Room CO2/VOC/Temperature/RH
QPA Series
Description
The QPA Series Room Carbon Dioxide Sensors monitor
and transmit changes in CO2 to the building control
systems. No calibration of the CO2 sensor is necessary
— these microprocessor-based units consist of a nondispersive infrared CO2 sensor that experiences less
than 1% drift per year for the rst two years of operation
and negligible drift thereafter. All variants for CO2 and
combination versions with Temperature or VOC deliver
0 to 10 Volt or 0 to 5 Volt (eld selectable) proportional
signals to the controller.
Features
• LCD display option
• Various models:
CO2
CO2/VOC
CO2/Temp
CO2/Temp/RH
• Built-in test function for troubleshooting
• Jumper selectable °C/°F units for temp models
w/display
• No Logo versions available
• QPA2080 and QPA2080D include multiple resistance
temperature elements
Room Carbon Dioxide & Temperature Sensor.
QPA2060D Q Series
Applications
These units are especially suited for applications where
precise, stable CO2 sensing is required.
E-35
Sensors
www.usa.siemens.com/hvac
![](/html/69/69c0/69c0405c5766914a5ae36384a056140b5ed4658c0857b0eb56617ae9b054c08b/bg2.png)
QPA Series Specifications
E-36
Sensors
General
Installation ................................... 18 AWG cable length shared in conduit
with other sensor wiring 750 ft. (229 m) max
Connections .................................................................... Screw terminals
Dimensions ................................................... 3.94" H x 3.54" W x 1.65" D
(100 mm x 90 mm x 42 mm)
Voltage Requirement ......................................................... 13.5 to 35 Vdc
Housing Protection Class ...........................................NEMA 1 (all types)
CO2 Element
Operating Range .................................................................. 0 - 2000 ppm
Accuracy at Room Temperature ≈ 73°F (20°C) .........................+2% mV
Operating Temperature .................................-23 to +113°F (-5 to +45°C)
Temperature Effect .....................................Less than 0.1% per degree C
Sensing Element.............................................NDIR CO2 sensing module
Output Signal ............................0 to 10 Vdc, 0-100% Linear, Proportional
Polarity Protection...............................................................................Yes
Permissible Air Velocity in the Room ......................................<26.2 ft./s
Temperature Element
(for Combination CO2/T unit only)
Operating Temperature ......................................23 to 113°F (-5 to 45°C)
Time Constant ...........................................................................<1 minute
Accuracy .......................................................................................... ±0.8K
Output Signal ............................................................................ 0-10 volts
Calibration ........................................................................ None Required
Humidity Element
Measuring Range................................................................ 0 to 100% RH
Accuracy ...................................................................................... ±5% RH
QPA Series Product Ordering
Application Description Part No.
CO2 0 to 5 V or 0 to 10 V QPA2000
CO2 and VOC 0 to 5 V or 0 to 10 V QPA2002
CO2 and VOC 0 to 5 V or 0 to 10 V, with Display QPA2002D
CO2 and Temp (Active) 0 to 5 V or 0 to 10 V QPA2060
CO2 and Temp (Active) 0 to 5 V or 0 to 10 V, with Display QPA2060D
CO2, Temp and RH (Active) 0 to 5 V or 0 to 10 V QPA2062
CO2, Temp and RH (Active) 0 to 5 V or 0 to 10 V, with Display QPA2062D
CO2 and Temp (Passive)* 0 to 5 V or 0 to 10 V T (Selectable R) QPA2080
CO2 and Temp (Passive)* 0 to 5 V or 0 to 10 V, T (Selectable R) with Display QPA2080D
*Units include interchangeable resistance elements for LG-Ni1000, Pt1000, Pt100, and NTC 10K Ohm.