Photoelectric Smoke Alarm
120 VAC and 220 VAC
Single Station Smoke Alarm
7000/7003
Applications
The 7000/7003 Series of photoelectric smoke alarms is designed
for residential, commercial residential and other occupancies
defined by NFPA 101 and IBC, including homes, apartments,
hospitals and hotels, in compliance with UL 217, UL1730, IBC
and NFPA 72. Available in many different models, the 7000/7003
Series is engineered to virtually eliminate nuisance alarms and
deliver outstanding performance wherever reliable fire protection
is required.
The Gentex 7000/7003 Series provides an exclusive patented
three position test feature that simulates a 0.85% and 3.5%
actual smoke condition in full compliance with NFPA 72, UL 217
and UL1730 standards. It also provides a maintenance indicator
and makes the 100% testing requirement easy.
Options include self-restoring 135°F fixed temperature integral or
isolated thermals, and Form A/Form C dry contacts for remote
annunciation. Tandem interconnection of up to 12 units is
available on several models; tandem interconnection of up to 6
units is available on “F” models, which activate the dry contacts
from a remote alarm through the tandem wire or a local alarm.
The 7003 Series provides the temporal 3 evacuation tone as
a standard feature. When testing the 7003 Series it may take
up to 16 seconds longer to go in or out of alarm.
Product Listings
SERIES
Standard Features
and 220V
vailable in 120V
A
•
• Horn Frequency 3100Hz (Nominal)
• Nominal 2.5% Sensitivity
Functional
•
• On-Site Maintenance Washing Program
• Quick-Disconnect Wiring Harness
90dBA
•
• Temporal 3 Evacuation Sounding Device (7003 Series)
• 1 Year Warranty From Date of Purchase
5-to-1 Signal-to-Noise Ratio
•
Pulsing LED Sensing Chamber
•
• Fully Insect Screened
Solid-State LED Condition Indicator
•
Mounting Hardware
•
• Dust Cover to Prevent Contamination During Installation
Complies W
•
Solid-State Non-Latching Piezo Horn
AC
est Switch — Patented
T
Adapts to Standard Junction Boxes
ith IBC/IFC (7003 Series)
AC
Three Position Test
• BFP (City of Chicago)
• MSFM Listing #1929
• BS+A/MEA #927-84-SA
• CSFM #7257-569:104
• UL 217 and UL1730 Listed
Product Compliance
72
A
• NFP
• NFPA 101
• IBC/IFC

7000 (7100/7200) Series - Solid State Piezo Sounder
Model
Number
7100 907-1109-002 120VAC
7100T 907-1110-002 120VAC
7100H 907-1111-002 120VAC
7100F 907-1113-002 120VAC
7100TF 907-1114-002 120VAC
7100HF 907-1115-002 120VAC
7200 907-1204-002 220VAC
7200T 907-1205-002 220VAC
7200H 907-1206-002 220VAC
7200F 907-1207-002 220VAC
Part
Number
Voltage Local
90dBA
Piezo
= =
= = =
= = =
= = =
= = = =
= = = =
= =
= = =
= = =
= = =
Integral
135oF
Thermal
Isolated
135oF
Thermal
7003 (7103/7203) Series - Temporal 3 Piezo Sounder
Tandem
o
Up T
12 Units
Tandem
o
Up T
6 Units
Form A/C
Contacts
Model
Number
7103 907-1116-002 120VAC
7103T 907-1117-002 120VAC
7103H 907-1118-002 120VAC
7103F 907-1120-002 120VAC
7103TF 907-1121-002 120VAC
7103HF 907-1122-002 120VAC
7203 907-1208-002 220VAC
7203T 907-1209-002 220VAC
7203H 907-1210-002 220VAC
7203F 907-1211-002 220VAC
Part
Number
Voltage Local
90dBA
Piezo
= =
= = =
= = =
= = =
= = = =
= = = =
= =
= = =
= = =
= = =
Integral
135oF
Thermal
Isolated
135oF
Thermal
Tandem
Up To
12 Units
Tandem
Up To
6 Units
Notes:
The 7000/7003 Series are round units. Square units as 710/713 also available.
Form A/C
Contacts

7000/7003 Series Wiring Diagrams
Tandem Wiring Diagram
120 VOL
60 HZ
TS
HOT
ELECTRICAL
BOX
TANDEM WIRE
NEUT
ELECTRICAL
BOX
ELECTRICAL
BOX
QUICK
DISCONNECT
TYPE PLUG
SMOKE
1
ALARM
2
3
SMOKE
1
ALARM
2
3
SMOKE
1
ALARM
2
3
LIMITATIONS:
A Maximum of 12 alarms
(7100/7103, 7100/7103T,
7100/7103H, 7200/7203,
7200/7203T, 7200/7203H)
may be connected together.
Do not exceed 125 feet
between each detector. Do
not exceed 1125 feet
between the first and last
detector. NOTE: Gentex
smoke alarms can not be
interconnected to detectors
from other manufacturers.
A MAXIMUM OF SIX (6)
ALARMS WITH A RELAY
MAY BE TANDEM INTERCONNECTED. (7100/7103F,
7100/7103TF, 7100/7103HF,
7200/7203F, 7200/7203TF,
7200/7203HF)
Relay Models
SMOKE
ALARM
ACCESS
CONTACTS
ALARM
CONTACTS
TANDEM
POWER
CAUTION:
RED/YELLOW wire to be capped
when not in use. This wire is for
tandem connection only. Do not
connect to any other circuit.
RED / YEL
WHT
BLK
Models
7100/7103F
7100/7103TF
7203/7203F
7200/7203TF
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL
BLK
WHT
TO ADDITIONAL
SMOKE OR HEAT
ALARMS
(MAX 12 ALARMS
PER SYSTEM)
Isolated thermal with optional
accessory contacts.
SMOKE
ALARM
HEA
SENSOR
ACCESS
CONT
Y
ALARM
HF ONL
CONT
ANDEM
T
POWER
T
ACTS
ACTS
RELAY CONTACTS
RATED LOAD RESISTIVE
@ 24 VDC
AMP
1.0
0.6 AMP @ 125 VAC MAX
0.3 AMP @ 220 VAC MAX

7000/7003
SERIES
Electrical Specifications
Operating Voltage (7100/7103) . . . . . . . . . . . . . . . . . . . . 120 VAC, 60Hz
Operating Voltage (7200/7203) . . . . . . . . . . . . . . . . . . . . 220 VAC, 50Hz
Operating Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .045 amps
Operating Current (Relay Options) . . . . . . . . . . . . . . . . . .070 amps
Operating Ambient Temp Range . . . . . . . . . . . . . . . . . . . 40°F to 100°F
Alarm Horn Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90dBA at 10 ft.
Nominal Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5% Obscuration
Auxiliary Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Form A & 1 Form C (0.6 amp)
“F”
“T” Integral Thermal (Self-Restoring) . . . . . . . . . . . . . . . . 135°F at 50 ft.
“H” Isolated Thermal Form A (Self-Restoring) . . . . . . . . . 135°F at 50 ft.
Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diameter: 6.5 in. OA (5.75 in. at Ceiling)
Architect & Engineering Specifications
The Photoelectric Smoke alarm shall be a Gentex Model 7100/7103/7200/7203 or approved equal which shall provide at least the
following features and functions.
1. Nominal sensitivity shall be 2.5%.
2. The alarm shall utilize an infrared LED sensing circuit which pulses in 4 to 5 second intervals when subjected to smoke. After 2
consecutive pulses in smoke, the alarm will activate.
3. The alarm shall provide minimum 5-to-1 signal-to-noise ratio in the optics frame to assure stability of operation in environments
of high RF and transient conditions.
4. The sensing chamber shall be fully screened to prevent entrance of small insects, thus reducing the probability of false alarms.
5. A solid state piezo alarm rated at 90dBA at 10ft.
6. A visual LED monitor (condition indicator) will slow pulse in normal operation and rapid pulse in alarm.
7. An easily accessible test knob shall be provided. The test knob in the TEST position will simulate an actual smoke condition of
approximately 3.5% causing the detector to alarm within 20-36 seconds. It will also have the capability of testing to 0.85% as a
required minimum. A magnetic switch closure or other switch closure, or smoke generating equipment which does not scatter
the light beam or test sensitivity is not sufficient, as indicated in National Code.
8. The detector shall have tandem interconnect capability of up to 12 units or 6 units with relay.
9. The alarm shall have tandem interconnection capabilites of 12 units on 7100/7100T/7100H/7103/7103T/7103H/7200/
7200T/7200H/7203/7203T/7203H and shall have tandem interconnection capabilites of 6 units on 7100F/7100TF/7100HF/
7103F/7103TF/7103HF/7200F/7200TF/7200HF/7203F/7203TF/7203HF
10.The manufacturer shall provide other compatible alarm models with the following optional features: a) 135°F isolated thermal
with normally opened contact for remote connection to local alarm or annunciator; b) 135°F integral thermal; c) auxiliary Form
A/Form C relay contacts for initiating remote functions and annunciation; d) relay option that is capable of activation by tandem
interconnect wire. Thermal sensor shall be self-restoring.
11. Unit must be UL 217 listed for both wall and ceiling mount.
12.Unit shall be listed by Underwriters Laboratories, California State Fire Marshal (CSFM) and the Bureau of Standards and
Appeals (NYC).
All equipment shall be completely factory assembled, wired and tested, and the contractor shall be prepared to submit a certified
letter testifying to this condition.
Alarms which do not meet all of the requirements of this specification will not be considered.
Depth: 2.625 in.
.
24 units per carton
32 pounds per carton
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes
only, are necessarily summary, and are not purported to serve as legal advice and should not be used
as such. Gentex makes no representations and warranties, express or implied, that these materials
are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws,
regulations and rules. The materials do not address all legal considerations as there is inevitable
uncertainty regarding interpretation of laws, regulations and rules and the application of such laws,
regulations and rules to particular fact patterns. Each person's activities can dif
obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be
used only for informational purposes and should not be used as a substitute for seeking professional
legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the
information contained in this material.