Sifam Tinsley Omega Xmer, Omega 20, Omega 10 Operating Manual

TRANSFORMER SERIES : Omega Xmer,
Operating Manual
Indication
Before initial operation we ask you to pay full attention to these assembling instructions in order to guarantee the reliability and to ensure the performance of the device.
Functional description
Current transformers of the model range Omega are inductive single conductor-current transformers operating according to the transformer principle. Due to the applicated measuring principle, current transformers of this type may only be installed in alternating current (AC) networks.
Safety instructions
In order to avoid personal and material damage the following assembling steps must by performed only by authorised, qualified and trained personnel.
If the secondary circuit is operated without a burden/load (open) high voltages may appear. These voltage values are dangerous for persons as well as for the functional reliability of the current transformer. It is forbidden to operate the current transformer without a secondary
circuit (open)!
Technical parameters
Primary current: 30A to 6000A Secondary current: 1A or 5A Accuracy class: 0.2, 0.2s, 0.5, 0.5s & 1 Over current limiting factor: FS5, FS10, Fs15 Rated frequency: 60Hz Rated continuos thermal
current (standard): 1,2 x In Rated short time thermal
current Ith: 60 x In, 1 s (Max 40kA) Rated isolation level: 0,72/3/-kV Place of installation: Indoor Altitude: up to 2000 m Degree of protection: Ip20 Degree of pollution: 2
Ambient temperature: -5°C ϑ ≤ +40°C (0…95% relative humidity, non condensing!
Storage temperature: -25°C ≤ ϑ ≤ +70°C
Applied standards: IEC - 61869 - Part : 1 & 2 : Performance IEC - 61010 - 2 : Safety.
Low Voltage-Current Transformer -
Omega Xmer Series
Omega 10, Omega 20,
Omega 10 Series Omega 20 Series
Subject to change without notice!
Sifam Tinsley Instrumentation Ltd.
Central Buildings, Woodland Close, Old Woods Trading Estate, Torquey, Devan, England, TQ27BB Website: www.sifamtinsley.com/uk Contact Number: +44(O) 1803 615139 E-mail: info@tinsley.co.uk
Sifam Tinsley Instrumentation
3105, Creekside Village Drive, Suite No 801,Kennesaw, Georgia 30144 Contact Number: +1.404.736.4903 Web: www.sifamtinsley.com
2-60-006-00-00575_Rev. A_01/2015
Assembly
1. Ensure a safe work environment during assembly, maintenance and inspection operations. If necessary interrupt the current supply of the primary conductor and take precautions against unintentional switching.
2.(i) For Split core CT : Open the current transformer and fix it on the primary conductor using the fixing clamps (mounting material).
(ii) For Window type CT : Bar or cable primary insert through primary cable or bus bar & fix it using mounting screw assembly.
P1: Direction of power supply P2: Direction of power source
Attention: (i) Do not close the current transformer, high voltages may appear on the open secondary leads. (ii) Check for cleanness of the cut surfaces of the split core
3. Connect the secondary wires of the current transformer with the measuring device (ampere meter, energy meter). Pay attention to the installation guide of the measuring device.
4. Now fasten the current transformer, press until the lock engage.
5. If necessary, start the current supply again.
6. Check whether the current transformer is assembled correctly and the secondary leads are connected properly.
7. For split core CT, use “lock pin” supplied along with CT to protect accidental opening of CT, during in use.
L
N
P
1
P
2
S1S
2
R
L
A
Wiring diagram
Environmental instruction
When the product has reached it´s “end of life“, it must be recycled. Pass it to an electrical waste disposal. Do not dispose as unsorted municipal waste!
This product was developed and manufactured in accordance with the applicable regulations (IEC 61010, IEC 61869) and meets the requirements of the low voltage guideline 2006/95/EG