Sierra Monitor Corporation 201, 203, 20X, 206 User Manual

The Model 20X Series are all-weather, solid-state, fixed-installation single­alarm monitors designed for continuous area monitoring of Combustible Gas, Hydrogen Sulfide or Carbon Monoxide.
The Model 20X Series consists of 3 gas sensor mod­ules, Model 201 for Combustible Gas, Model 203 for Hydrogen Sulfide and Model 206 for Carbon Monoxide. The monitors provide 0.5 Amp dry contract relay that is activated when the concentration of gas exceeds the factory-set (and user-adjustable) level. A TTL signal can be user configurable to interface with Sierra Monitor's alarm panels. This signal may be used to activate a remote alarm, fan or process controller.
The standard configuration has a normally operating open relay but a fail-safe normally operating closed relay is field selectable. A durable, cast aluminum explosion­proof enclosure houses the sensor electronics. The en­closure provides sealing for hazardous areas - Class I, Division 1, Groups C, D. The sensor with porous metal cover is assembled in an aluminum housing that screws directly into the electronics enclosure. The cover both protects the sensor and acts as a flame-arrestor. The monitor can be installed up to 500 feet from the power source.
Semiconductor-Type Sensor
Model 20X Series
Gas Sensor Monitors
Model 201 - Combustible Gas Model 203 - Hydrogen Sulfide
Model 206 - Carbon Monoxide
Remote Alarm Available
If a remote alarm is desired (required for 20X-00), the Model 2102 Dual Channel Alarm Panel can be connected up to 500 feet away from the monitors.
A solid-state semiconductor-type sensor and associated electronic circuitry ensure trouble-free, long-term opera­tion. There are no pumps, filters, or chemical cells to replace or maintain. Except periodic calibration to verify the alarm setting, no attention is required after installa­tion. The user may adjust the alarm level by using cali­bration gas with concentration equal to the alarm level.
Features Benefits
n Explosion-proof enclosure Can operate continuously in work areas where
n No chemical cells to replace, no periodic Maintenance free operation
maintenance required other than routine calibration
n All the electronic circuitry needed to operate Quick easy installation and connection to alarm
panel the monitor contained in a compact unit
Sierra Monitor Corporation 1991 Tarob Court Milpitas, California 95035 (408) 262-6611 (800) 727-4377 Fax: (408) 262-9042
Model 201 - Combustible Gas
The Model 201 can detect a wide range of combustibles. Typical applications include combustible gas monitor­ing in manholes, tanks, natural gas fields, parking ga­rages and vehicle maintenance facilities, sewage treat­ment plants, laboratories, chemical plants, and more.
hazardous gases could be present
Model 203 - Hydrogen Sulfide
The Model 203 can be used in such typical applica­tions as wastewater treatment plants, laboratories and chemical plants.
Model 206 - Carbon Monoxide
The Model 206 Carbon Monoxide Gas Sensor Module can be used to provide an early warning of Carbon Monoxide accumulation in tanks, laboratories, chemi­cal plants, parking garages, vehicle test facilities and more.
SPECIFICATIONS
SENSOR TYPE: Solid-State Metal Oxide Semiconductor
RANGE: (at 50% relative humidity)
Model 201 300 - 2,000 ppm Hydrogen
500 - 10,000 ppm Methane
Model 203 10-50 ppm Hydrogen Sulfide (H2S)
Model 206 50 - 500 ppm Carbon Monoxide (CO)
RESPONSE TIME:
Model 201 Less than 30 seconds Model 203 For 50 ppm alarm, if 50 ppm H2S is present:
Model 206 Less than 30 seconds
1-4 minutes, if >250ppm H2S is present: 30-90 seconds
PERIODIC MAINTENANCE: None, other than routine calibration
OPERATING TEMPERATURE RANGE: -4°F TO 158°F
INPUT: 9 - 24 VDC (
OUTPUT: 0.5 amp dry contact, 100 VDC, 130 VAC
INDICATORS: Internal LED for calibration
ENCLOSURE: Class I, Division 1, Groups C, D
ENCLOSURE Cast aluminum for protection against MATERIAL: galvanic corrosion
SIZE: 6.75 x 4.0 x 3.5 in
WEIGHT: 24 oz (678 g)
APPROVAL: UL 60950
(-20°C TO 70°C)
+ 1V), 250 mA
Nominal 5 volts DC (TTL), source 25mA. SAFE and ALARM signals.
(17.1 x 10.2 x 6.0 cm)
ORDERING INFORMATION
Combustible Gas 201-00 Hydrogen Sulfide 203-00 Carbon Monoxide 206-00
2007 by Sierra Monitor Corporation Printed in U.S.A.
Sierra Monitor Corporation 1991 Tarob Ct. Milpitas, CA 95035 (408) 262-6611 800-727-4377 FAX: (408) 262-9042
Visit our Web site at: www.sierramonitor.com E-Mail: sierra@sierramonitor.com
Rev. B 8/23/07
Loading...