Sime 2R7, 1R8, 2R8, 2R9, 2R10 User Manual

...
Remove the “Testing Certificate” from inside the combustion chamber and keep together with the instructions manual. The package of the “2R GT” boiler contains instructions for installation, ope­ration and maintenance of the diesel burner.
CONTENTS
1 BOILER DESCRIPTION
1.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1.3 TECHNICAL FEATURES
1.4 LOSS OF HEAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.5 COMBUSTION CHAMBER DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1.6 SOME BURNER BRANDS COMPATIBLE WITH “1R/2R” BOILERS
2INSTALLATION
2.1 BOILER ROOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.2 BOILER ROOM DIMENSIONS
2.3 CONNECTING UP SYSTEM
2.4 CONNECTING UP FLUE
2.5 BOILER BODY ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.6 FITTING THE CASING
2.7 ELECTRICAL CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.8 ASSEMBLY OF “RVA 43.222” CLIMATE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3 USE AND MAINTENANCE
3.1 COMMISSIONING THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.2 LIGHTING AND OPERATION
3.3 CLEANING THE BOILER
3.4 USER WARNINGS
3.5 HOW TO USE THE “RVA 43.222” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1R - 2R - 2R GT
ENGLISH
24
1.1 INTRODUCTION
The cast iron boilers “1R/2R freestan­ding” for gas-oil or gas has been desi-
gned in compliance with the European Directives 90/396/CEE, 89/336/CEE, 73/23/CEE, 92/42/CEE.
The cast iron boilers “2R GT” for gas-oil has been designed in compliance with the European Directive 92/42/CEE.
The components for “1R/2R free- standing” installation are supplied in three separate packages: boiler body,
casing with enclosed documents and control panel.
“2R GT” boilers are supplied in four separate packages: boiler body, casing with enclosed documents, control panel and burner with instructions.
1BOILERDESCRIPTION
1R6 1R7 1R8 1R9
Output kW 64.8 74.0 84.0 93.3
kcal/h 55,700 63,600 72,200 80,200
Input kW 73.4 83.1 93.8 103.4
kcal/h 63,100 71,500 80,700 88,900
P (depth) mm 595 670 750 825 Sections 6 7 8 9 Maximum water head bar 4 4 4 4 Water content l37.542.046.551.0 Loss of head
Smoke mbar 0.20 0.16* 0.22* 0.30* Water (Δt 10°C) mbar 30.0 34.0 40.0 45.5
Comb. chamber pressure mbar – 0.01 0.06 0.08 0.08 Suggested chimney depression
mbar 0.21 0.22 0.30 0.38
Smokes temperature °C 225 217 209 201 Smokes flow m
3
n/h 68.0 77.7 88.0 97.6
Adjustment range
Heating °C 30÷85 30÷85 30÷85 30÷85 Smokes volume dm
3
42 46 50 55
Weight kg 261 293 325 357
1.3 T EC HN IC AL F EAT UR ES
1.3.1 “1R” boiler
560 (1R) - 700 (2R)
P
125 (1R) 135 (2R)
ø 150 (1R)
ø 200 (2R)
270 (1R)
330 (2R)
925 (1R) - 1130 (2R)
70 (1R)
85 (2R)
695 (1R) - 875 (2R)
865 (1R) - 1075 (2R)
R
S
M
1.2 D IM EN SI ON AL DE TAI LS
Fig. 1
1R 2R/2R GT
MC.H. flow 1
1
/
2
”2
R C.H. return 1
1
/
2
”2
S Boiler/filling drain 3/4” 3/4”
* Without baf fles
25
1.4 LOS S OF H EA D
1.3. 2 “2 R/ 2R G T” b oi le r
Fig. 2
NOTE: The losses of head shown in the diagram were obtained with a Δt of 10°C
“1R” boiler
“2R/2R GT” boilers
6789101112131415
Output kW 100.6 123.8 147.1 165.1 179.7 197.7 213.4 230.2 248.8 266.9
kcal/h 86,500 106,500 126,500 142,000 154,500 170,000 183,500 198,000 214,000 229,500
Input kW 113.5 139.1 164.7 184.1 199.7 219.7 237.1 255.8 276.4 296.7
kcal/h 97,600 119,700 141,600 158,300 171,700 188,900 203,900 220,000 237,700 255,200
P (depth) mm 735 835 935 1,035 1,135 1,235 1,335 1,435 1,535 1,635 Sections 6 7 8 9 10 11 12 13 14 15 Max. water head bar 5 5 5 5 5 5 5 5 5 5 Wate r content l92107122136151165180194209223 Loss of head
Smoke mbar 0.10 0.15 0.22 0.29 0.24* 0.37* 0.39* 0.42* 0.49* 0.50* Water (Δt 10°C) mbar 61.0 76.0 85.0 92.0 100.0 1,120 118.0 121.0 125.0 130.0
Comb. chamb. press. mbar – 0.02 – 0.02 – 0.01 – 0.02 – 0.02 – 0.01 – 0.02 0.31 0.35 0.50 Suggested chimney depress.
mbar 0,12 0,17 0,23 0,31 0,26 0,38 0,41 0,73 0,84 1,00
Smokes temperature °C 238 236 234 232 229 224 219 215 211 207 Smokes flow m
3
n/h 105.2 129.2 153.3 171.9 186.9 205.4 221.6 238.9 257.9 276.6
Adjustment range
Heating °C 30÷85 30÷85 30÷85 30÷85 30÷85 30÷85 30÷85 30÷85 30÷85 30÷85 Smoke volume dm
3
83 92 101 110 119 128 138 147 157 167
Weight kg 462 520 578 636 676 734 792 850 908 966
12345678
0
10
20
30
40
50
Portata m3/h
Δp mbar
1R 8
1R 7
1R 6
1R 9
4 5 6 7 8 9 10 11 121314 15 16 17 18 19
0
20
40
60
80
100
Portata m3/h
Δp mbar
2R 6
2R 7
2R 9
2R 8
120
20 21 22 23
140
2R 10
2R 11
2R 12
2R 13
2R 14
2R 15
* Without baf fles
Flow m3/h
Flow m3/h
26
1.5 COMBUSTION CHAMBER DIMENSIONS
The dimensions of this direct passage combustion chamber are reported in fig. 3.
Fig. 3
“1R” 6789 A mm 310 310 310 310 B mm 310 310 310 310 L mm 448 524 600 676 Volume m
3
0,038510 0,045129 0,051748 0,058367
“2R - 2R GT” 6789101112131415 A mm 390 390 390 390 390 390 390 390 390 390 B mm 430 430 430 430 430 430 430 430 430 430 L mm 570 670 770 870 97 0 1.070 1.170 1.27 0 1.370 1.470 Volume m
3
0,081690 0,096314 0,110938 0,125562 0,140186 0,154810 0,169434 0,184058 0,198682 0,213306
1.6 SOME BURNER BRANDS COMPATIBLE WITH “1R/2R” BOILERS
In general, the oil burner that is compatible with the boiler should use full spray nozzles.
1.6.1 ECOFLAM gas-oil burners
1.6.2 RIELLO gas-oil burners
Boiler Model Atomising
Gulliver R. 40 REG R2000 angle
1R6 RG2 - RG2D G10 G120 60° 1R7 RG2 - RG2D G10 G120 60° 1R8 RG2 - RG2D G10 G120 60° 1R9 RG2 - RG2D - RG3 - RG3D G10 - G20 G214 - G230D 60° 2R6 RG3 - RG3D G20 G214 - G230D 60° 2R7 RG3 - RG3D G20 G214 - G230D 60° 2R8 RG3 - RG3D G20 G214 - G230D 60° 2R9 RG3 - RG3D G20 - G20D G214 - G230D 60° 2R10 RG4S - RG4D - RG5D G20 - G20D 60° 2R11 RG4S - RG4D - RG5D G20 - G20D 60° 2R12 RL28/1 - RL28/2 - RG5D 60° 2R13 RL28/1 - RL28/2 - RG5D 60° 2R14 RL28/1 - RL28/2 - RG5D 60° 2R15 RL28/1 - RL28/2 - RG5D 60°
Boiler Model Atomising
1 flame 2 flames angle
1R6 MINOR 8 60° 1R7 MINOR 8 60° 1R8 MINOR 12 60° 1R9 MINOR 12 60°
Boiler Model Atomising
1 flame 2 flames angle
2R6÷8 MAIOR P 15 MAIOR P 15 AB 60° 2R9÷12 MAIOR P 25 MAIOR P 25 AB 60° 2R13-14 MAIOR P 35 MAIOR P 35 AB 60° 2R15 –MAIOR P 45 AB60°
1.6.3 F.B.R. gas-oil burners
Boiler Model Atomising
angle
1R6÷8 G2 2001 60° 1R9 - 2R6 G2 MAXI 60° 2R7 FG 14 TC 60°
Boiler Model Atomising
angle
2R8 FG 14 TC 60° 2R9÷13 G 20 TC 60° 2R14-15 G 30/2 TC 60° - 45°
27
2.1 BOILER ROOM
The boiler room should feature all the characteristics required by standards governing liquid fuel heating systems.
2.2
BOILER ROOM DIMENSIONS
Position the boiler body on the founda­tion bed, which should be at least 10 cm high. The body should rest on a surface allowing shifting, possibly by means of sheet metal. Leave a clearance between the boiler and the wall of at least 0.60 m, and between the top of the casing and the ceiling of 1 m (0.50 m in the case of boilers with incorporated D.H.W. tank). The ceiling height of the boiler room should be less than 2.5 m.
2.3 CONNECTING UP SYSTEM
When connecting up the water supply to the boiler, make sure that the speci­fications given in fig. 1 are observed. All connecting unions should be easy to disconnect by means of tightening
rings.
A closed expansion tank system
must be used.
2.3.1 Filling the water system
Before connecting the boiler, thorou­ghly flush the system to eliminate scale which could damage the appliance.
Filling must be done slowly so as to allow any air bubbles to be bled off through the air valves. In closed-circuit heating systems, the cold water filling pressure and the pre-charging pressure of the expansion vessel should be no less than or equal to the height of the water head of the installation (e.g. for water head of 5 metres, the vessel pre-charging pres­sure and installation filling pressure should be at least 0.5 bar).
2.3.2
Water system characteristics
Water supplying the heating circuit must be treated in accordance with UNI-CTI 8065 standards. It is absolutely essential to treat water
in the heating system in the following cases: –for extensive systems (with high
contents of water);
–frequent addition of water into the
system;
– should it be necessary to empty the
system either partially or totally.
2.4 CONNECTING UP FLUE
The flue is of fundamental importance for the proper operation of the boiler; if not installed in compliance with the standards, starting the boiler will be difficult and there will be a consequent formation of soot, condensate and encrustation. The flue used to expel combustion pro­ducts into the atmosphere must meet the following requirements: –
be constructed with waterproof materials, and resistant to smoke temperature and condensate;
–be of adequate mechanical resilien-
ce and of low heat conductivity;
–be perfectly sealed to prevent coo-
ling of the flue itself;
–be as vertical as possible; the termi-
1.6. 5 Bu rn er f la nge
The dimensions of the diesel burner anchorage flange are given in fig. 4.
2INSTALLATION
A
B
C
Fig. 4
ABC
mm mm ø
1R 6 110 15 0 M 8 1R 7÷9 13 0 17 0 M 8 2R 6-7 13 0 17 0 M 8 2R 8÷15 16 0 19 0 M 10 2R GT 6-7 13 0 17 0 M 8 2R GT 8÷15 16 0 19 0 M 10
1.6. 4 RI EL LO gas b ur ne rs
Boiler Model Output (kW) Electrical Gas
1°stage 2°stage data type
1R 6÷9 GS10 42÷116 230V
±
10% ~50Hz G20/25 - G30/31
2R 6 GS10 42÷116 230V
±
10% ~50Hz G20/25 - G30/31
2R 7÷8 BS 3 65÷189 230V
±
10% ~50Hz G20/25 - G30/31
2R 9÷11 BS 4 110÷246 230V
±
10% ~50Hz G20/25 - G30/31
2R 8÷15 RS 28 81 163-325 230V
±
10% ~50Hz G20/25 - G30/31
2R 8÷15 RS 28/1 163÷349 230V
±
10% ~50Hz G20/25 - G30/31
nal section of the flue must be fitted with a static exhaust device that ensures constant and efficient extraction of products generated by combustion;
–to prevent the wind from creating
pressure zones around the chimney top greater than the uplift force of combustion gases, the exhaust outlet should be at least 0.4 m higher than structures adjacent to the stack (including the roof top) within 8 m;
–have a diameter that is not inferior
to that of the boiler union: square or rectangular-section flues should have an internal section 10% grea­ter than that of the boiler union;
–the useful section of the flue must
conform to the following formula:
S resulting section in cm
2
Kreduction coefficient for liquid
fuels: –0.045 for firewood – 0.030 for coal – 0.024 for light oil
– 0.016 for gas Pboiler input in kcal/h H height of flue in metres, measu-
red from the flame axis to the
top of the flue reduced by:
–0.50 m for each change of
direction of the connection union between boiler and flue;
–1.00 m for each metre of
union itself.
2.5 BOILER BODY ASSEMBLY
The boiler body comes supplied assem­bled. Where there is difficulty in gaining access to the boiler room, the body can be supplied in separate sections. For assembly, proceed as follows: –prepare the sections, cleaning the
seats of the tapered nipples with solvent;
– insert the bead of putty (fig. 5) in the
groove provided for fume tightness, pressing lightly;
– prepare one of the two intermediate
sections. After lubricating them with boiled linseed oil, insert the tapered nipples (fig. 6);
–prepare the head, proceeding as
above, and bring it up to the inter­mediate section. Add only one sec­tion at a time;
assemble the sections, using the tools provided consisting of a pair of
staybolts for assembly with the cor­responding accessories (code 6050900 - fig. 7), exerting pressure simultaneously on the top hub and on the bottom hub. If, during this ope­ration, the sections were to slot together in such a way as not to be even and parallel, slide a chisel in the
tighter side and, by applying a little force, bring the two pieces together so that they are parallel. The sections can be considered pro­perly joined together when their outer edges come into contact;
– insert the bead of putty in the groo-
ve of the section that has just been assembled, and then proceed to joi­ning up the other sections until the body is completed.
NOTE: befo re proceeding to con­nect the system, test the boiler block with a water pressure of 7.5 bar.
2.6 FITTING THE CASING
The casing and the control panel are supplied in separate cardboard packa­ges. The housing package also con­tains the boiler documents and the glass wool for insulating the cast iron body. To fit the casing, proceed as fol­lows (fig. 8): – fix the left front side angle bar (2)
and the right front side angle bar (3) to the upper tie rods using the two galvanized nuts provided;
– place the front cross bar (4) on the
lower tie rods before securing the angle bars with the two cap nuts provided;
– insulate the cast iron body with the
glass wool (1);
– fix the side parts (5) and (6) to the
angle bars using the ten self-tapping screws provided, and secure them at the back with the nuts placed on the tie rods;
28
Fig. 5
Fig. 6
KEY
1 Pin 2Flange ø 35/87 3 Biconical nipples 4Staybolt L. 900 + staybolt L. 980 5Flange ø 50/87 6 Stub 7 Thrust bearing 8 Nut 9Tightening wrench
Fig. 7
P
S=K
H
– assemble the lower rear panel (7)
with the eight self-tapping screws provided;
assemble the upper rear panel (8) with the six self-tapping screws pro­vided;
– fix the control panel (12) to the cover
(13) using the check nut (14);
– unwind the capillary tubes of the two
thermostats and thermometer by inserting their sensors inside the sheath (11), securing the assembly in position using the capillary tube retaining spring provided;
– screw the water gauge to the check
valve (10);
– complete assembly by fixing the
cover (13) and the front panel (9) to the side parts.
NOTE: Remove the “Testing Certifi­cate” from inside the combustion chamber and keep together with the instructions manual.
2.7 ELECTRICAL CONNECTION
(figg. 9 - 9/a)
The boiler is fitted with an electricity cable, and requires a a single-phase power supply of 230V - 50Hz throu­gh the main switch protected by fuses. The room thermostat (requi­red for enhanced room temperatu-
re control) must be connected to the terminals 4-5 after removing the link. Connect the burner cable supplied.
NOTE: Device must be connected to an efficient earthing system. SIME
declines all responsibility for injury caused to persons due to failure to earth the boiler. Always turn off the power supply before doing any work on the electri­cal panel.
29
Fig. 8
KEY IG Main switch TA Room stat (not supplied) PI C.H. pump (not supplied) TC Boiler stat TS Safety stat B Burner (not supplied) SB Burner lock-out lamp
NOTA: The room stat must be con­nected to the terminals 4-5 after removing the link.
Fig. 9
“1R/2R” boilers
2.8 ASSEMBLING THE RVA 43.222 CLIMAT CONTROLLER (fig. 10)
All functions of the “2R GT” boiler may be controlled using the controller, code 8096303, which is supplied with an outdoor temperature probe (SE) and a boiler immersion probe (SC). The controller is to be connected to an additional series of low voltage connec­tors for connection of the room tempe­rature control unit (the connectors are supplied in a bag inside the control panel). The probe bulb of the external hot water tank, if any, (SS) code 6277110, must be inserted in the hot water tank sheath, while the bulb of the boiler probe (SC) must be inserted in the boi­ler sheath.
When assembling the outdoor tempe­rature probe, follow the instructions provided in the probe package. Refer to fig. 9/a for wiring instructions.
IMPORTANT: To make sure that the unit works pro­perly, set the boiler control thermo­stat as high as it will go.
30
Fig. 9/a
“2R GT” boiler
KEY F Fuse (T 6A) IG Main switch SB Burner shutdown emergency light TC Two-stage control thermostat TS Safety thermostat BBurner PI System pump PB Boiler pump C Connectors for RVA 43.222 controller (black - red - brown) TA Environment thermostat
UA Type QAA70 room temperature control unit (optional) SE Outdoor temperature probe (optional) SC Type QAZ21 boiler probe (optional) SS Type QAZ21 hot water probe (optional)
NOTE: Connect the TA by removing the jumper from terminals 4-5. Connect up the RVA43.222 control device and remove the jumpers from ter­minal boards 4-5, 4-6, 9-10
12
Fig. 10
KEY
1 Cover 2 RVA 43.222 controller
3.1 COMMISSIONING THE BOILER
When commissioning the boiler it is recommended: –to make sure that the system has
been filled with water and adequa­tely vented;
–to make sure that the flow and
return valves are fully open;
–to make sure that flue and chimney
are free from obstructions;
– to make sure that the electrical con-
nections to the mains and the earthing are correct;
to make sure that no flammable liquids or materials are near the boiler.
3.2 LIGHTING AND OPERATION
3.2.1 Lighting the boiler
To lig h t t h e b oil e r p r oc e ed a s f ol l ow s (fig. 11): –check that the “Testing Certificate”
has been removed from inside the combustion chamber;
–switch on the main switch (1); the
burner will start ;
–turn the boiler stat knob (5) to the
desidered setting. For best results, set the boiler stat knob to a temperature no lower than 60°C to prevent the formation of condensate. The set temperature value can be checked on the thermometer (4).
3.2.2 Safety stat
The safety stat with automatic reset calibration set at 100°C (2 fig. 11)
trips, immediately turning off the bur­ner when the boiler accidentally overheats. To restore normal opera­tions, wait until the temperature drops below the thermostat calibra­tion setting.
3.2.3 System filling
Periodically check the pressure values of the hydrometer (3 fig. 11) which, when the system is cold, should range between 1 and 1.2 bar. If the pressure is less than 1 bar, reset the system.
3.2.4 Turning OFF boiler
To turn off the boiler, cut off the volta­ge by pressing the mains switch (1 fig. 11).
3.3 CLEANING THE BOILER
(fig. 12)
The boiler body and flue should be
cleaned at the end of each season. To clean the boiler, simply remove the burner-holding plate and the cleaning plate with their insulation and protec­tion panels; this operation gives easy access to the three front pockets and the combustion chamber. Before proceeding to clean the and “1R 6 - 2R/2R GT 6 ÷ 9” models, the baffles must be removed. Once maintenance has been comple­ted, reposition the baffles. Use the pig to clean the smoke pipes.
NOTE: Preventive maintenance must be carried out by authorized techni­cal staff.
3.4 USER WARNINGS
When faults occur and/or the equip­ment does not operate correctly, turn it off, without attempting to make any repairs or take direct action. For any operation only contact the authorised technical personnel in your area.
31
3 USE AND MAINTENANCE
Fig. 12
1 23
45
Fig. 11
“1R” boiler “2R/2R GT” boilers
TO TURN ON THE HEATING
–Turn on the main switch. – Set the correct hour of the day and the day of the week. – Place in automatic mode with the button .
TO SET THE HOUR
HOW TO USE THE AUTOMATIC MODE
In the automatic mode the temperature of the room is regu­lated on the basis of the periods of heating chosen.
– Push the button .
NOTE: Select the heating periods according to one’s daily
requirements; in this way it is possible to significantly
save on energy.
TO ACTIVATE CONTINUOUS HEATING
The continuous heating mode keeps the temperature of the room at the set level via the regulating knob.
– Push the “Continuous Operation” button . –Regulate the room temperature with the
regulating knob.
TO SET THE STANDBY MODE
(when the user is away for a long period of time)
The standby mode keeps the temperature of the room at the level of antifreeze protection.
– Push the “Standby mode” button .
MEANING OF THE SYMBOLS
On the display a few of the symbols indicate the current ope­rating state. The appearance of a line under one of these symbols signals that the corresponding operating state is “active”.
Heating at the nominal temperature (regulating knob)
Heating at reduced temperature (line ).
Heating at antifrost protection temperature (line ).
NOTE: For further information on the symbols and the
operating state refer to the detailed description of the
heating plant.
TO VARY THE HOT WATER PRODUCTION
The production of hot water can be activated or deactivated by the push of a button.
–Push the button “Hot water” .
IF THE HOT WATER IS TOO HOT OR TOO COLD
IF THE ROOMS ARE TOO HOT OR TOO COLD
–Check that current operating state on the display. – In the case of nominal temperature .
Increase or reduce the temperature of the room with the regulating knob.
– In the case of reduced temperature .
NOTE: After each regulation wait at least two hours for
the new temperature to expand through the room.
TO CHANGE THE HEATING PERIODS
With reference to the day chosen set the changes as following:
NOTE: The heating periods automatically repeat on a
weekly basis.
To this end select the automatic mode.
It is possible to reset the standard programme on line 23
by pushing the buttons + and – at the same time.
IF THE HEATING DOES NOT WORK PROPERLY
– Refer to the detailed documentation
on the heating system, following the fault finding instructions.
TO MEASURE GAS COMBUSTION
–Push the “chimneysweep” button .
The heating will work according to the level requested.
HOW TO SAVE ENERGY WITHOUT FOREGOING ON COMFORT
– A temperature of around 21°C is advised in the rooms
that are used. Every degree above this will increase hea­ting costs by 6–7%.
–Aerate the rooms only for a brief period, opening the win-
dows completely.
–In the rooms that are not used place the regulating valve
in the antifreeze position.
–Leave the space in front of the radiators free from
obstructions (remove furniture, curtains...).
– Close windows and blinds to reduce
dispersion of heat.
Select the Display Set the regulation line with the buttons
hour of the day
day of the week
1
2
14
15
Select the Display Pre-select the weekly block line or the single day
1-7 = week 1 = Lu/7 = Do
5
Period Push Display Set For requested button hour °C
Start
End
Start
End
Start
End
6
7
8
9
10
11
Select the Display Change the temperature line with the buttons
°C
14
Period 1
Period 2
Period 3
13
Select the Display Set the desired line temperature
°C
32
3.5 HOW TO USE THE “RVA 43.222”
To make the most of your “RVA 43.222” controller, follow the instructions provided below:
Loading...