Silcon DATAPOWER DP300E series User Manual

Page 1
1User Guide DP300E
7OA0001 GB rev.09
DATAPOWER™
DP300E Series User guide
Copyright © 1997 Silcon Power Electronics A/S
Due to continuous product development information given in this manual is subject to change without notice.
Page 2
2 User Guide DP300E
7OA0001 GB rev.09
Page 3
3User Guide DP300E
7OA0001 GB rev.09
Contents:
1.0 Introduction
1.1 General
1.2 The display unit
2.0 Stop-start
2.1 General
2.2 Stop
2.3 Start
3.0 Operation
3.1 Keyboard description
4.0 Programming parameters
4.1 General
4.2 Parameters
5.0 Reading out measurements
6.0 Alarms - what to do
6.1 General
6.2 The events stack
6.3 Alarm messages
6.4 The events logger
6.5 Displaying the events stack
7.0 Service bypass switch
7.1 Operating the external service bypass switch
7.2 Operating the external service bypass switch for parallel systems
8.0 Preventive maintenance
8.1 General
8.2 Fan
8.3 Battery
8.4 Battery capacity test
9.0 Economy operation
10.0 Software
10.1 Choice of software
10.2 Configuration codes
10.3 Choice of cable
11.0 How to contact Silcon
Page 4
4 User Guide DP300E
7OA0001 GB rev.09
Introduction
1.0 Introduction
1.1 General
Congratulations on your choice of UPS (Uninterruptible Power Supply). This UPS has been designed and produced for reliable and troublefree long-term use. For you it means that once installed and commissioned, you can forget it. You only have to arrange a preventive maintenance as described in section 8 of this manual.
1.2 The display unit
The display unit – placed on the front of the UPS – is the link between user and UPS. It consists of a display, an alarm LED, and a keyboard. The display is used for showing parameters, measured values, and alarm mes­sages. A background light is activated in case of an alarm or if one of the keys are pressed. No activity or no alarm for 5 minutes will automatically switch of the light.
By pressing and simultaneously you increase the contrast, and by
pressing and simultaneously you decrease the contrast.
The alarm LED is together with an acoustic signal the indicator for unusual operating situations. The light changes from green to red in case of alarm. The keyboard is used for programming of operating parameters and for calling read­outs of parameters / alarm messages.
Note:
The display accuracy is ±1%, ± 1 digit.
Page 5
5User Guide DP300E
7OA0001 GB rev.09
2.0 Stop – start
2.1 General
According to electrical regulations only the local authorized electrical installer is normally allowed to perform a complete switching in and out of the UPS, as it involves operation of the battery supply breaker, where touch of high voltage parts is possible. For above reasons the normal user can only switch the UPS into system off mode and from here back into normal operation via the “safe” push buttons.
2.2 Stop
Action Display shows Description
Open the front door and activate the ”ON” and “OFF” push-button simultaneously
2.3 Start
Action Display shows
Open the front door and activate the green “ON” push-button
Stop – start
System off
Alarm LED lights. Acoustic alarm sounds for 30 seconds.
Warning:
Please read maintenance section, if UPS has to be stopped for more than one week.
Normal operation Load power xx%
Page 6
6 User Guide DP300E
7OA0001 GB rev.09
Operation
3.0 Operation
The display is used to show parameters, alarms/messages, and measured values. The alarm LED is used with an audible alarm to indicate unusual operating situations. The keyboard is used for programming and control of displaying param­eters, alarm messages, and displaying measured values.
3.1 Keyboard description
Page 7
7User Guide DP300E
7OA0001 GB rev.09
Programming parameters
NOTE:
The system must not run in bypass mode for longer periods of time as the batteries will not be re­charged
4.0 Programming parameters
4.1 General
Some operating parameters can be programmed directly from the keyboard, but this has already been done during the commissioning. Unless you are quite sure of the consequence of changing the following parameters, then let it be a task for your local dealer, if needed. Parameters are programmed as shown in the example 4.2.3.
4.2 Parameters
4.2.1
Parameter Setting* Comments
Bypass YES, NO “YES” will switch the system into
bypass mode
Language GB, D, F, Language of text in display
DK, S, SF NL, PL, CZ E, P, SK, H
Autostart YES, NO Automatic restart by mains return.
Ensures quick battery recharge.
Remote shutdown YES, NO Shutdown of UPS by remote signal active
Remote shutdown HIGH, LOW Nature of remote shutdown signal polarity Remote shutdown time 0, 1, 2, 3, 4 Time delay on remote shutdown of UPS
5, 6, 7, 8, 9 10 min.
Battery capacity test - Initiates check of back-up time. The
measured time is from start until it reaches low DC warning level (See section 8.4)
Battery monitor test** - Initiates check of battery condition by
25% discharging.
Automatic battery test** NO, 3, 6 Activates the battery monitor test in cyclic
intervals (Unit - months)
Battery monitor reset** - Pressing the
and key after
selecting this parameter resets alarms
and flushes messages in the alarm stack Boost charge YES, NO “YES” results in boost charge (10 hours) Autoboost charge YES, NO “YES” results in boost charge after battery
operation (10 hours) Enter new date YYMMDD Local date can be entered Enter new time HHMMSS Local time can be entered
* Text in bold letters are the standard setting ** Only for systems with Battery Monitor active
Page 8
8 User Guide DP300E
7OA0001 GB rev.09
Programming parameters
To return to normal operation
Action Display shows
5. Press
to enter parameter stack
6. Press
or until
7. Press
until
8. Press to store
9. Press to exit
Programming of the other parameters can be performed in exactly the same way.
Bypass operation
: YES
Normal operation load power xx%
Bypass operation
: NO
4.2.2 Keys used for programming
4.2.3 Programming example - switch to bypass operation
Action Display shows
1. Press to enter parameter stack
2. Press or until
3. Press
until
4. Press to store
Bypass operation
: NO
Bypass operation
: YES
Page 9
9User Guide DP300E
7OA0001 GB rev.09
Measurements
5.0 Reading out measurements
Press as indicated below one key or two keys simultaneously (Used values are only random for illustration):
Action Display shows Description
96.04.16
10.22,13
Mains voltage
385 385 385 V
ac
Battery current
+ 2 A
dc
Mains Current
16 16 16 A
ac
Battery voltage
438 437 V
dc
Year, month, day Hour, minute, second
Mains voltage is 3 x 385 V
ac
Mains current is 3 x 16 A
ac
Battery voltage is 438 V
dc
on batt.1.
437 Vdc on batt.2. Charging current is (+) 2 A
dc
(Discharging current (÷)) Output voltage
is 3 x 380 V
ac
Output current is 3 x 15 A
ac
Output frequency is 50 Hz
Battery temperature is 25°C
Output peak current is 3 x 22A
ac
(only of interest for service engineers) Returns to normal status indication.
If not pressed, automatic switch back will be performed after 20 seconds.
Output voltage
380 380 380 V
ac
Output current
15 15 15 A
ac
Output frequency
50Hz
Battery temp.
25ºC
Output peak current
22 22 22 A
ac
Normal operation
load power xx%
Page 10
10 User Guide DP300E
7OA0001 GB rev.09
NOTE:
A battery monitor test can not be performed unless the battery is fully charged.
6.0 Alarms - What to do
6.1 General
Alarms are indicated by the red lamp (above the upper left corner of the keyboard) and by a 30 secs. acoustic signal. An alarm is registered in an alarm stack as long as it is present, and if more in the same succession as they arise.
6.2 The alarm stack
The alarm stack can be displayed by:
Action Description
1. Press
Access to the alarm stack
2. Press
or Scroll up or down through the alarm stack messages.
Last message is “No (further) alarm”.
3. Press
Exits the alarm stack. If not operated the system will exit the alarm stack automatically
after 30 seconds.
6.3 Alarm messages
The alarm messages are together with the events logger (described in section 7.0) part of a diagnostic system for the UPS service specialist. Before calling for assistance you may take one or more of the following actions.
1. “Battery defective” means no back-up capacity any longer. Call for assistance. “Battery Week” means reduced back-up capacity. Reset the “Battery week” alarm signal according to point 4.2 and start up a battery capacity test according to point 8.4. When finished – record the obtained back-up time and reset an eventual new alarm from the battery monitor. Let the UPS recharge the battery for at least 16 hours, and with the same load as before start up a second battery capacity test. If this results in improved back-up time continue with further capacity tests until none or insignificant improvements take place. Above might “wake up” the battery – else call for assistance.
2. Check the local mains power supply. One or more fuses may be blown or some­body could by accident have switched off the supply.
3. Check if the cooling air intake on your UPS has been blocked.
4. Check if somebody has switched more load on the UPS - the max. output capac­ity may be exceeded.
5. If there is no output voltage from the UPS - the mains supply is present and atempt to restart gives no result – bypass the UPS as described in the following section by means of the external service bypass switch if present.
Alarms
Page 11
11User Guide DP300E
7OA0001 GB rev.09
6.4 The events logger
The events logger is a memory stack, in which the last 250 events are stored in the same succession as they arose. (Showing the latest at first). Events stored are the alarms and the following operational modes:
Mode Comments
MPU is reset UPS has been totally switched off Stand-by UPS has been in stand-by mode by parallel
system Normal operation UPS has been in normal operation Battery operation UPS has been in battery operation Bypass operation UPS has been in bypass operation System off UPS has been off
6.5 Displaying the events stack
Action Description
1. Press
and
2. Press or
3. Press
4. Press
Alarms
Press the two keys simultaneously to get access to the events stack
Scroll up or down through the events stack (last message is “No (further) event”).
Displays the time where the event happened
Exit the events stack. If not operated the system will exit the events stack automatically after 30 seconds
Page 12
12 User Guide DP300E
7OA0001 GB rev.09
Warning:
If the UPS is out of service for more than 8 days the connected batteries might be damaged. Refer to total „Switching off“ as described in the Installation Guide.
Service Bypass Switch
7.1 Operating the external service bypass switch
7.1.1 Bypassing the UPS
Action
1. Press on the keyboard
2. Press
or on the keyboard until
3. Press
on the keyboard
4. Press on the keyboard
5. Check lamp indication on the bypass panel The Green lamp (H003) above the bypass switch handle (Q003) lights
6. Turn the external bypass switch (Q003) The Green lamp (H002)
to position „1“. above the output switch
handle (Q002) lights
7. Turn the output switch (Q002) to Only the lamp (H002) above
position “0”. the output switch handle
(Q002) lights now
8. Open the front door and press both the green
„ON“ and the red „OFF“ key simultaneously The acoustic alarm sounds for 30 secs.*
9. Turn the input switch to position „0“.
The red alarm LED below the display lights and the acoustic alarm sounds for 30 secs.
* The acoustic alarm can be reset by the key
EMERGENCY (UPS not alive)
1. Turn the input switch (Q001) to position „0“.
2. Turn the output switch (Q002) to position „0“.
3. Change released system input fuse(s), if any.
4. Turn the bypass switch (Q003) to position „1“.
Bypass operation
: NO
Bypass operation
: YES
**System OFF**
Display shows
Lamp indication on bypass panel
Display shows
7.0 Service bypass switch
DP
Page 13
13User Guide DP300E
7OA0001 GB rev.09
7.1.2 Switching the system from external bypass into normal UPS operation
Action*
1. Turn the input switch (Q001) to position „1“
2. Open the UPS front door and press the green „ON“ key
3. Press
on the keyboard
4. Press or on the keyboard until
5. Press on the keyboard
6. Press
on the keyboard
7. Check lamp indication on the bypass panel The Green lamp (H002)
above the output switch handle (Q002) lights
8. Turn the output switch (Q002) to position Now the green lamp (H003) „1“ above the bypass switch
handle (Q003) lights too
9. Turn the bypass switch (Q003) to position Only the green lamp (H003) „0“ above the bypass switch
handle (Q003) lights
10. Press
on the keyboard
11. Press
or on the keyboard until
12. Press
on the keyboard
13. Press on the keyboard
14. Press
on the keyboard
15. Press
on the keyboard
**System OFF**
Normal operation
load power 0%
Lamp indication on bypass panel
Display shows
Bypass operation
: YES
Bypass operation
: NO
Bypass operation
: YES
Bypass operation
: NO
Normal operation
load power xx%
No lamps on the bypass panel light any longer
Display shows
Service Bypass Switch
DP
Page 14
14 User Guide DP300E
7OA0001 GB rev.09
Service Bypass Switch
Bypass operation
: NO
Bypass operation
: YES
**System OFF**
Display shows
Display shows
Warning:
If the UPS is out of service for more than 8 days the connected batteries might be damaged. Refer to total „Switching off“ as described in Instal. Guide Chapter 7.0.
Lamp indication on bypass panel
Bypass operation
7.2.1 Bypassing the parallel UPS system
Action
Point 1-4 can be carried out with any of the parallel systems, however this will switch all systems into bypass operation.
1. Press
on the keyboard
2. Press or on the keyboard until
3. Press on the keyboard
4. Press
on the keyboard
All systems will transfer to bypass operation Do not switch off any of the UPS systems until
point 5-8 has been carried out
5. Check lamp indication on the bypass panel The green lamp (H003) above the bypass switch handle (Q003) lights
6. Turn the external bypass switch (Q003) The green lamp (H004)
to position „1“ above the output isolator
(Q004) and the green lamps (H002) above the output switch handles (Q002) light
7. Turn the output isolator (Q004) to position “0” The green lamp (H002) above the output isolator light
8. Turn all output switches (Q002) to position „0“ Only the lamp (H002) above the output switch handles (Q002) lights now
9. Open the front door and press both the green
„ON“ and the red „OFF“ key simultaneously in any of the systems The acoustic alarm sounds for 30 secs.* Repeat for (all) other system(s).
10. Turn all input switches (Q001) to position „0“
The red alarm LED below the display lights and the acoustic alarm sounds for 30 secs.
* The acoustic alarm can be reset by the key
7.2 Operating the external service bypass switch for parallel systems
DP300E
DP300E
Q003
Q001a
Q001b
Q002b
Q004
Q002a
Service Bypass Switch
LoadMains
Page 15
15User Guide DP300E
7OA0001 GB rev.09
Service Bypass Switch
EMERGENCY (UPS not alive)
1. Turn the input switches (Q001) to position „0“.
2. Turn the output switches (Q002) to position „0“.
3. Turn the output isolator (Q004) to position “0”.
4. Change possible released system input fuse(s).
5. Turn the bypass switch (Q003) to position „1“.
Page 16
16 User Guide DP300E
7OA0001 GB rev.09
Service Bypass Switch
7.2.2 Switching the parallel system from external bypass into normal UPS operation
Action
1. Check that output isolator (Q004) is in position “0”
2. Turn input switches (Q001) and output switches (Q002) to position “1”
3. Open the UPS front door and press the green “ON” key on all systems
Point 4-7 can be carried out with any of the parallel systems, however this will switch all systems to bypass operation
4. Press
on the keyboard
5. Press or on the keyboard until
6. Press
on the keyboard
7. Press on the keyboard
All systems will transfer to bypass operation
8. Check that green lamp (H004) above output isolator (Q004) lights
9. Turn the output isolator (Q004) to position “1” Now also the green lamp
(H003) above the bypass switch handle (Q003) lights
10. Turn the bypass switch (Q003) to position „0“ Only the green lamp (H003)
above the bypass switch handle (Q003) lights
Point 11-16 must be carried out with same UPS as was used for point 4-7
**System OFF**
Normal operation
load power 0%
Display shows
Lamp indication
on bypass panel
Bypass operation
: YES
Bypass operation
: NO
Note:
If battery has been discon­nected please refer to “Starting Up” in Instal. Guide Chapter 5.0 to connect battery(-ies) again.
Bypass operation
DP300E
DP300E
Q003
Q001a
Q001b
Q002b
Q004
Q002a
Service Bypass Switch
LoadMains
Page 17
17User Guide DP300E
7OA0001 GB rev.09
Service Bypass Switch
11. Press on the keyboard
12. Press
or on the keyboard until
13. Press
on the keyboard
14. Press on the keyboard
15. Press on the keyboard
No lamps on the bypass
panel lights any longer
Bypass operation
: YES
Bypass operation
: NO
Normal operation
load power xx%
Display shows
Page 18
18 User Guide DP300E
7OA0001 GB rev.09
Service Bypass Switch
7.2.3 Isolating one UPS for service/maintenance
In a redundant system one UPS can be isolated for service/maintenance without affecting the other parallel UPS(s).
1. Check that the remaining UPS(s) will be able to carry the load when one UPS is isolated.
2. Switch off the system to be isolated for maintenance by pushing both the green “ON” and the red “OFF” key simultaneously.
3. Disconnect battery, mains, and output by opening battery MCCB/fuse and turning input switch (Q001) and output switch (Q002) to position “0”.
When Q002 is in position “0” the UPS can be operated and tested as a single system without affecting the other parallel UPS(s).
Switching back the UPS to normal parallel/redundant operation
1. Turn the input switch (Q001) and the output switch (Q002) to position “1”.
2. Charge capacitors, connect battery and start up the UPS as described in chapter
5.0.
The UPS will automatically switch to normal operation and start load sharing with the other parallelled UPS(s).
Warning!
The system will discharge built­in capacitors. However, before working on the system check with a multimeter that there is no dangerous voltage on the terminals .
DP300E
DP300E
Q003
Q001a
Q001b
Q002b
Q004
Q002a
Service Bypass Switch
LoadMains
Page 19
19User Guide DP300E
7OA0001 GB rev.09
8.0 Preventive maintenance
8.1 General
The maintenance of the UPS systems should be carried out by trained service engineers. We recommend that you sign a service and maintenance contract.
8.2 Fan
It is recommended to replace the fans every 3rd year.
8.3 Battery
Systems with built-in batteries have as standard a battery monitoring feature (option in other systems). Every time automatic cyclic or manual check is activated, the condition of the battery is checked. The result is one of following:
1. Battery is OK - nothing will happen
2. Battery has reduced capacity - “Battery week” is given
3. Battery capacity far to low - “Battery defective” is given
The battery monitoring test is performed by taking out max. 25% of the energy in the battery. But if the battery monitor is not installed or the exact present back-up time has to be checked, a battery capacity test (8.4) is recommended at least every sixth month.
For safety reasons battery tests should preferably be made during uncritical periods for the loads connected.
Test the battery capacity / condition from the keyboard as follows:
Preventive maintenance
Page 20
20 User Guide DP300E
7OA0001 GB rev.09
Warning:
The UPS must at least be in operation for min. 16 hours in a 3 month period to ensure that the battery is sufficiently charged. If not the battery might be dam­aged.
Preventive maintenance
Actions Display shows Description
1. Press
2. Press or
until
3. Press
4. Press
5. Wait about 1 sec.
6. Wait until backup times expires and
a short alarm sounds. (No alarm in battery monitor test if battery is OK)
7. Press
8. Press
If the UPS has to be taken out of operation for a period of time it is recommended to disconnect the battery in order to prevent it from being totally discharged. The information how to do this can be found in the installation guide.
Battery capacity test : xxx
Starts the battery test. (To interrupt a r unning test – perform
point 1-2 and then press key and
)
“xxx” is actual obtained back-up time in minutes. (Battery capacity test only).
Exits the battery capacity test. If not operated the system will auto­matically exit this program after 30 seconds.
“xxx” is back-up time from last test – if no previous test has been per­formed or if the test has been aborted the display will show “???”! A battery monitor test can be per­formed in the same way by selecting “Battery monitor test” in the display. However, this test will not star t, unless the battery is fully charged.
The next step starts up the test! To abort press
.
8.4 Battery capacity test
Battery capacity
test : ON
Data stored
Battery operation
time : xxx min.
Note:
Expect 16 hours recharge time after a battery capacity test before full backup time is available.
Normal operation load power xx%
Battery capacity test : xxx
Normal operation load power xx%
Page 21
21User Guide DP300E
7OA0001 GB rev.09
Note:
When using economy mode there is NO power factor correction on the input, cabling dimensions should therefore be checked.
Economy Operation
9.0 Economy operation
9.1 General
In economy operation the load is supplied directly from the mains, however the UPS is monitoring the mains and the output voltages and will in case of mains failure switch to battery operation without interruptions.
The system will in order to keep the batteries fully charged at all times switch to normal operation in a pre-programmed sequence.
The operation of the system is the same as already described in this guide with the exception of the following points:
- When starting up, the system will at first go into normal operation to ensure a fully charged battery, but will then switch into bypass after the programmed time (8-10 hours).
Page 22
22 User Guide DP300E
7OA0001 GB rev.09
Software
10.0 Software
10.1 Choice of software
The CD is devided into two main parts:
- DP-SOFT CDX : for serial communication
- DP-SOFT+ : for parallel communication (e.g. for MLU-box)
Installation: See software guide included on the CD.
10.2 Configuration code at normal operation
(Regarding test, see further information in guide included on the CD).
Oper. system UNIX VMS Win3.1x Win95 WinNT OS/2 Novell Config. code 3 3 8 8 8 8 8
10.3 Choice of cable
Operating system Software DP-series Cable Windows 3.1x DP-SOFT
CDX
DP300E 0.801.179 Windows 95 Windows NT OS/2 Novell UNIX VMS
Windows 3.1x DP-SOFT+ DP300E 0.801.178 Windows 95 Windows NT OS/2 Novell
UNIX DP-SOFT+ DP300E 0.801.177 VMS
Page 23
23User Guide DP300E
7OA0001 GB rev.09
For further information:
Homepage: http://WWW.silcongroup.com
AUSTRIA Silcon Elektronik GmbH
Hausberggasse 1 A-7212 Forchtenstein Tel: +43 26 26 8 38 40-0 Fax: +43 26 26 8 35 64
CHINA Silcon (Qingdao) Power Electronics Co. Ltd.
1 Loushan Road CN-Qingdao P.C. 266043 Tel: +86 - 532 4810148 Fax: +86 - 532 4810147
DENMARK Silcon Power Electronics A/S
Silcon Allé DK-6000 Kolding Tel: +45 - 75 54 22 55 Fax: +45 - 75 54 27 89
GERMANY Silcon Elektronik GmbH
Industriestrasse 59a Postf ach 2233 D-40764 Langenfeld Tel: +49 - 2173 9239-0 Fax: +49 - 2173 25977
GREAT BRITAIN Silcon Electronics Ltd.
Milton Court, Bredbury Industr. Park Horsfield Way Stockport GB Cheshire SK6 2SU Tel: +44 - (0) 1614 066 866 Fax: +44 - (0) 1614 066 867
IRELAND Gotec Ltd.
Clonshaugh Industrial Estate IE-Dublin 17 Tel: +353 - (1) 848 6033 Fax: +353 - (1) 848 6040
POLAND Silcon Poland Ltd.
ul. E. Orzeszkowej 5 PL-02-374 Warzaw Tel: +48 - 82 26 59 75 01 Fax: +48 - 82 22 23 66 46
SWEDEN Silcon Power Support AB
Box 20195 S-161 02 Bromma Tel: +46 - 8 29 02 90 Fax: +46 - 8 28 33 53
SWITZERLAND Gutor Electronics Ltd.
Tägerhardstrasse 90 CH-5430 Wettingen Tel: +41 - 56 437 34 34 Fax: +41 - 56 437 34 44
THE NETHERLANDS Silcon B.V.
Pieter Lieftinckweg 8 NL-1505 HX Zaandam Tel: +31 - 75 681 4 681 Fax: +31 - 75 681 4 682
How to contact Silcon
11.0 How to contact Silcon
Loading...