Sentry Controller
MODBUS Memory Map
Detail
1 All Registers are MODBUS 16 bit registers
2 There are five different ways of using MODBUS registers (see italic reference number in left column for each
address)
2.1 As an Analog Value: In most cases these values are scaled by multiplying by 10.
2.2 As eight packed digital states, packed into one register. In this case the remaining 8 bits are unused.
2.3 As a digital state where the register value can only be “0” or “1”.
2.4 As a computed value, such as where “0” = no alarm, “1” = low alarm, “2” = high alarm.
2.5 Control registers, where the SCADA host can write a value, such as alarm reset to the Sentry, or to set
calibration concentration, or alarm set point. Note that these registers are read or write.
3 Where a series of registers apply only to sensor number 1, the following sequences for sensors 2, through 8 are
only referenced by the first applicable register number.
4 Some values can be found in more than one place in different formats. For example when Sensor Number 6 is in
high alarm and latched:
• Register 40001:5 is the bit which indicates present alarm condition.
• Register 40007:5 is the bit which indicate a latched condition, regardless of the present sensor reading (until
reset)
• Register 40466 is a computed value of “2”
Sentry MODBUS I/O Memory Map
5 Registers starting at 40224 provide the raw data read from each of the eight sensors. The following describes the
data for sensor 1, the remaining registers through 40463 are for sensors 2 through 8:
40224 Sensor 1 Input Value - Multiplex 0 – V0 (Reference value of 0 volts) 0 - 6553.5
40225 Sensor 1 Input Value - Multiplex 1 – Vsignal (Current sensor signal) 0 - 6553.5
40226 Sensor 1 Input Value - Multiplex 2 – CH2 (Auxiliary data by type) 0 - 6553.5
40227 Sensor 1 Input Value - Multiplex 3 – CH3(Auxiliary data by type) 0 - 6553.5
40228 Sensor 1 Input Value - Multiplex 4 – Type 0 - 6553.5
40229 Sensor 1 Input Value - Multiplex 5 – Vin (Channel voltage) 0 - 6553.5
40230 Sensor 1 Input Value - Multiplex 6 – Calibration Switch Position (0=On) 0 - 6553.5
40231 Sensor 1 Input Value - Multiplex 7 – Vref (Reference value of 2.5 volts) 0 - 6553.5
40232 Sensor 1 Calibration Due Days
To calculate the raw signal voltage (for example), since we know Vref :
V = (Vsignal – V0) / (Vref – V0) * 2.5v
March 4, 2005 Page: 1
Read Only Parameters
Modbus Address
Discrete40001:0 High alarm bits - sensor 1
40001:1 High alarm bits - sensor 2
40001:2 High alarm bits - sensor 3
40001:3 High alarm bits - sensor 4
40001:4 High alarm bits - sensor 5
40001:5 High alarm bits - sensor 6
40001:6 High alarm bits - sensor 7
40001:7 High alarm bits - sensor 8
40003:0 Common (High or low) alarm bits - sensor 1
40003:1 Common (High or low) alarm bits - sensor 2
40003:2 Common (High or low) alarm bits - sensor 3
40003:3 Common (High or low) alarm bits - sensor 4
40003:4 Common (High or low) alarm bits - sensor 5
40003:5 Common (High or low) alarm bits - sensor 6
40003:6 Common (High or low) alarm bits - sensor 7
40003:7 Common (High or low) alarm bits - sensor 8
Parameter Units FIX EGU
Sentry MODBUS I/O Memory Map
40004:0 Common high alarm, any sensor
40004:1 Common low alarm, any sensor
40004:2 Common any alarm, any sensor
40004:3 Calibrate mode
40004:4 Trouble alarm
40004:5 Power Flash (Startup mode)
40005:0 Sensor in calibration – sensor 1
40005:1 Sensor in calibration – sensor 2
40005:2 Sensor in calibration – sensor 3
40005:3 Sensor in calibration – sensor 4
40005:4 Sensor in calibration – sensor 5
40005:5 Sensor in calibration – sensor 6
40005:6 Sensor in calibration – sensor 7
40005:7 Sensor in calibration – sensor 8
40006:0 Bits indicating analog value is valid – sensor 1
40006:1 Bits indicating analog value is valid – sensor 2
40006:2 Bits indicating analog value is valid – sensor 3
40006:3 Bits indicating analog value is valid – sensor 4
40006:4 Bits indicating analog value is valid – sensor 5
40006:5 Bits indicating analog value is valid – sensor 6
40006:6 Bits indicating analog value is valid – sensor 7
40006:7 Bits indicating analog value is valid – sensor 8
March 4, 2005 Page: 2
Modbus Address
40007:0 High alarm relay latched – sensor 1
40007:1 High alarm relay latched – sensor 2
40007:2 High alarm relay latched – sensor 3
40007:3 High alarm relay latched – sensor 4
40007:4 High alarm relay latched – sensor 5
40007:5 High alarm relay latched – sensor 6
40007:6 High alarm relay latched – sensor 7
40007:7 High alarm relay latched – sensor 8