Sime SOLO 20 OF, SOLO 30 OF, SOLO 40 OF, SOLO 40 BF, DUETTO 20 OFi Installer's Instructions

...
65
CONTENTS
1 DESCRIPTION OF THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
3 CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
4 USE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
IMPORTANT
When carrying out commissioning of the boiler, you are highly recommended to perform the following checks: – Make sure that there are no liquids or inflammable materials in the immediate vicinity of the boiler. – Make sure that the electrical connections have been made correctly and that the earth wire is connected to a good
earthing system. – Check that the flue pipe for the outlet of the products of the combustion is unobstructed. – Make sure that any shutoff valves are open. – Make sure that the system is charged with water and is thoroughly vented. – Check that the circulator is not blocked.
INSTALLER INSTRUCTIONS
SOLO - DUETTO
ENGLISH
1.1 INTRODUCTION
One of the features of the cast iron thermal group with the integrated gas­oil burner is its functional silence and it has been designed in accordance with the european directives CEE 92/42. The perfectly balanced combustion and the high yield allows it to
economise considerably the operating costs. The instructions relative to the follow­ing models are indicated in the pre­sent manual: – “SOLO 20-30-40 OF/30-40 BF”
for heating only
“DUETTO 20-30-40 OFi/30-40
BFi” for heating and hot water pro­duction with instant tank
“BF-BFi” versions are boilers with airti­ght burners. The instructions given in this manual are provided to ensure proper installation and perfect opera­tion of the appliance and should be strictly followed.
66
1 DESCRIPTION OF THE BOILER
1.2 DIMENSIONS
Fig. 1
SOLO 20 OF SOLO 30-40 OF/BF DUETTO 20-30-40 OFi/30-40 BFi
P
Depth
650 750 (30 OF/BF) - 850 (40 OF/BF) 650 (20 OFi) - 750 (30 OFi/BFi) - 850 (40 OFi/BFi)
M
C.H. flow
G 1” (UNI ISO 228/1) G 1” (UNI ISO 228/1) G 1” (UNI ISO 228/1)
R
C.H. return
G 1” (UNI ISO 228/1) G 1” (UNI ISO 228/1) G 1” (UNI ISO 228/1)
C1
System load
G 1/2” (UNI ISO 228/1) G 1/2” (UNI ISO 228/1)
E
D.H.W. inlet
G 1/2” (UNI ISO 228/1)
U
D.H.W. outlet
G 1/2” (UNI ISO 228/1)
S
Boiler drain
G 1/2” (UNI ISO 228/1) G 1/2” (UNI ISO 228/1) G 1/2” (UNI ISO 228/1)
“SOLO 20-30-40 OF/DUETTO 20-30-40 OFi” version
“SOLO 30-40 BF/DUETTO 30-40 BFi” version
67
1.3 TECHNICAL FEATURES
SOLO 20 OF SOLO 30 OF/BF SOLO 40 OF/BF
Heat output minimum-maximum* kW 18.9-23.5 (20.7) 24.5-31.3 (27.5) 32.5-40.0 (35.2)
kcal/h 16,300-20,200 21,100-26,900 28,000-34,400
kcal/h (17,800) (23,700) (30,300)
Heat input minimum-maximum* kW 21.1-26.2 (23.0) 27.2-34.8 (30.6) 36.0-44.3 (39.0)
kcal/h 18,100-22,500 23,400-29,900 31,000-38,100
kcal/h (19,800) (26,300) (33,500)
Typ e B
23 B23 B23
Elements 3 4 5
Maximum water head bar 4 4 4
Water content l18 22 26
Expansion vessel
Water content/Preloading pressure l/bar 10/1 10/1 10/1
Loss of head smoke
Minimum-Maximum mbar 0.05-0.11 0.12-0.16 0.15-0.21
Combustion chamber pressure ** mbar – 0.02 – 0.02 – 0.05
Suggested chimney depression **
Minimum-Maximum mbar 0.07-0.13 0.14-0.18 0.17-0.23
Smoke temperature minimum-max. °C 160-185 160-185 160-185
Smoke flow minimum-max.* m
3
n/h 24.0-31.6 (26.4) 32.4-41.4 (35.9) 42.9-52.8 (46.3)
CO
2 % 12.5 12.5 12.5
Maximum temperature °C 95 95 95
Power consumption “OF/BF” W 220 200/230 180/210
Adjustment range heating °C 45÷85 45÷85 45÷85
D.H.W. production
D.H.W. flow rate EN 625 l/min – Contin. D.H.W. flow rate ∆t 30°C l/h
Minimum D.H.W. flow rate l/min
D.H.W. tank maximum water head bar
Gas-oil burner ***
Burner nozzle * 0.50-0.60 60°W 0.60-0.75 60°W 0.75-0.85 60°W
(0,50 60°W) (0.65 60°W) (0.85 60°W)
Pump pressure min.-max. * bar 12-12 (14) 14-14 (14) 14-14 (12)
Shutter position min.-max. for “OF” vers.* 3.2-3.7 (3.4) 3.0-5.2 (4.1) 5.0-6.2 (5.3)
Shutter position min.-max. for “BF” vers.*:
coaxial exhaust ø 80/125 1.7-4.1 (4.0) 1.8-3.6 (2.4)
separate flues ø 80 1,0-2,0
Diaphragm position for “BF” vers.*:
coaxial exhaust ø 80/125 D-G (D)
separate flues ø 80 M
Weight kg 112 137 162
* The date shown between the brackets refer to the factory settings ** For “OF” versions only *** After changing the calibration values of the burner, always check the C0
2 values.
68
DUETTO 20 OFi DUETTO 30 OFi/BFi DUETTO 40 OFi/BFi
Heat output minimum-maximum * kW 23.5 (20.7) 31.3 (27.5) 40.0 (35.2)
kcal/h 20,200 26,900 34,400
kcal/h (17,800) (23,700) (30,300)
Heat input minimum-maximum* kW 26.2 (23.0) 34.8 (30.6) 44.3 (39.0)
kcal/h 22,500 29,900 38,100
kcal/h (19,800) (26,300) (33,500)
Typ e B
23 B23 B23
Elements 3 4 5
Maximum water head bar 4 4 4
Water content l18 22 26
Expansion vessel
Water content/Preloading pressure l/bar 10/1 10/1 10/1
Loss of head smoke
Minimum-Maximum mbar 0.11 0.16 0.21
Combustion chamber pressure ** mbar – 0.02 – 0.02 – 0.05
Suggested chimney depression **
Minimum-Maximum mbar 0.13 0.18 0.23
Smoke temperature minimum-max. °C 185 185 185
Smoke flow minimum-max. * m
3
n/h 31.6 (26.4) 41.4 (35.9) 52.8 (46.3)
CO
2 % 12.5 12.5 12.5
Maximum temperature °C 95 95 95
Power consumption “OFi/BFi) W 215 200/230 180/210
Adjustment range heating °C 45÷85 45÷85 45÷85
D.H.W. production
D.H.W. flow rate EN 625 l/min 9.7 (8.7) 12.5 (11.0) 16.0 (14.2) Contin. D.H.W. flow rate ∆t 30°C l/h 670 (590) 890 (780) 1,140 (1,000)
Minimum D.H.W. flow rate l/min 2.5 2.5 2.5
D.H.W. tank maximum water head bar 6 6 6
Gas-oil burner ***
Burner nozzle * 0.60 60°W 0.75 60°W 0.85 60°W
(0.50 60°W) (0.65 60°W) (0.85 60°W)
Pump pressure min.-max. * bar 12 (14) 14 (14) 14 (12)
Shutter position min.-max. for “OFi” vers. * 3.7 (3.4) 5.2 (4.1) 6.2 (5.3)
Shutter position min.-max. for “BFi” vers. *:
coaxial exhaust ø 80/125 4.1 (4.0) 3.6 (2.4)
separate flues ø 80 1,0-2,0
Diaphragm position for “BFi” vers. *:
coaxial exhaust ø 80/125 G (D)
separate flues ø 80 M
Weight kg 151 176 201
* The date shown between the brackets refer to the factory settings ** For “OFi” versions only *** After changing the calibration values of the burner, always check the C0
2 values.
69
1
2
3
4 5
8
6
7
Fig. 2
1.4 MAIN COMPONENTS
1.4.1 “SOLO 20-30-40 OF/30-40 BF” version
2
10
1
11
9
12
11
6
7
8
5
4
3
Fig. 2/a
1.4.2 “DUETTO 20-30-40 OFi/30-40 BFi” version
KEY
1 Gas-oil burner 2 Bulb housing sheath 3 Control panel 4 Filling 5 Water switch 6 Hydrometer 7 System pump 8 Air intake for airtight burner
(“BF” versions)
KEY
1 Gas-oil burner 2 Bulb housing sheath 3 Control panel 4 Instant tank 5 Filling 6 Tank pump 7 Water switch 8 Hydrometer 9 System pump
10 Air intake for airtight burner
(“BFi” versions)
11 Control valve 12 Air vent valve
70
Fig. 3
1.5 FUNCTIONAL DIAGRAM
1.5.1 “SOLO 20-30-40 OF/30-40 BF” version
Fig. 3/a
1.5.2 “DUETTO 20-30-40 OFi/30-40 BFi” version
KEY
1 Boiler body 2 Filling 3 Safety valve 4 Air relief valve 5 Expansion vessel 6 Gas-oil burner 7 System pump 8 Hydrometer 9 Boiler drainer cock
10 Water switch
KEY
1 Boiler body 2 Filling 3 Safety valve 4 Air relief valve 5 Expansion vessel 6 Gas-oil burner 7 System pump 8 Hydrometer
9 Boiler drainer cock 10 C.H. water switch 11
D.H.W.
water switch 12 Instant tank 13 Control valve 14 Air vent valve 15 Tank pump
2.1 BOILER ROOM
The boilers with a rating of more than 35 kW must be equipped with a tech­nical room whose dimensions and requirements correspond to the cur­rent standards and regulations. The minimum distance between the walls of the room and the boiler must not be less than 0.60 m., while the min­imum height between the top of the boiler and the ceiling must be at least 1 m. which can be reduced to 0.50 m. for boilers with incorporated heaters (however the minimum height of the boiler room must not be less than 2,5 m). The boilers with a rating of less than 35 kW can be installed only in perfectly air-vented rooms. To circulate air in the room, air vents must be made on the outside walls which satisfy the following requirements: – Have a total surface area of at least
6 cm
2
for each installed Kw of ther­mal capacity and however not less than 100 cm
2
.
– To be situated as close as possible
to the floor, unobstructable and pro­tected by a grate which does not reduce the air passage area.
2.2 CONNECTING UP SYSTEM
Before proceeding to connect up the boiler, you are recommended to make the water circulate in the piping in order to eliminate any foreign bodies that might be detrimental to the oper­ating efficiency of the appliance. For connecting up the pipes, make sure to follow the indications illustrated in fig.
1. The connections should be easy to disconnect using pipe unions with ori­entable connections.
The shutoff valve must be connected to a suitable flow system and return pipes
2.2.1 System filling
The boiler and the relative system must be filled operating on the bearing tap and the pressure of cold charging the system must be included between 1 - 1.2 bar. During filling the main switch should be left open. Filling must be done slowly so as to allow any air bubbles to be bled off through the provided air vents. This operation can be made easy by posi­tioning horizontally the incision of the block screw of the shutoff valve. Upon completing the filling, put the
screw back to its original position. At the end of the operation make sure that the tap is closed (fig. 4).
2.2.2 D.H.W. production on “DUETTO OFi/BFi” version
To adjust water flow use the water pressure gauge flow regulator (fig. 5):
- Turn clockwise and the regulator
reduces water supply consequently increasing the relevant temperatu­re.
- Turn counter-clockwise and the
regulator increases water supply consequently reducing the relevant temperature.
2.2.3 Characteristics of feedwater
To prevent lime scale and damage to the tap water exchanger, the water supplied should have a hardness of no more than 20°F.
In all cases the water used should be tested and adequate treatment devi­ces should be installed. To prevent lime scale or deposits on the primary exchanger, the water used to supply the heating circuit should must be treated in accordance with UNI-CTI 8065 standards. It is absolu­tely essential that the water is to be treated in the following cases: – Very extensive systems (with high
contents of feedwater).
– Frequent addition of makeup water
into the system.
– In case it is necessary to empty the
system either partially or totally.
2.3 SMOKE EXHAUST
2.3.1 Connecting up flue
The flue is of fundamental importance for the proper operation of the boiler; if not installed in compliance with the standards, starting the boiler will be difficult and there will be a consequent formation of soot, condensation and encrustation.
A flue therefore must satisfy the fol­lowing requirements: – be constructed with waterproof
materials and resistant to smoke temperature and condensate;
– be of adequate mechanical resilience
and of low heat conductivity;
– be perfectly sealed to prevent cool-
ing of the flue itself:
– be as vertical as possible; the termi-
nal section of the flue must be fitted with a static exhaust device that ensures constant and efficient extraction of products generated by combustion;
to prevent the wind from creating pressure zones around the chim­ney top greater than the uplift force of combustion gases, the exhaust outlet should be at least
0.4 m higher than structures adja­cent to the stack (including the roof top) within 8 m;
– have a diameter that is not inferior
to that of the boiler union: square or rectangular-section flues should have an internal section 10% greater than that of the boiler union;
– the useful section of the flue must
conform to the following formula:
S resulting section in cm
2
71
2 INSTALLATION
P
S=K
H
OPEN
REGOLATORE DI PORTATA
Fig. 5
FLOW REGULATOR
Fig. 4
72
K reduction coefficient for liquid
fuels: 0.024 P boiler input in Kcal/h H
height of the flue in meters mea-
sured from the flame axis to the
flue outlet into the atmosphere.
When dimensioning the flue, the
effective height of the flue in
meters must be considered,
measured from the flame axis to
the top of the flue, reduced by:
– 0.50 m for each change of
direction of the connection union between boiler and flue;
– 1.00 for each horizontal
metre of the union itself.
Our boilers are the B
23 type and do
not need any particular connections other than the one to the flue as described above.
2.3.2 Smoke exhaust with ø 80/125 coaxial flue
“BF-BFi” version boilers are set to be
connected to ø 80/125 stainless steel coaxial flues that can be adju­sted to the most suitable direction for room requirements (fig. 6).
The maximum acceptable length of the flue must not be over 7.0 equi-
valent meters. Load losses in meters for each sin­gle accessory to be used in the exhaust configuration are indicated in Table A.
Only use original SIME accessories and make sure that connections are correct as indicated in the instruc­tions supplied with the accessories.
2.3.3 Exhaust with separate flues (ø 80)
“SOLO 30 BF -DUETTO 30 BFi” boi-
1
2
3
4
2
5
6
7
7
3
3
ø 80/125
min. 715
Fig. 6
KEY 1 Stainless steel coaxial flue L. 886 code 8096220 2 a Stainless steel extension L. 1000 code 8096121 2 b Stainless steel extension L. 500 code 8096120 3 a 90° stainless steel curve code 8095820 3 b 45° stainless steel curve code 8095920 4 Stainless steel vertical condensation recovery L. 135 code 8092820 5 Tile with hinge code 8091300 6 Roof outlet terminal L. 1063 code 8091203 7 Kit code 8098810
TABLE A
Load loss (mt) 90° stainless steel curve 1,80 45° stainless steel curve 0,90 Stainless steel extension L. 1000 1,00 Stainless steel extension L. 500 0,50 Roof outlet terminal L. 1063 1,00 Stainless steel coaxial flue L. 886 0,70 Stainless steel vertical condensation recovery L. 135 0,70
WARNING:
The maximum acceptable length of the flue must not be over 7.0 equivalent meters. Always use the condensation recovery (4) in outlets with vertical exhaust.
Loading...
+ 16 hidden pages