Sierra Monitor Corporation Combustible Gas 2001, 200X, Hydrogen Sulfide 2003, Carbon Monoxide 2006 User Manual

The Model 200X Series are compact, solid­state, fixed-installation single alarm monitors designed for continuous area monitoring of Combustible Gas, Hydrogen Sulfide, or Car­bon Monoxide.
Model 200X Series
Gas Sensor Monitors
Model 2001 - Combustible Gas
Model 2003 - Hydrogen Sulfide
Model 2006 - Carbon Monoxide
The Model 200X Series consists of three separate gas monitors, Model 2001 for Combustibles Model 2003 Hydrogen Sulfide and Model 2006 for Carbon Monoxide. A red LED (light-emitting diode) and audible alarm acti­vate when the concentration of gas exceeds the factory­set (and user-adjustable) level. A green LED indicator on the monitor shows that power is connected and it is a safe condition.
The standard configuration has a buzzer and normally operating open relay, a fail-safe normally operating closed relay is field selectable.
All the electronic circuitry needed to operate the moni­tor, except the DC input power, is contained in a com­pact unit. It may be mounted in any orientation. For a single-monitor installation and a local alarm, the accom­panying AC-to-DC power supply may be plugged into a standard AC source. The monitors accept 9 - 24 VDC.
Features
n Self-check feature signals sensor failure
Semiconductor-Type Sensor
A solid-state semiconductor-type sensor and associated electronic circuitry ensure trouble-free, long-term opera­tion. There are no pumps, filters or chemical cells to replace or maintain. Except periodic calibration to verify the alarm setting, no attention is required after installa­tion. The user may adjust the alarm level by using a different calibration gas concentration.
A sensor self-check feature will flash the LEDs on and off alternatively and sound an interrupted tone as a warn­ing should the sensor fail (open circuit).
Remote Alarm Available
If a remote alarm is desired, the Model 2102 Dual Chan­nel Alarm Panel can be connected up to 500 feet from the monitors.
Benefits
n Reliable operation
n Optional normally operating closed relay
n No chemical cells to replace, no periodic
maintenace other than routine claibration
n All the electronic circuitry needed to operate
the monitor contained compact unit, power suplly plugs into standard AC source
Sierra Monitor Corporation 1991 Tarob Court Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 Fax: (408) 262-9042
n Fail-safe configuration
n Maintenance free operation
n Quick easy installation and connection to
alarm panel
Gas Sensor Monitors
Model 2001 Combustibles Gas Monitor
The Model 2001 can detect a wide range of combus­tibles. Typical applications include combustible gas monitoring in basements near waste dumps, manhole, tanks, parking garages and vehicle maintenance facili­ties, laboratories, chemical plants, and more.
Model 2003 Hydrogen Sulfide Monitor
The Model 2003 can be used in such typical applica­tions as waste water treatment plants, laboratories and chemical plants.
SPECIFICATIONS
INDICATORS: Visual: Green LED for Monitor “ON"/Safe
Red LED for Alarm LEDs oscillate on/off for sensor failure
Audible: Sustained alarm tone for as long
as gas is present. Interrupted tone or sensor failure.
SENSOR TYPE: Solid-State Metal Oxide Semiconductor
RANGE; (at 50% relative humidity) Model 2001 300-2,000 ppm Hydrogen
500-10,000 ppm Methane
Model 2006 Carbon Monoxide Monitor
The Model 2006 Carbon Monoxide Gas Sensor Mod­ule can be used to provide an early warning of CO accumulation in tanks, laboratories, chemical plants, parking garages, vehicle test facilities and more.
OUTPUT: 0.5 AMP dry contact. 100 VDC, 130 VAC
Nominal 5 volts DC, source 25 mA, SAFE and ALARM signals 70 dB buzer. TTL interface to Model 2102 Alarm Panel is user configurable.
RESPONSE TIME: Model 2001 Less than 30 seconds
Model 2003 For 50 ppm alarm, if 50 ppm H2S is present,
1-4 min. If >250 ppm H2S is present, 30-60 seconds.
Model 2006 Less than 30 seconds
Model 2003 10-50 ppm Hydrogen Sulfide (H2S)
Model 2006 50-500 ppm Carbon Monoxide (CO)
FACTORY ALARM SETPOINT: Model 2001 1000 ppm Methane
Model 2003 50 ppm H2S
Model 2006 100 ppm CO
INPUT: 9 - 24VDC (+1V), 250 mA
Plug-in 120 VAC AC/DC Power Supply is provided
PERIODIC MAINTENANCE: None, other than routine calibration
OPERATING TEMPERATURE -4oF to158oF RANGE: -20°C to 70°C
ENCLOSURE MATERIAL: Aluminum
SIZE: 3.7 x 2.2 x 1.1 in. (9.4 x 5.7 x 2.8 cm)
WEIGHT: 3.8 oz (108 g)
APPROVAL: UL 60950
ORDERING INFORMATION
Combustible Gas 2001-00
Hydrogen Sulfide 2003-00
Carbon Monoxide 2006-00
Sierra Monitor Corporation 1991 Tarob Ct. Milpitas, CA 95035 (408) 262-6611 800-727-4377 FAX: (408) 262-9042
Visit our Web site at: www.sierramonitor.com E-Mail: sierra@sierramonitor.com
Rev. A2-8-23-07 © 2007 by Sierra Monitor Corporation