode is faulty;
90
2
3
1
4
1
5
1
6
7
Fig. 33
KEY 1 Screws 2 Frame 3 Left side 4 Right side 5 Front panel 6 Side panel 7 Upper bracket
SPIA LAMPEGGIANTE VERDE/ARANCIO
Fig. 34
FLASHING GREEN/ORANGE LED
it must be replaced.
– Replace the electronic board.
The gas valve does not modulate in hea­ting and hot water phases.
– The sensor is interrupted, it needs to be
replaced.
– The winding of the modulator is interrup-
ted.
– Check that the electricity to the modula-
tor is in compliance with the specifica­tions.
– Substitute the panel as it is faulty.
In the exchanger of the boiler there are noises and sparking.
– Check that the circulator is not blocked,
eventually unblock it.
– Remove impurities and sediment that
have accumulated around the rotor of the circulator.
– The circulator is burnt or the number of
turns is less than that foreseen; it must be replaced.
– Check that the power to the boiler is
adequate to the actual necessities of the heating system.
The safety valve of the boiler frequently intercepts.
– Check that the filling cock is closed. If it
does not close perfectly then replace it.
– Check that the filling pressure when the
system is cold is not too high, keep to the given values.
– Check whether the safety valve is calibra-
ted, eventually replace it.
– Check whether the capacity of the tank
is enough to hold the quantity of water of the system.
– Check the pre-loading pressure of the
expansion vessel.
– Replace the expansion vessel if faulty.
The radiators do not heat up in winter.
– The rotary switch is in the summer posi-
tion, put it on the winter position.
– The room stat is regulated too low or
needs to be replaced as it is faulty.
– The electrical connections of the room
stat are not correct.
The principal burner burns badly: flames too high, yellow flames.
– Check that the gas pressure to the bur-
ner is normal.
– Check that the burners are clean. – Check that the coaxial duct is correctly
installed (vers. “BF”).
Smell of combusted gas
– Check that the boiler is perfectly clean. – Check that the suction is suf ficient. – Check that there is not an excessive.
The boiler is functioning but the tempera­ture is not increasing.
– Check that the consumption of gas is not
below that foreseen. – Check that the boiler is clean. – Check that the boiler is proportional to
the system.
In the “BF” versions on request for hot water or heating the fan does not start.
– Make sure that the smoke pressure
switch is functioning and that the relative
contact is in rest conditions. – Check and if necessary remove impuri-
ties or condensation from the connec-
ting tubes of the smoke pressure switch. – It is necessary to replace the smoke
pressure switch. – Replace the electronic board.
91
92
USER INSTRUCTIONS
WARNINGS
– In case of fault and/or incorrect equipment operation, deactivate it, without making any repairs or taking any direct
action. Contact the authorised technical staff.
– The installation of the boiler and any servicing or maintenance job must be carried out by qualified personnel. Under
no circumstances, the devices sealed by the manufacturer can be tampered with.
– It is absolutely prohibited to block the intake grilles and the aeration opening of the room where the equipment is
installed.
LIGHTING AND OPERATION
BOILER IGNITION (fig. 1)
Open the gas valve and light the appliance by turning the rotary switch to summer position
. The green led indicates that electricity is being supplied to the appliance. –
With the rotary switch in the summer position , the boiler will start-up upon demand for domestic hot water, and run at full power to reach the selected tempe­rature. The gas feeding pressure will then automatically vary to ensure that the required temperature is kept constant.
– With the rotary switch in the winter posi-
tion , once the boiler has reached the value set on the heating potentiometer, it will start to modulate in automatically in
order to supply the required power out­put to the system. The operation of the boiler will be stop­ped through the intervention of the ther­mostat or timer.
TEMPERATURES ADJUSTMENT (fig. 2)
– The D.H.W. temperature can be adju-
sted by turning the knob of the D.H.W. potentiometer which has a range of between 40 to 60°C (fig. 2).
– The C.H. temperature can be adjusted by
turning the knob of the C.H. potentiome­ter which has a range of between 40 to 80°C. To ensure optimal boiler ef fi-
ciency at all times, we recommend not to drop below a minimum working tempera­ture of 50°C.
TURNING THE BOILER OFF (fig. 1)
To turn the boiler off place the rotary switch on the OFF position. If the boiler is not going to be used for a lengthy period it is advised to turn of f the electricity supply, close the gas cock, and if low temperatures are fore­seen, empty the boiler and the hydraulic system to avoid breakage in the tubes due to the freezing of the water.
GAS CONVERSION
Should it be necessar y to convert the appliance to a different gas from the one for which the boiler has been equipped, approach the technical staff.
CLEANING AND MAINTENANCE
Preventive maintenance and checking of the efficient operation of the equipment and safety devices must be carried out exclusively by the authorized technical staff. The boiler is supplied with an elec­tric cable. Should this require replace­ment, contact exclusively an authorised technical staff.
APRE
0
306090
120
bar
°C
034
1
Fig. 1
Fig. 2
OPEN
FAULT FINDING
– Ignition failure/safety stat intercep-
tion (fig. 3)
If the burner fails to start the red led that signals blockage will light up. To attempt star ting it again, the rotary swit­ch must be turned to the position ( ) and released soon af ter, returning to the summer
()
or winter
()
position.
If the failure should occur again, call the authorised technical staff to check the boiler.
Insufficient water pressure (fig. 4)
In case the index of the thermomanome­ter is below scale of the blue colour (2) the boiler is not functioning and the oran­ge bicolour detector is flashing. To resto­re functioning act on the filling cock taking the index of the manometer within the scale of the blue colour (2). Once filled close the filling tap. The blue coloured scale (1) shows the working field with heating system functioning.
Other faults (fig. 5)
In the “25/60 BF - 30/60 BF” versions in case the green bicolour detector (fan/pressure switch), deactive the boi­ler and call the authorised technical staf f for assistance. In case the orange bico­lour detector lights upt (heating sensor SM failure), deactive the boiler and call the authorised technical staff for assi­stance.
Smoke safety device vers. “25/60”
(fig. 6) If the green bicolour detector is flashing (fig. 5) the boiler is not functioning. To restore functioning reinstate the ther­mostat button.
If the failure should occur again, call the authorised technical staff for assi­stance.
93
SPIA ROSSA
Fig. 4
SCALA
COLORE
AZZURRO
0
30
60
90
120
bar
°C
0
3
4
1
SCALA COLORE BLU
SPIA LAMPEGGIANTE ARANCIO
0
30
60
90
120
bar
°C
0
3
4
1
Fig. 6
Fig. 3
CLOSE
Fig. 5
RED LED
BLU SCALE (2)
BLU
SCALE (1)
FLASHING ORANGE LED
TIME PROGRAMMER (optional)
With the selector in the “AUTO” position, the boiler operation is regulated according to the temperatures set for the program­med time periods. During star t-up, the second selector must be in the “RUN” position. Programming:
Setting the time (fig. 7)
Move the selector to . To change the hour on the display, press the “h” button, to change the minutes, press the “m” button. To set the day, press button “1...7” until the arrow points to the correct day (1 =
Monday ....... 7 = Sunday).
Setting the programme (fig. 8)
The programmer has 8 start-up pro­grammes and 8 shutdown options. To make programming easier, 3 star t-up and 3 shutdown programmes have already been set up for each day of the week, as follows:
NOTE:Programmes from 7 to 16 are not pre-set.
To select programmes other than those pre-set, move the selector to the “P” position: “0:00 1” will appear on the display: the first three figures indicate the hour and minutes, the fourth figure is the number of the programme. Programmes with odd numbers are swit­ch-on times (daytime temperature) and are indicated on the display by a light bulb symbol. Programmes with even numbers indicate the temperature reduction (night). Use button “1...7” to select the day of the week (from 1 to 7), or the period (1 ÷ 5, 6 - 7; 1 ÷ 6; or every day if the program­me has to be repeated every day of the week). Set the hour and minutes using buttons “h” and “m”. The operation in memorized by pressing button “P”
The display then changes to the further programme. Repeat the same opera­tions to set the successive programmes. At the end of the programming. Move the selector to the “RUN” position.
Cancelling one or more
programmes (fig. 9) The programmed switch-on time and switch-off time must be cancelled for each individual programme by moving selector (2) to the “P” position. Select the required programme with but­ton (3), press button (4) to cancel the settings for that day (the triangular day indicator should disappear). If a par t of the programme is cancelled, when selector (2) is returned to the “RUN” position, an error message will
appear on the clock display together with an indication of the incorrect program­me. To cancel all the programmes, move the selector to the “P” position and press buttons (3) and (5) simultaneously.
Setting the “SKIP” function (fig 9)
The SKIP function defused the program­mes when going out for the day, during which no heating is required. To start this function, press button (7); the button is only active when selector (2) is in the “RUN” position.
Once selected, the SKIP function beco­mes active at 0:00 of the following day and lasts for 24 hours. Once activated, it cannot be defused. Consequently the normal programme will only be resumed after 24 hours.
94
KEY 1 Manual/automatic operation selector 2 Programmer/timer setting selector 3 Programme button 4 Day button 5 Hour button 6 Minute button 7 SKIP function button 8 Reset button
Fig. 8
Fig. 9
Programa Hora de Hora de
encendido apagado 1 06,00 ­2 - 09,00 3 12,00 ­4 - 14,00 5 18,00 ­6 - 22,00
Fig. 7
Loading...