SIM SIM-04 Installation Instructions Manual

Page 1
SIM-04
DIGITAL DUAL DETECTOR
PIR AND MICROWAVE
INSTALLATION INSTRUCTIONS
Wide Angle Lens
AVOID THE FOLLOWING LOCATIONS:
Facing direct sunlight. Facing areas that may change temperature rapidly. Areas where there are air ducts or substantial
airflows.
Avoid screen, curtain that may block detection area.
Do not install outdoors.
SPECIFICATION
Detection Method PIR element & microwave pulse Doppler
Power Input 8.2 to 16 Vdc Current Draw Active : 25.5 mA
Standby: 16.5 mA Temperature
Compensation YES Alarm Period 2 +/- 1 sec Alarm Output N.C 28Vdc 0.1 A
with 10 Ohm series protection resistors
Tamper Switch N.C 28Vdc 0.1A with10 Ohm series protection resistor - open when cover is removed
Warm Up Period 1 min
LED Indications
Yellow blinking during warm up period and self testing
Red LED: ON during alarm Green LED: PIR CHANNEL Yellow LED: MW CHANNEL
Dimensions 115mm x 61mm x
37.5mm Weight 120g
INSTALLING THE DETECTOR
Holding
Screw
Cover
Base
WIRE REQUIREMENTS
Use #22 AWG (0.5mm) or wires with a larger diameter. Use the following table to determine required wire gauge (diameter) and length of wire between the detector and the control panel.
Wire Length m 200 300 400 800 Wire Diameter mm .5 .75 1.0 1.5 Wire Length ft 800 1200 2000 3400 Wire Gauge # 22 20 18 16
PCB LAYOUT
Page 2
WIRE CONNECTIONS DETECTOR SETTINGS
Terminal 1 - Marked - (GND)
Connect to ground of the control panel.
Terminal 2 - Marked + (+12V )
Connect to the positive Voltage output of 8.2 ~ 16Vdc source.
Terminals 3 & 4 - Marked TAMPER
Connect these terminals to a 24hour normally closed protective zone in the panel.
Terminal 5 - Marked EOL
End of line option.
Terminals 6 & 7 - Marked RELAY These are the output relay contacts of the detector. Connect to the control at zone input.
Switch 1: LED Control Position Right – ON - LEDs ENABLE The RED LED will activate when the detector is in alarm condition. Position Left – OFF - LEDs DISABLE
Note: the state of the switch “LED” does not affect the operation of the relay.
Switch 2: PULSE count for PIR. Position Left – OFF. High sensitivity 2 PULSES - for normal stable environment.
Position Right – ON. Low sensitivity 3 PULSES - for harsh environments.
Switch 3: MW range control according to the room size. Position Left – OFF – Long For room size 10m – 18m. Position Right – ON – Short For room size 5m – 9m.
Switch 4: the PET Immune function Position Right - ON - Immunity up to 15 kg Position Left - OFF - Immunity up to 25 kg
RANGE ADJUSTMENT
PIR SENSITIVITY
Use the Potentiometer marked “PIR” to adjust the detection sensitivity between 15% and 100%, according to walk test in the protected area.
Factory setting is 57%.
MW SENSITIVITY
The “MW” potentiometer adjusts the detection sensitivity of Doppler between 40% and 100% (factory set to 65%).
Rotate the potentiometer clockwise to increase sensitivity.
Rotate the potentiometer counter- clockwise to decrease sensitivity.
TESTING THE DETECTOR
Apply 12 Vdc power to the detector, wait 2 minutes to finish the detector warm up time. Conduct testing with the protected area cleared of all people.
Walk test
1. Remove front cover.
2. Make sure that PULSE switch is in position 1.
3. Make sure that LED switch is ON.
4. Replace the front cover.
5. Start walking slowly across the detection zone.
6. Observe that the detector’s LED lights whenever motion is detected.
7. Allow 5 sec. between each test.
8. After the walk test is completed, the LED and PULSE jumpers may be changed.
NOTE: Walk tests should be conducted, at least once a year, to confirm proper operation and coverage of the detector.
www.sim-security.net
Loading...