Sime BRAVA SLIM HE R Series, Brava Slim HE 20 R e, Brava Slim HE 40 R i, Brava Slim HE 20 R i, Brava Slim HE 40 R e Installation And Servicing Instructions

Cod.
Condensing wall mounted boiler
BRAVA SLIM HE R
INSTALLATION AND SERVICING INSTRUCTIONS
EN
Gas Safety Certified AS/NZS 4552 LN: SAI-400196
CAUTION
Fonderie SIME S.p.A.
6322891A - 05/2016 - R1
SAFETY WARNINGS AND REGULATIONS
RESTRICTIONS
m
m
WARNINGS
– After having removed the packaging make sure that
the product supplied is integral and complete in all its parts. If this is not the case, please contact the Dealer who sold the appliance.
– The appliance must be used as intended by
who is not responsible for any damage caused to persons, animals or things, improper installation, adjustment, maintenance and improper use of the appliance.
– In the event of water leaks, disconnect the appliance
from the mains power supply, close the water mains and promptly inform professionally qualified personnel.
– Periodically check that the operating pressure of the
water heating system when cold is
kPa)
. If this is not the case, increase the pressure or
contact professionally qualified personnel.
– If the appliance is not used for a long period of time,
at least one of the following operations must be carried out:
set the main system switch to "OFF";
-
-
close the gas and water valves for the water heating system.
– In order to ensure optimal appliance operations
Sime
recommends that maintenance and checks
are carried out
TWICE A YEAR
1-1.2 bar (100-120
.
Sime
WARNINGS
It is recommended that all operators
carefully in order to use the appliance in a safe and rational manner.
This manual
must therefore be kept for future reference and must always accompany the appliance in the event the appliance is transferred or sold to another Owner or User or is installed on another system.
Installation and maintenance
must be carried out by a qualified company or by a professionally qualified technician, or authorised person, in accordance with the instructions contained in the manual. The company or technician will, at the end of installation operations, issue a statement of compliance with national and local Technical Standards and Legislation in force
– This appliance is not suitable for pool or SPA heating
is an integral part of the appliance. It
read this manual
of this appliance
d
IT IS FORBIDDEN
– Do not allow appliance to be used by children or
unassisted disabled persons.
– Do not use electrical devices or appliances such as
switches, electrical appliances etc if you can smell fuel. If this should happen:
open the doors and windows to air the room;
-
-
close the gas isolation device;
-
promptly call for professional assistance.
– Do not touch the appliance with bare feet or with any
wet part of the body.
– Do not carry out any technical intervention or
cleaning operation before having disconnected the appliance from the mains power by setting the main switch to "OFF", and closing the gas supply.
– Do not modify the safety or adjustment devices
without authorization and instructions from the
manufacturer. – Do not block the condensate drain (if present). – Do not pull, detach or twist the electrical cables
coming out of the appliance even if the appliance is
disconnected from the mains power supply. – Do not expose the boiler to atmospheric agents.
These boilers can also be installed in partially
covered areas, as per EN 15502, with a maximum
ambient temperature of 60°C and a minimum
ambient temperature of - 5°C. It is recommended
that the boiler is installed below weathered roofs,
on the balcony or in a protected niche, to protect it
from exposure to weathering agents (rain, hail and
snow). The boiler is equipped as standard with an
antifreeze function. – Do not block or reduce the size of the ventilation
openings of the room where the appliance is
installed, if present. – Remove the mains power and gas supply from the
appliance if the external temperature could fall
below ZERO (risk of freezing). – Do not leave containers with flammable substances
in the room where the appliance is installed. – Do not leave packaging material around since it
could be dangerous. Therefore dispose of it as
prescribed by legislation in force. – Do not install the boiler in special environments
that may limit its optimum operation (e.g. marine
environment).
2
RANGE
MODEL CODE
Brava Slim HE 20 R i - (Natural gas) 8112265 Brava Slim HE 20 R e - (Natural gas) 8112266 Brava Slim HE 40 R i - (Natural gas) 8112267 Brava Slim HE 40 R e - (Natural gas) 8112268
TABLE OF CONTENTS
USER INSTRUCTIONS
TABLE OF CONTENTS 5
COMPLIANCE
Our company declares that the following Australian Standards – AS/NZS 5601 Gas Installations – AS/NZS 3500 Water services, Sanitary plumbing and drainage – AS/NZS 3000 Electrical installations, Buildings, structures
and premises
License Number:
SYMBOLS
a
WARNING
To indicate actions which, if not carried out correctly, can result in injury of a general nature or may damage or cause the appliance to malfunction; these actions therefore require particular caution and adequate preparation.
SAI-400196
Brava Slim HE R
.
boilers comply with
DESCRIPTION OF THE APPLIANCE
TABLE OF CONTENTS 13
INSTALLATION AND SERVICING INSTRUCTIONS
TABLE OF CONTENTS 21
f
d m
ELECTRICAL HAZARD
To indicate actions which, if not carried out correctly, could lead to injury of an electrical nature; these actions therefore require particular caution and adequate preparation.
IT IS FORBIDDEN
To indicate actions which MUST NOT BE carried out.
CAUTION
To indicate particularly important and useful information.
3
4
TABLE OF CONTENTS
USER INSTRUCTIONS
1 USING THE BOILER BRAVA SLIM HE R 6
1.1 Control panel ...................................6
1.2 Preliminary checks ..............................7
1.3 Ignition ........................................7
1.4 Adjusting the heating temperature .................7
1.5 Fault / malfunction codes.........................8
2 SHUTDOWN 8
2.1 Temporary shutdown.............................8
2.2 Shutting down for long periods ....................8
3 MAINTENANCE 9
3.1 Adjustments....................................9
3.2 External cleaning................................9
3.2.1 Cleaning the cladding................... 9
4 DISPOSAL 9
4.1 Disposal of the equipment (European Directive
2002/96/CE) ....................................9
5 HANDOVER INSTRUCTIONS 10
6 SERVICE RECORDS 10
5
1 USING THE BOILER BRAVA SLIM HE R
21
2
1.1 Control panel
NOTE:
seconds generates a fault on the display without preventing boiler operation. The warning disappears when normal conditions are restored.
2
l
n
d
t
f F v
Fig. 1
1
FUNCTIONAL BUTTONS
If pressed once or more than once for at least 1 second
y
during normal operation, this button allows the user to change the boiler operating mode in a cyclical sequence (Stand-by – Summer – Winter). If the boiler is experiencing a fault which can be reset, it allows boiler operation to be unblocked. (Note: the "SUMMER" mode is not applicable to this boiler).
In "parameter setting", the user can scroll through the
(
parameter index (decreasing) by pressing this button.
During normal operation, pressing this button displays
t
the flow temperature set point which can be between 20 and 80°C. In "parameter setting", the user can scroll through the parameter index (increasing) by pressing this button.
During normal operation, pressing this button allows
<
the user to reduce the flow temperature set point. In "parameter setting/display", the user can modify the parameter setting or value (decreasing) by pressing this button.
During normal operation, pressing this button allows
>
the user to increase the flow temperature set point. In "parameter setting/display", the user can modify the parameter setting or value (increasing) by pressing this button.
Programming connector cover plug.
c
p
A z E
m
pressing any one of these buttons for more than 30
DISPLAY
“SUMMER”
If the symbols that the chimney sweep function is active.
“WINTER”
operating in "Winter" mode. If no operating modes have been enabled both symbols
“RESET REQUIRED”
having repaired the fault, normal boiler operation can be restored by pressing the button
“HEATING”
operation or during the "chimney sweep function It flashes during the selection of the heating set point.
“BLOCK” DUE TO NO FLAME
“FLAME PRESENCE”
“POWER LEVEL”
the boiler is operating.
“PARAMETER”
parameter setting/display, or "info" or "counter", or in "activated alarms" (history).
“ALARM”
number specifies the cause which generated the alarm.
“CHIMNEY SWEEP”
sweep function" has been activated.
”ECO”, ALTERNATIVE ENERGY SOURCES
indicates that there is a solar system available.
CAUTION
– Access to the control panel of models
– On completion of the operations, refit the panel on
a
1
. The symbol for "Summer" mode is displayed.
and n are flashing, this indicates
l
. This symbol appears when the boiler is
and n will be off.
l
. The message indicates that after
.
y
. This symbol lights up during heating
.
.
. This indicates the power level at which
. This indicates that the user may be in
. This indicates that a fault has occurred. The
. This indicates that the "chimney
. Where active, it
Brava Slim
HE 20 R e
loosening screw (1) and removing panel (2).
the control panel and secure fully.
and
Brava Slim HE 40 R e
b
is possible after
Fig. 2
6
1.2 Preliminary checks
Commissioning of the out by professionally qualified personnel after which the boiler can operate automatically. It may however be necessary for the User to start the appliance autonomously without involving a technician: for example, after a holiday. First of all check that the gas isolation and water system valves are open.
Brava Slim HE R
boiler must be carried
1.3 Ignition
After having carried out the preliminary checks, perform the following to start the boiler: – set the main system switch to "ON" in order for the display to
show the pressure level in the system during refilling
make sure that the operating mode is set to "Stand-by";
not the case, press the button been selected
ON
– on the display (1), check that the heating system pressure
when cold is filling valve, which is to be prearranged on the system return, and fill until a pressure of the display (1)
– close the filling valve (2)
1-1.2 bar (100-120 kPa)
until "Stand-by" mode has
y
. Otherwise, open the
1-1.2 bar (100-120 kPa)
if this is
Fig. 3
is shown on
– set the room thermostat to the required temperature, or
if the system is equipped with a timed programmer or external temperature controller, check that this is ON and set accordingly.
1.4 Adjusting the heating temperature
If the heating temperature is to be increased or decreased, press the button desired temperature is reached. The temperature can be set to between 20 and 80°C.
followed by the buttons > or < until the
t
1
Fig. 4
– select the "WINTER" l operating mode by pressing the
button twice. the value of the delivery sensor detected at
y
that moment will appear on the display
7
1.5 Fault / malfunction codes
OFF
OFF
OFF
If a fault/malfunction is detected during boiler operation, the
“ALL”
message code (eg. If the message button
y
operating conditions are restored.
will appear on the display followed by the fault
“06”
- no flame detected).
d
for more than 3 seconds and check that the normal
also appears, press and hold the
– set the main system switch to "OFF" – close the gas valve.
Fig. 6
If this operation is not successful, be made, therefore: – close the gas isolation valve – set the main system switch to "OFF" – contact the Qualified Technical Personnel.
m
CAUTION
In case of failure, the fault code appears on the display. The list of all fault codes, with their descriptions, can be found in the section Commissioning.
ONLY ONE MORE ATTEMPT
Fig. 5
can
2 SHUTDOWN
2.1 Temporary shutdown
If the user wishes to interrupt boiler operation, press and hold the button mode"
n
“- -”
will appear on the display.
for at least one second, once if in "WINTER
y
or twice if in "SUMMER mode" l.
m
CAUTION
If the outside temperature might fall below ZERO, since the appliance is equipped with an "antifreeze function" and the "anti-freeze kit to -15°C":
– PUT THE BOILER INTO STAND-BY – leave the main system switch set to "ON" (boiler is
powered)
– leave the gas valve open.
2.2 Shutting down for long periods
If the boiler is to be left unused for a long period, the following operations need to be carried out: – press and hold the button
"WINTER mode" the boiler into stand-by
– set the main system switch to "OFF"
or twice if in "SUMMER mode" l to put
n
for at least 1 second, once if in
y
“- -”
will appear on the display
f
If the user is away temporarily, for a weekend, short trip etc and if the outside temperature is at ZERO: – press and hold the button
8
ELECTRICAL HAZARD
The boiler will still be powered.
y
or twice if in "SUMMER mode" by
once if in "WINTER mode" n
to put the boiler into stand-
l
– close the gas valve – close the heating system isolation valves – drain the heating system if there is the risk of freezing.
m
CAUTION
Contact the Qualified Technical Personnel if the procedure described above cannot be easily carried out.
Fig. 7
3 MAINTENANCE
4 DISPOSAL
3.1 Adjustments
For the appliance to operate correctly and efficiently it is recommended that the User calls upon the services of a Professionally Qualified Technician to carry out maintenance.
m
3.2 External cleaning
3.2.1 Cleaning the cladding
When cleaning the cladding, use a cloth dampened with soap and water or alcohol for stubborn marks.
d
CAUTION
Maintenance interventions must ONLY be carried out by professionally qualified personnel who will follow the indications authorised in the INSTALLATION AND MAINTENANCE INSTRUCTIONS.
IT IS FORBIDDEN
to use abrasive products.
BI-ANNUAL
4.1 Disposal of the equipment (European
Once it reaches the end of its operating life, the equipment MUST BE RECYCLED in line with current legislation. It can be handed over to recycling centres, if there are any, or to retailers that offer this service. Recycling prevents potential damage to the environment and health. It allows to recover a number of recyclable materials, with considerable savings in terms of money and energy.
d
Directive 2002/96/CE)
IT IS FORBIDDEN
dispose of the product as urban waste.
9
5 HANDOVER INSTRUCTIONS
Description
1 Fill in all the details on this Boiler manual.
Instruct the owner /users on the correct operation of the heating system, including how to turn the
2
systems on and off, adjust the time and temperature settings.
3 Instruct how to turn the heating system off in summer and on for winter.
Locate all major components, understand their functions and how to turn them on and off, their
4
functions and how to check and turn them on or off. Simple fault resolution i.e. power on.
5 Instruct how to check and remove air in the radiators. Provide a bleed key.
When done
Turn ON gas, bleed air out at the isolation valve unions. Reseal and check for gas leaks.
6
Turn gas OFF.
7 Underline the importance of these SERVICE RECORDS, keeping them safe & accessible.
Recommend that the boiler should be serviced at/ before the start of winter next year and then every
8
two years.
For any needs please contact Reece Customer Care 1800 080 055 or customercare@reece.com.au.
6 SERVICE RECORDS
Service – 1 – Year 1
Service technician
Service Company
Date
Name
PIC Licence No.
Contact phone number
Work Completed
Notes
10
Service – 2 – Year 3
Date
Service technician
Service Company
Contact phone number
Work Completed
Notes
Service – 3 – Year 5
Service technician
Service Company
Contact phone number
Name
Date
Name
PIC Licence No.
PIC Licence No.
Work Completed
Notes
Service – 4 – Year 7
Service technician
Service Company
Contact phone number
Work Completed
Notes
Date
Name
PIC Licence No.
11
Service – 5 – Year 9
Date
Service technician
Service Company
Contact phone number
Work Completed
Notes
Service – 7 – Year 11
Service technician
Service Company
Contact phone number
Name
Date
Name
PIC Licence No.
PIC Licence No.
Work Completed
Notes
Service – 8 – Year 13
Service technician
Service Company
Contact phone number
Work Completed
Notes
Date
Name
PIC Licence No.
For any needs please contact Reece Customer Care 1800 080 055 or customercare@reece.com.au.
12
TABLE OF CONTENTS
DESCRIPTION OF THE APPLIANCE
7 DESCRIPTION OF THE APPLIANCE 14
7.1 Characteristics ................................14
7.2 Check and safety devices ........................14
7.3 Identification ..................................14
7.4 Structure .....................................15
7.4.1 Brava Slim HE 20 R i
7.4.2 Brava Slim HE 20 R e
7.5 Technical features ..............................17
-
Brava Slim HE 40 R i....15
-
Brava Slim HE 40 R e...16
7.6 Main water circuit ..............................18
7.7 Sensors.......................................18
7.8 Expansion vessel ...............................18
7.9 Circulation pump...............................18
7.10 Control panel ..................................19
7.11 Wiring diagram ................................20
13
7 DESCRIPTION OF THE APPLIANCE
7.1 Characteristics
Brava Slim HE R
boilers which
Brava Slim HE R i
models installation, protected against atmospheric agents. The main elements choices made by are: – the total pre-mix microflame burner combined with a steel
– the sealed combustion chamber, with respect to the room
– the command and control microprocessor electronic board
Other special features of the – use of a smoke probe to control the relative temperatures. If
– the anti-freeze function which activates automatically if the
– the anti-blocking function of the pump and diverter valve, this
– the chimney sweep function lasts 15 minutes and makes the
– domestic hot water comfort function which allows the time
– screen display of the operating and self-diagnostic
Brava Slim HE R e
heat exchanger for heating and a rapid heat exchanger for DHW
where the boiler is installed
provides efficient management of both heating and hot water production. It can also be connected to a remote control with an Open Therm protocol or to room thermostat and/or external sensor. If connected to an external sensor, the boiler temperature varies on the basis of the external temperature according to a selected optimal climatic curve providing significant energy and economic savings.
the temperature exceeds 110°C the boiler will shut down in safety status, requiring intervention of the Technical Service department of qualified professional personnel
temperature of the water inside the boiler falls below the threshold of the value set at parameter "PAR 10" and , if there is an external sensor, if the external temperature falls below the threshold of the value set at parameter "PAR 11"
activates automatically every 24 hours if no request for heat has been made
job of the qualified technician easier when measuring the parameters and combustion efficiency
necessary for the hot water to become available to be reduced and ensures that the temperature is stable
parameters with error code display when the fault occurs. This makes repair interventions easier and allows appliance operation to be restored correctly.
are last generation condensing wall mounted
Sime
has produced for heating ONLY. Models
are designed for installation in rooms, while
are designed specifically for outdoor
Sime
for the
Brava Slim HE R
Brava Slim HE R
boilers are:
boilers
d
a
IT IS FORBIDDEN
to commission the appliance with safety devices which do not work or which have been tampered with.
WARNING
Safety device may only be replaced by professional
Sime
qualified personnel using
original spare parts.
7.3 Identification
The
Brava Slim HE R
1 Packaging label:
packaging and provides a code, the serial number of the boiler and the bar code
2 Technical Data Plate:
the boiler and provides the technical specification, appliance performance and any other information required by law.
1
2
boilers can be identified by means of:
this is located on the outside of the
this is located inside the front panel of
1
2
7.2 Check and safety devices
The
Brava Slim HE R
check and safety devices: – thermal safety thermostat 100°C – 3 bar (300 kPa) relief valve – heating water pressure transducer – delivery sensor – DHW sensor – smoke flue gas probe.
NOTE:
the proper fan operation of this boiler is checked electronically from the control panel. Then the use of an air pressure switch is not required.
14
boilers are equipped with the following
KEY:
1
Packaging label
2
Technical Data Plate
m
CAUTION
Tampering with, removing or failing to display the identification plate or carrying out any other operation which does not allow safe identification of the product or which may hinder installation and maintenance operations.
Fig. 8
7.4 Structure
10
12 13
232425
11
7.4.1
Brava Slim HE 20 R i
1
2
3
4
-
Brava Slim HE 40 R i
22
21
5
20
6
19
7
8
9
18
17
18
14
16
1
Heat exchanger bleed point
2
Heat exchanger
3
Combustion chamber door
4
Oversleeve
5
Flame viewing window
6
Ignition/detection electrode
7
Heat safety thermostat
8
Delivery sensor
9
Fan
10
Condensate siphon
11
Automatic by-pass
12
Control panel
13
Gas valve
14
System relief valve
15
Boiler drain
16
System pump
17
Water pressure transducer
18
Automatic bleed valve
19
Air-gas mixer
20
Expansion vessel
21
Air inlet pipe
22
Air-smoke chamber
23
Smoke flue gas probe
24
Air inlet
25
Smoke outlet
26
Coaxial duct
15
Fig. 9
15
7.4.2
Brava Slim HE 20 R e
26
24
25
23
1
2
3
4
5
-
Brava Slim HE 40 R e
22
21
20
6
7
8
9
10
11
12 13
1
Heat exchanger bleed point
2
Heat exchanger
3
Combustion chamber door
4
Oversleeve
5
Flame viewing window
6
Ignition/detection electrode
7
Heat safety thermostat
8
Delivery sensor
9
Fan
10
Condensate siphon
11
Automatic by-pass
12
Control panel
13
Gas valve
14
System relief valve
15
Boiler drain
19
18
14
16
System pump
17
Water pressure transducer
18
Automatic bleed valve
19
Air-gas mixer
20
Expansion vessel
21
Air inlet pipe
22
Air-smoke chamber
23
Smoke flue gas probe
24
Air inlet
25
Smoke outlet
17
16
15
Fig. 10
16
7.5 Technical features
DESCRIPTION
-
20 R e 40 R i
20 R i
CERTIFICATIONS Country of intended installation AUS Fuel NATURAL GAS / UNIVERSAL LPG SAI GLOBAL number SAI-400196 Class NO
x
HEATING PERFORMANCE HEAT INPUT Nominal MJ/h 80 140 Minimum MJ/h 16 28.0 HEAT OUTPUT Nominal (80-60°C) kW 19.7 34.5 Nominal (50-30°C) kW 21.4 37.5 Minimum NATURAL GAS (80-60°C) kW 3.9 6.9 Minimum NATURAL GAS (50-30°C) kW 4.3 7.5 Minimum UNIVERSAL LPG (80-60°C) kW 3.9 6.9 Minimum UNIVERSAL LPG (50-30°C) kW 4.3 7.5
EFFICIENCY Max useful efficiency (80-60°C) % 98.5 98.6 Min useful efficiency (80-60°C) % 97.5 98.6 Max useful efficiency (50-30°C) % 107.0 107.1 Min useful efficiency (50-30°C) % 107.5 107.1
ELECTRICAL SPECIFICATIONS Power supply voltage V 230 Frequency Hz 50 Absorbed electrical power W 105 135 Electrical protection degree IP X5D
COMBUSTION DATA Smoke temperature at Max/Min flow (80-60°C) °C 82/66 75 / 62 Smoke temperature at Max/Min flow (50-30°C) °C 59/45 54 / 39 Smoke flow Max/Min g/s 11.2/1.9 18.6 / 3.3 CO
2
at Max/Min flow rate (NATURAL GAS) % 9.0/9.0 9.0 / 9.0
CO
2
at Max/Min flow rate (UNIVERSAL LPG) % 10.0/10.0 10.0 / 10.0
NOZZLES  GAS Number of nozzles No. 1 Nozzle diameter (NATURAL GAS-UNIVERSAL LPG) mm 5.3 6.5 Gas consumption at Max/Min flow rate (NATURAL GAS) m
Gas consumption at Max/Min flow rate (UNIVERSAL LPG)
Gas supply pressure (NATURAL GAS/UNIVERSAL LPG)
3
/h 2.11/0.42 4.23 / 0.74
3
/h 0.83/0.16 3.10 / 0.74
m
mbar 11.3 / 27.5
kPa 1.13 / 2.75
TEMPERATURE  PRESSURE Max operating temperature °C 85 Heating adjustment range °C 20÷80
Max operating pressure
bar 3
kPa 300
Water content in boiler l 4.6 5.6
Brava Slim HE R
-
5 (< 70 mg/kWh)
40 R e
Lower Heat Output (Hs)
NATURAL GAS Hs.
37.78 MJ/m3 (15°C, 1013 mbar/101.3 kPa) -
UNIVERSAL LPG Hs.
95.65 MJ/m3 (15°C, 1013 mbar/101.3 kPa)
17
7.6 Main water circuit
12
TR
Resistance R (
0 800 1000 1200600400200
100
200
300
400
500
600/60
1 2
3
4 5
11
14
15 16 17
0°C 1°C 2°C 3°C 4°C 5°C 6°C 7°C 8°C 9°C
0°C
27279
26135
25044
24004
23014
22069
21168
20309
19489
18706
17959
17245
16563
15912
15289
14694
14126
13582
13062
8945 6247 4444 3216 2365 1766 1336 1024
12565
8622 6033 4300 3116 2296 1717 1300
998
Ω)
10°C
12090
11634
11199
10781
10382
9999
9633 6702 4751 3426 2512 1870 1411 1079
9281 6470 4595 3319 2437 1817 1373 1051
20°C
8313
8016
7731
7458
7196 5082 3653 2669 1982 1491 1137
6944 4913 3538 2589 1925 1451 1108
10
98
7
30°C
5828
5630
5440 3897 2839 2101 1577 1199
5258 3773 2753 2040 1534 1168
40°C 50°C 60°C 70°C 80°C 90°C
100°C
4161 3021 2229 1669 1266
973
4026 2928 2164 1622 1232
7.8 Expansion vessel
The expansion vessel installed on the boilers has the following
6
13
characteristics:
Description U/M
Total capacity l 9.0 10.0
Prefilling pressure
Useful capacity l 5.0 6.0 Maximum system content (*) l 124 140
kPa 100
bar 1.0
Brava Slim HE R
20 R i
-
20
R e
40 R i-40
R e
(*) Conditions of: Average maximum temperature of the system 85°C
Fig. 11
Start temperature at system filling 10°C.
KEY: M System delivery R System return G Gas supply Sc Condensate outlet S Safety valve outlet
1
Condensing heat exchanger
2
Combustion chamber
3
Fan
4
Thermal safety thermostat
5
Delivery sensor
6
Automatic by-pass
7
Water pressure switch
8
Automatic bleed valve
9
Pump
10
System expansion vessel
11
Gas valve
12
Boiler drain
13
System relief valve
14
Condensate siphon outlet
15
System delivery valve
16
Gas valve
17
System return valve
7.7 Sensors
The sensors installed have the following characteristics: – Dual sensor (thermal safety/output) NTC R25°C; 10kΩ β25°-
85°C: 3435 – domestic hot water sensor NTC R25°C; 10kΩ β25°-85°C: 3435 – external sensor NTC R25°C; 10kΩ β25°-85°C: 3435
Correspondence of Temperature Detected/Resistance
Examples of reading: TR=75°C → R=1925Ω TR=80°C → R=1669Ω.
18
m
CAUTION
– For systems with water content exceeding the
maximum system content (as indicated in the table) an additional expansion vessel must be prearranged.
– The difference in height between the relief valve
and the highest point of the system cannot exceed 6 metres. If the difference is greater than 6 metres, increase the prefilling pressure of the expansion vessel and the system when cold by 0.1 bar (10 kPa) for each meter increase.
7.9 Circulation pump
The flow-head performance curve available for the heating system is shown in the graph below.
RESIDUAL HEAD (mbar/kPa)
/50
/40
/30
/20
/10
0
m
CAUTION
The appliance is equipped with a by-pass which ensures water circulation in the boiler when the thermostatic valves or manual valves are used in the system.
40Ri - 40Re
20Ri - 20Re
FLOW (l/h)
Fig. 12
7.10 Control panel
21
2
Fig. 13
1
FUNCTIONAL BUTTONS
If pressed once or more than once for at least 1 second
y
during normal operation, this button allows the user to change the boiler operating mode in a cyclical sequence (Stand-by – Summer – Winter). If the boiler is experiencing a fault which can be reset, it allows boiler operation to be unblocked. (Note: the "SUMMER" mode is not applicable to this boiler).
In "parameter setting", the user can scroll through the
(
parameter index (decreasing) by pressing this button.
During normal operation, pressing this button displays
t
the flow temperature set point which can be between 20 and 80°C. In "parameter setting", the user can scroll through the parameter index (increasing) by pressing this button.
During normal operation, pressing this button allows
<
the user to reduce the flow temperature set point. In "parameter setting/display", the user can modify the parameter setting or value (decreasing) by pressing this button.
During normal operation, pressing this button allows
>
the user to increase the flow temperature set point. In "parameter setting/display", the user can modify the parameter setting or value (increasing) by pressing this button.
Programming connector cover plug.
c
NOTE:
pressing any one of these buttons for more than 30 seconds generates a fault on the display without preventing boiler operation. The warning disappears when normal conditions are restored.
2
DISPLAY
“SUMMER”
l
If the symbols that the chimney sweep function is active.
“WINTER”
n
operating in "Winter" mode. If no operating modes have been enabled both symbols
“RESET REQUIRED”
d
having repaired the fault, normal boiler operation can be restored by pressing the button
“HEATING”
t
operation or during the "chimney sweep function It flashes during the selection of the heating set point.
“BLOCK” DUE TO NO FLAME
f
“FLAME PRESENCE”
F
“POWER LEVEL”
v
the boiler is operating.
“PARAMETER”
p
parameter setting/display, or "info" or "counter", or in "activated alarms" (history).
“ALARM”
A
number specifies the cause which generated the alarm.
“CHIMNEY SWEEP”
z
sweep function" has been activated.
“EXTERNAL SENSOR”
e
sensor has been installed and that the boiler is working on a sliding temperature.
“HEATING SYSTEM PRESSURE”
a
pressure.
”ECO”, ALTERNATIVE ENERGY SOURCES
E
indicates that there is a solar system available.
m
CAUTION
– Access to the control panel of models
– On completion of the operations, refit the panel on
a
. The symbol for "Summer" mode is displayed.
and n are flashing, this indicates
l
. This symbol appears when the boiler is
and n will be off.
l
. The message indicates that after
.
y
. This symbol lights up during heating
.
.
. This indicates the power level at which
. This indicates that the user may be in
. This indicates that a fault has occurred. The
. This indicates that the "chimney
. This indicates that the external
. Display of heating system
. Where active, it
Brava Slim
HE 20 R e
loosening screw (1) and removing panel (2).
the control panel and secure fully.
and
Brava Slim HE 40 R e
is possible after
1
b
Fig. 14
19
7.11 Wiring diagram
230 V - 50 Hz
PI
N
BLACK
BLUE
BLACK
BLACK
CR
TA1
CN15
BLACK
BLACK
TA2
TPA
GND
RED
RED
RED
OUT
ORANGE
BLACK
SAUX
SE
321 4 5 6
BROWN
L
BLUE
GREEN
BLUE
GREEN
EV
CN13CN12
CN11
CN14
5V
GREEN
BLUE
BROWN
SF
V
4 3 2 1
BLUE
BLACK
GREEN
RED
F
BLACK
BLACK
CN2
CN3
BLUE
BLUE
TS
EAR
m
CD. 6302285
CN17
TRA
L
Line
N
Neutral
F
Fuse (3.15AT)
TRA
Ignition transformer
PI
System pump
V
Fan
EAR
Ignition / Detection electrode
EV
Gas solenoid valve
SM
Delivery sensor
To connect the "Air Thermostat" or, alternatively the "Remote Control", remove the bridge between terminals 5-6.
CAUTION
Users must:
– Use an omnipolar cut-off switch, disconnect switch
in compliance with AS/NZS Standards – Respect the connections L (Live) - N (Neutral) – Ensure that the special power cable is only replaced
with a cable ordered as a spare part and connected
by professionally qualified personnel – Connect the earth wire to an effective earthing
system. The manufacturer is not responsible for any
damage caused by failure to earth the appliance or
failure to observe the information provided in the
wiring diagrams.
CN6
CN5
d
CN4 CN1
RED
GREEN
SAUX
Auxiliary sensor
TS
Safety thermostat
TFU
Thermal fuse
SF
Smoke flue gas probe
TPA
Pressure transducer
TA1-TA2 SE
External sensor
SM
BLACK
BLUE
Air thermostat
TFU
IT IS FORBIDDEN
To use water pipes for earthing the appliance.
Fig. 15
20
INSTALLATION AND SERVICING INSTRUCTIONS
TABLE OF CONTENTS
8 INSTALLATION 22
8.1 Receiving the product ...........................22
8.2 Dimensions and weight..........................22
8.3 Handling ......................................22
8.4 Installation room ...............................22
8.5 New installation or installation of a replacement
appliance .....................................23
8.6 Cleaning the system ............................23
8.7 Water system treatment .........................23
8.8 Boiler installation ..............................23
8.9 Plumbing connections...........................24
8.10 Condensate outlet/collection .....................24
8.11 Gas supply ....................................24
8.12 Connecting the flue.............................25
8.12.1 Flue Terminal Positions ................ 25
8.12.2 Installation of coaxial flues 60/100mm –
80/125mm . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.12.3 Brava Slim HE 20 R i
8.12.4 Coaxial duct (Ø 60/100mm and Ø 80/125mm) 26
8.12.5 Brava Slim HE 20 R e
8.13 Electrical connections...........................27
8.13.1 External sensor....................... 28
8.13.2 Chrono-thermostat or Air Thermostat .... 29
8.13.3 EXAMPLE of use of the command/control device on some types of heating systems.. 29
8.14 Refilling or emptying............................30
8.14.1 REFILL operations .................... 30
8.14.2 EMPTYING operations ................. 30
-
40 R i.................26
-
40 R e................27
9 COMMISSIONING 31
9.1 Preliminary operations ..........................31
9.2 Before commissioning ..........................31
9.2.1 Self-calibrating procedure.............. 31
9.3 Parameter setting and display ....................32
9.4 List of parameters..............................32
9.5 Fault / malfunction codes........................33
9.6 Display of operating data and counters.............34
9.7 Checks after commissioning .....................35
9.7.1 Chimney sweeper function.............. 35
9.8 Gas conversion.................................36
10 MAINTENANCE 37
10.1 Adjustments...................................37
10.2 External cleaning...............................37
10.2.1 Cleaning the cladding.................. 37
10.3 Cleaning the inside of the appliance ...............37
10.3.1 Removing components................. 37
10.3.2 Cleaning the burner and the combustion
chamber ............................ 38
10.3.3 Checking the ignition/detection electrode . 38
10.3.4 Final operations ...................... 38
10.4 Checks .......................................38
10.4.1 Checking the smoke duct............... 38
10.4.2 Checking the expansion vessel pressure .. 38
10.5 Unscheduled maintenance .......................39
10.6 Possible faults and solutions .....................39
11 COMMISSIONING BOILER CHECKLIST 41
12 EXPLODED VIEWS 42
13 REMOVING COMPONENTS 48
13.1 Remove panels ................................48
13.1.1 Front panel .......................... 48
13.1.2 Side panels .......................... 48
13.2 Rotate control panel ............................48
13.3 Remove/replace sensor and thermostat............49
13.3.1 Smoke flue gas probe.................. 49
13.3.2 Delivery sensor ....................... 49
13.3.3 Heat safety thermostat................. 50
13.4 Remove electronic board ........................50
13.5 Remove/replace combustion head unit and fan . . . . . . 51
13.6 Remove/replace the ignition and flame detection
electrode .....................................52
13.7 Remove/replace the siphon ......................52
13.8 Remove/replace gas valve .......................53
13.9 Remove/replace the expansion vessel .............53
13.10 Remove/replace system pump....................54
21
8 INSTALLATION
H
m
CAUTION
The appliance must be installed by the Sime Technical Service only, or by a qualified professional.
8.1 Receiving the product
Brava Slim HE R
protected by cardboard packaging. Open the cardboard packaging, with appropriate tool and pull out the boiler.
The plastic bag found inside the packaging contains the following: – Installation, use and maintenance manual – Paper template for boiler installation – Certificate of warranty – Hydrostatic test certificate – System booklet – Bag with expansion plugs
d
IT IS FORBIDDEN
Do not leave packaging material around or near children since it could be dangerous. Dispose of it as prescribed by legislation in force.
appliances are delivered in a single unit
Fig. 16
8.2 Dimensions and weight
Description
W (mm) 400 450 400 450 D (mm) 250 256 250 303 H (mm) 700 917 700 917
Weight (kg) 28.5 30.0 30.0 32
20 R i 20 R e 40 R i 40 R e
Brava Slim HE R
8.3 Handling
Once the packaging has been removed, the appliance is to be handled manually, tilting it slightly, lifting it and applying pressure in the points indicated in the figure.
Fig. 18
d
a
IT IS FORBIDDEN
To grip the appliance casing. Hold the "solid" parts of the appliance such as the base and structural frame.
WARNING
Use suitable tools and accident protection when removing the packaging and when handling the appliance. Observe the maximum weight that can be lifted per person.
8.4 Installation room
The room where the appliance is to be installed must comply with the Technical Regulations and Legislation in force. The minimum temperature of the installation room must NOT
-5 °C
be lower than
m
W
22
D
Fig. 17
CAUTION
Remember to consider the space needed in order to access the safety/adjustment devices and to carry out maintenance interventions (see Fig. 19).
.
APPROXIMATE MINIMUM DISTANCES
≥ 300 mm
≥ 900 mm
≥ 50 mm
Before removing an old heat generator from an existing system, it is recommended that the user: – puts a descaling additive into the water system – allows the system to work with the generator active for a few
days
– drains the dirty water from the system and flushes the system
with clean water once or more than once. If the old generator has already been removed or is not available, replace it with a pump to circulate water in the system and then proceed as described above. Once cleaning operations have been carried out and before installing the new appliance, it is recommended that a fluid is added to the water system to protect it from corrosion and deposits.
Fig. 19
m
CAUTION
These minimum clearances must be maintained also in consideration of outdoor installations in confined spaces (e.g. alcoves).
8.5 New installation or installation of a replacement appliance
When
Brava Slim HE R
systems requiring updating, it is recommended the installer checks with appliance supplier for advice: – the connecting flue pipe is suitable for the combustion
temperature of the appliance, calculated and manufactured in compliance with Standards, current editions, that it is as straight as possible, air tight, isolated, with no obstructions or restriction and that it has appropriate condensate collection and evacuation systems
– the electrical system has been manufactured in compliance
with specific Standards and by professionally qualified personnel
– the fuel delivery line and the tank (LPG) comply fully with
specific Standards
– the expansion vessel ensures total absorption of the fluid
dilation in the system
– the pump flow-head performance is sufficient for the system
characteristics
– the system is clean, free of any sludge, deposits, de aerated
and air tight. For system cleaning, please refer to the relevant paragraph.
boilers are installed on old systems or
m
CAUTION
For further information on the type of additive and usage, please contact the appliance manufacturer.
8.7 Water system treatment
When filling and restoring the system it is good practice to use water with: – aspect: clear if possible – pH: 6÷8 – hardness: < 25°f. If the water characteristics are different from those indicated, it is recommended that a safety filter is used on the water delivery pipe to retain impurities, and a chemical treatment system to protect against possible deposits and corrosion which could affect boiler operation. If the systems are only low temperature systems, it is recommended that a product is used to prevent the development of bacteria. In any case, please refer to and comply with Legislation and specific Technical Standards in force.
8.8 Boiler installation
Brava Slim HE R
installation onto a solid wall. For installation: – remove the cladding (only on models
Brava Slim HE 40 R e
– place the steel sheet template (2) (if supplied) on the wall (1) – make the holes and insert the expansion plugs (3) – hook the boiler onto the plugs.
boilers leave the factory with a template for
Brava Slim HE 20 R e
)
3
and
1
m
d
CAUTION
Gas pipe sizing, flue installation and appliance ventilation must comply with AS/NZS 5601.
IT IS FORBIDDEN
Do not install the boiler in special environments that may limit its optimum operation (e.g. marine environment).
8.6 Cleaning the system
Before installing the appliance on a newly constructed system or replacing a heat generator on an existing system, it is important that the system is thoroughly cleaned to remove sludge, slag, dirt, residue etc.
2
Fig. 20
23
m
m
CAUTION
– The wall on which the appliance is to be hung must
be of adequate strength and capable of holding the weight of the appliance and associated components and pipework.
CAUTION
– The height of the boiler is to be such that disassembly
and maintenance interventions are facilitated.
8.9 Plumbing connections
The plumbing connections have the following characteristics and dimensions.
Brava Slim HE 20 R i
49
Sc
130 130 ==
M
Brava Slim HE 20 R e
-
40 R i
G R
400
-
40 R e
Sc
93
212
Fig. 21
8.10 Condensate outlet/collection
In order to collect the condensate, it is recommended that: – the appliance condensate outlets and the smoke outlet are
ducted
– a neutralising device is prearranged
>3%
– the outlet incline is
m
CAUTION
– The condensate outlet duct must be airtight,
suitably sized to that of the siphon and must not be restricted at any point.
– The condensate outlet must be constructed in full
compliance of the National or Local regulations in force.
– Before commissioning the appliance, fill the siphon
with water.
.
8.11 Gas supply
Brava Slim HE R NATURAL GAS
the need for any type of mechanical conversion. Select parameter the type of gas to be used. If changing the type of gas to be used, carry out the entire appliance Boiler connection to the gas mains must be carried out in full compliance with installation Standards in force. Before connecting the boiler to the gas mains, the user must ensure that: – the type of gas is correct for the appliance – the pipes are clean – the gas supply pipe is the same dimension as or greater than
that of the boiler fitting (G3/4") and with a load loss less than or equal to that contemplated between the gas mains and the boiler.
boilers leave the factory prearranged for gas
and can also work with
”03”
(see “Parameter setting and display") and set
“COMMISSIONING”
phase.
Universal LPG
without
73 Sc
130
M
Description
M - System delivery Ø 3/4" G R - System return Ø 3/4" G G - Gas supply (*) Ø 3/4" G Sc - Condensate outlet Ø 25 mm
(*) Brass adaptor for gas connection supplied. G3/4" to R3/4".
130 ==
G R
450
20 R i 20 R e 40 R i 40 R e
97
175 (20 R e) 216 (40 R e)
Brava Slim HE R
Sc
Fig. 22
a
m
WARNING
Once installation has been completed, check that the joints are air tight as indicated in the installation Standards.
CAUTION
It is recommended that the gas line has a suitable filter.
24
8.12 Connecting the flue
8.12.1 Flue Terminal Positions
a
j
w
f
DESCRIPTION
Flue terminal T Mechanical air inlet I Gas meter M Electricity meter of fuse box P Shaded area indicates prohibited area Below eaves, balconies and other projections (Appliances over 50MJ/h) a 300 From the ground, above a balcony or other surface b 300 From a return wall or external corner c 300 From a gas meter d 1000 From an electricity meter or fusebox/breaker panel e 500 From a drain pipe or soil pipe f 75 Horizontally from any building structure or obstruction facing a flue terminal g 500 From any other flue terminal, cowl or combustion air intake h 300
Horizontally from any opening window, door, non-mechanical air inlet or other opening into a building with the exception of sub-floor ventilation
From a mechanical air inlet including a spa blower. k 1000 Vertically below an opening window, non-mechanical air inlet or any other opening into a building with
the exception of sub-floor ventilation
n
I
c
k
j j
Door
k
h
T
h
h
T
g
e
e
P
d
d
M
j 300
n 500
c
g
b
Brava Slim HE R
Min. Clearance (mm)
T
Fig. 23
m
m
CAUTION
Use as a guide only. See AS/NZS5601 for flue design details.
Refer to AS/NZS5601, current version, or local gas fitting rules for specific locations.
CAUTION
– The location of the flue terminal must comply with
the clearances shown on this page. If you are unsure about clearances not indicated here, in general refer to AS/NZS 5601, or your local authority.
m
CAUTION
– All measurements are the minimum clearances
required.
– Terminals must be positioned so to avoid combustion
products entering the building.
– When the installer installs the flue through a
wall, the wall must be adequately sealed and the hole must not affect the building structure or fire resistance.
– Install a fire proof back board if installing on
combustible surfaces.
– The fixing method and the wall structure must be
sufficient to hold the weight of the boiler.
25
8.12.2 Installation of coaxial flues 60/100mm –
max 0.5 m
max 0.5 m
C33
C13
C13
C33
80/125mm
Coaxial flue kits that are supplied separately. The diagrams below, illustrate some examples of fluing options allowed and the maximum lengths than can be achieved. It is essential that a flue gas analysis point is made available directly above the boiler.
8.12.3
Permitted outlets
Brava Slim HE 20 R i
-
40 R i
8.12.4 Coaxial duct (Ø 60/100mm and Ø 80/125mm)
Description
Coaxial duct kit 8096250 8096253 Extension W. 1000 mm 8096150 8096171 Extension W. 500 mm 8096151 8096170
Vertical extension W. 140 mm with smoke analysis take-off point
Adapter for Ø 80/125 mm - 8093150 Additional 90° curve 8095850 8095870 Additional 45° curve 8095950 8095970
Roof outlet terminal W. 1284 mm
Ø 60/100 mm Ø 80/125 mm
8086950 -
8091205 8091205
Coaxial accessories
Load loss - Equivalent lengths
Model
90° curve 1.5 2 45° curve 1 1
Ø 60/100 mm Ø 80/125 mm
Minimum-Maximum Lengths
Duct Length
Ø 60/100
Model
Brava Slim HE 20 R i Brava Slim HE 40 R i
W
Horizontal
(m)
Min.
Max.
- 6 1.3 8 - 12 1.2 15
- 4 1.3 6 - 10 1.2 13
Code
Leq (linear metres)
Duct Length
Ø 80/125
H
Vertical
(m)
Min.
Max.
W
Horizontal
(m)
Min.
Max.
H
Vertical
(m)
Min.
Max.
C13
Concentric wall smoke outlet The pipes can start from the boiler but the outlets must be concentric or close together (no more than 50 cm) to be subject to similar wind conditions.
C33
Concentric roof smoke outlet The pipes can start from the boiler but the outlets must be concentric or close together (no more than 50 cm) to be subject to similar wind conditions.
m
WARNINGS
– The smoke flue and the connection to the flue pipe
must be in compliance with the national and local Standards and Legislation in force.
– The use of rigid ducts which are resistant to
temperature, condensate, mechanical stress and are air-tight is compulsory.
– Outlet ducts which are not isolated are a risk of
danger.
Fig. 24
26
8.12.5
302 ( 20 R e)
247 ( 40 R e)
450
OFF
1
The boilers supplied already complete with coaxial ducts for smoke outlet and combustion air inlet.
Brava Slim HE 20 R e
Brava Slim HE 20 R e
1
6
-
40 R e
and
Brava Slim HE 40 R e
2
3
are
4
5
8.13 Electrical connections
The boiler is equipped with a ready wired power cable which is to be connected to a 230V~50 Hz network. If this cable needs to be replaced, an original spare must be
Sime
requested from Therefore only the connections of the original components as shown in the table are needed. These are to be ordered separately from the boiler.
DESCRIPTION CODE
External sensor kit (ß=3435, NTC 10KOhm at 25°C) 8094101 Remote control HOME (open therm) 8092280 Remote control HOME PLUS (open therm) 8092281
.
KEY:
1
90° coaxial bend
2
Coaxial duct (supplied, but not fitted)
3
Air inlet
4
Smoke outlet
5
Outlet terminal (supplied, but not fitted)
6
Take-off point for smoke analysis
176
110
Fig. 25
m
a
To facilitate introduction of the connection wires of the optional components into the boiler: – disassemble the smoke outlet duct of the
– remove the screws (1), pull the front panel (2) forwards and
CAUTION
The maintenance interventions described must ONLY be carried out the professionally qualified personnel.
WARNING
Before carrying out any interventions described: – set the main system switch to "OFF" – close the gas valve – make sure that no hot parts inside the appliance are
touched.
Brava Slim HE 20 R e
Brava Slim HE 40 R e
and
release it from the top by lifting it
, if fitted
Fig. 27
2
Ø 60/100
Fig. 26
Fig. 28
27
– remove the screws (3) securing the control panel (4)
3
20 15 10 5 0 -10 -15-5 -20
°C
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
4
b
a
5
m
(*) The manufacturer is not responsible for any damage
d
CAUTION
It is compulsory: – to use an omnipolar cut-off switch, disconnect
switch in compliance with AS/NZS Standards
– if the power cable is to be replaced, that ONLY
a special cable is used with a factory produced re-wired connector, ordered as a spare part and connected by a professionally qualified person
– to connect the earth wire to an effective earthing
system (*)
– that before any intervention on the boiler, the mains
power is disconnected by setting the main system switch to "OFF".
caused by failure to earth the appliance or failure to observe the information provided in the wiring diagrams.
IT IS FORBIDDEN
To use water pipes for earthing the appliance.
Fig. 29
– insert the connection wires into the cable gland (6) and the
opening (7) on the control panel
6
7
Fig. 30
– bring the control panel (4) to the original position and secure
it with the screws (3) which were removed previously
– connect the component wires to the terminal board (8)
following the indications provided on the data plate (9).
8.13.1 External sensor
The boiler is prearranged for connection to an external air temperature sensor and can operate with a sliding temperature. This means that the delivery temperature sent to the boiler can vary on the basis of the external temperature depending on the climatic curve selected from those shown in the diagram (Fig.
32). When fitting the sensor on the outside of the building, follow the instructions provided on the packaging of the product itself.
Climatic curve
Delivery temperature
90
80
70
60
50
40
30
20
K=9 K=6 K=4.5 K=3
K=2.2
K=1.5
K=0.75
°C
External temperature
4
9
8
CR-TA
SE
SAUX
28
6 5 4 3 2 1
3
Fig. 31
m
Fig. 32
CAUTION
If there is an external sensor, in order to select the optimal climatic curve for the system and therefore the delivery temperature based on the external temperature:
– press the button – press buttons
been selected (within the range
for 1 second
t
or < until the required curve K has
>
K=0.0 - K=9.0
).
8.13.2 Chrono-thermostat or Air Thermostat
CR
SE
SE
The electrical connection of the chrono-thermostat or air thermostat has already been described. When fitting the component in the room where the readings are to be taken, follow the instructions provided with the device.
MULTI ZONE system - with zone valve, air thermostat and external sensor.
8.13.3 EXAMPLE of use of the command/control device on some types of heating systems
KEY M System delivery R System return CR Remote control SE External sensor TA÷TA3 Air thermostat for the zone VZ1-VZ3 Zone valves RL1-RL3 Zone relays P1-P3 Zone pump SP Hydraulic separator
ONE DIRECT ZONE system , external sensor and air thermostat.
SE
M
R
TA
TA
M
m
TA1
R
VZ1 VZ2 VZ3
TA2 TA3
Fig. 35
CAUTION
Set the parameter "tS 17 = DELAY SYSTEM PUMP ACTIVATION to allow the opening of zone valve Vz.
Fig. 33
MULTI ZONE system - with pump, air thermostat and external sensor.
TA
TA1
RL1
M
R
SP
TA2
RL2 RL3
TA3
P2P1
P3
Fig. 34
29
8.14 Refilling or emptying
Before carrying out the operations described below, make sure that the main system switch is set to "ON" in order for the display to show the pressure level in the system during refilling.
Make sure that the operating mode is set to "Stand-by";
the case, press the button
for at least 1 second until this
y
mode has been selected.
ON
if this is not
6 3
Fig. 36
8.14.1 REFILL operations
Remove the front panel:
– disassemble the smoke outlet duct of the
Brava Slim HE 40 R e
and
, if fitted
– remove the two screws (1), pull the front panel (2) forwards
and release it from the top by lifting it.
2
Brava Slim HE 20 R e
1
Fig. 37
NOTE:
to completely remove all air from the system, it is
recommended that this operation is repeated a number of times.
– check the pressure on the display and if necessary top up until
the correct pressure reading appears – close the automatic bleed valve (3) – fill the siphon disconnecting it from the pipe or using (by
means of) the smoke take-off point.
Refit the front panel of the boiler hooking it on at the top, pushing it forwards and securing it with the screw (1) which was removed previously. Fit the smoke outlet duct of the
Slim HE 40 R e
.
Brava Slim HE 20 R e
8.14.2 EMPTYING operations
Boiler:
– loosen the automatic bleed valve (3) – close the heating circuit isolation valves – check that the filling valve is closed – connect a rubber hose to the boiler drain valve (7) and open it – when it has fully emptied, close the drain valve (7) – close the automatic bleed valve (3).
and
Fig. 38
Brava
Heating circuit:
– open the isolation and air bleeding valves in the highest points
of the system – loosen the automatic bleed valve (3) – open the isolation valves of the heating circuit (if present) – Open the filling valve, which should be on the system return – Fill until the water overflows from the air bleeding valves and
shut off the valves again
1-1.2
– Continue filling until the pressure reaches
bar (100-120
kPa) as shown on the display – close the filling valve – check that there is no air in the system by bleeding all the
radiators and the circuit on the high points of the system – remove the front plug (6) of the pump and use a screwdriver
to check that the impeller is not blocked – replace the plug (6)
30
3
7
Fig. 39
9 COMMISSIONING
9.1 Preliminary operations
Before commissioning the appliance, check that: – the type of gas is correct for the appliance – the gas isolation valves for the heating system and the water
system are open – the pump impeller rotates freely – the siphon has been filled – the flue is fitted correctly.
9.2 Before commissioning
After having carried out the preliminary operations, perform the following to start the boiler: – set the main system switch to "ON"
ON
– as soon as the symbols begin to flash, release the buttons <
and press the button y,
and
>
– the "Automatic self-calibrating procedure" starts
ensure that the system isolation valves are open
– adjust the room thermostat to request status, at a high value – the values flash on the display:
followed by an "intermediate value" and finally value)
within 3 seconds
“100”
(maximum value),
“00”
(minimum
Fig. 40
– the type of gas for which the boiler has been calibrated,
“LG”
(methane) or
After this the correct representation of the symbols will be
checked and finally
– check that the system pressure as shown on the pressure
gauge when the system is cold , is between
and 120 kPa)
– press the button y twice to select "WINTER mode" n.
the value of the delivery sensor detected at that moment will
appear on the display
(LPG,) will appear followed by the power.
“- -”
will appear on the display
1 and 1.2 bar (100
“nG”
The operator must wait for approximately 15 minutes for the "self-calibrating procedure" to end and the message "WINTER mode" Once the procedure has terminated: – stop the heating request by adjusting the room thermostat. if there is a fault, the message the fault code (eg.
d
m
– adjust the air thermostat and check that the boiler starts and
operates correctly
– carry out the procedure "Chimney sweeper function",
to check the mains gas pressure, detect the combustion parameters and to measure the combustion efficiency required by legislation in force.
to reappear on the display.
n
“ALL”
will appear on the display,
“06”
- no flame detected) and the message
.
CAUTION
To restore the start conditions press and hold the button can be performed up to a maximum of 6 times without the "self-calibrating procedure" being interrupted.
for more than 3 seconds. This operation
y
9.2.1 Self-calibrating procedure
Carry out the "Automatic self-calibrating procedure" as follows: – press and hold down the buttons
approximately 12 seconds until the flashing symbols
appear on the display
n
and > at the same time for
<
l
and
31
9.3 Parameter setting and display
To go into the parameter menu: – from the selected mode (eg. WINTER)
– once the required parameter has been reached, press the
buttons
or <to modify the value within the permitted range.
>
The modifications are stored automatically.
– press the buttons ( and t (for approximately 5 seconds)
at the same time until
“PAR 01”
(parameter number) and the
value set (0-4) appears on the display
– press the button t to scroll up the list of parameters and
then
NOTE:
to scroll down the list
(
holding the buttons ( or t increases the speed of the
When all the parameter modifications have been made, exit the parameter menu by pressing and holding down the buttons
at the same time
and
t
NOTE:
In case of power failure all settings are stored.
until the initial screen is displayed.
scrolling movement.
9.4 List of parameters
Type No. Description Range U/M Step Default
CONFIGURATION
PAR 01
PAR 02
PAR 03
PAR 04
PAR 08 External sensor value correction -5 .. +5 °C 1 0 PAR 09 Ignition fan speed 80 .. 160 RPMx25 1 128
PAR 10 Boiler Antifreeze Threshold 0 .. +10 °C 1 3
PAR 11
PAR 12 Heating Curve Incline 0 .. 80 - 1 20 PAR 13 Minimum Heating Temperature Adjustment 20 .. PAR 14 °C 1 20 PAR 14 Maximum Heating Temperature Adjustment PAR 13 .. 80 °C 1 80 PAR 15 Maximum power heating 0 .. 100 % 1 100
PAR 16 Heating Post-Circulation Time 0 .. 99
PAR 17 Heating Pump Activation Delay 0 .. 60
PAR 18 Re-ignition Delay 0 .. 60 Min 1 3 PAR 21 Minimum power heating/domestic hot water (premixed) 0 .. 100 % 1 0
PAR 23
Index showing boiler power in kW 1 = 25; 2 = 30; 3 = 35; 4 = 40 Hydraulic configuration 0 = rapid 1 = storage tank with thermostat or heating only 2 = hot water tank with sensor 3 = bithermic 4=instant with solar power input 5 = open vent 6 = boiler with heat pump Gas Type Configuration 0 = NATURAL GAS; 1 = UNIVERSAL LPG Combustion configuration 0 = sealed chamber with combustion control
DOMESTIC HOT WATER - HEATING
External Sensor Antifreeze Threshold
-- = Disabled
External relay 1 function 0 = not used; 1 = remote alarm NO; 2 = remote alarm NC; 3 = zone valve; 4 = automatic filling; 5 = external request; 6 = recirculation pump; 7 = zone valve with OT; 8 = relaunch pump; 9 = boiler with heat pump (circulator)
1 .. 4 - 1 1 or 4
0 .. 6 - 1 1
0 .. 1 - 1 0
- - - 0
-9 .. +5 °C 1 -2
seconds
x 10
seconds
x 10
0 .. 9 - - 0
1 3
1 0
(
32
Type No. Description Range U/M Step Default
OFF
External relay 2 function
PAR 24
PAR 25
PAR 26 Zone Valve / Pump Relaunch Delay 0 .. 99 Min 1 1
PAR 29
PAR 35
PAR 40 Modulating Pump Speed
PAR 41 ∆T Modulating pump delivery/Return 10 .. 40 °C 1 20 PAR 42 Select heat pump or boiler convenience (only if PAR 02 = 6) -20 .. 30 °C - 5 PAR 43 Heat pump boiler aid activation delay (only if PAR 02 = 6) 1 .. 60 Min - 3
PAR 47
PAR 48 INST Parameter set to default 0 .. 1 - - 0
0 = not used; 1 = remote alarm NO; 2 = remote alarm NC; 3 = zone valve; 4 = automatic filling; 5 = external request; 6 = recirculation pump; 7 = zone valve with OT; 8 = relaunch pump; 9 = boiler with heat pump Auxiliary TA function 0 = according to TA 1 = TA Antifreeze 2= domestic hot water disabled
Anti-legionella Function (Only hot water tank)
-- = Disabled Digital / analogue Pressure switch 0 = water pressure switch 1 = water pressure transducer 2 = water pressure transducer (only pressure displayed)
System pump forcing (only in winter mode) 0 = Disabled 1 = Enabled
RESET
0 .. 9 - - 0
0 .. 2 - 1 0
50 .. 80 - 1 --
0 .. 2 - 1 1
-- = No modulation AU = Automatic 30
.. 100
0 .. 1 - 1 0
% 10 AU
In the event of a fault/malfunction the message on the display with the alarm number eg.
“ALL”
“ALL 05”
will appear
(Domestic
Hot Water Sensor Fault).
Before repairing the fault: – disconnect the appliance from the mains power by setting the
main switch to "OFF"
Fig. 41
– as a precautionary measure, close the gas isolation valve.
Repair the fault and start-up the boiler again.
NOTE:
after having repaired the fault, when the alarm number appears on the display together with the message (see figure), press the button
for approximately 3 seconds
y
d
to start the appliance up again.
9.5 Fault / malfunction codes
Type No. Description
AL 02 Low water pressure in system AL 05 Delivery sensor fault AL 06 No flame detection AL 07 Safety thermostat intervention AL 08 Fault in the flame detection circuit AL 09 No water circulating in the system AL 10 Auxiliary sensor fault AL 11 Gas valve modulator disconnected AL 12 Incorrect configuration of the open /sealed chamber AL 13 Smoke probe intervention AL 14 Smoke probe fault AL 15 Fan check cable disconnected AL 18 Condensate level fault AL 28 Maximum number of consecutive releases
ALL 30 Return sensor (SR) fault
AL 37 Fault due to low network voltage AL 40 Incorrect network frequency detected AL 41 Flame loss more than 6 consecutive times AL 42 Button fault AL 43 Open Therm communication fault
ALL 44 No flame valve opening time sum anomaly
AL 62 Self-calibrating procedure is required
AL 72 Incorrect positioning of the delivery sensor ALL 77 EV2 SGV current max/min absolute limits error ALL 78 EV2 SGV current upper limit error ALL 79 EV2 SGV current lower limit error
33
Type No. Description
ALL 80
AL 81 Block due combustion during start-up
ALL 82 Block due to numerous combustion control failures
AL 83 Irregular combustion (temporary error)
ALL 84
ALL 88 Internal error (board component protection) ALL 89 Unstable combustion feedback signal error ALL 90 Combustion set cannot be reached error
ALL 92
ALL 93 Combustion set cannot be reached error ALL 95 Flame signal micro interruptions error
AL 96 Block due to clogging in smoke outlet ALL 98 SW error, board start-up ALL 99 General board error
Fault on the valve control logic line/valve cable damaged
Flow rate reduced for (presumed) low pressure on mains gas
System has reached maximum air correction error (at the minimum flow rate)
9.6 Display of operating data and counters
Once the boiler is operating a qualified technician can view the operating data and the counters as follows: – from the operating screen in the "WINTER mode
– go into
same time
“DISPLAY”
by pressing the buttons ( and <
for more than 3 seconds until the following screen
appears
n
"
at the
– Once in this section, proceed with button t or (.
When all the values have been displayed, exit the menu by pressing and holding down the button yfor approximately 5 seconds until the initial screen is displayed.
TABLE OF INFORMATION DISPLAYED
Type No. Description
PAR 00 SW version
PAR 01 External sensor
PAR 02
PAR 03 Smoke probe
PAR 05 AUX auxiliary sensor
PAR 06
PAR 07 Power level
PAR 08 Flow meter rate
PAR 09
PAR 10
Delivery sensor temperature
Actual heating SET temperature
Water pressure transducer reading Display of current fan revolutions
Range
- 9 .. 99
- 9 .. 99
- 9 .. 99
- 9 .. 99
Pa r.
13 …
Pa r.
14
0 ..
99
0 ..
99
0 ..
99
0 ..
RPM x 100 1
99
U/M Step
°C 1
°C 1
°C 1
°C 1
°C 1
% 1
l/min 0.1
bar 0.1
From this point, the technician has 2 options: – scroll through the list of
(PARc)”
by pressing the button t. Scrolling will be in sequence
– display the
the button
34
“activated alarms”
(
“information (PAR)”
(no more than 10) by pressing
and
“counters
TABLE OF COUNTER DISPLAYED
Type No. Description
PAR c0
PAR c1
PAR c2
PAR c3 total no. faults
PAR c4
PAR c5
PAR c6
total no. of boiler operating hours
total no. of burner operating hours
total no. of burner ignitions
total no. of times installer parameters "ALL"accessed total no. of times OEM parameters accessed time unitl next maintenance intervention
Range
0 ..
99
0 ..
99
0 ..
99
0 ..
99
0 ..
99
0 ..
99
1 ..
199
U/M Step
0.1; from
h x 1000
h x 1000
h x 1000
x 1 1
x 1 1
x 1 1
months 1
0.0 to 9.9; 1; from 10
to 99
0.1; from
0.0 to 9.9; 1; from 10
to 99
0.1; from
0.0 to 9.9; 1; from 10
to 99
TABLE OF ACTIVATED ALARMS/FAULTS
3
Type No. Description
PAR A0 Last activated alarm/fault PAR A1 Last but one activated alarm/fault PAR A2 Third from last activated alarm/fault PAR A3 Previous activated alarm/fault PAR A4 Previous activated alarm/fault PAR A5 Previous activated alarm/fault PAR A6 Previous activated alarm/fault PAR A7 Previous activated alarm/fault PAR A8 Previous activated alarm/fault PAR A9 Previous activated alarm/fault
– close the gas valve – loosen the screw of the "mains pressure" point (6) and connect
a pressure gauge
9.7 Checks after commissioning
9.7.1 Chimney sweeper function
The chimney sweeper function is used by the qualified maintenance technician to check the mains gas pressure, detect the combustion parameters and to measure the combustion efficiency required by legislation in force.
This function lasts 15 minutes and is activated by proceeding as follows: – disassemble the smoke outlet duct of the
Brava Slim HE 40 R e
and
– if the panel (2) has not already been removed, remove the
two screws (1), pull the front panel (2) forwards and release it from the top by lifting it
2
, if not already removed
Brava Slim HE 20 R e
6
– open the gas valve – power the boiler by setting the main switch to "ON"
– press the button y for at least 1 second until "SUMMER"
mode
– press and hold down the buttons
for approximately 10 seconds until the message “Hi” appears on the display together with the flashing symbols
has been selected
l
ON
and > at the same time
<
l
Fig. 44
Fig. 45
and
n
1
Fig. 42
– remove the screws (3) securing the control panel (4) – move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
4
b
a
5
Fig. 43
– press the button > to make the boiler operate at maximum
power "Hi" and check that the mains gas pressure value on the pressure gauge is correct. Take a reading of the combustion data and measure the combustion efficiency.
– press the button
power "Lo". The message together with the flashing symbols
to make the boiler operate at minimum
<
“Lo”
will appear on the display
and
l
n
35
– take the combustion data reading – press the button
Procedure”. The boiler water delivery temperature will appear on the display
– disconnect the pressure gauge, carefully close the pressure
point (6), put the control panel back to the original position and refit the front panel (2).
Gas supply pressure
Type of gas NATURAL GAS UNIVERSAL LPG
Pressure (mbar/kPa) 11.3/1.13 27.5/2.75
to exit the "Chimney sweeper
y
9.8 Gas conversion
Brava Slim HE R
UNIVERSAL LPG without the need for any mechanical conversion. Select parameter and display") and set the type of gas to be used.
If changing the type of gas to be used, carry out the entire appliance
models can work with NATURAL GAS or
“COMMISSIONING”
”PAR 03”
phase.
(see "Parameter setting
36
10 MAINTENANCE
OFF
1
3
10.1 Adjustments
For the appliance to operate correctly and efficiently it is recommended that the User calls upon the services of a Professionally Qualified Technician to carry out maintenance.
m
a
CAUTION
The maintenance interventions described must ONLY be carried out the professionally qualified personnel.
WARNING
Before carrying out any interventions described: – set the main system switch to "OFF" – close the gas valve – make sure that no hot parts inside the appliance are
touched.
ANNUAL
Fig. 46
10.3 Cleaning the inside of the appliance
10.3.1 Removing components
To access the internal parts of the boiler: – disassemble the smoke outlet duct of the
Brava Slim HE 40 R e
and
– remove the screws (1), pull the front panel (2) forwards and
release it from the top by lifting it
2
, if fitted
Brava Slim HE 20 R e
10.2 External cleaning
10.2.1 Cleaning the cladding
When cleaning the cladding, use a cloth dampened with soap and water or alcohol for stubborn marks.
d
IT IS FORBIDDEN
to use abrasive products.
Fig. 47
– remove the screws (3) securing the control panel (4) – move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
4
b
a
5
Fig. 48
37
– loosen the clips (6) and extract the air inlet pipe (7)
10
6
6
7
8
– unscrew the swivel joint (8) – extract the connectors (9) from the fan and disconnect the
electrode cable (10)
9
m
CAUTION
Work carefully when removing the assembly (13) to prevent any damage occurring to the internal insulation of the combustion chamber and the door seal.
For more details refer to the drawings in the spare parts catalogue.
10.3.2 Cleaning the burner and the combustion chamber
The combustion chamber and the burner do not require any particular maintenance. Simply brush them with a soft brush.
10.3.3 Checking the ignition/detection electrode
Check the state of the ignition/detection electrode and replace if necessary. Check the measurements as per the drawing whether the ignition/detection electrode is replaced or not.
+0.5
6
+0.5
-0.5
4.5
-0.5
Fig. 51
Fig. 49
– Unscrew the four nuts (11) securing the combustion chamber
door (12)
– pull the fan-sleeve-door assembly (13) forwards and remove
it.
12
11
10.3.4 Final operations
After having cleaned the combustion chamber and the burner: – remove any carbon residue – check that the seal and the insulation of the door (12) to the
combustion chamber are integral. Replace if necessary
– refit the assembly by carrying out the same operations for
removal but in the reverse order and tighten the screws (11) of the door to the combustion chamber
– reconnect the connections to the fan and the electrode.
10.4 Checks
10.4.1 Checking the smoke duct
It is recommended that the user checks that the combustion air inlet duct and smoke outlet duct are integral and airtight.
10.4.2 Checking the expansion vessel pressure
It is recommended that the expansion vessel on the water side is drained and that the prefilling pressure is not less than
(100 kPa)
(see sectionExpansion vessel".
Once the checks described above have been completed: – refill the boiler as described in section "REFILL operations" – check that the siphon has been filled correctly – Start the boiler, activate the "Chimney sweeper function" and
– refit the front panel securing it with the two screws which
. If this is not the case, pressurize it to the correct value
carry out a smoke analysis and/or measure the combustion efficiency
were removed previously.
1 bar
11
13
38
Fig. 50
10.5 Unscheduled maintenance
If replacing the parameters as indicated in the table.
Type
No. Description
PAR 01
PAR 02
PAR 03
To enter "Parameter setting and display"refer to the indications provided in the specific section. Once the parameters in the table have been set, you must carry out the entire phase of "Self-calibrating procedure" described in the specific section.
gas valve
If the
burner
, and/or the
the entire phase of "Self-calibrating procedure" described in the specific section.
electronic board
Index showing boiler power in kW 1 = 20; 2 = 30; 3 = 35; 4 = 40 Hydraulic configuration 0 = rapid 1 = storage tank with thermostat or heating only 2 = hot water tank with sensor 3 = bithermic 4=instant with solar power input 5 = open vent 6 = boiler with heat pump Gas Type Configuration 0 = NATURAL GAS; 1 = UNIVERSAL LPG
and/or the
ignition/detection electrode
fan
are replaced, the user must still carry out
, the user MUST set the
Setting for
20 R i 20 R e 40 R i 40 R e
Brava Slim HE R
1 4
1
0 or 1
, and/or the
10.6 Possible faults and solutions
LIST OF MALFUNCTION/FAULT ALARMS
Type No. Fault Solution
ALL 02
ALL 03
ALL 05 Delivery sensor fault
ALL 06 No flame detection
ALL 07
ALL 08
Low water pressure in system
High water pressure in system
Sensor or safety thermostat intervenes
Fault in the flame detection circuit
- Restore pressure
- Check for any leaks in the system
- Empty the system via the drain valve on the hydraulic assembly and bring the pressure to approximately
1.2 bar (120 kPa)
- Check connections
- Replace the sensor
- Check the integrity of the electrode and check that it is not grounded
- Check gas availability and pressure
- Check the integrity of the gas valve and the card
- Check the sensor or thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the thermostat
- Check that the pump impeller is not blocked
- Check the integrity of the electrode and check that it is not grounded
- Check gas availability and pressure
- Check the integrity of the gas valve and the card
Type No. Fault Solution
- Check the rotation of the
ALL 09
ALL 11
ALL 12
ALL 13
ALL 14 Smoke probe fault
ALL 15
ALL 18
ALL 28
ALL 30
ALL 37
ALL 40
ALL 41
ALL 42 Button fault
ALL 43
ALL 62
ALL 72
ALL 77
ALL 78
ALL 79
ALL 80
ALL 81
ALL 82
ALL 83
ALL 84
No water circulating in the system
Gas valve modulator disconnected Incorrect configuration of the open /sealed chamber
Smoke probe intervention
Fan check cable disconnected
Condensate level fault
Maximum number of consecutive resets reached
Return sensor (SR) fault
Fault due to low network voltage.
Incorrect network frequency detected
Flame loss more than 6 consecutive times
Open Therm communication fault
Self-calibrating procedure is required
Incorrect positioning of the delivery sensor
EV2 SGV current max/min absolute limits error EV2 SGV current upper limit error EV2 SGV current lower limit error Fault on the valve control logic line/ valve cable damaged
Block due to combustion during start-up
Block due to numerous combustion control failures Irregular combustion (temporary error) Flow rate reduced for (presumed) low pressure on mains gas
pump rotor
- Check the electrical connections
- Replace the pump
- Check the electrical connection
- Set the parameter PAR 04 (Combustion configuration) to 0
- Replace the smoke probe
- Contact the Technical Assistance Centre
- Replace the smoke probe
- Check the electrical connection of the smoke probe
- Check the connection cable between the fan and the board
- Check for any clogging in the pipe which takes the condensate to the siphon
- Check that the siphon is not clogged
- Contact the Technical Assistance Centre
- Replace the return probe
- Contact the Technical Assistance Centre
- Check with tester
- Contact network provider (ENEL)
- Contact network provider (ENEL)
- Check the detection electrode
- Check the gas supply (open valve)
- Check mains gas pressure
- Check that buttons are working
- Check the electrical connection of the remote control
- Carry out the self­calibrating procedure (see the specific section)
- Check that the delivery sensor is attached to the delivery pipe
- Contact the Technical Assistance Centre
- Contact the Technical Assistance Centre
- Contact the Technical Assistance Centre
- Check the valve cable
- Contact the Technical Assistance Centre
- Check for blockage in chimney
- Bleed the air from the gas circuit
- Check electrode
- Check outlets
- Check for blockage in chimney
- Check gas flow rate
39
Type No. Fault Solution
ALL 88
ALL 89
ALL 90
Internal error (board component protection) Unstable combustion feedback signal error Combustion set cannot be reached error
- Contact the Technical Assistance Centre
- Contact the Technical Assistance Centre
- Contact the Technical Assistance Centre
System has reached
ALL 92
maximum air correction error (at the minimum flow
- Contact the Technical Assistance Centre
rate)
ALL 93
cannot be reached error
Combustion set
ALL 95
ALL 96
ALL 98
Flame signal micro interruptions error Block due to clogging in smoke outlet SW error, board start-up
ALL 99 General board error
- -
Frequent relief valve intervention
- Contact the Technical Assistance Centre
- Contact the Technical Assistance Centre
- Check for blockage in chimney
- Contact the Technical Assistance Centre
- Contact the Technical Assistance Centre
- Check circuit pressure
- Check expansion vessel
- Check the diverter valve
- -
Limited production of domestic hot water
- Check that plate heat exchanger is clean
- Check domestic hot water circuit valve
40
11 COMMISSIONING BOILER CHECKLIST
ü
A suggested method of commissioning the boiler; the actual method can vary according to the boiler make, type and installation. The boiler must always be installed and commissioned by an approved gas technician. The installer certifies that this Boiler has been installed to the manufacturer's instructions, has been filled, commissioned and is ready for use.
Description
When done
1 Read carefully the instruction manuals supplied with this boiler.
2 BEFORE INSTALLING T HIS BOILER FLUSH OUT THE PIPES UNTIL CLEAN WATER IS ACHIEVED.
Turn off all services to–this boiler - water, gas and power.
3
Install the boiler as shown in the instructions following and connect all services.
Turn on water to fill system, check for leaks regularly and bleed air from all points.
4
Bleed the air from all the pumps in the system, and rotate the impeller shaft.
Check that all radiators valves are open, remove the thermostatic valve heads, fully open all
5
lockshield valves.
Turn ON gas, bleed air out at the isolation valve union. Reseal and check for gas leaks.
6
Turn gas OFF.
Turn electricity on at the power point. At the boiler front panel set the temperature setting to the
7
lowest setting, switch boiler to ON position. The “Power on” Indicator should light. Turn the boiler off at the front panel.
Turn the room thermostat to the manual ON position set the temperature to a high level so that it
8
does not switch off during the commissioning phase. The thermostat will unusually click and show an an indicator in the window.
9 Switch the boiler ON at the boiler front panel control.
Boiler should start fan, pump and ignite gas. If it fails first few times this may be just residual air in
10
the gas line. A noisy water pump indicates there is air in the water pipes.
Boiler lights and heats the water. Check gas flame is the correct colour and for gas and water leaks
11
as the system heats up.
Check that heat is going to all radiators through the manual or thermostatic first and return via the
12
lockshield valve. If not STOP fix NOW and any leaks.
Allow the boiler to heat up to the set temperature and switch off. Re-adjust the boiler temperature to
13
a mid temperature point. CAUTION, If this is connected to a floor heating system. The boiler should re light and increase the water temperature to the new setting.
Check that all radiators are hot all the way up. If the radiator is cold at the top, then there is usually
14
air in the radiator Bleed the radiator. Balance the system so that all. radiators are hot as according to the radiator installation manual. Adjust the boiler water temperature.
Set the room thermostat to the correct times and temperatures according to the manufacture's
15
instructions.
On completion of the commissioning phase, complete the information sheet at the front of this manual. Hand over the installation to the owner and demonstrate how the system works plus basic
16
fault resolution and safety procedures. Make sure that this important document is kept in a safe accessible place.
41
12 EXPLODED VIEWS
Brava Slim HE 20 R i
-
Brava Slim HE 40 R i
42
Brava Slim HE 20 R e
-
Brava Slim HE 40 R e
43
Brava Slim HE 20 R i
-
Brava Slim HE 20 R e
-
Brava Slim HE 40 R i
-
Brava Slim HE 40 R e
44
Brava Slim HE 20 R i
-
Brava Slim HE 20 R e
-
Brava Slim HE 40 R i
-
Brava Slim HE 40 R e
45
Brava Slim HE 20 R i
-
Brava Slim HE 20 R e
-
Brava Slim HE 40 R i
-
Brava Slim HE 40 R e
46
Pos. Code Description
BRAVA SLIM HE R
20 i 20 e 40 i 40 e
1 6264560 Boiler fixing bracket x x 1 6264565 Boiler fixing bracket x x 2 6010890 Support exchangers bracket x x 2 6010894 Support exchangers bracket x x 3 6147412 Plug for air vent connection x x x x 4 6226464 O-ring 115 diam. 11.91x2.62 x x x x 5 6226624 Spring air vent knob x x x x 6 6278913 Main exchanger body x x 6 6278910 Main exchanger body x x 7 6277130 Probe NTC D.4X40 x x x x 8 6010892 Support exchangers bracket x x x x
9 6269008 Main exchanger door insulation x x x x 10 5188360 Main exchanger door x x x x 11 6248870 Combustion chamber O-ring x x x x 12 6248871 Glass fibre sealing cord x x x x 13 6311810 Glass fixing flange x x x x 14 6020103 Sight glass x x x x 15 6248872 Sight glass gasket x x x x 16 8076115 Burner + gasket kit x x 16 8076116 Burner + gasket kit x x 17 6174828 Gasket for burner flange x x x x 18 6278892 Air-gas hose x x x x 19 6174819 Air-gas hose gasket x x x x 20 6278891 Side low air-gas hose x x x x 21 6174809 Gasket for ignition electrode x x x x 22 6221670 Ignition-ionisation electrode x x x x 23 6285950 Bracket x x x x 24 6174816 Gasket for fan flange x x x x 25 6274390 Air/gas mixer x x 25 6274391 Air/gas mixer x x 26 6028703 Gasket for duct flange x x x x 27 6261412 Fan x x x x 28 6278703 Smoke chamber x x x x 29 6248855 P.C. inlet/oulet smokes gasket x x x x 30 6291150 Upper protection shield x x 30 6291151 Upper protection shield x x
31 5183729
Rectang. expans.vessel 9 l. 3/8" M
x x
31 5183730 Rectang. expansion vessel L.10 x x 32 2030225 Gasket Ø 5.5x11x2 x x x x 33 6147401 Plug 1/4" x x x x 34 6273608 Water pressure transducer x x x x 35 6226639 Spring clip x x x x 36 6226476 ORing diam.15x2 x x x x 37 6017405 Flexible pipe M.F. 3/8" L=300 x x x x 38 6226643 Pipe fixing spring x x x x 39 2030226 Gasket Ø 10.2x14.8x2 x x x x 40 6277211 Water trap x x x x 41 6119381 Cap G 1/2" x x x x 42 6034155 Condensate drainage pipe x x x x 43 2051123 Clamp diam. 24.2 x x x x 44 1010215 Rubber pipe dia. 15x2.5 x x x x 45 2051120 Clamp diam. 17.3 x x x x 46 6001162 Air intake pipe 40 x x x x 47 2051203 Hose clamp Ø 40-60 x x x x 48 6243838 Gas valve x x x x 49 2030249 Gasket Ø 24x17x3 x x x x
50 6277445
50 6277446
Pipe connecting gas val­ve-mixer Pipe connecting gas val­ve-mixer
x x
x x
51 6050471 Nozzle 530 x x 51 6050472 Nozzle 650 x x 52 6226477 Rubber gasket OR Ø 17x3 x x x x
Pos. Code Description
BRAVA SLIM HE R
20 i 20 e 40 i 40 e
53 6226636 D.H.W. elektrovalve fix.spring x x x x 54 6227462 Flowing pipe to C.H. system x x 54 6227466 Flowing pipe to C.H. system x x 55 6226412 O-ring 3068 x x x x 56 6231372 Temperature sensor x x x x 57 6146729 100° C safety stat x x x x
58 6226601
Spring for heat exchanger connection
x x x x
59 6227539 Return pipe from C.H. system x x x x
60 6226619
Spring for heat exchanger connection
x x x x
61 2030267 Piracriten gasket Ø 30x17x2 x x x x 62 6229500 Plug 1/2" x x x x 63 6304480 casing left/right side panel x 63 6304465 casing left/right side panel x 64 6325010 Casing front panel x x 65 6281545 Replacement rear insulat. kit x x x x
66 6265895
Flowing to C.H. system mani­fold
x x x x
67 6265835 C.H. return manifold x x x x 68 6277798 Pipe connecting x x x x 69 6226475 ORing diam.18.64x3.53 x x x x 71 6104708 M.F. bushing 3/4" UNIx3/4" NPT x x x x 72 6319650 Bitron transducer cap x x x x 73 6040211 Pressure relief valve 3 bar x x x x 75 6226626 Pipe fixing spring x x x x 77 6120560 Pump nipple 3/4" x x x x 78 6272348 Modulating circulating pump x x 78 6272349 Modulating circulating pump x x 79 6013182 Automatic air vent x x x x
80 6226644
Spring clip for rotating con­nection
x x x x
81 6034167 Condensate drainage pipe x x x x
84 6275911
Pressure relief valve operation lever
x x x x
86 2030227 Gasket Ø 12x18x2 x x x x 88 6157653 Pressure relief valve drain pipe x x x x 90 6304720 Control panel x x x x 91 6324920 Main P.C.B. x x x x 92 6305135 Rubber button x x 92 6305131 Rubber button x x 93 6304831 Interface panel x x x x 95 6305140 Rubber cap x x x x
96 6245380 Pump connector x x x x 100 6255814 Boiler casing x 100 6255816 Boiler casing x 101 6255883 Casing door x x 102 6255913 Flap door x x 103 6262910 Boiler casing support x x 104 6133100 Pin M5 ZnCr x x 105 8102110 Gasket and flange kit x x 106 8085606 90° elbow with take-off points x x 107 6230400 Rubber sealing ring Ø 100 mm x x 108 6230310 Flue terminal x x 700 6281534 Gaskets kit x x x x
701 6319695 Murelle-Format-.....o-ring kit x x x x
702 6211794 Peephole kit x x x x 703 6319700 Springs / clamps kit DIN x x x x 704 5202570 Complete control panel x x x x 705 6323874 4 pole cable connector CN13 x x x x 706 6323876 4 pole cable connector CN14 x x x x 707 6323872 9 pole cable connector CN1 x x x x 708 6323873 6 pole cable connector CN2 x x x x 709 6325602 6 pole cable connector CN12 x x x x 710 6325617 14 pole connector CN15+CN5 x x x x
47
13 REMOVING COMPONENTS
1
3
3
m
a
CAUTION
The maintenance interventions described must ONLY be carried out the professionally qualified personnel.
WARNING
Before carrying out any interventions described: – set the main system switch to "OFF" – close the gas valve – make sure that no hot parts inside the appliance are
touched.
13.1 Remove panels
13.1.1 Front panel
To access the internal parts of the boiler: – disassemble the smoke outlet duct of the
Brava Slim HE 40 R e
and
– remove the screws (1), pull the front panel (2) forwards and
release it from the top by lifting it
Brava Slim HE 20 R e
13.1.2 Side panels
– Unscrew the screws (3) – pull the side panel (4) outwards to release it from the top
4
Fig. 53
2
– proceed in the same way for the other panel.
13.2 Rotate control panel
– Remove front panel (see "Remove panels" on page 48) – remove the screws (3) securing the control panel (4) – move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
4
Fig. 52
b
a
5
Fig. 54
48
13.3 Remove/replace sensor and thermostat
2
2
1
3
13.3.1 Smoke flue gas probe
– Remove front panel (see "Remove panels" on page 48) – disconnect the connector (1)
1
13.3.2 Delivery sensor
– Remove front panel (see "Remove panels" on page 48) – disconnect the connectors (1)
Fig. 58
Fig. 55
– using a suitable tool, rotate the sensor 90° anti-clockwise (2)
Fig. 56
– extract the sensor (2)
– remove the rear locking clip (2) – disconnect the sensor (3) from the pipe
2
Fig. 59
Fig. 57
49
13.3.3 Heat safety thermostat
1
– Remove front panel (see "Remove panels" on page 48) – disconnect the connectors (1)
13.4 Remove electronic board
– Remove front panel (see "Remove panels" on page 48) – move the control panel (A) into a horizontal position (see "
Rotate control panel" on page 48)
– unscrew the screw (1) – press the catches (2) to remove the cover
– remove the rear locking clip (2)
2
Fig. 60
2
– open the cover (3)
3
2
A
Fig. 62
Fig. 63
Fig. 61
– unscrew the fixing screw (4) on the electronic board – remove the electronic board (5) by sliding upwards – disconnect all the connectors (6)
4
6
5
Fig. 64
50
13.5 Remove/replace combustion head unit and
6
fan
– Remove front panel (see "Remove panels" on page 48) – disconnect the fan connectors (1) – remove the clip (2) and air inlet pipe – unscrew the swivel joint (3)
– unscrew the screws (6) and unthread the combustion head (7) – unscrew the screws (8) and remove the fan (9)
7
2
1
3
– unscrew the nuts (4) – remove combustion head unit/conveyor/fan (5)
4
8
Fig. 65
9
Fig. 67
5
Fig. 66
51
13.6 Remove/replace the ignition and flame
1
2
4
1
2
A
detection electrode
– Remove front panel (see "Remove panels" on page 48) – disconnect the connectors (1) and (2)
Fig. 68
– remove the screws (3)
13.7 Remove/replace the siphon
m
– Remove the panelling (see "Remove panels" on page 48) – move the control panel (A) into a horizontal position (see "
– remove the spring clips (1) – remove the cover (2)
CAUTION
When disassembling, some residual water may leak.
Rotate control panel" on page 48)
3
Fig. 69
– carefully remove the ignition/flame detection electrode (4)
Fig. 71
– slide the siphon upwards (3) and remove
3
Fig. 72
Fig. 70
– check the electrode quotas as per chapter "Checking the
ignition/detection electrode" on page 38.
52
13.8 Remove/replace gas valve
2
4
3
1
– Close the gas valve – remove the front panel (see "Remove panels" on page 48) – move the control panel (A) into a horizontal position (see "
Rotate control panel" on page 48)
– disconnect the electrical connector (2)
A
Fig. 73
– unscrew the swivel joints (3) and the screws (4)
13.9 Remove/replace the expansion vessel
– Shut-off the valves to the system and empty the boiler – remove the front panel (see "Remove panels" on page 48) – disconnect the pipe (1) – unscrew the fixing screw (2) on the rear panel
2
– extract the gas valve (5)
the nozzle (6) MUST be used with the new valve
Fig. 76
– release the top section (4) – pivoting around the hook (5), turn and extract the expansion
vessel (3)
4
Fig. 74
3
5
Fig. 77
6
5
Fig. 75
53
13.10 Remove/replace system pump
2
5
3
4
8
6
– Shut-off the valves to the system and empty the boiler – remove the front panel (see "Remove panels" on page 48) – lift the connector (1) using a screwdriver (2)
Fig. 78
– unscrew the swivel joints (3) and (4) – disconnect the pipes (5) and (6) – unscrew the screw (7) – unscrew the nut (8) that secures the pump
1
7
Fig. 79
54
55
Fonderie Sime S.p.A - Via Garbo, 27 - 37045 Legnago (Vr)
Tel. +39 0442 631111 - Fax +39 0442 631292 - www.sime.it
Fonderie SIME S.p.A.reserves the right to make changes at any time without prior notice in order to improve its products
without compromising the essential characteristics.
Loading...