Electronic Damper Actuator 
Siemens  
Product Guard  
Warranty
Non-spring Return
OpenAir
TM
GLB Series
Easily Replaces:
• Belimo NM Series
88 lb.-in. Torque 
24 Vac, Floating Control  
0 to 10 Vdc, Modulating Control 
Description
The OpenAir GLB Series Direct-coupled 24 Vac 
Non-spring Electronic Actuator is designed for 0 to 10 
Vdc or oating control of building HVAC dampers.
Features
• Compact design
• Easy-to-see position indicator
• 0 to 10 V or oating models
• Self-adapting capability for maximum exibility in 
damper positioning
• UL, cUL, CE listed
• Quiet, low-power operation
• Rugged all metal housing, rated NEMA 2 
• Assembled in the U.S.A.
• Manual override
• Plenum-rated cable
• Modulating actuators contain built-in feedback
GLB Series Non-spring Return 
Electronic Damper Actuator.
Applications
The OpenAir GLB Series Damper Actuators are used in 
constant or variable air volume installations for the control 
requiring up to 88 lb.-in. (10 Nm) torque.
B-23
Damper Actuators
Options
• Independently adjustable dual auxiliary switches
• Adjustable start/span
• Potentiometer on oating control
Siemens 
Product Guard 
PLUS 3 Warranty
www.usa.siemens.com/hvac

GLB Series Specifications
B-24
Operating Voltage ..........................................................................24 Vac
Frequency .............................................................................. 50 to 60 Hz
Power Consumption ................................................. 3.3 VA (modulating)
     2.3 VA (oating)
Input Signal (8–2) 
 Voltage-Input ....................................................................... 0 to 10 Vdc 
 Input Resistance...................................................................100K Ohms
Position Output Signal (9–2) 
 Voltage-Output ..................................................................... 0 to 10 Vdc 
 Max. Output Current ....................................................................... 1 mA
Equipment Rating for Operating Voltage, 
Input Signal, and Position Output Signal  ...................................Class 2
Control Signal Adjustment 
 Offset (Start Point) ................................................... Between 0 to 5 Vdc 
 Factory Setting .................................................................................. 0 V 
 Span ..................................................................... Between 2 to 10 Vdc
Dual Auxiliary Switch 
 Contact Rating ................................. 4 A resistive, 2 A General Purpose 
 Voltage .........................................................................................24 Vac 
 Switch Range 
  Switch A .......................................................0 to 90° with 5° intervals 
  Recommended Range Usage ............................................... 0 to 45° 
  Factory Setting ............................................................................... 5° 
  Switch B.......................................................0 to 90° with 5° intervals 
  Recommended Range Usage ............................................. 45 to 90° 
  Factory Setting ............................................................................. 85° 
 Switching Hysteresis ........................................................................... 3°
Position Feedback 
 GLB132.1P ...................................................... .0 to 1000 Ohm <10 mA
Function 
 Torque ..........................................................................88 lb.-in.(10 Nm) 
  at 50 Hz ................................................................................ 150 sec. 
  at 60 Hz ................................................................................ 125 sec. 
 Nominal Angle of Rotation ................................................................. 90° 
 Max. Angular Rotation .......................................................................95°
Shaft Dimensions ....................................3/8 to 5/8-in. (8 to 16 mm) Dia. 
     1/4 to 1/2-in. (6 to 13 mm) Sq. 
Min. Shaft Length ............................................................ 3/4-in. (20 mm)
Housing Enclosure ..................................................................... NEMA 2 
Material ......................................................Plenum Rated Rugged Plastic
Temperature 
 Operation...................................................-25 to +130°F (-32 to +55°C) 
 Storage and Transport...............................-40 to +158°F (-40 to +70°C)
Humidity ...........................................................95% RH, non-condensing
Agency Approvals ......................................................................... UL873
     cUL C22.2 No. 24-93 
   CE 
Pre-cabled Connection .............................................................. AWG 18
Cable Length .......................................................................... 3 ft. (0.9 m)
Dimensions ........................................................ 5.4" H x 2.6" W x 2.3" D 
     (137 mm H x 68 mm W x 60 mm D)
Shipping Weight ................................................................06 lb. (0.45 kg)
Refer to page B-21 for Dimensions.
GLB Series Product Ordering
Damper Actuators
Input Signal Cabling
Floating, 24 Vac
0 to 10 Vdc
Accessories & Service Kits
3' Plenum Cable GLB131.1P — — GLB136.1P GLB132.1P 
6' Plenum Cable GLB131.1Q — — — — 
3' Plenum Cable GLB161.1P GLB163.1P GLB164.1P GLB166.1P — 
6' Plenum Cable GLB161.1Q — — — —
Standard
Span/Offset 
Adjustable
Part No.
Dual Aux. 
Switches & 
Span/Offset 
Adjustable
Dual Aux. 
Switches Only Potentiometer
B-49
www.usa.siemens.com/hvac