Silent Call 9120FT User Manual

Page 1
Photoelectric Smoke Alarm
9000/
120VAC and 220VAC with 9VDC Battery Back-Up Single/Multiple Station Smoke Alarm
Applications
The 9000/9003 Series of photoelectric smoke alarms is designed for residential and commercial residential applications, including homes, apartments, hospitals, hotels and motels, in compliance with UL 217, UL 1730 applicable IBC/IFC Standards and NFPA 72.
Available in many different models, the 9120/9123 Series is engi­neered to virtually eliminate nuisance alarms and deliver outstanding performance wherever reliable fire protection is required. The 9000/ 9003 Series is provided with a 9VDC alkaline battery for back-up in the event building power is lost. The battery impedance is verified and the alarm provides a low or missing battery warning.
The Gentex 9000/9003 Series provides an exclusive patented three position test feature that simulates a 0.85% and 3.5% actual smoke condition in full compliance with NFPA 72 and UL Standards.
Options include self-restoring 135°F integral or isolated heat thermals and Form A/Form C dry contacts for remote annunciation. Tandem interconnection of up to 12 units is available on several models; tandem interconnection of up to 6 units is available on “F” models, which activate the dry contacts from the tandem wire or a local alarm.
9003
SERIES
Easy WashTM­On Site Maintenance Program
Standard Features
vailable in 120V
A
• Horn frequency 3100 Hz (nominal)
• Nominal 2.5% sensitivity
• Patented three position test switch
• Quick-disconnect wiring harness
• 90dBA
• 90dBA
• 5-to-1 signal-to-noise ratio
• Pulsing LED sensing chamber
• Fully insect screened
• Interconnect with all Gentex tandem capable smoke alarms
• Easy W
• Red
• Mounting hardware adapts to standard junction boxes
• Dust cover to prevent contamination during installation
• Low or missing battery indicator
• 1 year warranty from date of purchase
continuous piezo horn (9120/9220 Series) temporal 3 evacuation piezo horn (9123/9223 Series)
ash
LED pulses every 30 seconds, green LED for
AC and 220VAC with 9VDC battery back-up
TM
on-site maintenance washing program
AC power on
Product Listings
• UL 217 and UL 1730 Listed
• CSFM #7257-569:117
• BS+A/MEA #285-91-E
• BFP (City of Chicago)
• MSFM Listing #1929
• Hong Kong FSD Listed (9220 Series ONLY)
Product Compliance
• NFPA 72
• IBC/IFC/IRC
Page 2
9000 (9120/9220) Series - Continuous Piezo Sounder
Model
Number
9120 917-0001-002 120VAC 9120T 917-0002-002 120VAC 9120H 917-0003-002 120VAC 9120F 917-0004-002 120VAC 9120TF 917-0009-002 120VAC 9120HF 917-0005-002 120VAC 9220 917-0026-002 220VAC 9220T 917-0027-002 220VAC
9220H 917-0028-002 220VAC 9220F 917-0029-002 220VAC 9220TF 917-0031-002 220VAC
9220HF 917-0030-002 220VAC
Part
Number V
oltage
Integral
135oF
Thermal
Isolated
135oF
Thermal
Tandem
o
Up T
12 Units
Tandem
o
Up T
6 Units
=
= =
= =
= =
= = =
= = =
=
= =
= =
= =
= = =
= = =
Form A/C
Contacts
9003 (9123/9223) Series - Temporal 3 Evacuation Piezo Sounder
Model
Number
9123 917-0012-002 120VAC 9123T 917-0013-002 120VAC 9123H 917-0014-002 120VAC 9123F 917-0015-002 120VAC 9123TF 917-0017-002 120VAC
9123HF 917-0016-002 120VAC 9223 917-0032-002 220VAC 9223T 917-0033-002 220VAC 9223H 917-0034-002 220VAC 9223F 917-0035-002 220VAC 9223TF 917-0037-002 220VAC
9223HF 917-0036-002 220VAC
Part
Number Voltage
Integral
135oF
Thermal
Isolated
135oF
Thermal
Tandem
Up To
12 Units
Tandem
Up To
6 Units
=
= =
= =
= =
= = =
= = =
=
= =
= =
= =
= = =
= = =
Form A/C
Contacts
NOTES:
Series available in round configuration only
• When testing 9123 Series, it may take up to 16 seconds longer for smoke alarm to go in or out of alarm mode.
• It is recommended that 9000/9003 Series smoke alarm be tested weekly
echnical Bulletin 002 for
• Refer to
• 9120/9220 units produce a non-temporal audible alarm and are therefore not intended for locations where the desired action of the occupant(s) is evacuation.
• 9123/9223 units produce a temporal 3 audible alarm. Per NFP
T
is required whenever the intended response is to evacuate the building.
Easy W
.
TM
ash
on site washing instructions
A
.
American National Standard Audible Emergency Evacuation Signal as defined in ANSI S3.41,
72, the
Page 3
9000/9003 Series Wiring Diagrams
Tandem Wiring Diagram
120 VOLTS 60 HZ
HOT
ELECTRICAL BOX
TANDEM WIRE
NEUT
ELECTRICAL BOX
ELECTRICAL BOX
QUICK DISCONNECT TYPE PLUG
SMOKE
1
ALARM
2
3
SMOKE
1
ALARM
2
3
SMOKE
1
ALARM
2
3
LIMITATIONS: Maximum of 12 alarms (9120/9123, 9120/9123T, 9120/9123H, 9220/9223, 9220/9223T, 9220/9223H) may be connected together. Do not exceed 125 feet between each detector. Do not exceed 1125 feet between the first and last alarm. NOTE: Gentex smoke alarms can not be intercon­nected to detectors from other manufacturers.
A MAXIMUM OF SIX (6) ALARMS WITH A RELAY MAY BE TANDEM INTERCONNECTED. (9120/9123F, 9120/9123TF, 9120/9123HF, 9220/9223F, 9220/9223TF, 9220/9223HF)
Relay Models
SUPERVISION WIRES
ACCESS
ACTS
CONT
ALARM
ACTS
CONT
TANDEM
POWER
CAUTION:
RED/YELLOW wire to be capped when not in use. This wire is for tandem connection only. Do not connect to any other circuit.
RED / YEL
WHT
BLK
Models 9120/9123F 9120/9123TF 9230/9223F 9220/9223TF
GRA
GRA
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL
BLK
WHT
TO ADDITIONAL GENTEX SMOKE ALARMS
Isolated Thermal with Optional Accessory Contacts
SMOKE ALARM
Y
Y
HEA SENSOR
ACCESS CONTACTS
ALARM
HF ONLY
CONTACTS
TANDEM
POWER
T
ACTS
CONT
Y
RELA RATED LOAD RESISTIVE
1.0 AMP @ 24 VDC @ 125 V
AMP
0.6
0.3 AMP @ 220 VAC MAX
AC MAX
Models 9120/9123H 9120/9123HF 9220/9223H 9220/9223HF
BRN
BRN GREY
GREY
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL
BLK
WHT
Page 4
9000/
9003
SERIES
Electrical Specifications
Operating Voltage (9120/9123) . . . . . . . . . . . . . . . . . . . . 120VAC, 60Hz
Operating Voltage (9220/9223) . . . . . . . . . . . . . . . . . . . . 220VAC, 50Hz
Operating Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .045 amps
Operating Current (Relay Options) . . . . . . . . . . . . . . . . . .070 amps
Operating Ambient Temp Range . . . . . . . . . . . . . . . . . . . 40°F to 100°F
Alarm Horn Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90dBA at 10 feet
Nominal Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5% obscuration
“F” Auxiliary Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Form A & 1 Form C (0.6 amp)
“T” Integral Thermal (Self-Restoring) . . . . . . . . . . . . . . . . 135°F at 50 feet
“H” Isolated Thermal Form A (Self-Restoring) . . . . . . . . . 135°F at 50 feet
Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diameter: 6.5 in. OA (5.75 in. at Ceiling)
Secondary Power Source . . . . . . . . . . . . . . . . . . . . . . . . Alkaline 9VDC battery
Architect & Engineering Specifications
The Photoelectric Smoke alarm shall be a Gentex Model 9120/9123/9220/9223 or approved equal which shall provide at least the following features and functions.
1. Nominal sensitivity shall be 2.5%.
2. The alarm shall utilize an infrared LED sensing circuit which pulses in 4 to 5 second intervals when subjected to smoke. After 2 consecutive pulses in smoke, the alarm will activate.
3. The alarm shall have a 9VDC alkaline battery as a back-up in the event building power is lost.
4. The 9VDC battery impedance shall be verified by the circuit of the smoke alarm.
5. The alarm shall provide an indicator when the battery is low in power or high impedance or is missing.
6. The alarm shall provide minimum 5-to-1 signal-to-noise ratio in the optics frame to assure stability of operation in environments
of high RF and transient conditions.
7. The sensing chamber shall be fully screened to prevent entrance of small insects, thus reducing the probability of false alarms.
8. A solid state piezo alarm rated at 90dBA at 10ft.
9. A visual LED monitor (condition indicator) will slow pulse in normal operation and rapid pulse in alarm.
10.An easily accessible test knob shall be provided. The test knob in the TEST position will simulate an actual smoke condition of
approximately 3.5% causing the detector to alarm within 20-36 seconds. It will also have the capability of testing to 0.85% as a required minimum. the light beam or test sensitivity is not sufficient, as indicated in National Code.
11. The detector shall have interconnect capabilities of up to 12 units or 6 units with relay.
12.The alarm shall have interconnection capabilites of 12 units on 9120/9120T/9120H/9123/9123T/9123H/9220/922T/9220H/9223/
9223T/9223H and shall have interconnection capabilites of 6 units on 9120F/9120TF/9120HF/ 9123F/9123TF/9123HF/9220F/9220TF/9220HF/9223F/9223TF/9223HF.
13.The manufacturer shall provide other compatible alarm models with the following optional features: a) 135°F isolated thermal
with normally opened contact for remote connection to local alarm or annunciator; b) 135°F integral thermal; c) auxiliary Form A/Form C relay contacts for initiating remote functions and annunciation; d) relay option that is capable of activation by tandem interconnect wire.
14.Unit must be UL 217 and UL 1730 listed for both wall and ceiling mount.
15.Unit shall be listed by Underwriters Laboratories, California State Fire Marshal (CSFM) and the Bureau of Standards and
Appeals (NYC).
All equipment shall be completely factory assembled, wired and tested, and the contractor shall be prepared to submit a certified
letter testifying to this condition. Alarms which do not meet all of the requirements of this specification will not be considered.
A magnetic switch closure or other switch closure, or smoke generating equipment which does not scatter
Thermal sensor shall be self-restoring.
Depth: 2.625 in.
24 units per carton 34 pounds per carton
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person's activities can dif obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.
ferently affect the
551-0040-02
Loading...