Photoelectric Smoke Alarm
9000/
120VAC and 220VAC with 9VDC Battery Back-Up
Single/Multiple Station Smoke Alarm
Applications
The 9000/9003 Series of photoelectric smoke alarms is designed for
residential and commercial residential applications, including homes,
apartments, hospitals, hotels and motels, in compliance with UL 217,
UL 1730 applicable IBC/IFC Standards and NFPA 72.
Available in many different models, the 9120/9123 Series is engineered to virtually eliminate nuisance alarms and deliver outstanding
performance wherever reliable fire protection is required. The 9000/
9003 Series is provided with a 9VDC alkaline battery for back-up in
the event building power is lost. The battery impedance is verified
and the alarm provides a low or missing battery warning.
The Gentex 9000/9003 Series provides an exclusive patented three
position test feature that simulates a 0.85% and 3.5% actual smoke
condition in full compliance with NFPA 72 and UL Standards.
Options include self-restoring 135°F integral or isolated heat
thermals and Form A/Form C dry contacts for remote annunciation.
Tandem interconnection of up to 12 units is available on several
models; tandem interconnection of up to 6 units is available on “F”
models, which activate the dry contacts from the tandem wire or a
local alarm.
9003
SERIES
Easy WashTMOn Site
Maintenance
Program
Standard Features
vailable in 120V
A
•
• Horn frequency 3100 Hz (nominal)
• Nominal 2.5% sensitivity
• Patented three position test switch
• Relays operate on battery back-up
• Quick-disconnect wiring harness
• 90dBA
• 90dBA
• 5-to-1 signal-to-noise ratio
• Pulsing LED sensing chamber
• Fully insect screened
• Interconnect with all Gentex tandem capable smoke alarms
• Easy W
• Red
• Mounting hardware adapts to standard junction boxes
• Dust cover to prevent contamination during installation
• Low or missing battery indicator
• 1 year warranty from date of purchase
continuous piezo horn (9120/9220 Series)
temporal 3 evacuation piezo horn (9123/9223 Series)
ash
LED pulses every 30 seconds, green LED for
AC and 220VAC with 9VDC battery back-up
TM
on-site maintenance washing program
AC power on
Product Listings
• UL 217 and UL 1730 Listed
• CSFM #7257-569:117
• BS+A/MEA #285-91-E
• BFP (City of Chicago)
• MSFM Listing #1929
• Hong Kong FSD Listed (9220 Series ONLY)
Product Compliance
• NFPA 72
• IBC/IFC/IRC
![](/html/f9/f9d5/f9d5df849f2b5ebb44409444f7c6111072b34f6d0fd9fc75315e22b372264b5b/bg2.png)
9000 (9120/9220) Series - Continuous Piezo Sounder
Model
Number
9120 917-0001-002 120VAC
9120T 917-0002-002 120VAC
9120H 917-0003-002 120VAC
9120F 917-0004-002 120VAC
9120TF 917-0009-002 120VAC
9120HF 917-0005-002 120VAC
9220 917-0026-002 220VAC
9220T 917-0027-002 220VAC
9220H 917-0028-002 220VAC
9220F 917-0029-002 220VAC
9220TF 917-0031-002 220VAC
9220HF 917-0030-002 220VAC
Part
Number V
oltage
Integral
135oF
Thermal
Isolated
135oF
Thermal
Tandem
o
Up T
12 Units
Tandem
o
Up T
6 Units
=
= =
= =
= =
= = =
= = =
=
= =
= =
= =
= = =
= = =
Form A/C
Contacts
9003 (9123/9223) Series - Temporal 3 Evacuation Piezo Sounder
Model
Number
9123 917-0012-002 120VAC
9123T 917-0013-002 120VAC
9123H 917-0014-002 120VAC
9123F 917-0015-002 120VAC
9123TF 917-0017-002 120VAC
9123HF 917-0016-002 120VAC
9223 917-0032-002 220VAC
9223T 917-0033-002 220VAC
9223H 917-0034-002 220VAC
9223F 917-0035-002 220VAC
9223TF 917-0037-002 220VAC
9223HF 917-0036-002 220VAC
Part
Number Voltage
Integral
135oF
Thermal
Isolated
135oF
Thermal
Tandem
Up To
12 Units
Tandem
Up To
6 Units
=
= =
= =
= =
= = =
= = =
=
= =
= =
= =
= = =
= = =
Form A/C
Contacts
NOTES:
•
Series available in round configuration only
• When testing 9123 Series, it may take up to 16 seconds longer for smoke alarm to go in or out of alarm mode.
• It is recommended that 9000/9003 Series smoke alarm be tested weekly
echnical Bulletin 002 for
• Refer to
• 9120/9220 units produce a non-temporal audible alarm and are therefore not intended for locations where the desired action of the occupant(s) is evacuation.
• 9123/9223 units produce a temporal 3 audible alarm. Per NFP
T
is required whenever the intended response is to evacuate the building.
Easy W
.
TM
ash
on site washing instructions
A
.
American National Standard Audible Emergency Evacuation Signal as defined in ANSI S3.41,
72, the