Signaline SKM-95 Instruction Manual

LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
Signaline SKM-95
Instruction Manual
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
Contents
1.0 General/Product Features
2.0 Technical Data
3.0 Installation Notes
3.1 Complete Monitoring in Accordance with EN54 pt5
3.2 Maximum Cable Length
4.0 Assembly Tools
5.0 Control Unit Indicators
5.1 End of Line Unit
6.0 Address Codes and Wiring
7.0 Testing the Unit
8.0 Calculating the Installed Length of Sensor Cable
9.0 Mounting the Sensor Cable in a Car Park
10.0 Troubleshooting
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
1.0 General/Product Features
The Signaline SKM-95 is a linear heat detector controller
The maximum length of cable per controller is 300m
Temperature increases are detected along the entire cable
length
The controller will accept the following cables:
Signaline HD, for use in general applications
Signaline HD-R, resistant to oils, chemicals and UV light
Signaline HD-S, exceptional mechanical protection
The system is easy and economical to install
The alarm indicator is in accordance with DIN 14 623
Approved to DIN/EN 54 pt5 Class C
The VdS approved certificate No. is G203077
The sensor cable system is an early warning fire detection system when used with the Signaline SKM-95 controller. It can be used to detect fires and over heats on conveyor belts, cable trays or tunnels. For detection in open areas it can be mounted on the ceiling or also be mounted directly above a cable tray.
The sensor cable will self adjust to ambient conditions. It is also unaffected by steam, dust, chemicals (HD-R), or smoke thereby reducing the likelihood of false alarms which can happen with traditional fire detection.
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
1.0 General/Product Features
Signaline Analogue Heat Sensing Cable System
1) Controller type SKM-95
2) End of line box for SKM-95 (included)
3) Sensor cable
standard (Signaline HD)
with Rilsan coated (Signaline HD-R)
with Stainless Steel protective braiding (Signaline HD-S)
Sensor Cable Construction
The cable is made of an inner and an outer conductor, the outer conductor is tinned copper braid. The insulation between both conductors is made from a plastic material with a negative temperature coefficient, which means with increasing temperature, the insulation resistance decreases.
In the end of line unit, at the end of the sensor cable, the sensor cable is connected with a defined resistor of 3K6 Ohm. Therefore, the whole system is always monitored for wire breakage (open circuit) and short circuit. A break or a short circuit on one of these conductors causes a fault alarm.
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
2.0 Technical Data
Detector
Operating Voltage Loop powered Current consumption standby <2 mA Current consumption alarm 3.2 mA Operating protocol Apollo XP95 Isolator voltage ca. 14V
Parallel indicator (external) -Ub max. 10mA
Fire relay contact N/A Fault relay contact N/A
Temperature range -25°C to +45°C
Indicators
Fire Alarm red LED
Operation no indication
Malfunction yellow LED
Dimensions Controller 110 x 110 x 65 mm
Weight 270g
Color grey, RAL 9002 Ingress Protection IP65 Dimensions end of line box W/H/D 80 x 80 x 52 mm
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
2.0 Technical Data
Heat Sensing Cable
Signaline HD
Red outer sheath
Plastic coaxial conductor
3.25 mm sensor cable diameter
1.6 Kg per 100 metres
Signaline HD-R
Black nylon outer sheath (Rilsan)
plastic coaxial conductor
4.00 mm sensor cable diameter
3.0 Kg per 100 metres
Signaline HD-S
Stainless steel outer braid
Red sheath
Plastic coaxial conductor
4.20 mm sensor cable diameter
3.75 Kg per 100 metres
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
3.0 Installation Notes
The Signaline SKM-95 Controller connected to the Signaline sensor cable should be mounted in the area requiring protection. The controller and cable are designed and certified in conformity with VdS and EN 54 pt5. Local fire regulations may vary, particularly outside Europe. Always conform to your local fire regulations.
The cable is not to be installed 6 metres higher than the protected area. The sensor cable must be installed as per
Figure 1
. It is important to make sure that the distance between the wall and the sensor cable is at least 0.5 metres. This also applies when laying parallel to beams. Crossing of ceiling beams is possible, but the length of sensor cable on the beams should not be longer than 10% of the overall cable length.
Before you install the sensor cable system, make a sketch drawing of the area which will be monitored and mark out the proposed layout. The sensor cable must be laid out in accordance with BS, EN, DIN or your local regulations. The following points should be adhered to:
The sensor cable should not have any contact with a material
which cools the cable because this causes an alarm delay
Laying on sharp objects and crushing the cable is to be
avoided so that the outer insulation of the sensor cable is not damaged
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
3.0 Installation Notes
When connecting two lengths of sensor cable use a Signaline
Universal Connector Box (Signaline UCB) available from your local Signaline distributor.
The minimum bend radius for Signaline Analogue Heat Sensing
Cables are as follows:
HD - 5mm
HD-R - 18mm
HD-S - 20mm
It is not advisable to mount Signaline Analogue Heat Sensing
Cables in direct contact with a surface. Please see
www.signaline.com
for suitable fixing solutions. See
Figure 3
for an example of a fixing solution.
The distance between the fixing clips should not exceed 1m.
Mounting the sensor cable near objects which radiate heat
must be avoided. These could be powerful light sources, steam pipes, heaters or similar and may cause false alarms.
The end of line box must be mounted in the same zone as the
controller.
The end of line box should, where possible, be mounted at a
height of 1,80m (+10cm/-20cm) and marked with a sign.
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
3.1 Complete Monitoring in Accordance with EN54 pt5
Figure 1
demonstrates a detection system which is in accordance with EN54 pt5 for 5 metres of sensor cable. It is important to make sure that from every point of the monitored area at least 5 metres of sensor cable is located within a radius of 3.6m.
Figure 1
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
3.2 Maximum Cable Length
The Figure below shows the maximum allowed cable length dependent on the maximum ambient temperature
Figure 2
An alarm will be detected when 5 metres of sensor cable is heated between 84°C and 100°C. If a large length of Signaline Analogue Heat Sensing Cable is heated then the alarm temperature will be proportionally lower.
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
0 50 100 150 200 250 300
Maximum Installation Ambient Temperature
for Lengths of Signaline HD Cable
Resistor = 3K6 Ohm 5m Signaline HD Cable, radius 3.6m
Ambient Temperature °C
Length of Signaline Cable in m
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
4.0 Assembly Tools
To attach the sensor cable to the protected area you can use dif­ferent clips depending on your application. The cable should be at least 5mm away from the ceiling.
The K clip is simple and easy to install, allowing lower installation time and cost. Simply drill a 6mm Ø hole, click the cable in place, and plug it in. K clips can be used with Signaline HD and Signaline HD-R cables.
Figure 3
For alternatives please contact our offices;
sales@lgmproducts.com
+44 (0) 1252 725257
www.signaline.com
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
5.0 Control Unit Indicators
The indicators for alarm and fault alarm are visible through the clear cover on the controller housing.
The alarm indicator is compliant with DIN 14 623
Figure 4
When there is no LED illuminated the Signaline SKM-95
Controller is operational
If there is a yellow LED then the Signaline SKM-95 Controller
has a fault
When the red LED is illuminated then the Signaline SKM-95
controller is indicating a fire
Yellow LED
Red LED
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
5.1 End of Line Unit
Signaline SKM-95 End of Line Unit
In the end of line unit (
Figure 5
) you will find a 3K6 Ohm resistor. This is used for monitoring incase of a cable break or short circuit. There is no setup required for this unit
Figure 5
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
6.0 Address Codes and Wiring
1234567 1234567 1234567 1234567 1=1000000 33=1000010 65=1000001 97=1000011 2=0100000 34=0100010 66=0100001 98=0100011 3=1100000 35=1100010 67=1100001 99=1100011 4=0010000 36=0010010 68=0010001 100=0010011 5=1010000 37=1010010 69=1010001 101=1010011 6=0110000 38=0110010 70=0110001 102=0110011 7=1110000 39=1110010 71=1110001 103=1110011 8=0001000 40=0001010 72=0001001 104=0001011 9=1001000 41=1001010 73=1001001 105=1001011
10=0101000 42=0101010 74=0101001 106=0101011 11=1101000 43=1101010 75=1101001 107=1101011 12=0011000 44=0011010 76=0011001 108=0011011 13=1011000 45=1011010 77=1011001 109=1011011 14=0111000 46=0111010 78=0111001 110=0111011 15=1111000 47=1111010 79=1111001 111=1111011 16=0000100 48=0000110 80=0000101 112=0000111 17=1000100 49=1000110 81=1000101 113=1000111 18=0100100 50=0100110 82=0100101 114=0100111 19=1100100 51=1100110 83=1100101 115=1100111 20=0010100 52=0010110 84=0010101 116=0010111 21=1010100 53=1010110 85=1010101 117=1010111 22=0110100 54=0110110 86=0110101 118=0110111 23=1110100 55=1110110 87=1110101 119=1110111 24=0001100 56=0001110 88=0001101 120=0001111 25=1001100 57=1001110 89=1001101 121=1001111 26=0101100 58=0101110 90=0101101 122=0101111 27=1101100 59=1101110 91=1101101 123=1101111 28=0011100 60=0011110 92=0011101 124=0011111 29=1011100 61=1011110 93=1011101 125=1011111 30=0111100 62=0111110 94=0111101 126=0111111 31=1111100 63=1111110 95=1111101 32=0000010 64=0000001 96=0000011
Address/Switch position: ON = 0 OFF = 1, use switch 8 to test alarm
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
6.0 Address Codes and Wiring
Connect the cable as shown in
Figure 6
below.
Figure 6
How to test the alarm
Use dip switch 8
Change the EOL resistor to a 2K Ohm resistor in place of the
3K2 Ohm resistor. Reset the 3K2 Ohm resistor after test
Remote Indicator
Earth
Loop +ve Loop +ve
Loop –ve
Loop –ve
Remote Indicator –ve
Sensor Cable -
Sensor Cable +
Sensor Cable
Earth
To EARTH
Loop -ve
Loop +ve
Loop -ve
Loop +ve
1 8
ON
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
7.0 Testing the System
Loop Device Recognition
Most Apollo XP95 or Discovery compatible panels should recognize the SKM-95 controller as an Apollo XP95 heat detector. Some panels recognise the SDKM-95 controller as an Apollo XP95 Hi
g
h
Temperature Heat detector.
Simulated Test
The controller will simulate a fire condition if the when address switch 8 is moved to the ON position
Heat Test
Using a hot air gun, heating 5 metres of sensor cable to 100°C (max. 115°C) will raise an alarm. When the cable has cooled, the controller may be reset.
IMPORTANT NOTE: If the sensor cable is heated up to 150°C or more then that part of the cable cannot be used any more and should be replaced.
WARNING: Obtain permission of the site safety manager before starting live heat tests. Live heat tests MUST NOT be conducted in a designated hazardous area or when the Signaline HD sensor cable forms part of an intrinsically circuit.
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
8.0 Calculating the Installed Length of Sensor Cable
If the total length of an installed sensor cable is not know, it is possible to be calculated with the help of a multi-meter. For this then both wires of the sensor cable should be clamped together in the end of line unit. The resistance of the cable should then be measured at the other end. The sensor cable has a resistance of
0.2 Ohms per metre.
The cable length is calculated as follows:
Length in metres = resistance (Ohms)
0.2 (
W
/m)
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
9.0 Installing Sensor Cable in a Car Park
Figure 7
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
9.0 Installing Sensor Cable in a Car Park
Figure 8
LGM PRODUCTS LTD UNIT 15 RIVERSIDE INDUSTRIAL PARK FARNHAM SURREY GU9 7UG UNITED KINGDOM
TEL +44 (0) 1252 725257
FAX +44 (0) 1252 727627
www.signaline.com
Version 2.1
10.0 Troubleshooting
Error Possible Solution Yellow LED alight Is there a short circuit on the loop?
Is the end of line box connected? Is the cable broken? +/- reversed loop? Is the cable crushed or too tightly
bent? Controller is not detected or address not found
Is the address correctly set on the
dip switches?
Do two devices have the same ad-
dress?
Is the controller in an isolated part
of the loop?
Fault on the panel?