Sime AQUA 30 OF, AQUA 40 OF, AQUA 30 BF, AQUA 30 OF INOX, AQUA 40 OF INOX User Manual

...
CONTENTS
1 DESCRIPTION OF THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
3 CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
4 USE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
IMPORTANT
When carrying out commissioning of the boiler, you are highly recommended to perform the following checks:
– Make sure that there are no liquids or inflammable materials in the immediate vicinity of the boiler.
earthing system.
– Check that the flue pipe for the outlet of the products of the combustion is unobstructed.
– Make sure that any shutoff valves are open.
– Make sure that the system is charged with water and is thoroughly vented.
– Check that the circulator is not blocked.
INSTALLER INSTRUCTIONS
AQUA OF/BF
ENGLISH
1.1 INTRODUCTION
One of the features of the cast iron thermal group with the integrated gas­oil burner is its functional silence and it has been designed in accordance with the european directives CEE 92/42. The perfectly balanced combustion
and the high yield allows it to economise considerably the operating costs. The instructions relative to the following models are indicated in the present manual: –
“AQUA 30-40 OF” for heating and hot water production with accumu­lative tank.
“AQUA 30-40 BF” for heating and hot water production with accumu­lative tank and airtight combustion
burner. The instructions given in this manual are provided to ensure proper installa­tion and perfect operation of the appli­ance and should be strictly followed.
66
1 DESCRIPTION OF THE BOILER
1.2 DIMENSIONS
550
1430
A
850
70
215
1230
340825
515
12 5
200
90
107 5
1230
825
515
12 5
200
90
107 5
215
70
340
U
C
E
U
C
E
75
75
S1
M
R
S2
S1
M
R
S2
ø80/125
ø130
Versione “BF”
Versione “OF”
=
=
=
=
Fig. 1
KEY M C.H. flow G 1” (UNI-ISO 228/1) R C.H. return G 1” (UNI-ISO 228/1) U D.H.W. outlet G 3/4” (UNI-ISO 228/1) E D.H.W. inlet G 3/4” (UNI-ISO 228/1)
C Recirculation G 3/4” (UNI-ISO 228/1) S Boiler drain S1 System safety valve drain S2 Boiler safety valve drain
550
ø80/125
ø130
Versione “BF”
Versione “OF”
850
A
1430
69 231,5
65
65
879
288
239
14 5
16 5
14 516 5
65
65
879
239
288
512,5
512,5
69
231,5
S2
U
C
E
S1
M
R
S
S2
U
C
E
S1
M
R
S
AQUA 30 BF AQUA 40 BF
Amm 75 175
AQUA 30 - 40 OF/BF
AQUA 30 - 40 OF/BF INOX
“BF” version “OF” version
“BF” version “OF” version
67
1.3 TECHNICAL FEATURES
AQUA 30 OF/BF AQUA 40 OF/BF AQUA 30 OF/BF INOX AQUA 40 OF/BF INOX
Heat output * kW 31.3 (27.5) 40.0 (35.2) 31.3 (27.5) 40.0 (35.2)
kcal/h 26,900 (23,700) 34,400 (30,300) 26,900 (23,700) 34,400 (30,300)
Heat input * kW 34.8 (30.6) 44.3 (39.0) 34.8 (30.6) 44.3 (39.0)
kcal/h 29,900 (26,300) 38,100 (33,500) 29,900 (26,300) 38,100 (33,500)
Type B
23 B23 B23 B23
Elements 4 5 4 5
Maximum water head bar 4 4 4 4
Water content l 28 33 24.5 30.5
Expansion vessel
Water content/Preloading pressure l/bar 10/1 12/1 10/1 12/1
Loss of head smoke mbar 0.16 0.21 0.16 0.21
Combustion chamber pressure ** mbar – 0.02 – 0.05 – 0.02 – 0.05
Suggested chimney depression ** mbar 0.18 0.23 0.18 0.23
Smoke temperature ° C 185 18 5 18 5 185
Smoke flow * m
3
n/h 41.4 (35.9) 52.8 (46.3) 41.4 (35.9) 52.8 (46.3)
CO
2 % 12.5 12.5 12.5 12.5
Maximum temperature °C 95 95 95 95
Power consumption “OF/BF” W 200/230 180/210 200/230 180/210
Adjustment range heating °C 45÷85 45÷85 45÷85 45÷85
Adjustment range D.H.W. °C 30÷60 30÷60 30÷60 30÷60
D.H.W. production
Tank capacity l 120 120 110 110
D.H.W. flow rate EN 625 l/min 20.9 20.9 20.9 20.9
Contin. D.H.W. flow rate t 30°C * l/h 840 (790) 840 830 (780) 830
D.H.W. expansion vessel l 4 4 4 4
D.H.W. tank maximum water head bar 7 7 7 7
Gas-oil burner ***
Burner nozzle * 0.75 60°W 0.85 60°W 0.75 60°W 0.85 60°W
(0.65 60°W) (0.85 60°W) (0.65 60°W) (0.85 60°W)
Pump pressure * bar 14 (14) 14 (12) 14 (14) 14 (12)
Shutter regulator position for “OF” version * 5.2 (4.1) 6.2 (5.3) 5.2 (4.1) 6.2 (5.3)
Shutter regulator position for “BF” version * 4.1 (4.0) 3.6 (2.4) 4.1 (4.0) 3.6 (2.4)
Diaphragm position for “BF” version * G (D)
_
G (D)
_
Weight kg 226 254 220 247
* The date shown between the brackets refer to the factory settings
** For “OF” versions only
*** Calibration values with the coaxial drain terminal code 8096220 installed
68
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
5
17
18
19
20
Fig. 2
1.4 MAIN COMPONENTS
1.4.1 “AQUA 30-40 OF/BF” version
KEY
1 Boiler drainer cock 2 Tank drainer cock 3 120 litre tank 4 Tank pump 5 Control valve 6 Gas-oil burner 7 Hublot 8 Bulb housing sheath
9 Control panel 10 Expansion vessel 11 System safety valve 3 BAR 12 Water switch 13 Air intake for airtight burner
(“BF” versions) 14 Hydrometer 15 System pump 17 Filling 18 Tank safety valve 7 BAR 19 Tank expansion vessel 20 Magnesium anode
69
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
5
Fig. 2/a
1.4.2 “AQUA 30-40 OF/BF INOX” version
16
KEY
1 Gas-oil burner 2 Hublot 3 Filling 4 Tank pump 5 Control valve 6 Tank expansion vessel 7 Control panel 8 Expansion vessel
9 110 litre tank in inox 10 Bulb housing sheath 11 Water switch 12 System safety valve 3 BAR 13 Air intake for airtight burner
(“BF” versions) 14 Hydrometer 15 System pump 16 Magnesium anode
70
1
2
34
5
6
7
8
9
8
14
10
11
12
19
18
17
16
15
Fig. 3
1.5 FUNCTIONAL DIAGRAM
1.5.1 “AQUA 30-40 OF/Bf” version
Fig. 3/a
1.5.2 “AQUA 30-40 OF/BF INOX” version
KEY
1 System safety valve 2 System expansion vessel 3 Boiler body 4 Air relief valve 5 Water switch 6 Hydrometer 7 System pump 8 Control valve
9 Gas-oil burner 10 Filling 11 Tank safety valve 12 Tank expansion vessel 14 Tank pump 15 Tank drainer cock 16 Boiler drainer cock 17 Magnesium anode 18 D.H.W. probe 19 120 litre tank
KEY
1 Boiler body 2 Hydrometer 3 Air relief valve 4 System pump 5 Tank pump 6 Control valve 7 Tank expansion vessel 8 Tank safety valve
9 Magnesium anode 10 Tank drainer cock 11 System expansion vessel 12 Boiler drainer cock 13 Filling 14 System safety valve 15 Gas-oil burner 16 110 litre tank 17 Water switch
2.1 BOILER ROOM
The boilers with a rating of more than 35 kW must be equipped with a tech­nical room whose dimensions and requirements correspond to the cur­rent standards and regulations. The minimum distance between the walls of the room and the boiler must not be less than 0.60 m., while the min­imum height between the top of the boiler and the ceiling must be at least 1 m. which can be reduced to 0.50 m. for boilers with incorporated heaters (however the minimum height of the boiler room must not be less than 2,5 m). The boilers with a rating of less than 35 kW can be installed only in perfectly air-vented rooms. To circulate air in the room, air vents must be made on the outside walls which satisfy the following require­ments: – Have a total surface area of at least
6 cm
2
for each installed Kw of ther­mal capacity and however not less than 100 cm
2
.
– To be situated as close as possible
to the floor, unobstructable and pro­tected by a grate which does not reduce the air passage area.
2.2 CONNECTING UP SYSTEM
Before proceeding to connect up the boiler, you are recommended to make the water circulate in the piping in order to eliminate any foreign bodies that might be detrimental to the oper­ating efficiency of the appliance. For connecting up the pipes, make sure to follow the indications illustrat­ed in fig. 1. The connections should be easy to dis­connect using pipe unions with ori­entable connections.
The shutoff valve must be connected to a suitable flow system and return pipes.
2.2.1 System filling
The boiler and the relative system must be filled operating on the bearing tap and the pressure of cold charging the system must be included between 1 - 1.2 bar. During filling the main switch should be left open. Filling must be done slowly so as to allow any air bubbles to be bled off through the provided air vents. This operation can be made easy by positioning horizontally the incision of
the block screw of the shutoff valve. Upon completing the filling, put the screw back to its original position. At the end of the operation make sure that the tap is closed (fig. 4).
2.2.2 D.H.W. production
In order that the boiler be capable of supplying treated water, all the air in the boiler’s serpentine must be bled off at the first ignition. This operation is made easy by positioning horizontal­ly the incision of the block screw of the shutoff valve (5 fig. 2-2/a). After all the air has been bled off, put the screw back to its original position.
2.2.3 Characteristics of feedwater
To prevent lime scale and damage to the tap water exchanger, the water supplied should have a hardness of no more than 20°F. In all cases the water used should be tested and adequate treatment devi­ces should be installed. To prevent lime scale or deposits on the primary exchanger, the water used to supply the heating circuit should must be treated in accordance with UNI-CTI 8065 standards. It is absolu­tely essential that the water is to be treated in the following cases: – Very extensive systems (with high
contents of feedwater).
– Frequent addition of makeup water
into the system.
– In case it is necessary to empty the
system either partially or totally.
2.3 SMOKE EXHAUST
2.3.1 Connecting up flue
The flue is of fundamental importance for the proper operation of the boiler; if not installed in compliance with the standards, starting the boiler will be difficult and there will be a consequent formation of soot, condensation and encrustation.
A flue therefore must satisfy the fol­lowing requirements: – be constructed with waterproof
materials and resistant to smoke temperature and condensate;
– be of adequate mechanical resilience
and of low heat conductivity;
– be perfectly sealed to prevent cool-
ing of the flue itself:
– be as vertical as possible; the termi-
nal section of the flue must be fitted with a static exhaust device that ensures constant and efficient extraction of products generated by combustion;
to prevent the wind from creating pressure zones around the chim­ney top greater than the uplift force of combustion gases, the exhaust outlet should be at least
0.4 m higher than structures adja­cent to the stack (including the roof top) within 8 m;
– have a diameter that is not inferior
to that of the boiler union: square or rectangular-section flues should have an internal section 10% greater than that of the boiler union;
– the useful section of the flue must
conform to the following formula:
71
2 INSTALLATION
Fig. 4
OPEN
S resulting section in cm
2
K reduction coefficient for liquid
fuels: 0.024 P boiler input in Kcal/h H
height of the flue in meters mea-
sured from the flame axis to the
flue outlet into the atmosphere.
When dimensioning the flue, the
effective height of the flue in
meters must be considered,
measured from the flame axis to
the top of the flue, reduced by:
– 0.50 m for each change of
direction of the connection union between boiler and flue;
– 1.00 for each horizontal
metre of the union itself.
Our boilers are the B
23 type and do
not need any particular connections other than the one to the flue as described above.
2.3.2 Smoke exhaust with ø 80/125 coaxial flue
“BF” version boilers are set to be
connected to ø 80/125 stainless steel coaxial flues that can be adju­sted to the most suitable direction for room requirements (fig. 6).
The maximum acceptable length of
the flue must not be over 7.0 equi­valent meters. Load losses in meters for each sin­gle accessory to be used in the exhaust configuration are indicated in Table A.
Only use original SIME accessories and make sure that connections are correct as indicated in the instruc­tions supplied with the accessories.
2.4 FUEL ADDUCTION
The fuel can be fed into the thermal group sideways, the ducts must be passed through the aperture on the
72
P
S=K
H
1
2
3
4
2
5
6
7
7
3
3
ø 80/125
min. 715
KEY 1 Stainless steel coaxial flue L. 886 code 8096220 2a Stainless steel extension L. 1000 code 8096121 2b Stainless steel extension L. 500 code 8096120 3a 90° stainless steel curve MF code 8095820 3b 45° stainless steel curve MF code 8095920 4 Stainless steel vertical condensation recovery L. 135 code 8092820 5 Tile with hinge code 8091300 6 Roof outlet terminal L. 1063 code 8091203 7 Kit code 8098810
Fig. 6
TABLE A
Load loss (mt) 90° stainless steel curve MF 1,80 45° stainless steel curve MF 0,90 Stainless steel extension L. 1000 1,00 Stainless steel extension L. 500 0,50 Roof outlet terminal L. 1063 1,00 Stainless steel coaxial flue L. 886 0,70 Stainless steel vertical condensation recovery L. 135 0,70
WARNING: The maximum acceptable length of the flue must not be over 7.0 equivalent meters. Always use the condensation recovery (4) in outlets with vertical exhaust.
right or left hand side of the shell for connection to the pump (fig. 7 - 7/a).
Important
– Make sure, before turning on the
boiler, that the return tube is free. An excessive counter-pressure would break the pump seal.
– Make sure that the tubes are
sealed.
– The maximum depression of 0.4 bar
(300 mmHg) (see
Table 1
) must not be exceeded. Gas is freed from the fuel above that value and can cause cavitation of the pump.
– It’s advisable to bring the return
tube in the depression systems up to the same height of the intake tube. In this case the foot valve is unnecessary. If instead the return tube arrives above the fuel level, the foot valve is indispensable.
Starting the pump
Turn on the burner to start the pump and check the flame ignition. If a “lock out” occurs before fuel arrival, wait for at least 20 seconds then press the burner release button “RESET” and wait for the whole start­up operation to repeat until the flame lights up.
2.5 BURNER ADJUSTMENTS
Each unit is shipped with a burner unit equipped with a nozzle and calibrated at the factory; it is recommended, however, that the settings listed under point 1.3 be checked, with reference to atmospheric pressure at sea level. If it is necessary to adjust the burner differently from the factory settings, this should be done by authorised per­sonnel following the instructions pro­vided below. Remove the shell door to access the burner unit’s controls.
2.5.1 Air lock adjustment
To adjust the air lock, loosen the screw (1 fig. 8) and slide the graduated scale (2 fig. 8) indicating the position air lock position.
The values for adjustment of each unit are given in point 1.3.
2.5.2 Pump pressure adjustment
To adjust gas-oil pressure, turn the
screw (3 fig. 8/a) and check pressure with a pressure gauche connected to the intake (2 fig. 8/a), making sure pressure corresponds to the value given under point 1.3.
73
H max 4 mH
H
1 2
3
4
5
6
7
8
10 99
Fig. 7
Fig. 7/a
H L (meters)
meters øi tube øi tube
8 mm 10 mm
035100
0,5 30 100
125100
1, 5 2 0 9 0
215 70 38 30
3,5 6 20
CONNECTIONS
1 Vacuometer attachment 2 Pressure regulator 3 Manometer attachment 4 By-pass screw 5 Back-flow flexible pipe
(included in supply)
6 Suction flexible pipe
(included in supply) 7 Auxiliary pressure intake 8Valve 9 Racor 3/8” (included in supply)
10 Fuel feed line filter
(included in supply)
ATTENTION:
- loosen the pump joints (5-6) before pointing the flexible pipes for bringing them out from the prefixed opening on the right/left hand side of the shell. Afterwards tighten the joints to the pump.
- The pump is prearranged for the double-tube function. Remove the by-pass screw (4) for single tube function.
H = Difference in level L = Maximum length
of the intake tube
TABLE 1
2.6 HEATER UNIT
In “AQUA 30 OF/BF” and “AQUA 30 OF/BF INOX” models, the heater unit
comes on with the consensus of the burner, after a delay of a maximum of 90 seconds required to bring fuel in the nozzle holder area up to a tempera­ture of 65°C. Once this temperature has been reached, the thermostat, which is located above the preheater (1 fig. 14/b), will give consensus for the burner to start. The heater will remain on for as long as the burner stays on
and go off when the burne goes off.
NOTE:
“AQUA 40 OF/BF” and “AQUA 40 OF/BF INOX” model have no heater unit, as it is not required.
2.7 ELECTRICAL CONNECTION
The boiler is supplied with an electric cable and the electric power supply to the boiler must be 230V-50Hz single­phase through a fused main switch. The stat cable, whose installation is compulsory for obtaining a better
adjustment of the room temperature, must be connected as shown in fig. 9­9/a.
NOTE: Device must be connected to an effi­cient earthing system. SIME declines all responsibility for injury or damage to persons resulting from the failure to pro­vide for proper earthing of the appliance. Always turn off the power supply before doing any work on the electri­cal panel.
74
1
2
5
6
7
RESET TWICE ONLY
12
1
2
3
bar
KEY
1 Gas-oil pump 2 Pressure gauche intake 3 Pressure adjustment screw
Fig. 8
Fig. 8/a
75
2.7.1 “AQUA OF/BF - AQUA OF/BF INOX” wiring diagram
Fig. 9
KEY IG Main switch TB Tank stat R Relay TL Limit stat TS Safety stat EI Summer/Winter switch TC Boiler stat SPA Water pressure gauge triggered light SA Power on light SB Burner “lock out” warning light PA Water switch PI C.H. pump PB Tank pump B Gas-oil burner TA Room stat OP Timer programmer (optional) TI Anti thermal inertia thermostat
NOTE: When connecting the room stat (TA) remove the bridge between terminals 20-21 When connecting the Timer Programmer (OP) remove the bridge between terminals 30-31.
76
2.7.2 “AQUA OF/BF - AQUA OF/BF INOX” wiring diagram with optional RVA 43.222 unit
Fig. 9/a
KEY IG Main switch TB Tank stat R Relay TL Limit stat TS Safety stat EI Summer/Winter switch TC Boiler stat SPA Water pressure gauge triggered light SA Power on light SB Burner “lock out” warning light PA Water switch PI C.H. pump PB Tank pump B Gas-oil burner TA Room stat C RVA 43.222 control unit connectors (optional) SS Type QAZ21 boiler immersion probe (optional) SC Type QAZ21 boiler immersion probe (optional) SE Outdoor temperature probe QAC31 (optional) UA Type QAA70 room thermometer (optional) TI Anti thermal inertia thermostat
NOTE: When connecting the RV 43 222 unit remove the bridge between terminals 20-21 and remove the relay (R).
77
~
5 s
~
12 s
~
12 s0÷150 s 0÷150 s
2.7.3 “AQUA 30 OF/BF - AQUA 30 OF/BF INOX” functional diagram
Consensus for start-up
Heater stat
Heater
Motor
Ignition transform.
Gas-oil valve
Flame
Stop light
Normal Stopped due to failure to ignite
~
5 s
~
12 s
~
12 s
Consensus for start-up
Motor
Ignition transform.
Gas-oil valve
Flame
Stop light
2.7.4 “AQUA 40 OF/BF - AQUA 40 OF/BF INOX” functional diagram
Normal Stopped due to failure to ignite
78
3.1 COMBUSTION CHAMBER DIMENSIONS
The combustion chamber is a direct passage type and is conform to the EN 303-3 standard annex E. The dimen­sions are shown in fig. 10. An ade­quate protection panel is mounted on the inside wall of the rear head of all the models.
3.2 SYSTEM AVAILABLE HEAD
The head available for the heating plant is shown as a function of the flow in graph in fig. 11.
3.3 ANTI THERMAL
INERTIA THERMOSTAT
The purpose of the anti thermal inertia thermostat (TI) is to restart the boiling unit pump when the boiler reaches the temperature of 90°C, discharging the excess heat due to the thermal inertia of the cast iron body towards the boi­ling unit. The circulator will automati­cally stop working as soon as the boiler temperature falls below 90°C.
4.1 RVA 43.222 UNIT (optional)
The control panel allows the use della centralina RVA 43.222 supplied in kit form upon request, complete with mounting instructions (fig. 12). Make the electric connection as
shown in point 2.7.
4.2 TANK MAINTENANCE
The preparation of hot treated water is guaranteed by a heater in INOX AISI 316L, complete with magnesium
anode for protecting the heater and inspection flange for control and cleaning.
The magnesium anode (20 fig. 2 - 16 fig. 2/a) should be periodically con­trolled and substituted whenever worn out.
3 CHARACTERISTICS
4 USE AND MAINTENANCE
L Volume
mm dm
3
AQUA 30 405 24,0 AQUA 40 505 30,5
Fig. 12
L
270
280
Fig. 10
0
200
1600
140012001000800600400
P OR TATA (l/h)
PREVALENZA RESIDUA (mbar)
500
400
10 0
200
300
AQUA - AQUA INOX - ESTELLE B INOX
1800
Fig. 11
FLOW RATE (l/h)
RESIDUAL HEAD (mbar)
REMOVE
79
4.4 DISASSEMBLY OF OUTER CASING
The shell can be completely disassem­bled for an easy maintenance of the boiler by following the numeric steps shown in fig. 13.
4.5 DISASSEMBLY OF EXPANSION VESSEL
The heating expansion tank is disas­sembled in the following manner: – Make sure that the boiler has been
emptied of water.
– Unscrew the union which connects
the expansion tank.
– Remove the expansion tank.
Before filling up the system make sure that the expansion tank is reloaded at the pressure of 0.8 ÷ 1 bar.
3
8
4
1
2
7
5
6
7
8
3
9
4
1
6
5
2
Fig. 13
AQUA 30 - 40 OF/BF
AQUA 30 - 40 OF/BF INOX
4.6 BURNER MAINTENANCE
To dismantle the burner from the boiler door, remove the nut (fig. 14). –
To access the internal part of the burner, remove the air lock unit held in place by two screws to the sides and remove the right hand shell, which is held in place by four screws, taking care not to damage the O-ring seal. OR.
– To dismantle the nozzle holder and
heater unit, proceed as follows: – open the cover, which is held in
place by a screw, and remove the heater cables (1 fig. 14/a) pro­tected by a heat resistant sheath; remove the fairlead and pass the cables through the hole.
– remove the two cables from the
ignition electrodes fastened in place with a faston.
loosen the union (2 fig. 14/a) and remove the four screws which fas­ten the collar (3 fig. 14/a) to the burner.
– To dismantle the eater or thermo-
stat, refer to figure 14/b.
4.7 CLEANING AND MAINTENANCE
Preventive maintenance and checking of the efficient operation of the equip­ment and safety devices must be car­ried out at the end of each heating season exclusively by the authorised technical staff.
4.7.1 Cleaning smoke ducts
Use an adequate swab for cleaning the smoke ducts of the boiler. After cleaning, position the circulators in their original position (fig. 15).
4.7.2 Cleaning combustion head
The combustion head is cleaned in the following manner (fig. 16): – Disconnect the high tension cables
from the electrodes.
– Unscrew the fixture screws of the
circulator support and remove it.
– Brush the propeller delicately (tur-
bulence disc).
– Carefully clean the photo-resistance
of eventual deposits of dirt deposit­ed on its surface.
– Clean the remaining components of
the combustion head of eventual deposits.
80
Fig. 14
2
1
3
Fig. 14/a
2
1
3
Fig. 14/b
RONDO' 3/4 OF ESTELLE 3/4 OF
RONDO' 5/6 OF ESTELLE 5/6 OF
Fig. 15
KEY
1 Control bow cables 2 Connection 3 Collar
KEY
1 Heater stat 2 Cap 3 Heater
81
– Upon completion re-assemble the
unit in the opposite way as described above taking care to respect the indicated measure­ments.
4.7.3 Substitution of nozzle
The nozzle should be substituted at the beginning of every heating system for guaranteeing the correct fuel flow and a good spray efficiency. The nozzle is substituted in the follow­ing manner: – Disconnect the high tension cables
from the electrodes.
– Loosen the fixture screw (A fig. 16)
of the electrodes support and remove it.
– Block the spray door using a n°19
spanner and unscrew the nozzle with a n°16 spanner (fig. 17).
4.8 FAULT FINDING
There follow a list of some reasons and the possible remedies for a series of faults which could happen causing a failure or an irregular function of the appliance. A function fault, in most cases, causes the “lock out” signal on the control panel to turn on. When this light turns on, the burner can only function again after the reset button
has been pressed; once this has been done and a regular ignition occurs, the failure can be defined momentary and not dangerous. On the contrary, if the “lock out” per­sists, then the cause of the fault as well as the remedy must be looked for in the following faults:
The burner does not ignite
– Check the electric connections. – Check the regular fuel flow, the
cleanness of the filters, of the nozzle and air vent from the tube.
– Check the regular spark ignition and
the proper function of the burner.
The burner ignites regularly but the flame goes out immediately
– Check the flame detection, the air
calibration and the function of the appliance.
Difficulty in regulating the burner and/or lack of yield
– Check: the regular flow of fuel, the
cleanness of the boiler, the non obstruction of the smoke duct, the real input supplied by the burner and its cleanness (dust).
The boiler gets dirty easily
– Check the burner regulator (smoke
analysis), the fuel quantity, the flue
obstruction and the cleanness of the air duct of the burner (dust).
The boiler does not heat up
– Control the cleanness of the shell,
the matching, the adjustment, the burner performances, the pre­adjusted temperature, the correct function and position of the regula­tion stat.
– Make sure that the boiler is suffi-
ciently powerful for the appliance.
Smell of unburnt products
– Control the cleanness of the boiler
shell and the flue, the airtightness of the boiler and of the flue ducts (door, combustion chamber, smoke ducts, flue, washers).
– Control the quality of the fuel.
Frequent intervention of the boiler shutoff valve
– Control the presence of air in the
system, the function of the circula­tion pumps.
– Check the load pressure of the appli-
ance, the efficiency of the expansion tanks and the valve calibration.
Fig. 17
4 ± 0,3 mm
A
2 - 2,5 mm
Fig. 16
82
BOILER IGNITION
Press the main switch for lighting the boiler. The green light turns on to indi­cate that the appliance is powered (fig.
18).
Choose the position Summer/Winter on the switch (fig. 19): –
The boiler operates in treated phase with the switch in the position (SUMMER)
The boiler operates both in treated phase as well as for heating with the switch in the position (WIN­TER). The room stat or the chrono­stat will stop the operation of the boiler.
TEMPERATURE ADJUSTMENT
The heating temperature can be adjusted by turning the knob of the thermostat (fig. 20).
The heating temperature can be adjusted by turning the knob of the thermostat which has a range of between 45 and 85°C. The temperature setting can be checked on the thermometer.
To ensure optimal boiler efficiency at all times, we recommend not to drop below a minimum working tem­perature of 60°C (fig. 21).
USER INSTRUCTIONS
WARNINGS
– In case of fault and/or incorrect operation, deactivate it without making any repairs or taking any direct action. If fuel or
combustion is smelt, air the room and close the fuel interception device. Contact the authorised technical staff.
The installation of the boiler and any servicing or maintenance job must be carried out by qualified personnel.
It is absolutely prohibited to block the intake grilles and the aeration opening of the room where the equipment is
installed. The intake grilles are indispensable for a correct combustion.
IGNITION AND OPERATION
Fig. 18
Fig. 19
Fig. 20
60°C
Fig. 21
GREEN LIGHT ON
SAFETY STAT
The safety stat is of the manually resetting type and opens, causing the main burner to turn off immediately, whenever the temperature of 110°C is exceeded in the boiler. To restore boil­er operation, unscrew the black cap and reset the button (fig. 22).
Should the appliance “lock out” again, please approach the authorised tech­nical staff.
BURNER RESTART
In case that ignition or operation faults occur, the main burner “locks out” and the red lamp lights up on the control panel. Press the “RESET” button to restart the ignition conditions until the flame lights up (fig. 23). This operation can be repeated 2-3 times at maximum and in case of fail­ure contact the authorised technical staff.
ATTENTION: Make sure that there is fuel in the tank and that the taps are open. After each fill up of the tank it
is advisable to interrupt the opera­tion of the burner for about one hour.
TURNING OFF BOILER
It is sufficient to press the main switch to turn off the boiler (fig. 18).
Close both the gas-feed pipe tap and the water tap if the boiler remains inoperative for a long period.
SYSTEM FILLING
Check periodically that the hydrometer
83
RESET TWICE ONLY
Fig. 23
Fig. 22
RESET BUTTON
RED WARNING LIGHT ON
has pressure values at a switched-off system of 1 - 1.2 bar. If the orange water pressure gauge light turns on inhibiting boiler opera­tions, restore operations by turning the supply tap counter-clockwise. After the operation check that the tap is properly closed (fig. 24). Should the pressure exceed the fore-
seen limit, discharge the superfluous amount by operating on the vent knob of any radiator.
CLEANING AND MAINTENANCE
At the end of each heating season, it is essential to have the boiler thoroughly
checked and cleaned out.
Preventive maintenance and checking of the efficient operation of the equip­ment and safety devices must be car­ried out exclusively by the authorised technical staff.
84
04
13
2
bar
04
13
2
bar
Fig. 24
OPEN
AQUA 30-40 OF/BF AQUA 30-40 OF/BF INOX
ORANGE LIGHT ON
DICHIARAZIONE DI CONFORMITA’
CALDAIE A COMBUSTIBILE LIQUIDO
La FONDERIE SIME SpA, con riferimento all’art. 5 DPR n°447 del 6/12/1991 “Regolamento di attuazione della legge 5 marzo 1990 n°46”, dichiara che le proprie caldaie a com- bustibile liquido serie:
AR SOLO RONDO’ B
ARB DUETTO ESTELLE B
1R OF AQUA ESTELLE
2R OF/OF S/GT OF RONDO’
sono complete di tutti gli organi di sicurezza e di controllo previsti dalle norme vigenti in mate­ria e rispondono, per caratteristiche tecniche e funzionali, alle prescrizioni delle norme:
UNI 7936 (dicembre 1979), FA130-84, FA168-87 EN 303-1994.
Le caldaie a gasolio sono inoltre conformi alla DIRETTIVA RENDIMENTI 92/42 CEE.
La ghisa grigia utilizzata è del tipo EN-GJL 150 secondo la norma europea UNI EN 1561.
Il sistema qualità aziendale è certificato secondo la norma UNI EN ISO 9001: 2000.
Legnago, 5 settembre 2006
Il Direttore Generale
ing. Aldo Gava
Fonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Vr) - Tel. 0442 631111 - Fax Servizio Tecnico 0442 631292 - www.sime.it
TAGLIARE LUNGO LA LINEA TRATTEGGIATA
Cod. 6276007C - 04/09 - Documentation Dpt.
Fonderie Sime S.p.A Via Garbo, 27 - 37045 Legnago (Vr) Tel. + 39 0442 631111 - Fax +39 0442 631292 www.sime.it
Loading...