• The operating manual is aimed at specialists and semi-skilled personnel.
• Before each step, read through the relevant advice carefully and keep to the specified order.
• Thoroughly read and understand the information in the section “Safety instructions”.
If you have any problems or questions, please contact your supplier or contact us directly at:
Struthweg 7-9 • D - 34260 Kaufungen
+49 5605 803-0 • +49 5605 803-
Hazard signs and other symbols used:
This sign indicates dangers which could lead to serious health defects or to death.
This sign indicates dangers that cause personal injuries that can lead to health defects or cause con-
This sign indicates actions which could lead to possible damage to material or environmental damage.
ADHERE TO OPERATING MANUAL!
The device must not be disposed of together
with domestic waste!
Pay attention to and comply with information
that is marked with this symbol.
Follow the specified instructions and steps.
Adhere to the given order.
This sign indicates important notices, tips or
information.
Reference to another section, document or
source.
• Item
Copyright notice:
The reproduction, distribution and utilization of this operating manual as well as the communication of its contents
to others without express authorization is prohibited. Offenders will be held liable for the payment of damages. All
rights reserved in the event of the grant of a patent, utility model or design.
The frequency divider TU 7052 divides the high frequencies of the input signal in order to provide a
lower pulsed output signal. The division ratio can be set freely between 1:1 and 1:999.
All SIKA flow or volumetric sensors can be connected to the TU 7052.
Design / Components:
Casing:
The TU 7052 has a plastic casing for rail mounting in
accordance with DIN EN 60715.
Terminals:
For the electrical connection of TU 7052.
Front panel:
Protects the electronics against static discharges and
mechanical damage.
Coding switches:
The coding switches for adjusting the division ration are
located behind the front panel.
Electrical connection:
Connecting diagrams for the supply voltage, the inputs
and the outputs are printed on both sides of the casing.
Type plate:
The type plate displays the serial and manufacturing
number.
Scope of delivery:
• 1x TU 7052.
• 1x Pull-up / Pull-down resistor 5kΩ: Fastened to the side of the plastic casing of TU 7052.
1.1 Intended use
The frequency divider TU 7052 should only be used to divide the frequency signals of SIKA flow or
volumetric sensors.
The suitability of other sensors must be tested prior to the delivery of TU 7052. Please contact your
supplier or SIKA for more details.
The operational safety of the supplied equipment is only guaranteed if it is operated according to its
intended use. The specified limit values (see 8 “Technical data”) should never be exceeded.
Always make sure that TU 7052 is suitable for your requirements prior to installation and commissioning.
2 Safety instructions
Before you install the TU 7052, read through this operating manual carefully. If the instructions contained within it are not followed, in particular the safety guidelines, this could result
in danger for people, the environment, and the device and the system it is connected to.
The TU 7052 correspond to the state-of-the-art technology. This concerns the accuracy, the operating mode and the safe operation of the device.
In order to guarantee that the device operates safely, the operator must act competently and be
conscious of safety issues.
Technical changes reserved - 3 -
TU 7052 Connections and functions
Divider
frequencyInput
frequencyOutput =
SIKA provides support for the use of its products either personally or via relevant literature. The
customer verifies that our product is fit for purpose based on our technical information. With this
verification all hazards and risks are transferred to our customers; our warranty is not valid.
Qualified personnel:
The personnel who are charged for the installation, operation and maintenance of TU 7052 hold
a relevant qualification.
This can be based on training or relevant tuition. The personnel must be aware of this operating
manual and have access to it at all times.
The electrical connection should only be carried out by a fully qualified electrician.
General safety instructions:
In all work, the existing national regulations for accident prevention and safety in the workplace
must be complied with. Any internal regulations of the operator must also be complied with,
even if these are not mentioned in this manual.
Degree of protection IP20:
The device is not intended for outdoor use or for use in damp conditions.
Special safety instructions:
Warnings that are specifically relevant to individual operating procedures or activities can be found
at the beginning of the relevant sections of this operating manual.
The divider is set via the three coding switches of TU 7052. Use a screwdriver to set the switches
to a value between 0 and 9.
The value of the respective switch is displayed on the front panel.
The desired value of the divider is simply set, like written a number, from
top to bottom:
The top coding switch is used to set the hundreds (*100),
the middle coding switch is used to set the tens (*10) and
the bottom coding switch is used to set the units (*1).
SPECIAL SETTINGS:
Setting "0 0 0" switches off the output.
The frequency is not divided at setting "0 0 1".
6 Commissioning
Commissioning occurs after the electrical connections have been carried out and tested:
Switch on the supply voltage.
The TU 7052 is ready for operation:
As soon as a medium passes through the connected flow or volumetric sensor, the frequency of
the input signal is divided by the set value of the divider. The lower square-wave pulse signal appears at the outputs.
7 Maintenance, decommissioning and disposal
Maintenance:
The TU 7052 is maintenance-free and cannot be repaired by the user. In the unlikely event of a defect, the device has to be returned to the manufacturer for repair work.
TIP:
Check all connection cables and the supply voltage to eliminate other error sources in advance.
Decommissioning:
Switch off the system.
Make sure that the system is isolated from all possible sources of supply and is completely de-
energised.
Disconnect the electrical connections and remove TU 7052 from the mounting rail.
Disposal:
Compliant with the Directives 2011/65/EU (RoHS) and 2012/19/EU (WEEE)*, the device
must be disposed of separately as electrical and electronic waste.
Take the TU 7052 to your local recycling plant
or
send it back to your supplier or to SIKA for correct disposal.
* WEEE reg. no.: DE 25976360
Technical changes reserved - 7 -
TU 7052 Technical data
TU 7052
Input signal characteristics (sensor)
Input frequency
0 ... max. 1.700 Hz
Signal level NPN / PNP
"Low": < 3,3 V
"High" > 6 V
Signal level sinus signal (inductive)
10 … 200 mV
Sensor supply
U
Sensor
= U
Supply
- < 2 VDC
Frequency output characteristics
Divider (division range)
1:1 … 1:999 • can be set via rotary switches
Type of signal
Square-wave signal • duty cycle 1:1
NPN/PNP output: (short-circuit proof)
- Signal current
Max. 20 mA, limited current
Optocoupler output: (without a protective circuit)
- Max. load voltage
≤ 30 VDC
- Max. load current
≤ 10 mA
- Load resistance
5 kΩ (recommendation)
Electrical characteristics
Supply voltage (U
Supply
)
12 … 24 VDC ±10%
Current consumption
< 25 mA at 24 VDC (without a sensor) • max. 1 W
Electrical safety measures
Reverse polarity protection (supply voltage)
Protection class
IP 20
further technical data
Ambient temperature
0 … 60 °C
Storage temperature
-10 … +80 °C
Casing
Plastic casing for rail mounting
8 Technical data
The technical data of customised versions may differ from the data in the instructions. Please observe the information specified on the type plate.