Siemon HD5 Series, HD6 Series Instructions Manual

Page 1
Note: All panel styles have either S110 or S310
style termination posts. All are designed for use
with a standard 110 type punch
-
HD5 & HD6 Series Wall & Rack Mount Patch Panel Instructions
Tools
1
Rack Mount Style Panels
Vertical Wall Mount Style Panels
Mount Panel
Mount S89D bracket with screws (not
included) suitable for mounting
surface being used.
Temporarily snap on vertical panel
with termination side out to allow for
easier cable termination.
Rack Mount Wall Mount
Route Cables (For ease of installation)
Route half of the
cables to each side of
panel.
Route cables such
that they feed into
center of connecting
blocks.
Using the #12
-
24 machine
screws and washers provided,
mount the panel to the desired
location on a 19” equipment
rack or equivalent.
Strip a minimum of 50mm (2 in.)
of cable jacketusing Siemon
AllPrep
TM
tool (p/n: CPT
-
RGTP)
or equivalent.
Prep cable
Lace conductors
S310 style
S110 style
Arrange pairs in accordance with the desired wire scheme as
detailed on the color coded sticker provided. Lace conductors
by pressing firmly into position from both sides of lacing post.
Tip: Begin lacing on side of panel wherecables feed from to avoid
cable bundle interference.
Required Tools:
-
Jacket stripper
-
Phillips screw driver.
-
Cable cutters
-
110 punch tool
Optional Tools:
-
Multipair 110 punch
tool (for S110 style
terminations only).
19” Flat & Angled Rack Mount
Style Panels
Vertical Wall
Mount Style
Panels
234
See cross
-
reference to outlet pin #’s on bottom of back page.
Page 2
HD5 & HD6 Series Wall & Rack Mount Patch Panel Instructions
Global Headquarters
Watertown, Connecticut USA
Tel: (1) 866
-
548-5814
For a complete listing of our global offices visit our web site
www.siemon.com
© 2018 Siemon 12/18 100.11056 Rev.
i
Terminateconductors
Correct tool alignment
S310 style block
Incorrect tool alignment
(tool not perpendicular).
Terminate conductors using a Siemon S814 tool or equivalent
110 style single punch tool. Alternately a high impact multi
-
punch tool can be used with the S110 style blocks
S110 style block
REQUIRED for S310 Style
OPTIONAL for S110 Style
Snap on termination caps prior to
testing.
Note: Screwdriverslot provided
for removal of S310 style.
Attach rear cable manager
into slots provided on rear of
19” panel. Secure cables
with cable ties or hook & loop
managers.
Install manager & secure cables
Rack mount
Wall mount
Caution
: Donot over
-
tighten cable ties to
prevent deforming the cable jacketand potential
transmission performance degradation.
Install caps
Install labeling
Loosely secure /bundle cables
with cable ties or hook & loop
managers. Panel can now be
flipped back over with port
access facing out.
Peel paper backing from one of the adhesive
backed designation options
i.e. clear plastic
holder or icon/label holder (see note 1). Locate
bottom lip of holder to top edge of jacksand
press firmly.
Slide paper label strip into place and/or snap
optional colored icons into holder as desired.
Notes: 1). Both label options not available on some
panel styles. 2). Laser printable labels can be
ordered separately. Visit our web site or contact
Siemon Technical Servicesfor our labeling software
template.
To ensureyou have the latest revision to this document, pleasevisit:
http://www.siemon.com/us
567
8
To assistsafe installations, complywith the following:
A. Use cautionwhen installingor modifyingtelecommunications circuits.
B. Never touchuninsulatedwire terminals unlessthe circuit has been disconnected.
C. Never installthis devicein awet location.
D. Never installwiring during a lightning storm.
Lors de l'installation, respectez lesconsignes de sécurité suivantes:
A. Utiliser avec prudence lors del'installationoude lamodification circuits de télécommunications.
B. Ne jamaistoucher les bornes de fil métalliquenon isolés sauf si le circuit aété débranché.
C. Ne jamais installer cetappareil dansun endroithumide.
D. Ne jamais installer pendantun orage.
Loading...