Sime ECOMFORT SYSTEM 25 HE, ECOMFORT 30 HE, ECOMFORT 35 HE, Ecomfort System Plus 25 HE, Ecomfort Plus 25 HE Installation And Servicing Instructions

Ecomfort
Installation and
servicing instructions
GB
Ecomfort System 25 HE: Ecomfort 25 HE:
Gas Council number 41-283-04 Gas Council number 47-283-06
Gas Council number 47-719-25 Gas Council number 47-283-04
These appliances comply with the S.E.D.B.U.K. scheme, band “B”
Please refer to commissioning instructions for filling in the log book
Note: All CORGI registered installers carry a CORGI ID Card.
You can check your installer is CORGI Registered by calling 01256 372300
CONTENTS
1 DESCRIPTION OF THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 3
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 7
3 CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 15
4 USE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 18
5 FAULT FINDING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 21
6 REPLACEMENT OF PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 24
7 EXPLODED VIEWS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 26
SIME COMBINATION BOILERS
Installer checklist
Please remember to carry out the following checks after installation. This will achieve complete customer satisfaction,
and avoid unnecessary service calls. A charge will be made for a service visit where the fault is not due to a manufac-
turing defect.
– Has a correct by-pass been fitted and adjusted?
– Has the system and boiler been flushed?
– Is the system and boiler full of water, and the correct pressure showing on the pressure gauge?
– Is the Auto Air Vent open?
Has the pump been rotated manually?
– Is the gas supply working pressure correct?
– Is the boiler wired correctly? (See installation manual).
Has the D.H.W. flow rate been set to the customer requirements?
– Has the customer been fully advised on the correct use of the boiler, system and controls?
– Has the log book provided been completed?
Has the Aquaguard Filter been cleaned (see 4.9)?
Has the condensate trap been filled (see section 2)?
IPX4D
3
1.1 INTRODUCTION
“ECOMFORT” is a boiler that has a con-
densing heat exchanger downstream from
the fan to allow the heat contained in exhaust fumes to be recovered. The boiler is equipped as standard with frost protection and circulating pump anti-
jamming system. The instructions given in this manual are provided to ensure proper installation and correct operation of the appliance.
1 DESCRIPTION OF THE BOILER
70
70
70
70
50
30
55
55
22
718
25
12 5
60
335
450
245
16 5
ø 60/100
90
700
1.2 DIMENSIONS
TABLE 1/a - Connections “ECOMFORT 25 HE - 30 HE - 35 HE”
R C.H. return 22 mm Compression
M C.H. flow 22 mm Compression
G Gas connection 15 mm Compression
E D.H.W. inlet 15 mm Compression
U D.H.W. outlet 15 mm Compression
S3 Condensation outlet ø 20
TABLE 2 - Minimum clearances
For ventilation For servicing
ABOVE THE APPLIANCE CASING 400 mm 300 mm
AT THE R.H.S. 15 m m 15 m m
AT THE L.H.S. 15 m m 15 m m
BELOW THE APPLIANCE CASING 200 mm 200 mm
IN FRONT OF THE APPLIANCE 100 mm 500 mm
TABLE 1 - Connections “ECOMFORT SYSTEM 25 HE”
R C.H. return 22 mm Compression
M C.H. flow 22 mm Compression
G Gas connection 15 mm Compression
S3 Condensation outlet ø 20
245
19 0
ø 80/125
16 5
55
55
22
30
50
700
450
25
12 5
60
335
70
70
70 70
=
=
R
M
G
EU
S3
718
G
Fig. 1
ECOMFORT SYSTEM 25 HE ECOMFORT 25-30 HE
ECOMFORT35 HE
4
1.3 TECHNICAL FEATURES
ECOMFORT SYSTEM 25 HE 25 HE 30 HE 35 HE
Heat output nominal (80-60°C) kW 24.7 24.7 29.1 33.5
Heat output nominal (50-30°C) kW 26.5 26.5 31.2 36.0
Heat output minimum (80-60°C) kW 9.5 9.5 12.7 12.5
Heat output minimum (50-30°C) kW 10.0 10.0 13.6 13.0
Heat input nominal kW 25.5 25.5 30.0 34.8
Heat input minimum kW 10.2 10.2 13.5 13.5
Efficiency min./nom. output (80-60°C) % 93.6/97.0 93.6/97.0 94.4/96.9 92.7/96.3
Efficiency min./nom. output (50-30°C) % 98.2/103.9 98.2/103.9 100.5/103.9 96.7/103.4
Seasonal efficiency rating (SEDBUK) (B) (B) (B) (B)
Termal efficiency (CEE 92/42 directive) ★★★★ ★★★★ ★★★★ ★★★★
Class NOx 3 3 3 3
Smokes temperature maximum (80-60°C) °C 78 78 80 88
Smokes temperature minimum (80-60°C) °C 74 74 74 80
Smokes temperature maximum (50-30°C) °C 50 50 51 55
Smokes temperature minimum (50-30°C) °C 42 42 44 48
Smokes flow kg/h 57.3 57.3 65.0 71.0
CO2 maximum/minimum G20 % 6.1/2.2 6.1/2.2 7.3/3.1 7.3/2.6
CO2 maximum/minimum G30/G31 % 7.5/2.8 7.5/2.8 8.5/3.5 8.8/3..1
Adsorbed power consumption W 150 150 160 160
Electrical protection grade IP X4D X4D X4D X4D
CE certification 1312BQ4473 1312BQ4473 1312BQ4473 1312BQ4473
Category II2H3+ II2H3+ II2H3+ II2H3+
Type
B22-52/C12-32-42-52-82 B22-52/C12-32-42-52-82 B22-52/C12-32-42-52-82 B22-52/C12-32-42-52-82
WEIGHT kg 41 43 43 43
CENTRAL HEATING
Maximum water head bar 3 3 3 3
Maximum temperature °C 85 85 85 85
Water content boiler l 5.0 5.0 5.0 5.0
C.H. setting range °C 30/80 30/80 30/80 30/80
Expansion vessel capacity l 8 8 8 8
Expansion vessel pressure bar 1 1 1 1
DOMESTIC HOT WATER
Minimum/Maximum pressure bar - 0.5/7.0 0.5/7.0 0.5/7.0
D.H.W. flow rate (EN 625) l/min - 11.5 13.0 14.7
Continuous D.H.W. flow rate ∆t 30° C l/min - 11.8 13.8 15.8 Continuous D.H.W. flow rate ∆t 35° C l/min - 10.1 11.9 13.0
D.H.W. setting range °C - 30/60 30/60 30/60
GAS PRESSURE AND NOZZLES
Gas supply pressure G20 mbar 20 20 20 20
Gas supply pressure G30 mbar 28-30 28-30 28-30 28-30
Gas supply pressure G31 mbar 37 37 37 37
Nozzles quantity 12 12 14 15
Nozzles diameter G20 ø 1.30 1.30 1.30 1.30
Nozzles diameter G30/G31 ø 0.77 0.77 0.77 0.80
Burner gas pressure min./max. G20 mbar 2.0/11.5 2.0/11.5 2.6/11.5 2.2/13.5
Burner gas pressure min./max. G30 mbar 4.8/28.5 4.8/28.5 6.3/28.5 4.5/28.2
Burner gas pressure min./max. G31 mbar 4.8/36.5 4.8/36.5 6.3/36.2 4.5/36.2
C.H gas consumption G20 m3/h 2.70 2.70 3.17 3.68
C.H. gas consumption G30 kg/h 2.01 2.01 2.37 2.74
C.H. gas consumption G31 kg/h 1.98 1.98 2.33 2.70
1
23
4
5
7
8
9
11
14
15
13
18
19
20
25
2624
17
16
S3
RMG
5
20
19
21
22
23
24
25
26
RMGEU
18
14
15
13
11
12
9
10
7
8
6
5
4
1
2
3
17
S3
16
KEY
1 Post-condenser 2 Smoke stat 95° 3 Fan 4 Main exchanger 5 SM sensor (thermister) 6 Aqua Guard Filter System 7 Safety stat 100° 8 Thermometer sensor
9 Gas valve 10 D.H.W. exchanger 11 Water flow switch 12 Divertor valve 13 Automatic by-pass 14 Circulating pump 15 Auto air vent 16 Expansion vessel 17 Condensation water trap 18 Safety valve 19 Temperature/pressure gauge
20 Boiler drain 21 D.H.W. filter 23 D.H.W. inlet cock
24 Gas cock
25 C.H. flow cock 26 C.H. return cock
R C.H. return M C.H. flow G Gas connection E D.H.W. inlet U D.H.W. outlet S3 Condensation outlet ø 20
1.4 FUNCTIONAL DIAGRAM
Fig. 2
ECOMFORT SYSTEM 25 HE
ECOMFORT 25 - 30 - 35 HE
6
1.5 MAIN COMPONENTS
Fig. 3
KEY
1 Water flow switch 2 Water trap 3 Safety stat 100° 4 Aqua Guard Filter System 5 Main exchanger 6 SM sensor (thermister) 7Fan 8 Smoke stat 95°
9 Smoke pressure switch 10 Positive test point 11 Post-condenser 12 Combustion chamber 13 Ignition/ionization electrode 14 Burner 15 Gas valve 16 Automatic air vent 17 Control panel 18 Negative test point
WATER SENSOR
ECOMFORT SYSTEM 25 HE
ECOMFORT 25 - 30 - 35 HE
7
The boiler must be installed in a fixed loca­tion and only by specialized and qualified per­son in compliance with all instructions con­tained in this manual. The boiler should be installed in accordance with the Gas Safety Regulations.
It is important that the condensate trap be filled prior to operating the boiler. The trap can be filled by pouring water care­fully into the inner flue connection prior to installation of the flue. Care should be taken not to allow any water to enter the outer flue.
2.1 VENTILATION REQUIREMENTS
Detailled recommendations for air supply are given in BS5440:2. The following notes are for general guidance: – It is not necessary to have a purpose pro-
vided air vent in the room or compart­ment in which the appliance is installed.
2.3 CONNECTING UP SYSTEM
Before proceeding to connect up the boiler, you are recommended to flush out the sys­tem in order to eliminate any foreign bodies that might be detrimental to the operating efficiency of the appliance. When making the hydraulic connections, make sure that the clearances indicated in fig. 1 are respected. To facilitate the hydraulic con­nections the boiler is equipped with a valve pack code 5184817 complete with instruc­tions sheet. A safety valve set at 3 bar is
fitted to the appliance, the discharge pipe provided should be extended to terminate safely away from the appliance and where a discharge would not cause damage to persons or property but would be detect­ed. The pipe should be a minimum of 15 mm Ø and should be able to withstand boiling water, any should avoid sharp cor­ners or upward pipe runs where water may be retained.
The gas connection must be made using seamless steel or copper pipe (Mannesmann type), galvanized and with threaded joints provided with gaskets, excluding three-piece connections, except for initial and end connections. Where the piping has to pass through walls, a suitable insulating sleeve must be provided. When sizing gas piping, from the meter to the boil­er, take into account both the volume flow rates (consumption) in m
3
/h and the rela­tive density of the gas in question. The sec­tions of the piping making up the system must be such as to guarantee a supply of gas sufficient to cover the maximum demand, limiting pressure loss between the gas meter and any apparatus being used to not greater than 1.0 mbar for family II gases (natural gas). An adhesive data badge is sited inside the front panel; it contains all the technical data identifying the boiler and the type of gas for which the boiler is arranged.
2.3.1 Connection of condensation water trap
The drip board and its water trap must be connected to a civil drain through a pipe with a slope of at least 5 mm per metre to ensure drainage of condensation water.
The plastic pipes normally used for civil drains are the only type of pipe which is appropriate for conveying condensation to the building’s sewer pipes.
2.3.2 Requirements for
sealed water systems
The heating system design should be based on the following information: a)
The available pump head is given in fig. 16.
b) The burner starts when the C.H. flow
reaches 400÷450 l/h. This safety con­dition is ensured by the flow switch.
c) The appliance is equipped with an inter-
nal by-pass that operates with system heads (H) greater than 3 m. The maxi­mum flow through the by-pass is about 300 l/h. If thermostatic radiator valves are to be installed, at least one radiator should be without a thermostatic valve (usually the bathroom radiator).
d) A sealed system must only be filled by a
competent person using one of the approved methods shown in fig. 4. The system design should incorporate the connections appropriate to one of these methods.
2.4 CHARACTERISTICS OF FEEDWATER
– All recirculatory systems will be subject
to corrosion unless an appropriate water treatment is applied. This means that the ef ficiency of the system will deteriorate as corrosion sludge accu-
mulates within the system, risking dam­age to pump and valves, boiler noise and circulation problems.
For optimum performance after installa­tion this boiler and its associated central heating system must be flushed in accordance with the guidelines given in BS 7593 “Treatment of water in domes­tic hot water central heating systems”.
– This must involve the use of a propri-
etary cleanser, such as Sentinel X300 or X400, or Fernox Superfloc. Full instructions are supplied with the prod­ucts, but for immediate information please contact GE Betz (0151 420
9563) or Fernox (01799 550 811) directly.
– For long term protection against corro-
sion and scale, af ter flushing it is rec­ommended that an inhibitor such as Sentinel X100, or Fernox MB-1 or Copal is dosed in accordance with the guide­lines given in BS 7593.
Failure to flush and add inhibitor to the system may invalidate the appli­ance warranty.
– It is important to check the inhibitor
concentration after installation, system modification and at every service in accordance with the manufacturer’s instructions. (Test kits are available from inhibitor stockists).
– At every service the Aquaguard Filter
(4.9) should be checked and cleaned.
2.5 COAXIAL DUCT ø 60/100 (only for “25-30 HE models”)
The air inlet-smoke outlet assembly, code 8096250, is included in the standard sup­ply of the appliance complete with mounting instructions.
NOTE: to use only special accessories for condensing boilers.
2 INSTALLATION
ALTERNATIVE METHODS OF FILLING A SEALED SYSTEM
Fig. 4
2.5.1 Coaxial flue diaphragm
The boiler is normally supplied with ø 87.5 diaphragm (fig. 4/a).
ATTENTION: the diaphragm should be used only when the length of the coaxial duct is below 1 m (only for “25 HE” model).
2.5.2 Coaxial duct accessories
The accessories to be used for this type of installation and some of the connecting sys­tems that may be adopted are illustrated in fig. 5.
With the pipe bend included in the kit, the maximum length of the piping should not exceed 3.0 meter. When the vertical extension code 8086950 is used, the ter­minal par t of the pipe must always come out horizontally.
2.6 COAXIAL DUCT ø 80/125 (only for “35 HE” model)
The air inlet-smoke outlet assembly ø 80/125 is supplied in a kit code 8096253 complete with mounting instructions.
With the pipe bend included in the kit, the maximum length of the piping should not exceed 3.0 meter.
The diagrams in fig. 7/a illustrate a num­ber of examples of different coaxial outlets ø 80/125.
Fig. 5
KEY 1a-b Coaxial duct kit code 8096250 2 Extension L. 1000 code 8096150 3 Vertical extension L. 140
with take-off point code 8086950 4 a 90° additional bend code 8095850 4 b 45° additional bend code 8095950
max 3.0 m
NOTE: Place the duct horizontally.
NOTE: Before instal­ling accessories, lubricate the internal part of gaskets with silicon-based pro­ducts. Avoid using oils and greases.
IMPORTANT: – Each additional 90° curve installed reduces
the available length by 1.0 metres.
– Each additional 45° curve installed reduces
the available length by 0.50 metres.
ONLY FOR “25 HE” MODEL
Fig. 4/a
8
Only for “25-30 HE” models
9
C12
C32
C42
2
7
6
4
1
2
max 4 m
3
x
y
x + y = max 3 m
3
2
1
max 3 m
Fig. 5/a
KEY 1 Coaxial duct kit code 8096253 2 a Extension L. 1000 code 8096171 2 b Extension L. 500 code 8096170 3 Adapter ø 80/125 code 8093150 4 a 90° additional bend code 8095870 4 b 45° additional bend code 8095970 6
Hinged tile code 8091300
7 Coaxial roof exit terminal L. 1285 code 8091205
IMPORTANT: – Each additional 90° cur ve installed reduces the available length by 1.0 metres. – Each additional 45° cur ve installed reduces the available length by 0.50 metres.
Only for “35 HE” model
2.7 POSITIONING THE OUTLET TERMINALS
The outlet terminals for forced-draught appliances may be located in the external
perimeter walls of the building. To provide some indications of possible solu­tions, Table 3 gives the minimum distances to be obser ved, with reference to the type of building shown in fig. 6.
2.8 SEPARATE PIPES ø 80 (Optional alternative twin pipe system)
A special kit may be used to separate the
10
Terminal position Minimum spacing A Directly below an openable window, air vent
or any other ventilation opening 300 mm 12 in
B Below guttering, drain pipes or soil pipes 75 mm 3 in C/D Below eaves, balconies or carport roof 200 mm 8 in E From ver tical drain pipes or soil pipes 75 mm 3 in F From int ernal or external cor ners 300 mm 12 in G Above adjacent ground, roof or balcony level 300 mm 12 in H From a surface facing the terminal 600 mm 24 in I From a terminal facing the terminal 1,200 mm 48 in J From an opening in the carpor t
(eg door, window into dwelling) 1,200 mm 48 in
K Vertically fr om a terminal on the same wall 1,500 mm 60 in L Horizont ally from a terminal on the same wall 300 mm 12 in M Horizontally from a ver tical terminal to a wall 300 mm 12 in N Horizontally from an openable window or other opening 300 mm 12 in P Above an openable window or other opening 300 mm 12 in
TABLE 3
– If the terminal discharges into a pathway or passageway check that combus-
tion products will not cause nuisance and that the terminal will not obstruct the passageway.
– Where the lowest part of the terminal is fitted less than 2 m (78 in) above
ground, above a balcony or above a flat roof to which people have access, the terminal MUST be protected by a purpose designed guard. Terminal guards are available from Quinnell, Barrett, and Quinnell, Old Kent Road, London. State model C2, (G.C. Part No 382946).
– Where the terminal is fitted within 850 mm (34 in) of a plastic or painted gut-
ter, or 450 mm (18 in) of painted eaves, an aluminium shield at least 1,500 mm (59 in) long mus t be fitted t o the underside of the painted surface.
– The air inlet/outlet flue duct MUST NOT be closer than 25 mm (1 in) to com-
bustible material.
– In certain weather conditions the terminal may emit a plume of steam. This is
normal but positions where this would cause a nuisance should be avoided.
Fig. 6
11
flue gas outlet from the fresh air intake (fig.
7).
The maximum overall length of the intake and exhaust ducts depends on the head losses of the single fittings installed (excluding the doublers) and must not be greater than 9.0 mm H2O (“25 HE” model) - 7.0 mm H2O (“30 HE” model) and
4.0 mm H2O (“35 HE” model).
For head losses in the fittings, refer to Table
4.
NOTE: To use only special accessories for condensing boilers.
2.8.1 Separate pipe accessories
Kit code 8089912 is supplied for this pur­pose (fig. 8).
2.9 ELECTRICAL CONNECTION
The boiler is supplied with an electric cable. Should this require replacement, it must be purchased exclusively from SIME. The electric power supply to the boiler must be 230V - 50Hz single-phase through a fused main switch, with at least 3 mm spac­ing between contacts. Respect the L and N polarities and the earth connection.
NOTE: SIME declines all responsibility for injury or damage to persons, animals or property, resulting from the failure to pro­vide for proper earthing of the appliance.
2.9.1 Electrical board (fig. 12)
Before performing any kind of operation,
disconnect the unit from the power supply
using the bipolar switch of the plant.
Placing the boiler selector in position “OFF”
does not disconnect the electric board
from the power supply.
Remove the three screws (9) fixing the con-
trol board, and pull forward the panel until it
tilts downwards. In order to gain access to
the electrical board components, unscrew
the four screws fixing the control panel
cover.
2.9.2 Room thermostat (fig. 12)
After having removed the jumper, connect electrically the room thermostat to termi­nals 1-2 of the junction box (8).
In order to have better room comfort and temperature control, we suggest you to use a room thermostat belonging to Class II, as specified by standard EN60730.1 (clean contact).
KEY 1 Gasket ø 125/95 2 Fixing screw 3 Flue outlet flange 4 Inlet air diaphragm
115
ø 80
ø 80
110
16 5
255
10 0
245
Fig. 7
TABLE 4
Accessories ø 80 Head loss (mm H2O) “25 HE” model Head loss (mm H2O) “30/35 HE” model
Inlet Outlet Roof outlet Inlet Outlet Roof outlet
90° elbow MF 0.30 0.40 0.30 0.45 – 45° elbow MF 0.20 0.30 0.20 0.35 – Extension L. 1000 (horizontal) 0.20 0.30 0.20 0.35 – Extension L. 1000 (vertical) 0.30 0.20 0.30 0.25 – Outlet terminal 0.30 0.35 – Inlet terminal 0.10 0.10 – Doubler fitting 0.20 0.30 – Roof outlet terminal L. 1381 0.50 0.55
1
2
3
4
N° segments Total load loss mm H2O
to remove “25 HE” model
- 0 ÷ 2,0
n° 1 2,0 ÷ 3,0 da n° 1 a 3 3,0 ÷ 4,0 da n° 1 a 4 4,0 ÷ 5,0 da n° 1 a 5 5,0 ÷ 6,0 da n° 1 a 7 6,0 ÷ 7,0 da n° 1 a 9 7,0 ÷ 8,0
without diaphragm 8,0 ÷ 9,0
Fig. 8
N° segments Total load loss mm H2O
to remove “30 HE” model
n° 1 e 2 0 ÷ 2,0 da n° 1 a 3 2,0 ÷ 3,0 da n° 1 a 4 3,0 ÷ 4,0 da n° 1 a 6 4,0 ÷ 5,0 da n° 1 a 8 5,0 ÷ 6,0
without diaphragm 6,0 ÷ 7,0
N° segments Total load loss mm H2O
to remove “35 HE” model
da n° 1 a 8 0 ÷ 1,0 da n° 1 a 9 1,0 ÷ 2,0
da n° 1 a 10 2,0 ÷ 3,0
without diaphragm 3,0 ÷ 4,0
12
8
125
4
67
9
Fig. 12
ATTENTION: After having removed the three screws (9) tilt the panel downwards to gain access.
KEY 1 Thermohydrometer 2 Time programmer (optional) 4 Main PCB 5 Earth faston 6 Control panel protection 7 Cover (TA) 8 Connector (TA) 9 Fixing screw
IMPORTANT
Before performing any kind of operation, disconnect the unit
from the power supply using the bipolar switch of the plant.
Placing the boiler selector in position “OFF” does not disconnect
the electric board from the power supply.
13
JUMPERS
JP4
CN1
CN6 (cód. 6299987)
CN7 (cód. 6299924)
CN2 (cód. 6299988)
WHITE
GREY
95 °C SMOKE STAT
TERMINAL BOARD
100 °C SAFETY STAT
RELAY
Fig. 13
2.9.3 ECOMFORT SYSTEM 25 HE wiring diagram
NOTE: – The room thermostat (TA) may be connected to the terminals 1. – To remote control the boiler connect an external clock to the terminals 1-2 (24 V) of the “TA” connector and set the
built-in clock to “constant” mode (see user instructions for details).
JUMPERS POSITION AND FEATURES
JUMPER POSITION AND FEATURE SUPPLY POSITION
CLOSED OPEN
JP4 - METANO/GPL Ready to function with LPG Ready to function with natural gas Open
WATER SENSOR
14
JUMPERS
JP4
CN1
CN6 (cód. 6299923)
CN7 (cód. 6299924)
CN2 (cód. 6299988)
95 °C SMOKE STAT
TERMINAL BOARD
100 °C SAFETY STAT
Fig. 13/a
2.9.4 ECOMFORT 25 - 30 - 35 HE wiring diagram
NOTE: – The room thermostat may be connected to the terminals 15-16 (CN1) of the “TA” connector af ter having removed the
link.
– To remote control the boiler connect an external clock to the terminals 1-2 (24 V) of the “TA” connector and set the
built-in clock to “constant” mode (see user instructions for details).
JUMPERS POSITION AND FEATURES
JUMPER POSITION AND FEATURE SUPPLY POSITION
CLOSED OPEN
JP4 - METANO/GPL Ready to function with LPG Ready to function with natural gas Open
WATER SENSOR
15
3.1 ELECTRONIC BOARD
The electronic board is manufactured in compliance with the EEC 73/23 low-volta­ge directives. It is supplied with 230V. The electronic components are guaranteed against a temperature range of 0 up to +60°C. An automatic and continuous modulation system enables the boiler to adjust power to the various system requi­rements or the user’s needs.
3.1.1 Fault and malfunction signaling
The indicator LEDS signaling irregular and/or incorrect operation of the equip­ment are indicated in fig. 14.
3.1.2 Devices
The electronic board is equipped with the following devices (fig. 15):
Connector “JP4” (4)
With the connector disconnected, the boiler is ready to function with METHANE; with the connector connected with GPL.
ATTENTION: It is essential that the opera­tions described above be carried out by authorized technical staff.
3.2 TEMPERATURE SENSOR
Antifreeze system managed by active hea­ting NTC sensor when water temperature is 6°C. The heating sensor works also as a
limit thermostat which switches off the bur­ner when temperature is over 90°C.
When sensor (SM) is interrupted, neither of the boiler's heating services will func­tion.
Table 5 shows the resistance values (Ω)
obtained on the heating sensor as the tem­perature varies.
3 CHARACTERISTICS
Fig. 14
121045
3
7 8
9
Fig. 15
TABLE 5
Temperature (°C) Resistance ()
20 12.090 30 8.313 40 5.828 50 4.161 60 3.021 70 2.229 80 1.669
KEY
1 Jumper JP2 2 Fuse (1,6 AT) 3 D.H.W. potentiometer 4 Connector “JP4” 5 Rotay switch 7 Block red led 8 C.H. potentiometer 9 Bi-colour led gree/orange
10 Connector “TA”
Bi-colour green led off if power is cut-off.
Bi-colour orange led: C.H. sensor (SM) fault.
Green led flashing: fan/smoke pressure switch.
F
lashing orange led no water circulation.
Flashing red led indicates a problem in the line post-condenser.
Red led on, ignition blocked/safety stat /smoke stat tripped:
turn the rotar y switch in the position ( )
to restore functioning
16
3.3 ELECTRONIC IGNITION
Ignition and flame detection is controlled by a sole electrode located on the burner. It guarantees maximum safety with interven­tion times, for accidental switching off or gas failure, within one second.
3.3.1 Operating cycle
Rotate the selector knob to summer or win­ter, and verify that green LED ( ) lights up to confirm the presence of voltage. The burner must be ignited within 10 seconds max. However, it is possible for ignition failures to occur, with consequent activation of “locked out” signal:
Gas failure
The electrode continues spark discharge for a maximum of 10 sec. If the burner does not light, the board - after a 5 second ventilation stop - reactivates discharge for further 10 seconds. This cycle will be repeated 5 times, after that, the lock-out red LED will light up.
This may occur upon first ignition or after
long periods of boiler lay-off when there is air in the pipes. It may be caused by the gas cock being closed or by one of the valve coils having a break in the winding, so that the valve cannot open.
– Ignition electrode fails to spark
The electrode continues spark discharge for a maximum of 10 sec. If the burner does not light, the board - after a 5 second ventilation stop - reactivates discharge for further 10 seconds. This cycle will be repeated 5 times, after that, the lock-out red LED will light up.
This may be due to a break in the wire of
the electrode or to the wire not properly fastened to the ignition transformer ter­minal. The electrode itself may touch earth or may be heavily worn out and needs repla­cing. The electronic board is defective.
When there is a sudden voltage failure, the burner shuts down immediately; when the power supply returns, the boiler will start up again automatically.
3.4 FLOW SWITCH SAFETY VALVE
A flow switch safety valve (8 fig. 2) interve-
nes, blocking the operation of the burner if the boiler is without water due to the for­mation of air bubbles in the heat exchanger or if the circulator is not working correctly or because the “Aqua Guard” heating cir­cuit filter is clogged.
3.5 SYSTEM AVAILABLE HEAD
The head available for the heating plant is shown as a function of the flow in graph in fig. 16. To obtain the maximum head available to the system, turn of f the by-pass by turning the union to the vertical position (fig. 16/a).
0
10 0
800
700600500400300200
PORTATA (l/h)
PREVALENZA RESIDUA (mbar)
500
400
10 0
200
300
Format.zip PC
600
By-pass inserito By-pass escluso
900
1000
110 0
25
30-35
25
30-35
Fig. 16
By-pass inserito
By-pass escluso
Fig. 16/a
BY-PASS ON
BY-PASS OFF
D.H.W. FLOW RATE ADJUSTER (it does not include SYSTEM 25 HE)
Flow rate (l/sec)
Available head (mbar)
By-pass on By-pass off
17
3.6 SMOKE PRESSURE SWITCH
The air pressure switch is factory set to the values 42-52 Pa (“25 HE” model), 52-62 Pa (“30 HE” model) and 65-75 Pa (“35 HE” model) to guarantee boiler func­tioning even with intake and flue pipes at the maximum permitted length. The value of the signal to the pressure
switch is measured using a special instru­ment connected to the pressure intake (10-18 fig. 3).
3.7 ELECTRICITY CONNECTION FOR ZONE SYSTEMS
When installing a system of this type, use a
separate electrical line to which room ther­mostats with their local valves will be con­nected. Connect micro switches or relay contacts on terminals 15-16 of the “TA” connector of the electronic card after removing the existing jumper (fig. 17).
CR1
CR
Connettore "TA"
Fig. 17
L
N
TA
TA 1
VZ
R
VZ1
R1
KEY TA-TA1 Zone r oom stat VZ-VZ1 Zone valve R-R1 Zone relay CR-CR1 Relay contact or micro zone valve
NOTE: Relays are used only if the area valves have no microswitches.
“TA” connector
18
SIME SUPPORT THE BENCHMARK INITIATIVE
All relevant sections of the logbook must be filled in at the time of installation and there­after service information on the back page of the logbook. Commissioning of the boiler is not complete until the logbook is filled in.
4.1 FILLING THE WATER SYSTEM
– Open the flow and return valves. – Loosen the automatic air vent cap. – Open all radiator valves and system air
vents. Fill the system with water using one of the approved methods described in section 2.3.2 to about 0.5 bar greater than the system design pres­sure. Close all air vents. Do not close
the A.A.V. – Check the system for water soundness. –
Completely drain the appliance and heat-
ing system, thoroughly flush the system,
and refill the system design pressure. –
Before refillimg check and clean the Aqua-
guard filter (4.9).
4.1.1 Flow Rate Adjustment
The DHW flow rate should be set using the flow rate adjuster (see fig. 16/a) to the value shown in section 1.3.
4.2 GAS VALVE
The boilers are equipped standard with the SIT 845 SIMGA/HONEYWELL VK 4105M /SIEMENS VGU 50 gas valve (fig. 21). The gas valve is set at two pressure values: maximum and minimum. According to the type of gas burnt, these correspond to the values given in Table 6. The gas pressures at the maximum and minimum values, are factory set. Conse­quently they must not be altered. Only when you switch the appliance from one type of gas supply (methane) to another (butane or propane), it is permitted to alter the opera­ting pressure.
4.3 GAS CONVERSION
This operation must be performed by authorised personnel using original Sime components.
To convert from natural gas to LPG or vice versa, perform the following operations (fig.
22): – Close the gas cock. – Disassemble the burner manifold (3). – Replace the main nozzles (6) supplied in
a kit, inser ting the copper washer (4). Use a ø 7 spanner to perform this ope­ration.
Remove the “METANO/GPL” connector link on the card and set it in the posi-
tion corresponding to the gas to be used (4 fig. 15).
– To set the values of maximum and mini-
mum gas pressure, follow the instruc­tions given in section 4.5.1.
– After have ultimated the conversion of
the boiler, please stick onto the casing panel the plate showing the relevant fee­ding gas which is included into the kit.
NOTE: When reassembling components which you have removed, replace gas seals; test all gas connections after assembly using soapy water or a product made specifically for the purpose, being sure not to use open flame.
4.5.1
Adjusting valve pressure
Set maximum and minimum pressure on gas valves as follows (fig. 22/a): – Connect the column or a manometer to
the intake downstream of the gas valve.
Disconnect the valve VENT pressure test point tube (5 fig. 21).
– Remove the cap (1) from the modulator. – Place the hot tap water potentiometer
knob at the maximum position.
– Turn on the boiler using the four-way
switch and turn on a hot water tap all the way.
– Remember that rotating clockwise will
increase pressure while rotating anti-
4 USE AND MAINTENANCE
3
4
2
1
5
6
1
2
4
3
5
SIT 845 SIGMA HONEYWELL VK 4105M
KEY 1 Modulator 2 EV1-EV2 coils 3 Pressure inlet upstream 4 Pressure inlet downstream 5 VENT pressure test point
TABLE 6
Burner Modulator Burner Modulator
Type of gas max. pressure mbar current min. pressure mbar current
25 HE 30 HE 35 HE mA 25 HE 30 HE 35 HE mA
G20 * 11.5 11.5 13.5 130 2.0 2.6 2.2 0
G30 28.5 28.3 28.2 165 4.8 6.3 4.5 0
G31 36.5 36.2 36.2 165 4.8 6.3 4.5 0
(*) Max. bur ner pressure is guaranteed only when the supply pressure exceeds the max. burner pressure by at
least 3 mbar.
Fig. 21
Fig. 22
KEY
1 Swivel connection 1/2” 2 Locknut 1/2” 3 Burner manifold 4 Washer ø 6.1 5 Burners 6 Nozzle M6 7 Screw
WARNING: To ensure a perfect seal, always use the washer (4) supplied in the kit when replacing nozzles, even in burner units for which it is not specified.
1
2
3 4 5
SIEMENS VGU 50
19
clockwise will diminish it.
– Adjust maximum pressure using the nut
(3) with a wrench to the maximum pres­sure value indicated in Table 6.
– Do not adjust minimum pressure until
you have adjusted maximum pressure.
– Turn off the supply power to the modula-
tor, and keep the hot water tap turned on.
– Lock the nut (3) in place, turn the screw
/nut (2) to the minimum pressure indi­cated in Table 6.
– Turn off the boiler and turn it back on
again several times, keeping the hot water tap turned on at all times and checking that the maximum and minimum pressu­re values correspond to the established values; correct the settings if necessary.
– Adjust, checking that you have restored
the power to the modulator.
– Put the pipe back on the valve VENT
pressure test point.
– Remove the manometer, remembering
to tighten the screw for closing the pres­sure test point.
– Put the plastic cap (1) back on the modu-
lator and seal with a drop of coloured sealant if necessary.
4.8 REMOVAL OF OUTER CASING
It is possible to completely disassemble the shell for an easy maintenance of the boiler as showed in fig. 21.
4.9 CLEANING AND MAINTENANCE
Preventive maintenance and checking of efficient operation of equipment and safety devices must be carried out exclusively by authorized technical personnel.
4.10 CLEANING THE C.H. WATER FILTER “AQUA GUARD” (fig. 22)
To clean the filter, close the flow/return val­ves, turn off the power to the control panel, remove the casing and empty the boiler using the drain provided until the hydrome­ter shows “zero”. Place a container for col­lection underneath the filter, unscrew the cap and proceed to clean the filter, remo­ving impurities and limestone deposits. Check the seal o-ring before reassembling the cap with the filter.
1
2
Fig. 21
Fig. 22
Fig. 22/a
3
2
1
KEY 1 Plastic tap 2 Minimum pressure adjusting nut 3 Maximum pressure adjusting nut
SIT 845 SIGMA HONEYWELL VK 4105M
SIEMENS VGU 50
20
4.11 CHIMNEY SWEEP FUNCTION
(fig. 23)
To carry out the verification of combustion in the boiler turn the selector and stop on the position ( ) until the green/orange led starts to flash intermittently. From that moment the boiler will start func­tioning in heating mode at the maximum power, with switching of f at 80°C and restarting at 70°C.
Before activating the chimney sweep func­tion make sure that the radiator valves or eventual zone valves are open.
The test may be carried out also during hot­water service functioning. To do so it is enough, after having activated the chimney sweep function, to take some hot water from one or more cocks. Even in this condition the boiler functions at the maximum temperature always with the primary controlled between 80°C and 70° C. During the entire duration of the testing the hot water taps must remain open. After verifying the combustion the boiler should be switched off by placing the selec­tor on the OFF position; then return the selector to the desired function.
ATTENTION: After about 15 minutes, or once the hot water request has been ful­filled, the chimney sweep function auto­matically deactivates.
4.12 BOILER SERVICING
4.12.1 Routine Servicing
To ensure continued efficient operation of the appliance, it is recommended that it is checked and serviced at regular intervals. The frequency of service will depend on the particular installation and conditions of usage, but in general once a year should be adequate. It is the law that a competent person such as a CORGi registered engineer, must carry out any service work.
4.12.2 Combustion Check
Incorporated into the flue elbow or vertical adaptor is a sampling point. The grey plastic cap should be unscrewed and the flue gas sampled using a flue gas analyser. During the test the boiler can be operated in “chimney sweep mode” see 4.11. The correct CO2 reading can be found in section 1.3.
4.12.3 Burner inspection
Remove the burner as described in section
6.3. Inspect the burner and if necessary clean using a soft brush.
Check the Ignition/ionisation electrode, check the gap (4mm+/- 0.5mm)
4.12.4 Combustion Chamber
Remove any loose debris from the combu­stion chamber using a soft brush and a vacuum cleaner. Take care not to damage the rear insulation panel.
4.12.5 Condensate Trap
The condensate trap would not normally require removal during service, but it can be checked. Water should be poured into the inner flue. Great care must be taken to ensure no water enters the outer flue. Check that the water flows freely to the drain. Should it require removal, firstly remove wire clip securing the condensate drain rub­ber pipe to the condensate trap. Remove the pipe. Remove the two screws securing the con­densate trap bracket. Clean the trap and refit in reverse order.
4.12.6 Flow Switch
The operation of the flow switch should be checked at each service. Remove small cover retaining screw and remove the cover. When the pump is running and water is flowing around the boiler, the actuator lifts off the microswitch. Check the operation of the actuator. Ensure that it is free and that it lifts and returns. If necessary lubricate the pivot point of the actuator. Isolate the boiler. Drain it using the drain provided. Remove the microswitch by carefully pulling it forward off its mounting pins. Remove the screw securing the mounting plate, then pull off the plate. Pull out the actuator pin.
Lubricate the centre “O” ring. Refit the actuator ensuring that the flat side of the round section is to the bottom. Re-assemble remaining parts. (see 4.12.6 before refilling the boiler).
4.12.7 Aquaguard Filter
It is recommended that the aquaguard filter is checked at each service. See section 4.10.
Spia lampeggiante verde/arancio
2
4
5
3
Fig. 23
Bi-colour green/orange flashing led
21
If an electrical fault occurs on the appliance the preliminary electrical system checks contained in the British Gas Multimeter Instruction Booklet must be carried out first. When any service or replacement of electrical components which has required the breaking and re-making of electrical connections has taken place, the following tests must be repeated: – ear th continuity; – shor t circuit; – polarity; – resistance to earth.
5.1 EARTH CONTINUITY CHECK
Appliances must be electrically disconnect-
ed, meter set on Ω (ohm) x 1 scale and
adjust zero if necessary. Tests leads from any appliance earth point (e.g. inside control box) see wiring diagrams (section 7) to earth pin on plug. Resistance should be less
than 1 (ohm). If the resistance is greater than 1 (ohm) check all earth wires for
continuity and all contacts are clean and tight. If the resistance to earth is still
greater than 1 Ω (ohm) then this should be
investigated futher.
5.2 SHORT CIRCUIT CHECK
Switches turned FULL ON - meter set on
(ohms) x 1 scale. Test leads from L to N on appliance terminal block, if meter reads 0 then there is a short circuit.
Meter set on Ω (ohm) x 100 scale. Repeat
it with leads from L to E. If meter reads less
than infinity () there is a fault.
NOTE: Should it be found that the fuse has failed but no fault is indicated, a detailed continuity check (i.e. by disconnecting and checking each component) is required to trace the faulty component. It is possible that a fault could occur as a result of local burning/arcing but no fault could be found under test. However, a detailed visual inspection should reveal evidence of burning around the fault.
5.3 POLARITY CHECK
Appliance reconnected to mains supply and meter set on 300 V ac scale. Test at appli­ance terminal block. – Test leads from L to N meter reads
approx.: 240 V ac.
– Test leads from L to E “ ” meter reads
approx. 240 V ac.
Test leads from N to E “ ” meter reads from 0 to 15 V ac.
5.4 RESISTANCE TO EARTH CHECK
Appliance must be disconnected from main
supply and meter on (ohm) x 100 scale.
All switches including thermostat on test leads from L to E - if meter reads other than
infinity () there is a fault which should be
isolated. A detailed continuity check is required to trace the faulty component.
IMPORTANT: These series of checks are the first elec­trical checks to be carried out during a fault finding procedure. On completion of the service/fault finding task which has required the breaking and remaking of electrical connections then the checks 5.1 Earth continuity, 5.3 Polarity and 5.4 Resistance to earth must be repeated.
5 FAULT FINDING
22
5.5 C.H. MODE - FAULT FINDING
Start from cold Rotary switch set to WINTER position.
Room thermostat (if fitted) calling for heat and all D.H.W. taps off. C.H. thermostat set to maximum position. Clock in the on position (if fitted).
NOTE: After completing fault finding reset the room thermostat (if fitted) to the required setting. If the appliance will not function check the wiring to the clock and if necessary, replace the clock.
Is there power
at the external
socket?
Make
power
available
Does
the pump
start?
Does
the fan
start?
Turn the clock
in the right
position
Is fuse
at mains
plug OK?
Is the clock in
the correct band time?
Is there voltage
available
to the fan?
Replace
the clock
Replace fuse in
mains plug
Check the
time clock does
his contacts open and close when the clock
turns?
Replace
the fan
Make it free to
rotate
Put a jumper
on the room
thermostat connection
Check the
power supply
cable
Is pump shaft
free to rot ate?
Is there voltage
available
to the pump?
Replace
the pump
Check pump
connection
Does the boiler lock-out without
starting the
burner?
The boiler
lock-out starting
the burner
Is there a spark
at the ignition
electrode?
Is the ionization probe connected to the main PCB and the ground?
Check the gas supply
Check for continu-
ity between ignition
electrode and igni-
tion transformer
The gap between ignition electrode
and hood
is correct?
Fit correctly the
ignition electrode
Is the gas available?
Check the
connection of
the gas valve on
the control board
PCB
Is there voltage at
the gas valve?
Replace the
gas valve
Yes
No
Is there a jumper
on the room
thermostat
connection?
No
Yes
No
Yes
No
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
Yes
No
No
Yes
YesYes
No
No
Yes
No
No
No
No
Yes
No
Verify that the
safety and fume
thermostats are
working correctly?
Replace the
thermostats
No
Is the connection of the fume and
safety
thermostats
correct?
Reset the
connection
No
Yes
Restor e the
connection
Verify that the safety and fume thermostats are
working correctly?
No
Yes
Yes
Check the
connection of
the thermostats
Replace the thermostats
No
Yes
23
5.6 D.H.W. MODE - FAULT FINDING
Start from cold - rotary switch set to SUMMER position, D.H.W. thermostat set to maximum, and all D.H.W. taps OFF.
Is there power at the external
socket?
Make
power
available
Open any tap.
Is there an
adequate flow
rate of D.H.W.
available?
Does the
microswitch of the
divertor valve
operate correctly?
Does the fan start?
Is fuses at mains plug OK?
Clean or replace
the divertor val ve
Is there voltage
available
to the fan?
Replace fuses in
mains plug
Does
the pump
start?
Replace
the fan
Make it free to
rotate
Replace the
microinterruptor
Check the
power supply
cable
Is pump shaft
free to rot ate?
Check pump
connection
Replace
the pump
Does the boiler lock-out without
starting the
burner?
The boiler
lock-out
starting
the burner
Is there a spark
at the ignition
electrode?
Is the ionization
probe connected
to the main PCB and the ground?
Check the
gas supply
Check for continu-
ity between ignition
electrode and igni-
tion transformer
The gap between ignition electrode
and hood
is correct?
Fit correctly the
ignition electrode
Is the gas available?
Restor e the
connection
Check the
connection of
gas valve on
the control board
PCB
Is there voltage at
the gas valve?
Replace the
gas valve
Yes
No
No
Yes
No
No
Yes
No
Yes
Yes
Yes
Yes
Yes
No
Yes
No
No
Yes
Yes
No
Yes
No
No
No
Is there voltage
available
to the pump?
No
Yes
Yes
No
Yes
Yes
Verify that the safety and fume thermostats are
working correctly?
Replace the
thermostats
No
Is the connection of the fume and
safety
thermostats
correct?
Reset the
connection
No
Yes
Yes
No
Verify that the
safety and fume
thermostats are
working correctly?
Yes
Check the
connection of
the thermostats
Replace the
thermostats
No
24
Note: Use silicone grease to ease the fit­ting of any push fit connections.
6.1 Expansion Vessel
– Isolate power supply – Remove boiler cover – Isolate flow and return valves – Drain boiler using fitted drain vent – Disconnect expansion pipe – Remove expansion vessel securing nut – Remove vessel – Check new vessel for correct pressure
1- 1.25 bar
– Refit in reverse order
6.2 Ignition/Ionisation electrode
– Isolate power supply – Remove boiler cover – Remove sealed chamber cover – Remove PCB cover – Disconnect ignition lead – Carefully remove lead through PCB
cover and burner compar tment
– Remove electrode fixing screw and
remove electrode from burner
– Replace in reverse order
6.3 Main Burner
– Isolate power supply – Isolate gas supply – Remove boiler cover – Remove sealed chamber cover – Remove burner cover – Disconnect gas connection to burner – Remove locknut securing burner assem-
bly – Remove ignition/ionisation electrode – Carefully lift out burner assembly – Refit in reverse order – Test for gas soundness
6.4 Fan assembly
– Isolate power supply – Remove boiler cover – Remove sealed chamber cover – Disconnect wiring to fan – Remove two fan fixing screws – Carefully pull fan forward and to the
right to disconnect fan from post con-
denser – Remove air pressure switch sensing
tube – Apply light coating of silicone grease to
nozzle of new fan – Refit in reverse order
6.5 Main Heat Exchanger
– Isolate power supply – Isolate gas supply – Isolate flow and return valves
– Drain boiler using drain vent – Remove fan assembly as described in
6.4
– Remove 4 screws and remove fan
mount ing plate – Disconnect thermistor (SM sensor) – Disconnect flow and return connections – Lif t out heat exchanger – Refit in reverse order
6.6 95°C Limit stat
– Isolate power supply – Remove boiler cover – Remove sealed chamber cover – Remove fan as described in 6.4 – Remove wires from 95°C stat – Remove stat fixing screws – Apply heat sink compound to new stat – Refit in reverse order
6.7 Air Pressure Switch
– Isolate power supply – Remove boiler cover – Remove sealed chamber cover – Remove screws securing air pressure
switch – Note position of wires before removal – Note position of sensing tube before
removal – Refit in reverse order
6.8 100°C Safety Stat
– Isolate power supply – Remove boiler cover – Disconnect 100°C safety stat – Remove fixing screws – Refit in reverse order
6.9 Thermistor (SM sensor)
– Isolate power supply – Remove boiler cover – Remove sealed chamber cover – Isolate flow and return valves – Drain boiler using drain vent – Disconnect thermistor – Unscrew thermistor (catch any water
lost) – Refit in reverse
6.10 Gas Valve
– Isolate power supply – Isolate gas supply – Remove boiler cover – Disconnect wiring from gas valve – Disconnect sensing tube – Remove gas valve – Refit in reverse order ensuring seals are
replaced as required – Recommission boiler and adjust gas
pressures as described in section 4.5.1
– Check for gas soundness
6.11 Circuit Board (PCB)
– Isolate power supply – Remove screws securing control panel – Lower panel to horizontal position – Remove PCB cover – Disconnect all wiring – Remove control knobs – Remove PCB fixing screws – Transfer trimmer spindles to new board – Ensure PCB links are matched to old
board – Refit in reverse order – Recommission boiler
6.12 Pump Motor
– Isolate power supply – Remove boiler cover – Isolate flow and return valves – Drain boiler using drain vent – Remove plug connection – Remove 4 x fixing screws, catch any lost
water – Refit in reverse using new washers
6.13 Diverter Valve Microswitch
– Isolate power supply – Remove boiler cover – Pull microswitch assembly forward off
the diverter valve head – Refit in reverse order
6.14 Domestic Hot Water
Heat exchanger
– Isolate power supply – Isolate flow and return – Turn on DHW tap – Close cold water supply isolation valve – Drain boiler using drain vent – Remove diverter valve microswitch as
described in 6.13 – Remove microswitch actuator from top
of diverter valve – Remove 3 x heat exchanger fixing
screws – Remove plate heat exchanger, catch any
water lost – Ensure that the four “O” rings are remo-
ved from the technil assembly – Fit the new “O” ring supplied with the
new heat exchanger to the heat exchan-
ger – Refit in reverse order
6.15 Diverter Valve
– Remove Diverter valve microswitch as
described in 6.13 – Remove plate heat exchanger as descri-
bed in 6.14
6 REPLACEMENT OF PARTS
25
– Remove the securing clip at retaining
the plug at the LHS of diverter assembly NOTE: a internal spring will push of f the
plug. Retain – Remove internal bush from spindle – Remove diverter valve head securing
clip – Pull diverter valve head from assembly – Remove spindle from assembly comple-
te with bush and spacer – Replace in reverse order replacing “O”
rings as required
6.16 Auto Air Vent (AAV)
– Isolate power supply – Isolate flow and return valves – Remove boiler cover – Drain boiler using drain vent
– Remove AAV – Replace in reverse order
6.17 Safety Valve
– Isolate power supply – Isolate flow and return valves – Remove boiler cover – Drain boiler using drain vent – Disconnect pipe from safety valve – Remove safety valve securing clip – Remove safety valve, catch any water
lost
– Refit in reverse
6.18 Pressure / Temperature Gauge
– Isolate power supply
– Isolate flow and return valves – Remove boiler cover – Drain boiler using drain vent – Remove the clip securing the pressure
sensor
– Remove the clip securing thermometer
bulb – Carefully remove the gauge – Refit in reverse order
26
7 EXPLODED VIEWS
7.1 ECOMFORT SYSTEM 25 HE
COD. T YPE DATE PAGE
3830017/388 ECOMFORT SYSTEM 25 HE 17.09.2007 1/3
27
Fonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Verona) - Tel. +39-0442-631111 - Fax +39-0442-631292 - www.sime.it
POSITION CODE DESCRIPTION MODEL NOTE
COD. TYPE DATE PAGE
• Recommended stock par ts - Componenti da tener e a scorta
POSITION CODE DESCRIPTION MODEL NOTE
1 6138570 Side frame part
2 6138771 Frame assembly upper support
3 6255431 Expansion vessel lower support
4 • 5139130 Expansion vessel l.8 - 3/8” M
5 6146305 Brass Nut 3/8”
6 6288120 Sealed chamber rear panel
7 6034153 Condensate drainage pipe
8 6257521 Combustion chamber lower air deflector
9 6010827 Post-condenser fixing bracket
10 6300800 Post-condenser
11 6248855 P.C. inlet/oulet smokes gasket
12 6112320 P.C. smokes stat extension
13 6226443 O-Ring Ø 11,5 x 1,5
14 6146722 95°C safety stat
15 6257522 Air deflector
16 6288430 Combustion chamber rear panel
17 5190700 Main burner assembly
18 • 6235931 Ignition-ionisation electrode
19 6146301 Brass nut 1/2”
20 6288510 Combust. chamber right hand side panel
21 6288610 Combust. chamber left hand side panel
22 6139773 Combustion chamber rear insulation
23 6139792 Combustion chamber side insulation
24 6257519 Comb. chamber right/left air deflector
25 6028707 Air intake gasket
26 6288000 Air intake
27 6174243 Heat exchanger
28 • 6231351 Plunged sensor
29 • 6022010 Sensor gasket
30 6260616 Smoke chamber upper panel
31 6225630 Fan
32 6288720 Combustion chamber front panel
33 6139786 Combustion chamber front insulation
34 6264831 C.H. return pipe
35 • 6226412 O-ring 3068
36 6226616 Pipe fixing spring
37 6227210 Exchanger-post condenser inlet pipe
38 • 6226601 Spring for heat exchanger connection
39 2005201 Screw “HI-LO” TSP 3x12
40 6264731 C.H. flow pipe
41 6247360 Cap for time programmer
42 2030228 Gasket Ø 17x24x2
43 • 6146701 100°C safety stat
44 • 6277204 Water trap
45 6189574 Water trap fixing bracket
46 6226612 Pipe fixing double spring
47 • 6017310 Flexible pipe
48 6226414 O-ring 117 Ø 13,1x2,62 EP851
49 2030226 Gasket Ø 10,2x14,8x2
50 6138880 Frame assembly lower side
51 6146302 Brass nut 3/4”
52 6226607 Pipe fixing spring
53 6028705 Gasket EP709 for Dab
54 2000201 Screw M5x40
55 • 6040201 Pressure relief valve
56 6100202 Ogive for pipe Ø 15
57 6168401 Locking nut for pipe Ø 15
58 • 6226602 Pipe fixing spring
59 6288200 Sealed chamber side panel
60 • 6225724 Air pressure switch 52-62 Pa
61 6280500 3-ways junct. with press. test nipple
62 6280550 Cap for 3-ways junction
63 6146303 Brass Nut 1/8”
64 6243820 SIT gas valve type 845 SIGMA
65 6226850 Gas inlet pipe
66 6226945 Pipe connecting gas valve-main burner
67 2030227 Gasket Ø 12x18x2
68 6289818 Control panel
69 6273210 Guidelight - 2 ways out
70 • 6217003 Temperature and pressure gauge
71 6301400 Main PCB
72 6201505 Trimmer spindle Ø 6
73 6201502 Trimmer spindle Ø 6
74 2211610 Earth faston
75 • 6269810 Ignition cable
76 6289900 Control panel protecting cover
3830017/388 ECOMFORT SYSTEM 25 HE 17.09.2007 2/3
28
Fonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Verona) - Tel. +39-0442-631111 - Fax +39-0442-631292 - www.sime.it
POSITION CODE DESCRIPTION MODEL NOTE
COD. TYPE DATE PAGE
• Recommended stock par ts - Componenti da tenere a scor ta
POSITION CODE DESCRIPTION MODEL NOTE
77 6290300 Control panel cable cover
78 6290200 Room stat connection cover
79 6290100 White knob Ø 40
80 6009585 Control panel bracket
81 • 6131401 Microswitch for flowmeter
82 6009557 Relay fixing bracket
83 6247326 Cap for knob hole
84 6290014 Flap door
85 6226605 Fixing spring
86 2051100 Retaining spring
87 6288310 Sealed chamber front panel
88 6001210 Peephole
89 6287331 Casing
90 2013302 Fastener for self tapping screw
91 2004510 Screw 8Px7/8”
92 6112420 Control panel screw
93 • 6028624 Air diaphragm Ø 87.5
94 6154402 Main burner nozzle NP 130 natural gas
94 A 6154410 Main burner nozzle NP 77 GLP
95 6177505 Ball cock 3/4” x 22
96 6022004 Copper washer Ø 6
97 6177530 Gas cock 3/4” F x 15
98 6157602 Pressure relief valve drain pipe
99 • 5192600 Dab VA55 pump kit
100 6281521 Flange + OR for Dab pump
101 5192200 Gasket for sealed chamber
102 6263912 Fan pressure test point
103 • 6149303 Flow water switch
104 6227520 Pipe connecting water flow switch
105 • 6190403 Relay Omron G2R-1-T
106 2211004 Terminal strip
107 6290350 Terminal strip protection cover
108 • 6017210 Manual air vent 1/4”
109 • 6013101 Automatic air vent
110 6296916 By-pass
111 6281500 Straight fitting 3/4”
5184818 Fitting cocks kit
5187370 Technyl hydraulic group
5191185 Complete control panel
6031206 Main cable L=2000
6299924 6 pole Stocko connector CN7
6299987 14 pole Lumberg cable connecto
6299988 4 pole Lumberg cable connector
5144719 L.P.G. conversion kit
Products reference:
8104010: Ecomrof t system 25 HE
Check the correspondence with the boiler data plate.
3830017/388 ECOMFORT SYSTEM 25 HE 17.09.2007 3/3
29
7.2 ECOMFORT 25-30-35 HE
COD. T YPE DATE PAGE
3830008/394 ECOMFORT 25-30-35 HE 10.09.2007 1/3
30
Fonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Verona) - Tel. +39-0442-631111 - Fax +39-0442-631292 - www.sime.it
POSITION CODE DESCRIPTION MODEL NOTE
COD. TYPE DATE PAGE
• Recommended stock par ts - Componenti da tener e a scorta
POSITION CODE DESCRIPTION MODEL NOTE
1 6138570 Side frame part
2 6138771 Frame assembly upper support
3 6255431 Expansion vessel lower support
4 • 5139130 Expansion vessel l.8 - 3/8” M
5 6146305 Brass Nut 3/8”
6 6288120 Sealed chamber rear panel
7 6034153 Condensate drainage pipe
8 6257521 Combustion chamber lower air deflector
9 6010827 Post-condenser fixing bracket
10 6300800 Post-condenser
11 6248855 P.C. inlet/oulet smokes gasket
12 6112320 P.C. smokes stat extension
13 6226443 O-Ring Ø 11,5 x 1,5
14 6146722 95°C safety stat 25-30
14 A 6146701 100°C safety stat 35
15 6257522 Air deflector
16 6288430 Combustion chamber rear panel
17 5190752 Main burner assembly 30
17 A 5190700 Main burner assembly 25
17 B 5190760 Main burner assembly 35
18 • 6235931 Ignition-ionisation electrode
19 6146301 Brass nut 1/2”
20 6288510 Combust. chamber right hand side panel 25-30
20 A 6288511 Combust. chamber right hand side panel 35
21 6288610 Combust. chamber left hand side panel 25-30
21 A 6288611 Combust. chamber lef t hand side panel 35
22 6139773 Combustion chamber rear insulation
23 6139792 Combustion chamber side insulation
24 6257519 Comb. chamber right/left air deflector
25 6028707 Air intake gasket
26 6288000 Air intake
27 6174243 Heat exchanger
28 • 6231351 Plunged sensor
29 • 6022010 Sensor gasket
30 6260616 Smoke chamber upper panel
31 6225630 Fan
32 6288720 Combustion chamber front panel
33 6139786 Combustion chamber front insulation
34 6264831 C.H. return pipe
35 • 6226412 O-ring 3068
36 6226616 Pipe fixing spring
37 6227210 Exchanger-post condenser inlet pipe
38 • 6226601 Spring for heat exchanger connection
39 6264746 Pipe conn. C.H. filter-C.H. exchanger
40 6264748 C.H. flow pipe
41 • 6295500 C.H. filter 3/4”M x 3/4”M
42 2030228 Gasket Ø 17x24x2
43 • 6146701 100°C safety stat
44 • 6277204 Water trap
45 6189574 Water trap fixing bracket
46 6226612 Pipe fixing double spring
47 • 6017310 Flexible pipe
48 6226414 O-ring 117 Ø 13,1x2,62 EP851
49 2030226 Gasket Ø 10,2x14,8x2
50 6138880 Frame assembly lower side
51 6146302 Brass nut 3/4”
52 6226607 Pipe fixing spring
53 6028705 Gasket EP709 for Dab
54 2000201 Screw M5x40
55 • 6040201 Pressure relief valve
56 6100202 Ogive for pipe Ø 15
57 6168401 Locking nut for pipe Ø 15
58 • 6226602 Pipe fixing spring
59 6288200 Sealed chamber side panel
60 • 6225715 Air pressure switch 30
60 A • 6225724 Air pressure switch 52-62 Pa 25
60 B • 6225713 Air pressure switch 35
61 6280500 3-ways junct. with press. test nipple
62 6280550 Cap for 3-ways junction
63 6146303 Brass Nut 1/8”
64 6243820 SIT gas valve type 845 SIGMA
65 6226850 Gas inlet pipe
66 6226945 Pipe connecting gas valve-main burner
67 2030227 Gasket Ø 12x18x2
68 6289817 Control panel
69 6273210 Guidelight - 2 ways out
3830008/394 ECOMFORT 25-30-35 HE 10.09.2007 2/3
31
Fonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Verona) - Tel. +39-0442-631111 - Fax +39-0442-631292 - www.sime.it
POSITION CODE DESCRIPTION MODEL NOTE
COD. TYPE DATE PAGE
• Recommended stock par ts - Componenti da tener e a scorta
POSITION CODE DESCRIPTION MODEL NOTE
70 • 6217005 Temperature and pressure gauge
71 6301400 Main PCB
72 6201505 Trimmer spindle Ø 6
73 6201502 Trimmer spindle Ø 6
74 2211610 Ear th faston
75 • 6269810 Ignition cable
76 6289900 Control panel protecting cover
77 6290300 Control panel cable cover
78 6290200 Room stat connection cover
79 6290100 White knob Ø 40
80 6009585 Control panel bracket
81 • 6131401 Microswitch for flowmeter
82 5191900 Divertor valve microswitch + support
84 6290014 Flap door
85 6226605 Fixing spring
86 2051100 Retaining spring
87 6288310 Sealed chamber front panel
88 6001210 Peephole
89 6287331 Casing
90 2013302 Fastener for self tapping screw
91 2004510 Screw 8Px7/8”
92 6112420 Control panel screw
93 • 6028624 Air diaphragm Ø 87.5 25-30
94 6142330 Quarter bend 1/2” x 15
95 6177505 Ball cock 3/4” x 22
96 6177506 Ball cock 1/2” x 15
97 6177530 Gas cock 3/4” F x 15
98 6157602 Pressure relief valve drain pipe
99 • 5192601 Dab VA65 circulating pump kit 30-35
99 A • 5192600 Dab VA55 pump kit 25
100 6281521 Flange + OR for Dab pump
101 5192200 Gasket for sealed chamber
102 6263912 Fan pressure test point
103 6226429 O-ring 121
104 • 6013101 Automatic air vent
105 • 6281522 14 plate heat exchanger kit 25-30
105 A • 6281525 16 plate heat exchanger kit 35
106 • 6226421 O-ring Dalmar R12
107 6281500 Straight fitting 3/4”
108 6281501 Straight fitting 1/2”
109 • 6017210 Manual air vent 1/4”
110 • 6281502 Flow water switch spare parts
111 • 6281504 Divertor valve
112 6281512 Water rate adjuster
113 6022004 Copper washer Ø 6
114 6154402 Main burner nozzle NP 130 natural gas
114 A 6154410 Main burner nozzle NP 77 GLP 25-30
114 B 6154406 Main burner nozzle NP 0,80 35
115 6247360 Cap for time programmer
116 2005201 Screw “HI-LO” TSP 3x12
5187323 Technyl hydraulic group 25-30
5191180 Complete control panel
6127210 Main cable L=2000
6299923 14 pole Lumberg cable connector CN6
6299924 6 pole Stocko connector CN7
6299925 4 pole Lumberg cable connector for time clock 25-30
6299988 4 pole Lumberg cable connector
• 6233506 Fuse T1,6A 250V
6281523 C.H. Technyl manifold
6281524 D.H.W. Technyl manifold
8085606 90° elbow with take-off points 25-30
8102110 Gasket and flange kit 25-30
6289580 Cable + electrode P.C. resistance
5184817 Fitting cocks kit
• 5144716 Conversion kit to LPG 35
5187325 Technyl hydraulic group 35
5144719 Conversion kit to LPG 25-30
Products reference:
8104002: Ecomfort 30 HE
8104003: Ecomfort 25 HE
8104005: Ecomfort 35 HE
Check the correspondence with the boiler data plate.
3830008/394 ECOMFORT 25-30-35 HE 10.09.2007 3/3
Cod. 6272272C - 09/07 - Documentation Dpt.
Sime Ltd
Unit D2 Ent erprise Way, Bradford Road, Bradford, West Yorkshire, BD10 8EW
Tel. 0870 9911114 - Fax 0870 9911115
www.sime.ltd.uk - e-mail: enquiries@sime.ltd.uk
Ecomfort 30 HE
User instructions
GB
PLEASE LEAVE THIS INSTRUCTION
WITH THE USER
1
OPERATING INSTRUCTIONS FOR THE USER
1.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 APPLIANCE OPERATION
1.3 OPERATING INSTRUCTIONS
1.4 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 ROUTINE SERVICING
1.6 GENERAL INFORMATION
1.7 SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.8 TIMER PROGRAMMER
These appliances comply with the S.E.D.B.U.K. scheme, band “B”
CONTENTS
VERY IMPORTANT!
PLEASE MAKE SURE YOUR LOG BOOK ENCLOSED IS FILLED IN CORRECTLY.
ALL CORGI REGISTERED INSTALLERS CARRY A CORGI ID CARD.
BOTH SHOULD BE RECORDED IN YOUR CENTRAL HEATING LOG BOOK.
YOU CAN CHECK YOUR INSTALLER IS CORGI REGISTERED
BY CALLING ON 01256 372300
2
OPERATING INSTRUCTIONS FOR THE USER
Fig. 1
KEY A Temperature/pressure gauge B Time programmer C Selector switch summer/winter D D.H.W. thermostat E C.H. thermostat
THE GAS SAFETY (INSTALLATION AND USE) REGULATIONS
1996. It is the law that all gas appliances are installed by a registered person, in accordance with the above regulations. Failure to install appliances correctly could lead to prosecu­tion. It is in your own interest, and that of safety, to ensure that the law is complied with.
It is essential that the appliance is correctly earthed. An electricity supply of 240 V - 50 Hz fused at 3 A is required.
Read these instructions carefully before attempting to oper­ate the appliance.
1.1 INTRODUCTION
The Sime “ECOMFORT 30 HE” is a fully automatic, wall mounted, room sealed, fan assisted combination boiler. When operating in winter mode, the appliance provides central heat­ing as required and produces instantaneous hot water upon demand. When operating in summer mode, the central heating is not operational however the appliance continues to supply hot water whenever it is required. The heat output is automati­cally controlled by the fully modulating gas valve (within its pre­set limits), and there are user adjustable potentiometers to control the temperature of both central heating and domes­tic hot water. A temperature/pressure gauge is fitted and an overheat thermostat is incorporated to protect against fault conditions.
1.2 APPLIANCE OPERATION
A demand of hot water will be sensed by the appliance detecting water flow (providing that the flow rate is above 2 l/m - 0.5 gal/min). The fan will start and the burner will light at full output. If
the draw off rate is near the maximum design flow rate the appliance will run continuously at full output until a tap is either turned off or the flow rate is reduced in which case the heat output will reduce accordingly to maintain a steady temperature. Hot water is made available almost immediately at the appli­ance outlet, but the final temperature and time taken for the hot water to reach a tap depends upon the potentiometer setting, the rate at which water is drawn off, and the length of the pipe between the boiler and the tap. When the tap is turned off, the appliance will revert to C.H. mode (if set on winter position) otherwise the burner will be extinguished pending the next demand for hot water.
1.3 OPERATING INSTRUCTIONS
1.3.1 To light the appliance (see fig. 1)
– Check that the electricity supply is off and that the D.H.W.
isolation valve is in the open position (lever ver tical). Check that the gas supply is on.
– Turn the selector switch summer/winter (C) to SUMMER
(water only) position “ ”.
– Switch on the electricity supply and full open any D.H.W.
tap. The burner will light. If the burner fails to light, turn the selector switch sum­mer/winter to “ “ position and release it immediately; then turn it to the SUMMER position: the burner should now light. Turn off the tap.
– Check that the room thermostat and time clock are call-
ing for heat. Turn the heating potentiometer (E) to maxi­mum (fully clockwise).
– Turn the selector switch summer/winter to the WINTER
position “" and the burner will light to serve the heating load.
Set the required temperature for the C.H. and D.H.W. by
A EC
F
B D
DHW
ISOLATION VALVE
3
rotating the potentiometers (D - E) clockwise to increase or anticlockwise to decrease the temperature.
NOTE: when operating in winter mode, priority is auto­matically given to providing hot water when the demand arises.
1.3.2 To turn off the appliance (see fig. 1)
For short periods:
Set the selector switch (C) to the OFF position and urn off the DHW Isolation valve. When required, restore turn the selector switch to either the SUMMER or WINTER posi­tion and turn on the DHW Isolation valve.
For longer periods:
Set the selector switch (C) to the OFF position, turn off the DHW Isolation valve, turn off the gas isolation cock. When required, manually rotate the pump, open the gas isolation cock, turn on the DHW Isolation valve and turn the selector switch to either the SUMMER or WINTER position.
NOTE: If frost protection is required-turn the selector switch to the summer position, do no
t isolate the gas
supply, turn off the DHW Isolation valve.
1.4 MINIMUM CLEARANCES
The following MINIMUM CLEARANCES must be available for
servicing the appliance:
1.5 ROUTINE SERVICING
To ensure continued efficient operation of the appliance, it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage but in general once a year should be adequate. It is the law that any service work must be carried out by a registerd person (C.O.R.G.I.).
1.6 GENERAL INFORMATION
1.6.1 Fault finding indicators (LEDS)
The appliance is fitted with a safety cut-out thermostat. In the event of overheating this will interrupt the power supply and prevent the appliance from functioning. If this occurs, allow the appliance to cool, turn the selector switch sum­mer/winter to “ “ position, then turn it back to the previous position (see fig. 2). If the cut-out condition is repeated, turn off the electrical supply and consult your installer or service engineer.
For ventilation For servicing
ABOVE THE APPLIANCE CASING 400 mm 300 mm
AT THE R.H.S. 15 m m 15 m m
AT THE L.H.S. 15 m m 15 m m
BELOW THE APPLIANCE CASING 200 mm 200 mm
IN FRONT OF THE APPLIANCE 100 mm 500 mm
Fig. 2
Bi-colour green led off if power is cut-off.
Bi-colour orange led: C.H. sensor (SM) fault.
Green led flashing: fan/smoke pressure switch.
F
lashing orange led no water circulation.
Flashing red led indicates a problem in the line post-condenser.
Red led on, ignition blocked/safety stat/smoke stat tripped:
turn the rotar y switch in the position ( )
to restore functioning
4
1.6.2 Temperature/pressure gauge
The gauge (A fig. 1) on the facia panel indicates the approxi­mate system pressure. The normal operating pressure is between 1 and 1.5 bar. If the normal running pressure is seen to decrease over a period of time there is a water leak and you should consult your installer or service engineer.
1.6.3 Electrical supply
The mains plug used must be a 3 pin type to BS1363, and fused at 3 A. THIS APPLIANCE MUST BE EARTHED.
NOTE: an interruption in the electricity supply whilst the burner is alight may cause the overheat thermostat to operate. If this is suspected, turn the rotary switch to “ “ position, then turn it back to the previous position.
TO CONNECT A PLUG
As the colour of wires in the mains lead of this appliance may not correspond with the coloured markings identifying the terminals in your plug, proceed as follows: the wire which is coloured green and yellow must be con­nected to the terminal in the plug which is marked with the letter E or by the earth symbol - or coloured green and yel­low; the wire which is coloured blue must be connected to the terminal marked with the letter N or coloured black; the wire which is coloured brown must be connected to the ter­minal marked with the letter L or coloured red.
1.6.4 Ventilation
If the appliance is installed in a cabinet, the latter MUST NOT be used for storage purposes. Any ventilation provided for the appliance during installation MUST NOT be blocked and a periodic check must be made to ensure that the vents are free from obstructions.
1.6.5 Cleaning
Use only a damp cloth and mild detergent to clean the appli­ance outer casing. DO NOT use abrasive cleaners.
1.7 SAFETY
It is essential that the instructions in this booklet are strict­ly followed for the safe and economical operation of this appliance. The appliance functions as a fan assisted bal­anced flue unit.
The flue terminal MUST NOT BE OBSTRUCT­ED under any circumstances. If damaged, turn off the appli­ance and consult the installer, service engineer, or gas suppli-
er. If it is known or suspected that a fault exists on the appli­ance it MUST NOT be used until the fault has been rectified by a competent person.
WARNING: IF A GAS LEAK IS SUSPECTED OR EXISTS, TURN OFF THE GAS SUPPLY TO THE APPLIANCE AT THE GAS SERVICE COCK. DO NOT OPERATE ANY ELECTRICAL SWITCHES. DO NOT OPERATE ANY ELECTRICAL APPLI­ANCE. OPEN ALL WINDOWS AND DOORS. DO NOT SMOKE. EXTINGUISH ALL NAKED LIGHTS. CONTACT THE GAS SUPPLIER IMMEDIATELY.
1.7 TIMER PROGRAMMER (Fig. 3)
Setting the time
The time of day can be set by grasping the outer edge of the black dial and turning it in a clockwise direction until the cor­rect time is in line with the white pointer.
Setting the “switching time”
The “ON” periods are set by sliding the blue tappets, adjacent to the time periods required, to the outer edge of the dial. The tappets that remain at the centre of the dial will be the “OFF” periods.
N.B.: The smallest switching time (ON or OFF) is 15 minutes.
– To select “Timed” mode move the selector switch in the
middle of the clock face to the “”position
– To select “Constant” mode move the selector switch in the
middle of the clock face to the “I” position.
– To select “OFF” mode move the selector switch in the mid-
dle of the clock face to the “O” position.
MECHANICAL 24 hr VERSION
Slide blue tappets
OUT for ON period
Slide blue tappets IN for OFF period
Mode selector switch
Fig. 3
All descriptions and illustrations provided in this manual have been carefully prepared but we reserve the right to make changes and improvements in our products that may affect the accuracy of the information contained in this manual.
Cod. 6272273 - 03/06 - Documentation Dpt.
Sime Ltd
Unit D2 Enterprise Way, Bradford Road, Bradford, West Yorkshire, BD10 8EW
Tel. 0870 9911114 - Fax 0870 9911115
www.sime.ltd.uk - e-mail: enquiries@sime.ltd.uk
Loading...