Sigma 30-H, 40-H, 47-H, 58-H, 62-H Installation And Operation Manual

...
Page 1
MANUFACTURERS
OF H YDRONIC
H EATING
P
Unit Heaters
Installation and Operation Manual
www.sigmaproducts.com Tel: (905) 453
-0446 Fax: (905) 453-0675
Rev 2
Page 2
I NSTALLERS R ESPONSIBILITY
This equipment has been inspected, tested and shipped free of defects. However, it is
the installer’s responsibility to check for loose wires, leaks, or loose fasteners, and correct any problem that may be found. Inspect the equipment immediately when received to determine if there is any damage from shipment. First, check for visible damage to the unit. Turn the fan by hand to determine if any damage has occurred. If any damage has been found, the receiver should note the damage on the bill of lading and immediately file a claim with the transport company.
It is the equipment owner’s responsibility to provide any scaffolding or other apparatus to allow service or periodic maintenance to this equipment.
INSTALLATION
Unit Heaters
Installation & Operation Manual
1
www.sigmaproducts.com Tel: (905) 453
-0446 Fax: (905) 453-0675
Warning: Disconnect all power, steam, or water supplies before installing or servicing the unit. Do not depend on a thermostat or other switch as sole means of disconnecting power. Always disconnect power at the main breaker.
Caution: Insure that all power sources conform to the requirements of the unit heater or damage to the unit will result. All external wiring and piping must conform to the local and national codes.
Warning: Improper installation, adjustment, alteration, service, or
maintenance can cause damage, injury, or death. Read this manual thoroughly before installing, operating, or servicing.
Rev 2
Page 3
U NIT MOUNTING
Install unit heaters to meet Occupational Safety and Health Act (OSHA). Unit heaters
mounted less than 8 feet (2.4 meters) above the floor must be equipped with a fan guard. Ensure that all hardware used in the suspension of each unit heater is more than adequate. Failure to do so may result in extensive property damage, severe personal injury, or death.
Suspension nuts are provided on the top of all models. Support rods should be installed so that they support the total weight of the unit heater to assure that no strain is placed on the supply and return piping. Provisions for removal of the unit from the suspension rods may be desirable for future servicing. Otherwise, the provision of sufficient clearance around the unit heater for future maintenance and servicing is required.
Note: Increasing clearance distances may be necessary if there is any possibility of distortion or discoloration of adjacent
materials.
It is assumed that the type of system to be used has been selected by the design engineer. The diagrams shown in the manual are for different types of steam or hot water systems.
It is important that the system be kept clean and free of foreign substances, such as
excessive joint materials, etc.
For steam systems it is recommended that the unit be mounted level for proper condensate drainage. Swing joints should be used in piping, and piping should be pitched down so condensate can drain freely.
Isolators are not required, but may be desirable for some applications. Refer to dimensional drawings for unit weights.
Hanging hardware is not included with the unit (to be field supplied).
Place unit heaters at points of greatest heat loss. Blanket outside doorways and provide ample coverage of window areas. Keep the unit heaters away from objects that will impede the full and natural air delivery of the units.
PIPING
Refer to the appropriate model dimensional drawing to determine the piping connection type, size, and location. Follow standard practices and codes when installing piping. Provide swing joints for expansion purposes, unions and shut-off valves for servicing purposes, as well as valves and traps for control purposes. Refer to Typical Piping Connections Diagrams for details.
Unit Heaters
Installation & Operation Manual
2
www.sigmaproducts.com Tel: (905) 453
-0446 Fax: (905) 453-0675
Rev 2
Important: Unit heaters must be hung
level from side to side, and front to back. Failure to do so will result in poor performance and/or premature failure of the unit.
Page 4
C OIL OPERATION
Maximum recommended steam pressure for standard units is 15 psig at 275ºF. The
maximum recommended pressure for hot water applications is 150 psig at 275ºF. For higher operating temperatures and pressures, special coils and ratings are required.
U NIT OPERATION
Most basic unit heater systems are controlled by a room thermostat. Install thermostat on an inner wall or column to
achieve optimum control of that area. Set thermostat for desired temperature.
For steam systems, a low temperature set­point limit could be used to prevent the fan from blowing cold air when there is no steam passing through the coil.
Small hot water systems could have the circulating pump controlled directly by the
room thermostat. Large systems may use zone valves to control individual unit heaters where constant water circulation is used on the pain system.
A louvered cone air diffuser is available as an optional accessory for vertical unit heaters.
MAINTENTANCE
Motor Lubrication. Standard motors are
pre-lubricated and normally are not equipped with grease fittings. For motors that are equipped with grease fittings, contact the local motor manufacturer service facility to obtain information on the grease or oil type, and the method and frequency of lubricating. The frequency of lubricating will depend on operating conditions and length of running time.
Unit Heaters
Installation & Operation Manual
3
www.sigmaproducts.com Tel: (905) 453
-0446 Fax: (905) 453-0675
Warning: Disconnect all power, steam or water supplies before installing or servicing the unit. Do not depend on a thermostat or other switch as sole means of disconnecting power. Always disconnect power at the main breaker.
Caution: Allow rotating fans to stop before servicing to avoid serious injury to fingers and hands.
Rev 2
Page 5
C LEANING
For cleaning or maintenance purposes, the fan-motor assembly can be removed from
the unit heater. The unit casing, fan, diffuser, and coil should be cleaned thoroughly once each year. The heating performance and air throw depend on cleanliness of the coil and fan blades.
When cleaning the fan-motor assembly, wipe all excess dirt or lubricant from the motor casing. Buildup on the motor casing will cause it to run hot and eventually cause inconvenience or discomfort due to random automatic thermal overload shut down, or could cause internal motor damage. Note: standard unit heater motors have integral automatic thermal overload protection.
Clean the coil by loosening dirt with a brush on the fan side of the coil, then operate the
unit allowing the fan to blow the loosened dirt through the unit. Use high pressure air or steam on the coil away from the fan.
Use a damp cloth to clean the casing, fan blades, or diffuser. If rust spots are found on the casing, they should be cleaned and repainted.
Tighten the fan guard, motor frame and fan bolts. Check the fan for clearance in the
panel orifice and free rotation.
The heater system should be checked once per year by a qualified technician. All maintenance and service information should be recorded.
TABLE 1 TROUBLE-SHOOTING CHART
SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION
Leaking Coil 1. Frozen coil
2. Defective coil
3. Corrosion
4. Leak in joint
1. Replace coil.
2. Replace coil.
3. Replace coil.
4. Braze joint if joint is exposed where leak has occurred.
Poor output on steam
1. Check for air in coil
2. Lint on coil fins
1. Repair or replace thermostatic air vent.
2. Clean coil and fins. Check filter and clean.
Poor output on steam or hot water
1. No circulation of water through coil
2. Short cycling of motor
3. Backward rotating motor
1. Check circulation pump. Check for blocked tubes.
2. Check voltage and correct. Remove and service motor to confirm if automatic overload needs repair.
3. Change direction of motor rotation to by making appropriate wiring changes as recommended by the motor manufacturer.
Noisy or vibrating unit
1. Damaged fan
2. Dirty fan
1. Change fan.
2. Clean fan.
Unit Heaters
Installation & Operation Manual
4
www.sigmaproducts.com Tel: (905) 453
-0446 Fax: (905) 453-0675
Rev 2
Page 6
F IGURE 1
DIMENSION D IAGRAM
FOR HORIZONTAL U NIT
H EATER WITH
SERPENTINE C OIL
(30-H & 40 -H)
F IGURE 2
DIMENSION D IAGRAM
FOR HORIZONTAL U NIT
HEATER WITH MULTI-
CIRCUITED C OIL (47 -H TO 245-H)
TABLE 2 H ORIZONTAL UNIT H EATER SPECIFICATIONS
D
IMENSIONS (IN
) M
AX THROW (FT
)
MODEL
F IGURE
REF.
A B C D E F G
WT
(LB)
MAX.
MTG.
HT (FT)
W/ H ORIZ.
L
OUVERS
W/ V ERT.
L
OUVERS
30-H 1 22 13.5 4.75 8 7.50 15.5 0.50 40 9 18 23 40-H 1 22 13.5 4.75 8 7.50 15.5 1.25 40 10 23 29 47-H 2 27 16.5 5.00 8.5 7.75 16.25 1.25 48 10 23 29 58-H 2 27 16.5 5.00 8.5 9.50 18.0 1.25 48 10 28 35 62-H 2 31.5 19.5 5.625 10 9.50 19.5 1.25 71 10 25 30
84-H 2 31.5 19.5 5.625 10 7.50 17.5 1.50 76 12 32 40 133-H 2 37.0 24.0 5.875 10 7.75 17.75 1.50 108 13 40 50 200-H 2 42.5 28.5 5.50 10 9.50 19.5 1.50 148 15 50 64 245-H 2 46.5 31.5 5.50 10 9.50 19.5 1.50 172 16 54 68
Unit Heaters
Installation & Operation Manual
5
www.sigmaproducts.com Tel: (905) 453
-0446 Fax: (905) 453-0675
Rev 2
Page 7
F IGURE 3
DIMENSION D IAGRAM
FOR V ERTICAL UNIT
HEATER
TABLE 3 VERTICAL UNIT HEATER SPECIFICATIONS
DIMENSIONS (IN)
M
ODEL
A B C D E F G H J
40-V 18.5 10 2.625 1.25 1.5 3/8-16 UNC 2.75 6.125 1.25 50-V 18.5 10 2.625 1.25 1.5 3/8-16 UNC 2.75 6.125 1.25 54-V 22 13 2.625 1.25 1.5 3/8-16 UNC 2.75 6.125 1.5 67-V 22 13 2.625 1.25 1.5 3/8-16 UNC 2.75 6.125 1.5 78-V 26.5 16 2.625 1.25 1.5 3/8-16 UNC 2.75 7.625 1.625
100- V 26.5 16 2.625 1.25 1.5 3/8-16 UNC 2.75 7.625 1.625
145-V 30.875 20 3.375 1.5 2 3/8-16 UNC 2.75 7.625 2 210-V 36.875 25 3.375 1.5 2 3/8-16 UNC 2.75 7.625 2.375 300-V 44.125 30 4.125 2 2.5 1/2-13 UNC 3 9.125 3 370-V 44.125 30 4.125 2 2.5 1/2-13 UNC 3 13.625 3 375-V 44.125 30 4.125 2 2.5 1/2-13 UNC 3 9.125 3 480-V 44.125 30 4.125 2 2.5 1/2-13 UNC 3 13.625 3
DIMENSIONS (IN) MAX. MTG. H T. (FT)
MODEL
K L M N P R S
WT (LB)
WITHOUT
L OUVER
WITH
L OUVER
40-V 3 11.5 12.25 6 1.125 6.25 8.875 49 12 16 50-V 3 11.5 12.25 6 1.125 6.25 8.875 50 17 22 54-V 3 11.875 14.375 6 1.25 7 10 62 13 16 67-V 3 11.875 14.375 6 1.25 7 10 63 19 23 78-V 2 12.25 16.375 7 1 7.25 10.625 85 14 17
100- V 2 12.25 16.375 7 1 7.25 10.625 90 21 25
145-V 2.375 13.5 20.375 7 1.5 9 13.25 118 23 28 210-V 4 15.25 24.5 7 1.25 8.5 11.875 146 26 32 300-V 3 15.875 30.5 7 0.75 9.5 13.75 200 26 32 370-V 1.875 19.25 30.5 7 0.75 9.5 13.75 265 28 34 375-V 4.5 17.375 30.5 8 0.75 9.5 13.75 205 40 48 480-V 2.5 19.875 30.5 8 0.75 9.5 13.75 270 42 52
Unit Heaters
Installation & Operation Manual
6
www.sigmaproducts.com Tel: (905) 453
-0446 Fax: (905) 453-0675
Rev 2 Rev 2
Page 8
F IGURE 4 TYPICAL PIPING CONNECTIONS
Unit Heaters
Installation & Operation Manual
7
www.sigmaproducts.com Tel: (905) 453
-0446 Fax: (905) 453-0675
Rev 2