Silent Call 710ls User Manual

Photoelectric Smoke Alarm
710/713CS/LS
with Visual Signaling Appliance
Applications
The 710/713CS/LS and 7109/7139CS/LS smoke alarms are designed to give reliable early warning of the presence of smoke where both audible and visual alarms are required. The series features a 90dBA solid state piezo signal and a 177 Candela strobe with “FIRE” lettering. The strobe is listed per UL 1971.
The 713/7139 Series provides the temporal 3 evacuation tone as a standard feature. When testing the 713/7139 Series it may take up to 16 seconds longer to go in or out of alarm.
The smoke alarm operates on the light scattering principle, a superior method of detection in smoldering fires, utilizing a pulsing LED light source and a photodiode sensor in a fully screened sensing chamber.
Every 4 to 5 seconds the pulsing LED emits an infrared beam that by passes the photodiode under normal conditions. However, when smoke enters the sensing chamber, the infrared beam is deflected onto the sensor by the smoke particles. The LED pulse rate increases to 8 times the normal rate, and after the photodiode confirms that smoke is present for 2 consecutive pulses, it will produce the signal necessary to trip an alarm.
Upon activation, the alarm will emit a 90dBA local audible signal and activate the high intensity strobe. During the alarm period the strobe will flash at a brightness of 177 Candela 60 times per minute. After the smoke has cleared from the detector, the unit will revert to the normal stand-by condition.
Standard Features
• 177 Candela Rating (UL1971)
• Solid State 90dBA Horn
• Temporal 3 Evacuation Sounding Device (713CS/LS & 7139CS/LS Series)
• Nominal 2.5% Sensitivity
Full Function Test Switch—Patented Three Position Test Fully Insect Screened
• Quick-Disconnect Wiring Harness (CS Models)
9 VDC Battery Back-Up (7109/7139CS/LS) w/Audible Low Battery Chirp
(Visual Does Not Operate on Battery Back-Up)
• Form C Auxiliary Relay Contacts for
andem Connection up to 6 Detectors Per System (CS Models)
T
• 9 Foot Line Cord (LS Models)
• Mounting Hardware
• Warranty is 1 Year From Date of Purchase Dry Contacts Will Activate From the Tandem Wire
• Relays Operate on Battery Back-Up, Visual Does Not Operate
• Horn Frequency 3100Hz (Nominal)
photoelectric single station
Remote Annunciation (CS Models)
7109/7139CS/LS
SERIES
Product Listings
UL 217
CAN/ULC 552-02/553-02 Listed
(710CS & 7109CS Only)
• BFP (City of Chicago) BS+A/MEA
• MSFM Listing #1929
• CSFM Listing #7257-569:104 (710/713CS/LS)
• CSFM Listing #7257-569:118 (7109/7139CS/LS)
Also UL and Commercial Residential Multiple-station Smoke Alarms.
Product Compliance
• NFPA 72
• Americans with Disabilities Act (ADA)
#285-91-E
1730 listed for Commercial Residential
710 Series Photoelectric Smoke Detector with Signaling Appliance
Model
Number
710CS-W 907-0231-002 120 VAC
710CS-C 907-0232-002 120 VAC
710CSX-W 907-0235-002 120 VAC
710CSX-C 907-0236-002 120 VAC
710LS 907-0239-002 120 VAC
7109CS-W 917-0007-002 120 VAC
7109CS-C 917-0008-002 120 VAC
7109CSX-W 917-0010-002 120 VAC
7109CSX-C 917-0011-002 120 VAC
7109LS 917-0006-002 120 VAC
Part Number Voltage Local
90dBA
Piezo
= = = =
= = = =
= = = =
= = = =
= = =
= = = = =
= = = = =
= = = = =
= = = = =
= = = =
Wall
Mount
Ceiling
Mount
9 Foot
Line
Cord
Tandem Up To 6
Units
Form C
Contacts
713 Series Photoelectric Smoke Detector with Signaling Appliance and Temporal 3 Sounder
Model
Number
713CS-W 907-0248-002 120 VAC
713CS-C 907-0249-002 120 VAC
713CSX-W 907-0252-002 120 VAC
713CSX-C 907-0253-002 120 VAC
713LS 907-0256-002 120 VAC
7139CS-W 917-0019-002 120 VAC
7139CS-C 917-0020-002 120 VAC
7139CSX-W 917-0021-002 120 VAC
7139CS-C 917-0022-002 120 VAC
7139LS 917-0018-002 120 VAC
Part Number Voltage Local
90dBA
Piezo
= = = =
= = = =
= = = =
= = = =
= = =
= = = = =
= = = = =
= = = = =
= = = = =
= = = =
Wall
Mount
Ceiling
Mount
9 Foot
Line
Cord
Tandem Up To 6
Units
Form C
Contacts
9VDC
Battery
Back-Up
9VDC
Battery
Back-Up
NOTES:
Candela Rating: 177 Candela UL Listed Strobe Light Flash Rate per Minute : 60 Minimum
Available in square configuration only. Ceiling mount not available in line cord models. The X models have the ability to turn the strobe on from a field mounted relay.
*“W” = Wall Mount *“C” = Ceiling Mount
Wiring Diagram
710CS 7109CS 713CS 7139CS
QUICK-DISCONNECT PLUG
710CS 7109CS 713CS 7139CS
OR
HOT
NEUT
TANDEM
SMOKE DETECT
POWER
AUXILIARY
ACTS
CONT
UNIVERSAL MOUNTING PLATE
1
11
10
4
9
3
BLK
WHT
RED/YEL
YEL
ORN
BLU
RELAY CONTACTS RATED LOAD RESISTIVE
0.6 AMP @ 125 VAC MAX 0R 1 AMP @ 24 VDC MAX
Electrical Specifications
Operating Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120 VAC, 60Hz
Operating Current . . . . . . . . . . . . . . . . . . . . . . . . . .0.400 amps (Peak)
Operating Ambient Temp Range . . . . . . . . . . . . . . . . . . .40°F to 100°F
Alarm Horn Rating . . . . . . . . . . . . . . . . . . . . . . . .90 Decibels at 10 Ft.
Nominal Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . .2.5% Obscuration
Auxiliary Relay (Standard) . . . . . . . . . . . . . . . . . . .1 Form C (0.6 amp)
(710/713CS and 7109/7139CS)
*9 VDC alkaline battery (supplied)
The CSX models are used for remote annunciation of the strobe.
SMOKE DETECT
OR
710/713CS/LS
7109/7139CS/LS
SERIES
Architect & Engineering Specifications
The Photoelectric Detector Shall be a Gentex Model 710/713LS/7109/7139LS or approved equal which shall provide at least the following features and functions.
1. Nominal sensitivity shall be 2.5%.
2. The alarm shall utilize an infrared LED sensing circuit which pulses in 4 to 5 second intervals; when subjected to smoke the pulse rate shall increase 8 times. After 2 consecutive pulses in smoke, the detector will alarm.
3. The alarm shall provide minimum 5-to-1 signal-to-noise ratio in the optics frame to assure stability of operation in environments of high RF and transient conditions.
4. The sensing chamber shall be fully screened to prevent entrance of small insects, thus reducing the probability of false alarms.
5. A solid state piezo alarm rated at 90dBA at 10 ft.
6. A visual LED monitor (condition indicator) will pulse in normal operation and steady on in alarm.
7. The visual signal shall have a minimal light output of 177 Candela.
8. An easily accessible test knob shall be provided. The test knob in the TEST position will simulate an actual smoke condition of approximately 3.5% causing the detector to alarm within 20-36 seconds. Also the alarm shall test for the most sensitive setting. An alarm during this test will be a maintenance indicator.
9. The alarm shall be provided with a 9 foot line cord with a strain relief connection, if a portable unit.
10. Unit must be capable of providing a monitored battery back-up.
11. Unit must be UL 217 listed for wall mount.
12. Unit shall also meet all requirements of the State of California Fire Marshal, Bureau of Standards and Appeals and the Americans with Disabilities
Act (ADA).
Architect & Engineering Specifications
The Photoelectric Detector Shall be a Gentex Model 710/713CS/7109/7139CS or approved equal which shall provide at least the following features and functions.
1. Nominal sensitivity shall be 2.5%.
2. The alarm shall utilize an infrared LED sensing circuit which pulses in 4 to 5 second intervals; when subjected to smoke the pulse rate shall
increase 8 times. After 2 consecutive pulses in smoke, the detector will alarm.
3. The alarm shall provide minimum 5-to-1 signal-to-noise ratio in the optics frame to assure stability of operation in environments of high RF and
transient conditions.
4. The sensing chamber shall be fully screened to prevent entrance of small insects, thus reducing the probability of false alarms.
5. A solid state piezo alarm rated at 90dBA at 10 ft.
6. A visual LED monitor (condition indicator) will pulse in normal operation and will remain solid in alarm.
7. The visual signal shall have a minimal light output of 177 Candela and will flash one time per second.
8. An easily accessible test knob shall be provided. The test knob in the TEST position will simulate an actual smoke condition of approximately
3.5% causing the detector to alarm within 20-36 seconds.
Also the detector shall test for the most sensitive setting.
be a maintenance indicator. Return to Gentex for maintenance.
9. The alarm shall be provided with a Form C contact for remote annunciation purposes.
The manufacturer shall provide other compatible detector models with the following optional features: a) auxiliary Form C relay contact for
10.
initiating remote functions and annunciation; b) relay option that is capable of activation by tandem interconnect wire.
11. Unit must be capable of providing a monitored battery back-up.
12. Unit must be UL 217 and UL 1971 listed for wall mount.
13. Unit shall also meet all requirements of the State of California Fire Marshal, Bureau of Standards and Appeals and the Americans with
Disabilities Act ADA).
All equipment shall be completely factory assembled, wired and tested, and the contractor shall be prepared to submit a certified letter testifying to this condition. Detectors which do not meet all of the requirements of this specification will not be considered.
An alarm during this test will
12 units per carton 21 pounds per carton
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to par­ticular fact patterns. Each person's activities can differently affect the obligations that exist under applica­ble laws, regulations or rules. and should not be used as a substitute for seeking professional legal advice. Gentex will not be responsi­ble for any action or failure to act in reliance upon the information contained in this material.